PT Persero Tbk
8.1 Device
8.1.1 Smoke Detector
Smoke detector shall be photoelectric type. Response time shall be 1 sec for sensitivity part
as minimum.
Smoke detector shall be equipped with integral red LED to indicate alarm and fault condition.
Smoke detector shall be located in enclosed areas where an ordinary combustible or an
electrical type fire may occur.
Photoelectric smoke detectors shall be cross-zoned within a fire zone which covered by clean
agent system to minimize false alarms.
8.1.2 Heat Detector
Combination rate-of-rise/fixed temperature heat detectors shall be used in open and confined
areas, and within enclosures, where normal temperature variations will not trip the detector.
Sensors shall be located directly over, and in close proximity to, the probable heats source(s).
Ventilation and air movement shall be considered when locating the sensors.
Each heat detector shall be self-resetting, be addressable, produce and increase signal in
circuit when it detects heat. Otherwise, system shall be capable to indicate at least for internal
circuit conditions, i.e. short circuit fault, false alarm, and open circuit fault.
The detector spacing shall be in accordance with NFPA 72.
Within each fire zone, heat detectors shall be connected in parallel. Heat detectors shall not
be designed for cross-zone application.