Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

 

PT Persero Tbk

SPECIFICATION FOR FIRE AND GAS SYSTEM

Document No. Rev. CONTRACTOR Job No.


Page 11 of 23
EIC-PS-005 2 -
 
8.1.3 Flame Detector
Flame detectors shall be multi-spectrums triple IR devices and as such shall be mounted clear
of all major obstructions. As maintenance and cleaning of the detector is critical, location shall
consider ease of access, as well as a view of the hazard.
The system design shall consider cross-zone logic for the detectors in order to minimize false
alarms.
Infrared flame detectors shall include an automatic self-checking feature, which will generate
an alarm in both local control station and local SCADA on a fault condition at the unit.
Flame detector device shall have field of view 90º horizontal and 90º vertical.
Ultraviolet detectors may be used where arc welding, lightning, or other similar occurrences
do not influence the detection of a fire source.
Combination type ultraviolet infrared detectors shall be used where arc welding, lightning,
normal heating sources, and other similar occurrences influence the detection of a fire source.
Triple radiation-band-type-infrared detectors shall be used where automatic fire suppression
equipment is activated from the fire detection system.
8.1.4 Gas Detector
Gas detectors shall be infrared. Gas detector shall be have interval level 0 – 100 % LEL.
Visual and audible alarms shall be provided for two levels of detection, i.e. minimum level
shall be 20% of LEL and maximum level shall be 60% of LEL. Alarm levels shall be
adjustable.
Gas detector shall have SMART sensor technology (HART) transmitter automatically
recognizes sensor configuration.
Gas detectors shall have analog output signals including dry contact. Gas leak detector shall
be ultrasonic type.
8.1.5 Hydrogen Gas Detector
Hydrogen Detectors shall have Hazardous Area Classification of Class I, Zone 1. Hydrogen
detectors shall be infrared type. Detection range shall be 0-100% LEL or 0-2000 ppm.
Response Time shall be < 6 Second, and accuracy shall be ±3% < 50 % LEL, ±5% > 50 %
LEL. Power supply shall be 24 VDC and electrical connection shall be 1/2" NPT(F).
Hydrogen detectors shall have 0-20 mA, HART protocol and shall have alarms of 20% LEL or
400 ppm (1st alarm), 75% LEL or 1500 ppm (2nd alarm) which alarm indication is integral
LED to indicate alarm, health and fault condition. Cable shall be 3 wired terminations.
 
PT Persero Tbk

SPECIFICATION FOR FIRE AND GAS SYSTEM

Document No. Rev. CONTRACTOR Job No.


Page 12 of 23
EIC-PS-005 2 -
 
Enclosure material shall be reinforced polyester DMC antistatic and enclosure protection shall
be Toxic / Corrosive Gas Resistant, Eex"d".
Hydrogen detectors shall have certification of ATEX, UL or FM Listed and shall be equipped
with IP 65. Mounting style shall be integral with sensor (2" Pipe Mounting Stanchion or wall)
and tagging material is 316 SS.
Hydrogen gas detector shall be linked to exhaust fan (industrial type) to control run/stop the
exhaust fan if hydrogen gas detected.
8.1.6 Manual Alarm Call Point
Manual alarm call point for hazardous area shall be complied with UL requirement for
hazardous location Class I, zone 1.
Hazardous alarm call point shall be pull/push type with lift/flap cover. Non-hazardous alarm
call point shall have plastic glass cover element.
Operations handle feature white arrows to show basic operation direction. Manual alarm call
point can be opened for inspection and maintenance without initiating an alarm.
Manual call points shall be provided as shown on approved drawings. They shall be
addressable and connect into the standard addressable loop of the gas detector.
8.1.7 Horn & Strobe Fire Alarm
Horn & strobe is designed to complied UL standard requirement for emergency signalling
devices for the hearing impaired. Strobe provides selectable candela intensity field selector for
maximum performance.
Horn & strobe shall be installed at hazardous and non-hazardous area. Voltage for power
supply shall 24 VDC.
Horns shall emit sound audible 70-100 dBA at 1 meter and 80 dBA in still air at 1 km. Sound
alarms shall be emitted for at least 5 minutes, unless acknowledged and silenced at the
Human Machine Interface (HMI).
The tone or signal from the audible alarm shall not be similar to any other normal noise, tone
or sound in the area.
For outdoor purposes, the visual alarm shall use high intensity strobe lights, visible for
500meters and shall be emitted for at least 5 minutes.
The colour of outdoor strobes shall not be similar to any other light used in the area. Outdoor
audible alarms shall be electronic horns. Sound alarms shall be emitted for at least 5 minutes,
unless acknowledged and silenced at the HMI.
 
PT Persero Tbk

SPECIFICATION FOR FIRE AND GAS SYSTEM

Document No. Rev. CONTRACTOR Job No.


Page 13 of 23
EIC-PS-005 2 -
 
8.1.8 Fire Alarm Bell and Flashing Light
Fire alarm bell shall have a minimum output rating of 85 dB. Bell shall be able to use at
outdoor service area. Bell shall meet UL requirement.
Bell shall be surface mounted and swivel type to protect the sound in any direction.
Flashing light shall be provided with alarm bell for annunciation of fire. The output of flashing
light shall be at least 110 peak candle power.
In all cases, flashing red lamps shall be provided in addition to the audible alarm in a clearly
visible location, preferably above every exit door, to indicate a hazardous situation in there
spective room or area.
Audible and visual alarms shall be provided as shown on approved detail drawings. A
common audible and visual alarm may be used for areas comprised of multiple fire zones
provided that the alarm annunciation is not shielded from the affected fire zone. The audible
alarms shall not be less than 95 dBA throughout the protected area.
8.1.9 Manual Discharge & Abort Station
Manual release switch is a dial actuation device which provides a means of manually
discharging the automatic fire extinguishing system.
The system abort switch is designed to be used in conjunction with other system equipment. It
provides a temporary manual means by which the agent actuation circuit may be interrupted
before automatic actuation occurs.
8.1.10 Warning Sign
The warning sign provides an easy to understand and universal solution to your fire safety
sign needs. All sign includes both text and symbols to help the viewer understand the
message being conveyed. The material shall be semi-rigid PVC.
8.1.11 Junction Box
Junction box and panel enclosures shall be robust and capable of withstanding pull-out cable
load.
a. The panel enclosures shall be:
- 3 mm thick, aligned and rigid, applicable for outdoor use and provided with a roof
for shade;
- Provided with lifting and securing devices.
- IP42 for indoors use.
- IP 55 for outdoor non-hazardous areas (safe areas);
- Increased safety (ex “e").
 
PT Persero Tbk

SPECIFICATION FOR FIRE AND GAS SYSTEM

Document No. Rev. CONTRACTOR Job No.


Page 14 of 23
EIC-PS-005 2 -
 
b. Junction boxes shall be made of stainless steel and suitable for outdoor use. All
junction boxes shall be increased safety (ex “e”) type with minimum IP 55 enclosure.
Contractor shall provide valid copy of hazardous area certificate which approved by
UL, CENELEC, or FM.
c. All panel enclosures shall be made of corrosion-proof material or a corrosion proof
painting and coating system and comply with international Codes and Standards.
8.1.12 Detector Installation
Smoke and heat detectors shall be installed within the enclosures and raise floor according to
the approved drawings and block diagram.
Detectors and circuits shall be continuously monitored for faults.
Any fault detector shall give an alarm only. Where detectors are paired and one is fault,
detection of fire or gas by the healthy detectors shall initiate action as though detection has
been by both detectors.
9. FIRE EXTINGUISHING SYSTEMS
Gas-based Fire Extinguishing System using environmentally friendly gas shall be installed at
the specified location. The system shall comply with NFPA 2001 - The Standard on Gas Clean
Agent Fire Extinguishing System (FM 200).
The gas clean extinguishing agent shall be non-ozone depleting potential which contain no
chlorine or bromine and non-suffocating material, and it shall be designed that the extinguish
system shall not have suffocating effect to the people inside protected area.

9.1 Design Conditions


Design concentrations shall be 7% for protected rooms, enclosures or process modules.
The individual zone / system shall be dimensioned to give a complete discharge of the agent
in less than 10 seconds into the affected zone.
Contractor shall submit the calculation of the amount of nozzle of discharging agent to
Employer for approval.
The system shall be designed that a fire condition in a protected area shall actuate
automatically the total flooding of clean agent in that area independently.
The clean agent shall be consist of primary and secondary cylinder and can be rechargeable
on site.
 
PT Persero Tbk

SPECIFICATION FOR FIRE AND GAS SYSTEM

Document No. Rev. CONTRACTOR Job No.


Page 15 of 23
EIC-PS-005 2 -
 
9.2 Activation Rules
The extinguishing system shall be able to be activated through manual operation via manual
station and automatic operation via detection system by cross zone logic.
Manual operation shall only be able to initiate alarm and not directly activate the discharging
agent.
The actuation of one detector (smoke or heat) in a zone shall not be sufficient to cause the
discharge of the agent.
The agent shall only be actuated to discharge on activation of another adjacent detector in
that zone after a certain time delay.
The time delay circuit shall have a delay period adjustable from zero to 180 seconds.
The system shall have manual delay button to prevent operator from trapped inside the
discharged room.

9.3 Sequence of Activation to Discharge


When one detector is activated, and followed by another detector in the same zone is also
activated, the following functions shall be executed:
The discharge warning sirens shall be activated.
After a present time delay of between 0-180 sec (adjustable) has expired, the gas actuator
shall release the gas into that particular zone.
At the time of gas discharge, the "GAS DISCHARGE DO NOT ENTER" signs of that particular
zone shall be flashing.
"EVACUATE AREA" signage and flashing lights shall be provided along the aisle ways and
routes of exit upon activation of the first detector.
"GAS DISCHARGE DO NOT ENTER" signs shall be provided at the entrance to all zones and
to such other areas to warn unauthorized personnel not to enter the protected area upon the
total flooding of the extinguishing gas.
The illuminated warning signs shall flash until they are manually reset after the fire has been
put out and the system restored to normal.

9.4 Cylinders and Discharge System


The extinguishing agent shall be environmental friendly clean agent-based i.e. FM 200 or
equal with physical properties conforming to NFPA Standard 2001.

You might also like