Mechanical Daily Report
for the OEA Site Issue: Date:
1 26/10/2022
1 General housekeeping. Please cover ends of all FCU’s where installation works are
not on-going.:
Fig 1: GF HVAC
2 GF HVAC drawing pinned to wall at GF workshop / store entrance does not indicate
fresh air ductwork and so far none appears to have been installed. Please clarify the
intention regarding fresh air provision and which code is being followed.
Report No:
002
Mechanical Daily Report
for the OEA Site Issue: Date:
1 26/10/2022
3 AC units at 3rd appear to have intakes close to beams at rear. Please confirm this has
been considered and is ok for the design air flows.
4 Lift Motor Rooms appear to have had previous through the wall AC units removed.
Please confirm the intention regarding cooling / extract for these rooms.
Report No:
002
Mechanical Daily Report
for the OEA Site Issue: Date:
1 26/10/2022
5 3F AC unit serving IT/Comms room is in the room itself. It is best practise and
Telecommunications code (BICSI etc) that high level FCU’s are located outside the space.