ATV 1200

High-voltage Drive
Green Your Power

Catalogue
Schenider Electric
Make The Most of
Your energy

As a global specialist in energy management with operations in more than


100 countries, Schneider Electric offers integrated solutions across multiple
market segments, including leadership positions in energy and infrastructure,
industrial processes, building automation, and data centers/networks, as well as
a broad presence in residential applications. Focused on making energy safe,
reliable, and efficient, the company’s 110,000 employees achieved sales of
more than 19.6 billion euros in 2010, through an active commitment to help
individuals and organizations “Make the most of their energy!
ATV1200: Preference of Energy-
saving and Efficiency-improving
Schenider Electric is a global energy management expert,

+
and the ATV1200 high-voltage drive further perfects the
global product series provided to customers in fields of
power distribution, motor control and control system etc.
optimizes the energy management solutions, and is the
preferred equipment to meet the requirement of energy Up to 40% energy saving

saving and efficiency improving.

Reduce energy costs


Protect motor and equipment
Increase competency
Reduce maintenance costs

Our Innovation Bring You Generous Profits


More Excellent Technology More Users’ Benefits
p Multiple-pulse rectifier, THDi < 2% p  o need of additional filter
N
p PWM unit serial output, perfect sine wave measures, easily meet the strict
output requirement of harmonic standard
p I nterlocking circuit uses certified safe p No need of output filter, easy
devices installation
p Auxiliary control based on PLC p No impact to motor insulation,
p A ccess drive setting with 10” touch screen produce no pulse torque,
p Integrated PID function compatible with of old motor in
p S ynchronous control between output and retrofit
power grid p Guarantee safety of operators
p Matured technology, reliable
operation, simple maintenance
p Simple commissioning, easy
maintenance
p Easily integrated into the process
control
p Smooth bypass control
ATV1200: Widely Used in the
Industrial Field

Cement
• K
 iln head exhaust fan
• K
 iln tail exhaust fan
• K
 iln head high-temperature fan
• C
 ement rotary kiln (single drive,
multiple drives)
• C
 ement mill (multiple drives)
• A
 nd so on

Water Industry
• W
 ater suction pump
• W
 ater supply pump
• P
 rimary suction pump
• S
 econdary clean water pump


Coal Mine Power Plant
• Belt conveyor (single drive, • B
 oiler induced draught fan
multiple drives) • B
 oiler forced draught fan
• Mine ventilator • P
 rimary fan
• And so on
• C
 ondensate pump
• S
 ewage pump etc.

Petroleum and Petrifaction Metallurgy


• Kiln head exhaust fan • K
 iln head exhaust fan
• Air compressor • B
 last-furnace blower
• Water injection pump • P
 rimary dust-removing fan
• Submersible pump • D
 ry quenching circulating fan
• Desolvente raw material pump • M
 ain exhaust fan for sintering
• Distillation tower bottom pump • H
 igh-pressure phosphorous
• Coking furnace radiation pump removal pump
• Diesel oil transfer pump • A
 nd so on
• And so on


ATV1200: Green and Compact
ATV1200 inverter is composed of transformer cabinet, power unit and control
cabinet

M~
3 b Integrated transformer
•M  uch less cable connection
and commissioning work
• 2 4-48 pulse operation
b Power unit
• E asy for replacement
•M  ulti-stage PWM control
Control cabinet b Control
Power unit • Integrating multiple
Rectifier
Transformer cabinet
Incoming line
cabinetcabinet

Integrated dry-type isolation transformer, integrated


design;
Transformer Up to 48 pulse, low harmonic;

cabinet Class H insulation, entirely manufactured in vacuum


immersion process;
With three temperature inspecting instrument
Low voltage IGBT unit serial technology, matured and
reliable;
Power unit Multi-stage PWM control, output perfect sine wave;
cabinet Sliding rail installation, convenient replacement;
Optical fiber connection, high speed and reliable
Advanced master control system based on DSP,
CPLD and FPGA;
Optical fiber connection, high speed and reliable
Control Integrated small PLC, matured technology,
convenient and reliable
cabinet 10 inch touch screen, easy commissioning;
UPS as default offer, to guarantee master control can
work in any situations.


ATV1200: Green and Compact
Internal Principle and Topological Structure Diagram of 6 KV Frequency
Converter

3-phase input
power supply

b Clean power
• I nput by 24-48 pulse rectifier, Almost
Three phase 6 KV produce no harmonic THDi < 2 %
b Friendly to motor
• PWM multilevel output
• T he influence of dv/dt on motor can be
neglected
• Perfect sine wave output

Waveforms of Input Voltage (Green) and


Current (Orange) at Power Supply Side

Waveforms of Output Voltage (Green) and


Current (Orange) at Motor Side


ATV1200: Friendly User Interface

• M
 ultiple languages operation ATV1200
(Chinese and English etc.) Version 1.0.1
• 10 inch color liquid crystal display
• I nherit good menu design pattern of
ATV series
• C an store parameters and
operation records

Interface Display
Resolution Ratio: 800 * 480


ATV1200: Functional Description

Internal P I D Functions
Users can set and regulate the expected values of controlled variables (such as pressure
and flow etc.). The drive will automatically regulate the output frequency of the drive and
control the motor speed according to the actual value of the controlled variable and the
PID parameters set by the system, thus making the actual values of the controlled variables
change automatically with the expected values.

Setpoint of Process
Parameters

+
_ PID Drive M

Feedback of Process
Parameters

Power-down Maintenance Function


The drive can operate with full load without tripping during five periods of instantaneous
power down, the machine will not stop within 10s of power down and can maintain operation
at maximum limit.

Power-down Recovery and Automatic Re-start Function


If the power supply is power-down and recovers l within the set time, the drive can
automatically start and can automatically identify and trace the motor speed to realize
non-impact re-start, thus recovering to the original working status.

Time scale in case of


continuous operation Instantane
power downp Recover
System
voltage
Instantaneous
stop detection
Instantaneous
stop detection Recover
and confirm
Motor speed
0ms Accelerate
Intermediate
DC voltage

Regenerative mode during


instantaneous stop Re-start

Catch on fly Function


Can be used to start a spinning motor smoothly


ATV1200: Functional Description

Programmed Running Function Fault Query Function


Users can fill the required automatic running The drive has fault positioning and query
speed data in a sheet of drive, and drive can functions, in case of minor fault, alarm
automatically operate in different modes information will be displayed on the
and at different speed in different time interface, and in case of major fault, the
according to users’ arrangement, so as to be drive will pop up fault interface, and users
convenient for users to use. can intuitively see the types and positions of
generated fault.

Operation Data Recording Smooth Bypass Function


Function The output of the drive can be synchronous
ATV1200 has function of automatically with the power grid to realize undisturbed
recording operation parameters. Users switching function of power frequency.
can make corresponding records of each
operation and the corresponding time of the
drive.

Schematic Diagram
of Bypass Function

Frequency
converter

Reactor
(Options)

Switching
Circuit


ATV 1200: Technical Specification
General Features
Type of Drive
Input 24-48 pulse diode rectifier bridge
Output Multilevel PWM inverter, and each inverter unit is a 2 level NPC low-voltage IGBT inverter
Input voltage p Standard: 3/3.3 KV, 6/6.6 KV, 10 KV

p Variation: standard±15%

p Option: maximum – 20% (x4)

Allowable voltage fluctuation The drive is subject to de-rating operation when the voltage drop of power supply is within -35%
Input frequency 50/60 Hz ±10%
Acceleration deceleration time 0-3200 s
Overload capability p ����������������������������������������������������������������������
Standard load:120% 1 min/10 min, 150% 3 s, Instant Trip Threshold 200%
p ����������������������������������������������������������������
Heavy-load (optional): rated current 150% 1 min/10 min or higher
Total harmonics THDI Comply with the requirements of China national standard GB14549-93 and power quality standard of
IEEE519-1992
Frequency resolution 0.01 HZ
Trigger signal transmission Fiber optic transmission
Power factor > 0.96
Efficiency at rated power The efficiency of the integral device including drive and input transformer is 0.97
Type of motor power supplied Asynchronous motor, synchronous motor
Three-phase output voltage for
motor connection Standard: 0...3000 V - 0 ... 3300 V - 0...6000 V - 0...6600 V - 0...10000 V
Output frequency Asynchronous motor, synchronous motor
Input transformer Integrated in the frequency variable device, the dry phase-shifting transformer can be supplied with
24 – 48 pulse rectifier
Control power supply p Standard: 380 V three-phase with neutral, capacity :3 KVA

p Option: double power supplies switching to provide DC/AC 200 V single phase or UPS

Protection class p Standard: IP31

p Option: IP42

Paint RAL 7032


Cooling Air cooling type
Reference standard IEC EN 61800-3, IEC EN 61800-4, IEC EN 61800-5-1, IEC EN 60204-11, IEC EN 60529,IEEE 519 and other
optional ones

Control Features
Motor control mode V/f control, sensorless flux vector control, closed-loop control, dynamic acquisition and critical speed
suppression
Number of quadrant 2
Steady operation Speed precision in steady state: ±0.5%
Closed-loop speed precision: ±0.1%
Protection Over-current, main fuses, over-voltage, under-voltage, CPU fault, cooling fan stop
Interface HMI: 10 inch large LCD touch screen (Chinese/English)
Communication Standard: Profibus, Modbus
PID function Integrated PID regulator, and parameters can be set
I/O function Sufficient I/O ports and can be expanded according to users’ requirements
Operation mode Local/remote, PID self-regulation
Frequency setting Manual operation/analog quantity setting/digital setting
Human-Machine interface display Output frequency, voltage, current, power and input voltage, current, power, power factor, fault/alarm and
their records, parameters setting, waveform display etc.
Protection Over-current, short-circuit, earthing, over-voltage, under-voltage, over-load, over-heating, phase loss, unit
failure etc.

Environment Features
Storage temperature -10°C - 60°C (transport temperature: -10°C - 70°C (sustain 60°C to 70°C for 24 h )
Working temperature 0-40°C
Cooling method Forced air cooling
Relative moisture 90% (without condensate), Optional: maximum up to 95%
Altitude < 1000 m above the seal level, can be customized for high altitude
Vibration Acceleration: 4.9 m/s2 acceptable (10-50 Hz)
Noise level ≤ 75 dB (A) (including the noise of the cooling fan on the cabinet top)

(*1) The applicable motor output is the reference value of the standard 3/6/10 kV Grade 3 motor.
(*2) It the machine is subject to cold start in the condition that the temperature of cooling fins is lower than 40°C, it will be 120% and continuous for 60 s.
(*3) If it needs to additionally install other options, please contact with the local office salers.


ATV 1200: Product Specifications
Power Specifications
Voltage Class 3� kV
��
Transformer
Output current Motor Power Air Fflowratelow Dimension Weight
Model Capacity Outside View
(A) (kW) (M3/h) (L*D*H) mm (kg)
(kVA)

ATV1200-250-A30 50 200 250 9900 3160*1200*2671 Figure 1 4300

ATV1200-305-A30 60 245 305 9900 3160*1200*2671 Figure 1 4300

ATV1200-365-A30 70 290 365 9900 3160*1200*2671 Figure 1 4300

ATV1200-375-A30 75 300 375 9900 3160*1200*2671 Figure 1 4300

ATV1200-500-A30 100 400 500 9900 3160*1200*2671 Figure 1 4300

ATV1200-700-A30 135 560 700 13200 3762*1200*2671 Figure 2 4600

ATV1200-790-A30 150 630 790 13200 3762*1200*2671 Figure 2 4600

ATV1200-890-A30 175 710 890 13200 4464*1200*2671 Figure 3 6200

ATV1200-1000-A30 195 800 1000 16500 4664*1200*2671 Figure 4 6200

ATV1200-1125-A30 220 900 1125 16500 4664*1200*2671 Figure 4 6200

ATV1200-1250-A30 240 1000 1250 16500 4664*1200*2671 Figure 4 6200

ATV1200-1440-A30 280 1150 1440 16500 4664*1200*2671 Figure 4 6200

ATV1200-1565-A30 305 1250 1565 23100 5466*1200*2671 Figure 4 7100

ATV1200-1750-A30 345 1400 1750 23100 5766*1200*2671 Figure 5 A 8300

ATV1200-2000-A30 390 1600 2000 23100 5766*1200*2671 Figure 5 A 8300

ATV1200-2250-A30 440 1800 2250 23100 5766*1200*2671 Figure 5 A 8300

ATV1200-2500-A30 480 2000 2500 26400 5766*1200*2671 Figure 5b 9100

Remarks:
1. The standard over-load capability of the above drive is 120%/min, and is allowed to overload 1 min every 10 min.
2. For higher over-load capability(u 150%/min). Please consult the local office.
3. The dimension are only for reference, and the final design drawings shall prevail.
4. For higher power at each output voltage level, please consult the local office.

Identification Code
AT V1200 _X X X A yy

Serial Name Drive (kVA) Air cooling Output voltage�


3 0→3 0 0 0 V
6 0→6 0 0 0 V
6 6→6 6 0 0 V
For Example 1 0 0→1 0 0 0 0 V
AT V 1 2 0 0 -2 5 00 - A30:
The capacity of 1200 series of high-voltage drive is 2500 KVA, and the output voltage is 3000 V

10
3 KV series with depth of 1200 mm (the unit of data in the following size diagram is mm)

2341

2671
2341
2671
2341
2671

900 400 1800 1502 400 2100 1904 400


1800
3762 4464
3160
Figure 2 Figure 3
Figure 1
2341

2341
2671

2671
2100 1904 600 2400 2706 600
4664 5766

Figure 4 Figure 5 A
2341
2671

2400 2706 600 1200


5766

Figure 5b Depth

11
ATV 1200: Product Specifications

Voltage Class 6 kV
Transformer
Output current Motor Power Air Flowrate Dimension Weight
Mode Capacity Outside View
(A) (kW) (m3/h) (L*D*H) mm (kg)
(kVA)

ATV1200-275-A60 25 220 275 13200 3662*1200*2671 Figure 1 4300

ATV1200-350-A60 35 280 350 13200 3662*1200*2671 Figure 1 4300

ATV1200-400-A60 40 315 400 13200 3662*1200*2671 Figure 1 4300

ATV1200-500-A60 52 400 500 13200 3662*1200*2671 Figure 1 4300

ATV1200-565-A60 55 450 565 13200 3662*1200*2671 Figure 1 4300

ATV1200-625-A60 62 500 625 13200 3962*1200*2671 Figure 1 4300

ATV1200-700-A60 65 560 700 13200 3962*1200*2671 Figure 2 5700

ATV1200-790-A60 75 630 790 13200 3962*1200*2671 Figure 2 5700

ATV1200-890-A60 90 710 890 13200 3962*1200*2671 Figure 2 5700

ATV1200-1000-A60 100 800 1000 13200 3962*1200*2671 Figure 2 5700

ATV1200-1125-A60 115 900 1125 16500 4562*1200*2671 Figure 3 6500

ATV1200-1250-A60 125 1000 1250 16500 4562*1200*2671 Figure 3 6500

ATV1200-1400-A60 135 1120 1400 16500 4562*1200*2671 Figure 3 6500

ATV1200-1500-A60 145 1200 1500 29900 4862*1200*2753 Figure 4 7700

ATV1200-1565-A60 150 1250 1565 29900 4862*1200*2753 Figure 4 7700

ATV1200-1750-A60 175 1400 1750 19800 5264*1200*2671 Figure 5 A 8100

ATV1200-2000-A60 200 1600 2000 19800 5264*1200*2671 Figure 5 A 8100

ATV1200-2250-A60 220 1800 2250 23100 5264*1200*2671 Figure 5 A 8100

ATV1200-2500-A60 240 2000 2500 23100 5264*1200*2671 Figure 5b 9500

ATV1200-2815-A60 275 2250 2815 43200 5764*1300*2753 Figure 6 11700

ATV1200-2875-A60 280 2300 2875 43200 5764*1300*2753 Figure 6 11700

ATV1200-3125-A60 310 2500 3125 29700 6970*1300*2671 Figure 7 12900

ATV1200-3375-A60 330 2700 3375 29700 6970*1300*2671 Figure 7 12900

ATV1200-3625-A60 360 2900 3625 29700 6970*1300*2671 Figure 8 12900

ATV1200-3940-A60 390 3150 3940 29700 6970*1400*2671 Figure 8 12900

ATV1200-4065-A60 400 3250 4065 33000 7270*1500*2671 Figure 9 14600

ATV1200-4500-A60 440 3600 4500 33000 7270*1500*2671 Figure 9 14600

ATV1200-4750-A60 465 3800 4750 56500 7270*1500*2753 Figure 10 14600

ATV1200-5000-A60 480 4000 5000 56500 7270*1500*2753 Figure 10 14600

Remarks:
1. The standard over-load capability of the above drive is 120%/min, and is allowed to overload 1 min every 10 min.
2. For higher over-load capability(u 150%/min). Please consult the local office.
3. The dimension are only for reference, and the final design drawings shall prevail.
4. For higher power at each output voltage level, please consult the local office.

12
6 KV series with depth of 1200 mm (the unit of data in the following size diagram is mm)

2341
2671
2341
2671

2341
2671
1800 1202 600 2100 1202 600 2100 1802 600 1200
3662 3962 4562
Depth
Figure 1 Figure 2 Figure 3

2341
2671
2341
2753

2671
2341

2400 1802 600 2400 2204 600 2400 2204 600


4862 5264 5264

Figure 4 Figure 5 A Figure 5b

6 KV series with depth of 1300 mm (the unit of data in the following size diagram is mm)
2753

2341
2671
2341

2700 2404 600 2700 3610 600 1300


5764 6970
Figure 6 Depth
Figure 7

6 KV series with depth of 1400 mm (the unit of data in the following size diagram is mm)
2341
2671

2700 3610 600


6970
1400

Figure 8 Depth

6 KV series with depth of 1500 mm (the unit of data in the following size diagram is mm)
2753
2341
2341
2671

3000 3610 600 3000 3610 600 1500


7270 7270

Figure 9 Figure 10 Depth

13
ATV 1200: Product Specifications

Voltage Class 6.6 kV


Transformer
Output current Motor Power Air Flowrate Dimension Weight
Model Capacity Outside View
(A) (kW) (m3/h) (L*D*H) mm (kg)
(kVA)

ATV1200-275-A66 25 220 275 13200 3962*1200*2671 Figure 1 4400

ATV1200-350-A66 30 280 350 13200 3962*1200*2671 Figure 1 4400

ATV1200-400-A66 35 315 400 13200 3962*1200*2671 Figure 1 4400

ATV1200-500-A66 45 400 500 13200 3962*1200*2671 Figure 1 4400

ATV1200-565-A66 50 450 565 13200 3962*1200*2671 Figure 1 4400

ATV1200-625-A66 60 500 625 13200 4262*1200*2671 Figure 2a 5800

ATV1200-700-A66 62 560 700 13200 4262*1200*2671 Figure 2a 5800

ATV1200-790-A66 70 630 790 13200 4262*1200*2671 Figure 2a 5800

ATV1200-890-A66 85 710 890 13200 4262*1200*2671 Figure 2a 5800

ATV1200-1000-A66 90 800 1000 13200 4262*1200*2671 Figure 2b 5800

ATV1200-1125-A66 100 900 1125 16500 4862*1200*2671 Figure 3 6300

ATV1200-1250-A66 115 1000 1250 16500 4862*1200*2671 Figure 3 6300

ATV1200-1400-A66 130 1120 1400 16500 4862*1200*2671 Figure 3 6300

ATV1200-1500-A66 135 1200 1500 16500 4862*1200*2671 Figure 4 7500

ATV1200-1565-A66 145 1250 1565 29900 5164*1200*2753 Figure 5 7500

ATV1200-1750-A66 160 1400 1750 19800 5766*1200*2671 Figure 6a 8600

ATV1200-2000-A66 175 1600 2000 19800 5766*1200*2671 Figure 6a 8600

ATV1200-2250-A66 200 1800 2250 23100 5766*1200*2671 Figure 6a 8600

ATV1200-2500-A66 220 2000 2500 23100 5766*1200*2671 Figure 6b 9600

ATV1200-2815-A66 255 2250 2815 43200 6066*1300*2753 Figure 7 11700

ATV1200-2875-A66 260 2300 2875 43200 6066*1300*2753 Figure 7 11700

ATV1200-3125-A66 280 2500 3125 43200 6066*1300*2753 Figure 7 11700

ATV1200-3375-A66 300 2700 3375 33000 7572*1400*2671 Figure 8 13700

ATV1200-3625-A66 320 2900 3625 33000 7572*1400*2671 Figure 9 13700

ATV1200-3940-A66 350 3150 3940 33000 7572*1400*2671 Figure 9 13700

ATV1200-4065-A66 360 3250 4065 33000 7572*1400*2671 Figure 10 13700

ATV1200-4500-A66 400 3600 4500 33000 7572*1400*2671 Figure 10 13700

ATV1200-4750-A66 420 3800 4750 36300 7872*1500*2671 Figure 10 15400

ATV1200-5000-A66 445 4000 5000 36300 7872*1500*2671 Figure 10 15400

Remarks:
1. The standard over-load capability of the above drive is 120%/min, and is allowed to overload 1 min every 10 min.
2. For higher over-load capability(u 150%/min). Please consult the local office.
3. The dimension are only for reference, and the final design drawings shall prevail.
4. For higher power at each output voltage level, please consult the local office

14
6.6 kV series with depth of 1200 mm (the unit of data in the following size diagram is mm)

2320
2320

2320
2671
2671

2671
1800 1502 600 2100 1502 600 2100 1502 600
3962 4262 4262
Figure 1 Figure 2a Figure 2b

2320
2320

2320
2671

2753
2671

2100 2104 600 2400 2104 600 2400 2104 600


4864 5164 5164

Figure 3 Figure 4 Figure 5

2320
2320

2671
2671

2400 2706 600 2400 2706 600


5766
1200
5766

Figure 6a Figure 6b Depth

6.6 kV series with depth of 1300 mm (the unit of data in the following size diagram is mm)
2320

2320
2753

2671

2700 2706 600 600


6066
2700 4212 1300
7572

Figure 7 Figure 8 Depth

6.6 kV series with depth of 1400 mm (the unit of data in the following size diagram is mm)
2320
2671

2700 4212 600


7572
1400

Figure 9 Depth

6.6 kV series with depth of 1500 mm (the unit of data in the following size diagram is mm)
2320
2671

3000 4212 600 1500


7872

Figure 10 Depth

15
ATV 1200: Product Specifications

Voltage Class 10 kV
Transformer
Output current Motor Power Air Flowrate Dimension Weight
Mode Capacity Outside View
(A) (kW) (M3/h) (L*D*H) mm (kg)
(kVA)
ATV1200-395-A100 25 315 395 16500 4564*1200*2671 Figure 1 7500
ATV1200-500-A100 32 400 500 16500 4564*1200*2671 Figure 1 7500
ATV1200-565-A100 35 450 565 16500 4564*1200*2671 Figure 1 7500
ATV1200-625-A100 39 500 625 16500 4564*1200*2671 Figure 1 7500
ATV1200-700-A100 40 560 700 16500 4564*1200*2671 Figure 1 7500
ATV1200-790-A100 45 630 790 16500 4564*1200*2671 Figure 1 7500
ATV1200-890-A100 53 710 890 16500 4564*1200*2671 Figure 1 7500
ATV1200-1000-A100 62 800 1000 16500 4564*1200*2671 Figure 1 7500
ATV1200-1125-A100 65 900 1125 19800 4864*1300*2671 Figure 2 7500
ATV1200-1250-A100 75 1000 1250 19800 4864*1300*2671 Figure 2 7500
ATV1200-1400-A100 85 1120 1400 19800 4864*1300*2671 Figure 2 7500
ATV1200-1565-A100 90 1250 1565 19800 4864*1300*2671 Figure 2 7500
ATV1200-1750-A100 100 1400 1750 23100 5164*1300*2671 Figure 3 11900
ATV1200-2000-A100 120 1600 2000 23100 6064*1300*2671 Figure 4 13000
ATV1200-2250-A100 135 1800 2250 23100 6064*1300*2671 Figure 4 13000
ATV1200-2500-A100 150 2000 2500 43200 6064*1400*2753 Figure 5 13000
ATV1200-2815-A100 170 2250 2815 26400 6868*1400*2671 Figure 6 13600
ATV1200-3125-A100 180 2500 3125 26400 6868*1400*2671 Figure 6 13600
ATV1200-3500-A100 200 2800 3500 26400 6868*1400*2671 Figure 6 13600
ATV1200-3750-A100 220 3000 3750 26400 6868*1400*2671 Figure 6 13600
ATV1200-3940-A100 235 3150 3940 26400 6868*1400*2671 Figure 6 13600
ATV1200-4250-A100 250 3400 4250 56500 7168*1500*2753 Figure 7 16000
ATV1200-4500-A100 265 3600 4500 56500 7168*1500*2753 Figure 7 16000
ATV1200-4875-A100 280 3900 4875 56500 7168*1500*2753 Figure 7 16000
ATV1200-5000-A100 295 4000 5000 42900 9076*1500*2671 Figure 8 20400
ATV1200-5375-A100 315 4300 5375 42900 9076*1500*2671 Figure 8 20400
ATV1200-5750-A100 340 4600 5750 42900 9376*1500*2671 Figure 9 20400
ATV1200-6000-A100 355 4800 6000 42900 9376*1500*2671 Figure 9 20400
ATV1200-6250-A100 365 5000 6250 42900 9376*1500*2671 Figure 9 20400
ATV1200-6625-A100 390 5300 6625 42900 9376*1500*2671 Figure 9 21000
ATV1200-7000-A100 410 5600 7000 42900 9376*1600*2971 Figure 10 21000
ATV1200-7375-A100 435 5900 7375 42900 9376*1600*2971 Figure 10 21500
ATV1200-7750-A100 455 6200 7750 42900 9376*1600*2971 Figure 10 21500
ATV1200-8125-A100 480 6500 8125 42900 9376*1600*3053 Figure 11 21500

Remarks:
1. The standard over-load capability of the above drive is 120%/min, and is allowed to overload 1 min every 10 min.
2. For higher over-load capability(u 150%/min). Please consult the local office.
3. The dimension are only for reference, and the final design drawings shall prevail.
4. For higher power at each output voltage level, please consult the local office

16
10 kV series with depth of 1200 mm (the unit of data in the following size diagram is mm)

2320
2671

2100 1804 600 1200


4564
Depth
Figure 1

10 kV series with depth of 1300 mm (the unit of data in the following size diagram is mm)

2320
2320

2671
2671

2400 1804 600 2700 1804 600


4864 5164

Figure 2 Figure 3
2320
2671

2700 2704 600 1300


6064
Figure 4 Depth

10 kV series with depth of 1400 mm (the unit of data in the following size diagram is mm)
2320
2753

2700 2704 600


6064

Figure 5
2320
2671

2700 3508 600 1400


6868
Depth
Figure 6

17
ATV 1200: Product Specifications

10 kV series with depth of 1500 mm (the unit of data in the following size diagram is mm)

2320
2671
2320
2753
3000 3000 5416 600
3508 600
9076
7168

Figure 7 Figure 8

2320
2671

3000 5416 600 1500


9376
Depth
Figure 9

10 kV series with depth of 1600 mm (the unit of data in the following size diagram is mm)
2620
2971

3300 5416 600


9376

Figure 10
2620
3053

3300 5416 600 1600


9376
Depth
Figure 11

18
ATV 1200: Maintenance and
Installation Size
Side View

Front View Space for upper 500mm


maintenance

Control
Transformer cabinet Power unit cabinet cabinet 800mm D 1500mm
W Back maintenance Front maintenance
space space

Installation Size Diagram

D Amplification
1:5

Base U-bar of Frequency Inverter


120mm
5mm

±0.00mm
D
±0.00mm Embedded foundation U-bar

800mm

300 Cement concrete (for reference) or


interrupted weight and area of thrust surface
are constructed according to national standards

19
ATV 1200: Standard Wiring Diagram
Standard wiring diagram of ATV1200 6 kV input/6 kV output or 10 kV input/10 kV output

a SIG2A
6/10 KV

b SIG2A
6/10 KV
c SIG2A
6/10 KV
ECT_SYM BOL
ECT_D ESC

Site transformer
QF1

High-voltage DCS Variable- Local/ High-voltage switchgear


switchgear Heavy Light frequency remote Drive is Allow
failure failure Running control Ready switching on Failure trip
SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B

DPS
MCC
RC1

TC1
SC1

TC
RC

380 V 220 V
L3
L2
L1

Power supply Control


ATV1200 of cooling fan power supply
W
U
V

SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B

Encoder
interface

SIG5B SIG5B SIG5B SIG5B


W
U
V

Emergency External external


4-20 mA 4-20 mA 4-20 mA Start Stop Standby Switching on
ECT_SYM BOL
U stop heavy light feedback
failure failure
ECT_D ESC

B C Current Speed Speed High-voltage


A
feedback feedback setpoint DCS switchgear
M

6/10 KV
Wiring diagram of ATV1200 10 kV input/6 KV output with star-delta switching cabinet

a SIG2A
10 KV
b SIG2A
10 KV
c SIG2A
10 KV
ECT_SYM BOL
ECT_D ESC

High-voltage
Site transformer

switchgear
QF1

DCS Variable- Local/ High-voltage switchgear


Heavy Light frequency remote Drive is Allow
failure failure Running control Ready switching on Failure trip

UPS
SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B

QS1 MCC
TC1
SC1
RC1

RC

TC

R S T
star-delta switching cabinet

380 V 220 V
L2

L3
L1

Power supply Control


ATV1200_6 KV of cooling fan power supply
W
V
U

SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B SIG5B

QS2 Encoder
interface

SIG5B SIG5B SIG5B SIG5B


W
V
U

Emergency External external Standby Switching on


ECT_SYM BOL

B
ECT_D ESC
U
C
4-20 mA 4-20 mA 4-20 mA Start Stop
stop heavy light feedback
A Current Speed Speed failure failure High-voltage
feedback feedback setpoint DCS switchgear
QS3 ECT_SYM BOL
ECT_D ESC
10 KV M

X Y Z

ECT_SYM BOL
ECT_D ESC

20
ATV 1200: Definition of Typical I/O
Interface
Logic Input Function (6 logic input. Expandable)
Start instruction Voltage free contact, effective in case of 2s pulse closing, the drive starts running.
Stop instruction Voltage free contact, effective in case of 2s pulse closing, the drive stops normally (stop pulse has higher priority ).
Emergency stop Normal close contact, can be used as emergency stop signal, the drive will inhibit the pulse and stop automatically
when receiving this signal. (in case DCS remote emergency stop is required)
External light failure Alarm signal from DCS to the drive, the drive will stop according to the deceleration ramp. (in case the DCS system
has light failure).
External heavy failure Fault signal from DCS to drive, the drive will immediately inhibit the pulse output and simultaneously trip the
upstream high-voltage circuit breaker.. (in case the DCS system has heavy failure)
Feedback signal of high- When the high-voltage switch is in off status, the auxiliary contact closes:
voltage switching on
Status signal of input Close after switching on
breaker

Logic Output Function (8 logic output . Expandable)


Drive Ready Self diagnosis passed, Ready for start
Drive Running Drive is running.
Control Source of drive Open:Local control;
Close:Remote control
Drive has light fault Drive has alarm l, including cabinet door open, - transformer overtemperature, power down of control power
supply, broken of set signal, power unit (overheat, over-voltage, under-voltage, phase loss, trigger fault, high envi-
ronment temperature) and other information
Drive has heavy fault Drive has heavy fault,which shall immediately switch off the output and cut off the high voltage. including over-
current, optical fiber fault, serious overheat of transformer.
Standby Defined by users
High-voltage failure In case of drive failure,, it can be used to automatically trip high-voltage switch,. NO contact..
tripping
All the above-mentioned digital values are output by means of voltage free contacts and are defined as valid when the contacts are closed. Un-
less otherwise stated, the contact capacities are AC220 V/3 and DC24V/1A.

Analog Input Function (4 analog input . Expandable)


Speed setpoint
Standby Four circuits of 4-20mA current source input, which can be self-defined according to different requirements of
Standby users, so as to meet the demand of users in multiple aspects, and three circuits are standby
Standby

Analog output Funtion (2 analog output . Expandable)


Output frequency Two circuits of 4-20mA current sources outputs (power supplied by drive), the load capacity : 500Ω.
Output current Signal scale adjustable

21
Make the most
of your energy
Setting and Support Services Benefit
From Group Internationalization

We apply our own industrialization capability in


the service filed, thus to guarantee your success.

Professional Competency of Schneider


Electric
Our service expert can help you at any time:
p Get maximum pay back from the investment
p Optimize the values in the whole service life of the facilities

Relevant Services with Wide Contents


p Audit and consultation:
-C onsultation of line power supply (compensation, filtering,
harmonic ect.)
- Research of axis line (torque force analysis etc.)
- Energy efficiency, aims to determine optimum solutions for drive

p Customized project management

p C
 arry out factory test at maximum power with or without
motor

p Installation and start, including:


- Assistance and failure check
- Special maintenance contract (may include remote visit and
re-adjustment)

p Customized training

p Provide rapid and flexible service

23
Make Your Life More Convenient Based
on Integrated Solutions
ATV1200 solution
ATV1200 is open to most power grids and can be integrated into is based on
any high-voltage or low-voltage system structures. a combination of
transformer, drive
Relying on ATV1200, Schneider Electric creates comprehensive, and mediate-voltage
safe and consistent product for the following aspects: motor. Schneider
• Control and power supply of the equipment Electric can provide
• Improve energy a Turnkey solution
including the drive and
relevant equipment
As a world leading enterprise providing power distribution and
(power distribution
control system, Schneider Electric provides a series of products,
and control system)
solutions and services in terms of the following aspects: If you want to know
• Energy conversion and classification more information,
• Perform automatic control and power supply for the please contact our
machinery and process in complete safe conditions local office.
• Guarantee safe equipment operation

Contents of Global Solutions of


Schneider Electric

Electricity management
a monitoring

Transformer
substation

GIS distributor High-voltage/ AIS 12


HV power transformer HV distributor

HV motor and Drive AIS HV Distributor High voltage/


Control of HV
HV transformer
motor starter

Secondary substation

Low-voltage Low-voltage motor control LV frequency


distribution box distribution board converter

24
Guarantee reliability of Facilities Based
on Simply Open-type System Structure
• Innovated control system is based on the Easy for
latest generation of 32 bit processor. programming and
diagnosis
• Seamlessly integrated into the control The drive has
advanced parameters
system structure.
setting and diagnosis
functions.
• Easily realized advanced control Through key value
functions: signals (real-time
- Simple sensorless vector control current and voltage
- L
 ocal (through terminal or PC) and etc.), it can visit the
remote diagnosis and maintenance equipment status.

Operator station
Ethernet
Information
Server

Fieldbus
Control

PLCs

Equipment

ATV 1200
ATV 1200

HV drive
HV distributor

25
Green Your Power

+
ATV1200: Inquiry List of HV Drive
Filling description:
1. Blank parameters shall be manually filled.
2. C ontents with “p” marks are information that must be filled, and for parts with no mark, please fill as far as possible, if not filled, it will be treated
according to standard configuration.
3. The optional configuration will increase the costs greatly, if selected, please describe the reasons in the remarks column.

询价人信息
Name Inquiry Date Business Division Subsidiary District
Allocation
Parameter Name Parameter Values Remarks
p Name of purchaser
p Name of user
p Transport place
v Power; v Steel iron; v Other metallurgy; v Mining industry;
p Subsidiary industry v Cement; v Petrifaction; v Municipal; v Paper;
Others:
v Fan; v Pump; v Compressor; v Belt conveyor; v Mill;
p Load type
Others: (For special demand, please indicate)
p Altitude m, standard configuration (within 1000m). Customized design for 1000 m – 4500 m.

v 3KV; v 3.3 KV�; v 6 KV�����;���� v 6.6 KV�����;���� v 10 KV ;�


p Power grid voltage
Others:
Project Quantity* Motor Power* Motor Motor fre- Motor Motor
type Voltage* quency* speed* current
1 kW kV Hz rmp A
p Motor parameters 2 kW kV Hz rmp A
3 kW kV Hz rmp A

Description: the motor parameters play decisive effect to the costs, and please do guarantee the
authenticity of motor parameters.
p Bypass program v None; v Single motor with manual bypass cabinets;
p Delivery time week (calculate from order placing) or specific date
Standard configuration: 12 months after commissioning or 18 months after delivery, the first arrived shall
p Warranty period
prevail. Special demand:

Rated current of isolation v Standard configuration;630 A/20 KA


switch/4 s thermal stable v 1000 A/31.5 KA optional;������������������ v 1250 A/40 KA optional;
current Others: (Please mark out for special demand)
Description: if bypass control is needed, please select this option.
Control power supply v Standard configuration:Single circuit AC220 V-5 A������������������ v AC/DC 220 V-5 A optional.
Power supply (for fans etc) v standard configuration Customer provide AC380 V three-phase with neutral;������������������ v Not available.
UPS v On-line 1 KVA, Optional����������������
Communication protocol v standard configuration Modbus;������������������ v Profibus optional.
Digital Digital input, six circuits for standard configuration; extension� (Please mark out for special demand)
input/output Digital output, eight circuits for standard configuration; extension� (Please mark out for special demand)
Analog Analog input, four circuits for standard configuration; extension� (Please mark out for special demand)
input/output Analog output, two circuits for standard configuration; extension� (Please mark out for special demand)
Indoor temperature* Minimum:�� °C Minimum:�
��������� °C
Outdoor temperature Minimum:�� °C Minimum:�
��������� °C
Protection level v IP31 standard configuration����������������������������� v IP42 Optional.
v Back/front standard configuration;��������������������������� v Only the front is optional;
Optional configuration�� v Cabinet heater;���������������������� v Other options;
Color RAL7032 (lacte) standard configuration; Other: �� (Please mark out for special demand)
Overload capability v 120%/1 min standard configuration;���������������������� v 150%/1 min optional.
(Please mark out for special demand)
Other parameters
Description: for example, over-load requirement, special function, and non-standard parameters.

27
Remarks

28
Schneider Electric (China) Co., Ltd.

Schneider Electric (China) Schneider Building,No.6 Wangjing East Road, Chaoyang District, Beijing, P.R.C Postcode: 100102 Phone: (010) 84346699 Fax: (010) 84501130
Co., Ltd.
■ Shanghai Branch Office Building5-14, Changfeng International Building, No.89 East Yunling Road, Putuo Postcode: 200062 Phone: (021) 60656699 Fax: (021) 60656688
District, Shanghai City,
■ Zhangjiang Office No.9 Building, No.3000 Longdong Street, Shanghai City Postcode: 201213 Phone: (021) 61598888
■ Guangzhou Branch Floor 25, Development Center Building, No.3 Linjiang Street, New Zhujiang City, Postcode: 510623 Phone: (020) 85185188 Fax: (020) 85185195
Office Guangzhou City
■ Wuhan Branch Office Units 01, 02, 03 and 05, Floor 37, Building I, New World International Trade Buil- Postcode: 430022 Phone: (027) 68850668 Fax: (027) 68850488
ding, No.568 Jinshe Street, Hankou, Wuhan City
■ Tianjin Office Room 2205-07, Floor 22 Tianxin Building, No.125 Weidi Street, Hexi District, Postcode: 300074 Phone: (022) 28408408 Fax: (022) 28408410
Tianjin City
■ Tianjin Branch Office Room 1401-1404, Bandung Pacific Mansion, No.78 11 JingRoad, Hedong District, Postcode: 300171 Phone: (022) 84180888 Fax: (022) 84180222
Tianjin City
■ Jinan Office Floor 31, Qilu Bank Building, No.176 Shunhe Street, Jinan City Postcode: 250001 Phone: (0531) 81678100 Fax: (0531) 86121628
■ Qingdao Office Room 413, NO.2 Qingdao Fortune Center, No.18 Qinling Road, Laoshan District, Postcode: 266061 Phone: (0532) 85793001 Fax: (0532) 85793002
Qingdao City
■ Shijiazhuang Office Room 1201, Floor 12, Office Building, World Trade Plaza Hotel, No.303 Shandong Postcode: 050011 Phone: (0311) 86698713 Fax: (0311) 86698723
Road, Shizhong District, Shijiazhuang City
■ Shenyang Office Huaxin International Building, Stands F/G/H/I, No.219 Qingnian Street, Shenhe Postcode: 110016 Phone: (024) 23964339 Fax: (024) 23964296/97
District
■ Ha’erbin Office Stand J, Floor 21, Aoweisi Development Building, No.15, Hongjun Street, Nangang Postcode: 150001 Phone: (0451) 53009797 Fax: (0451) 53009640
District, Ha’erbin City
■ Changchun Office Room 1211-12, Changchun Guangda Bank Building, No.2677 Jiefang Road, Postcode: 130061 Phone: (0431) 88400302/03 Fax: (0431) 88400301
Changchun City
■ Dalian Office Room 201-I, No.17 Building, No.267 Wuyi Road, Shahekou District, Dalian Postcode: 116023 Phone: (0411) 84769100 Fax: (0411) 84769511
■ Xi’an Office Room 201 Xiyuege, No.72 No.2 Keji Road, High-tech Zone, Xi’an City, Shanxi Postcode: 710075 Phone: (029) 65692599 Fax: (029) 65692555
Province, China
■ Taiyuan Office Room 1003, B Area, Lihong Building, No.268, Fuxi Street, Taiyuan City Postcode: 030002 Phone: (0351) 4937186 Fax: (0351) 4937029
■ Urumchi Office Room 2521, Mirage Hotel, No.5 North Xinhua Road, Urumchi Postcode: 830002 Phone: (0991) 2825888 ext. 2521 Fax: (0991) 2848188
■ Nanjing Office Room 2001-2005, Huijie Plaza, No.268 Zhongshan Road, Nanjing City Postcode: 210008 Phone: (025) 83198399 Fax: (025) 83198321
■ Suzhou Office Room 1711-1712, International Building, No.2 Suhua Road, Industrial Park, Suzhou Postcode: 215021 Phone: (0512) 68622550 Fax: (0512) 68622620
City
■ Wuxi Office Floor 17, Wuxi Comprehensive Industrial and Commercial Building, No.28 Yonghe Postcode: 214021 Phone: (0510) 81009780 Fax: (0510) 81009760
Road, Taihu Plaza, Wuxi City
■ Nantong Office Room 1103, Stand A Huachen Building, No.111 Gongnong Road, Nantong City, Postcode: 226000 Phone: (0513) 85228138 Fax: (0513) 85228134
Jiangsu Province
■ Changzhou Office Room 1216, Changzhou Chunting Hotel, No.2 Juqian Street, Changzhou City Postcode: 213000 Phone: (0519) 8130710 Fax: (0519) 8130711
■ Hefei Office Room 913, Holiday Inn, No.1104 East Changjiang Road, Hefei City Postcode: 230001 Phone: (0551) 4291993 Fax: (0551) 2206956
■ Hangzhou Office Floor 10, Hengxin Building, No.588 Jiangnan Street, Binjiang District, Hangzhou Postcode: 310053 Phone: (0571) 89825800 Fax: (0571) 85825801
City
■ Nanchang Office Room 1001-1002, AVIC International Plaza, No.1 North Ganjiang Street, Honggu Postcode: 330043 Phone: (0791) 2075750 Fax: (0791) 2075751
Beach, Nanchang City, Jiangxi Rrovince
■ Fuzhou Office Unit 101, Building 29, Phase II of River Hot Spring Residential District, No.169, Postcode: 350000 Phone: (0591) 87114853 Fax: (0591) 87112046
Minjiang Street, Jinaxin Town, Cangshan District, Fuzhou City
■ Luoyang Office Room 609, Huayang Plaza International Hotel, No.88 West Kaixuan Road, Jianxi Postcode: 471003 Phone: (0379) 65588678 Fax: (0379) 65588679
District, Luoyang City
■ Xiamen Office Room 2502—03B, Bank Center, No.189 Xiahe Road, Siming District, Xiamen City Postcode: 361003 Phone: (0592) 2386700 Fax: (0592) 2386701
■ Ningbo Office Room 833, CITIC International Hotel, No.1 North Jiangdong Road, Ningbo City Postcode: 315040 Phone: (0574) 87706808 Fax: (0574) 87717043
■ Wenzhou Office No.B2, Floor 9, Gaolian Office Building, Station Street, Wenzhou City Postcode: 325000 Phone: (0577) 86072225/6/7/9 Fax: (0577) 86072228
■ Chengdu Office Units 1, 2, 3 and 5, Floor 22, Lippo Tower, No.62 North Kehua Road, Chengdu City Postcode: 610041 Phone: (028) 66853777 Fax: (028) 66853778
■ Chongqing Office Room 1211-12, Chongqing Metropolitan Plaza, No.68 Zhourong Road, Yuzhong Postcode: 400010 Phone: (023) 63839700 Fax: (023) 63839707
District, Chongqing City
■ Foshan Office Room 2622-2623, Floor 26, Baihua Plaza, No.33 Zumiao Road, Foshan City Postcode: 528000 Phone: (0757) 83990312/0029/1312 Fax: (0757) 83991312
■ Kunming Office Units 07-08, Floor 10, Brillian Plaza, No.6 Sanshi Street, Kunming City Postcode: 650021 Phone: (0871) 3647549 Fax: (0871) 3647552
■ Changsha Office Rooms 01, 10, 11, Floor 14, Hunan Jiacheng Hotel, No.215, West Laodong Road, Postcode: 410011 Phone: (0731) 85112588 Fax: (0731) 85159730
Changsha City
■ Zhengzhou Office Floor 2, West Wing of Stand C, Zhongzhou Crown Plaza Hotel, No.115 Jinshui Road, Postcode: 450003 Phone: (0371) 6593 9211 Fax: (0371) 6593 9213
Zhengzhou City
■ Taizhou Office Room 8512, Xinyongtai Hotel, No.39 South Qingnian Road, Taizhou City, Jiangsu Postcode: 225300 Phone: (0523) 86397849 Fax: (0523) 86397847
Province
■ Zhongshan Office Room 1103, Stand 3 Zhonghuan Plaza, No.1 Xingzheng Road, East District, Postcode: 528403 Phone: (0760) 8235971 Fax: (0760) 8235979
Zhongshan City
■ Anshan Office Room 2009, Vanke Office Building, No.21 South Shengli Road, Tiedong District, Postcode: 114001 Phone: (0412) 5575511/5522 Fax: (0412) 5573311
Anshan City
■ Yantai Office Room 2516, Jindu Building, No.9 South Street, Yantai City Postcode: 264001 Phone: (0535) 3393899 Fax: (0535) 3393998
■ Yangzhou Office Room 2018, Yangzhong Hotel, No.52 North Qianjin Road, Yangzhong City Postcode: 212000 Phone: (0511) 88398528 Fax: (0511) 88398538
■ Nanjing Office Floor 10, Guangxi Development Building, No.111 Minzu Street, Qingxiu District, Postcode: 530000 Phone: (0771) 5519761/9762 Fax: (0771) 5519760
Nanning City
■ Dongguan Office Unit A406, Hongxi Center, No.2 Sport Road, Nancheng District, Dongguan City Postcode: 523070 Phone: (0769) 22413010 Fax: (0769) 22413160
■ Shenzhen Office Room H-I, Shenzhen Development Bank Building, No.5047 East Shennan Road, Postcode: 518001 Phone: (0755) 25841022 Fax: (0755) 82080250
Luohu District, Shenzhen City
■ Guiyang Office Room 1204, Guihang Building, No.49 South Zhonghua Road, Guiyang City Postcode: 550003 Phone: (0851) 5887006 Fax: (0851) 5887009
■ Haikou Office Room 607, Floor 6, Hainan Wenhua Hotel, No.18 Wenhua Road, Haikou City, Postcode: 570305 Phone: (0898) 6859 7287 Fax: (0898) 6859 7295
Hainan Province
■ Schneider Electric East Wing, Floor 13 TaiKoo Place Heyu Building, No.979 King’s Road, Quarry Bay, Phone: (00852) 25650621 Fax: (00852) 28111029
(Hongkong) Co., Ltd. Hongkang
■ S
 chneider Learning Schneider Building, No,6 East Wangjing Road, Chaoyang District, Beijing City Postcode: 100102 Phone: (010) 84346699 Fax: (010) 84501130
Institute China
The Copyright belongs to Schneider Electric China

Hot Line of Customer Care Center: 4008101315


Schneider Electric China Schneider Electric Building, No. 6, Schneider Electric Building, No. 6, Due to changes of standards and materials, only the features described
East WangJing Rd., Chaoyang East WangJing Rd., Chaoyang District in the text and figures in the data have been confirmed by our business
www.schneider-electric.cn department, can they have constraint to us.
District Beijing 100102 P.R.C.
Beijing 100102 P.R.C. Tel: (010) 8434 6699
The Manual is printed with ecological papers.
Tel: (010) 8434 6699 Fax: (010) 8450 1130
Fax: (010) 8450 1130

SCDOC 1688 2012.02