Professional Documents
Culture Documents
Bond of High-Strength Concrete Under
Bond of High-Strength Concrete Under
Bond of High-Strength Concrete Under
9, November, 545–557
An experimental investigation was conducted on high-strength concrete specimens to examine the bond strength
characteristics under monotonic loading. The range of compressive strengths tested was between 70 and 95 MPa.
The influences of load history, confining reinforcement, bar diameter, concrete strength, reinforcement spacing and
rate of pull out were investigated experimentally. The internal concrete strains close to the contact surface and also
the steel strain were measured. The test set-up, load application, instrumentation and measurement, and test
procedure were designed to measure strains and deformations. Several specimens with reinforcement bar diameters
of 20, 25 and 35 mm were tested. The test results revealed that the bond strength of high-strength concrete is higher
than the corresponding normal strength concrete. However, the bond behaviour of high-strength concrete is more
brittle in comparison with normal strength concrete. The concrete strains were measured around the steel reinforce-
ment. Concrete strain measurements are useful to identify the internal crack pattern and to predict possible failure
modes. The area under the curve of the bond stress–slip curve can define the bond energy. The bond energy is
related to ductility and can be used along with the bond strength in evaluating the bond behaviour of high-strength
concrete.
parameter on the bond behaviour under monotonic short-bonded length was used. Three concrete strain
loading was examined. gauges were used to measure the concrete strain at the
middle and edge of the specimen. In each testing series
a minimum of three specimens were fully instrumented
to measure steel and concrete strain gauges. The posi-
Test specimens
tion of the concrete strain gauges is shown schemati-
The test specimen represented the confined region of cally in Fig. 2 for a typical test specimen that was
a joint in high-strength concrete structures. The test considered in this investigation.
set-up, specimen size, number of specimens and testing
parameters were similar to that conducted on normal- Concrete mix design
8
strength concrete by Eligehausen et al. The reinforced The high-strength concrete mixture contained a nor-
high-strength concrete specimen was confined by extra mal Portland cement, type 10 in accordance with Cana-
9
reinforcement representing the joint reinforcement. The dian Standards Association CSA, and 10% of silica
confinement index is calculated as defined by the fume used on the basis of weight as detailed in Alavi-
9 10
Canadian Building Code CSA. Fard. The cement content ranged between 450 and
The confinement index for the tested specimen was 470 kg/m3 and a water : cement ratio of 0.29 was used.
greater than 2.5 without the contribution of the extra A non-chloride water-reducing agent, retarder and
steel confining reinforcement. Extra top and bottom superplasticiser were used in the mix. The target com-
10 mm stirrups were added to the specimens to ensure pressive strengths for the high-strength concrete speci-
good confinement of reinforcement. The dimensions of mens ranged between 70 and 95 MPa.
tested specimen were 250 mm in length, 15db (tested Local aggregates were used for the concrete mix
bar diameter) in width and 5db to 7db in thickness as design. The coarse aggregate was mostly crushed quart-
shown in Fig. 1. The bond length is located at the zite sandstone with a maximum nominal size of
middle of the specimen and the rest of the specimen is 20 mm. The fine aggregate was identical in composi-
de-bonded by the use of two small PVC pipes at the tion to the coarse aggregate with a minor percentage of
end of each specimen. The embedded length of rebar sandstone and shale. The tested specimens were cured
diameters of 25 and 35 mm in the high-strength con- for 28 days at the concrete laboratory, and then were
crete block were taken as 75 and 100 mm, respectively, transferred for the structural laboratory for testing.
as well as extra reinforcement provided with top and
bottom stirrups. These embedment lengths were short Steel reinforcement
enough to result in a fairly uniform bond stress when The reinforcing bars were steel conforming to Cana-
the rebar is pulled out, but not long enough to reduce dian Standard Association CSA-G40.20-M94. Two
the scatter usually observed in test results when a very samples of each bar size with diameter of 10, 25 and
Magazine of Concrete Research, 2004, 56, No. 9 547
548
MPa
M2 Confining Monotonic 2HNM-8-1 100 7.01 270.64 23.84 5.422 5.126 1.058
reinforcement in tension 2HNM-8-2 100 6.43 253.23 22.61 5.142 5.126 1.003
2HNM-8-3 100 17.54 272.54 24.34 5.536 5.126 1.080
2HNM-8-4 100 5.14 190.16 16.98 3.862 5.126 0.753
2HNM-8-1 73 8.71 168.79 29.14 6.716 5.025 1.337
2HNM-8-2 73 8.41 171.23 29.65 6.833 5.025 1.360
2HNM-8-3 73 8.48 168.23 29.14 6.628 5.126 1.293
2HNM-8-4 73 - - - - - -
Monotonic in 2HNM-8-1 73 6.83 193.84 33.45 7.709 5.025 1.534
compression 2HNM-8-2 73 3.23 185.54 32.05 7.386 5.025 1.470
. 2HNM-8-3 73 5.94 186.37 31.93 7.261 5.126 1.417
2HNM-8-4 73 2.32 115.29 19.91 4.528 5.126 0.883
M3 Rebar Monotonic in 3HNM-12-1 73 7.29 112.67 24.89 5.825 4.909 1.187
diameter tension 3HNM-12-2 73 6.84 143.55 24.84 5.537 5.283 1.048
3HNM-12-3 100 6.82 220.66 19.69 4.436 5.198 0.853
* ìt ¼ peak load/(ðdL); d ¼ rebar diameter; L ¼ bond length.
Magazine of Concrete Research, 2004, 56, No. 9
5·5db
Stirrups
120 mm
250 mm
250 mm
120 mm
Test bar (d 10 mm)
PVC pipe
Bond free length
5db–7db
3·5db
Fig. 3. Specimen during testing: (a) test set-up; (b) specimen close-up
a
Bond stress
c
b
e
Slip
0·6
A
C
0·4
1
0·2
B
0
0 0·2 0·4 0·6 0·8 1 1·2
Normalised displacement
1·2
1HNM-19-1 (fc′ 81·70 MPa pull-out)
1HNM-19-1A (fc′ 86·00 MPa pull-out)
1 1HNM-19-1B (fc′ 85·12 MPa pull-out)
1 1HNM-19-1C (fc′ 85·12 MPa pull-out)
Normalised bond stress
0·8 1A
1B
0·6
1C
0·4
0·2
0
0 0·2 0·4 0·6 0·8 1 1·2
Normalised displacement
the sudden drop of the stress level at the beginning of the result of the value of tested bond stress divided by
the descending section of the curve followed by the cube root of compression strength of concrete.
gradual decrease of stress. The slope of the curves in
the ascending section in case of the push-in was higher Concrete and steel strains
than that of the pull-out test. Hence, the total bond The steel strain and internal concrete strain for a
energy in compression is slightly higher than expected typical specimen with embedded bar diameter 35 mm
for the pull-out test. However, this difference is not is plotted in Figs 9 and 10. The specimen is tested
large enough to provide a distinct difference between under push-in load. The two strain gauges STC1 and
the two behaviours. STC2 are installed in the bond area and the strain
The average equivalent bond stress for experimental gauge STC3 is far from the bond area, as shown sche-
phase of this investigation is calculated as the result of matically in Fig. 2. There are differences between the
tension or compression force divided by contact surface magnitudes of concrete strain reading of STC1 and
area (bond area). The curves are normalised based on STC2 due to the location of the strain gauges and the
552 Magazine of Concrete Research, 2004, 56, No. 9
Bond of high-strength concrete under monotonic pull-out loading
1·2
1HNM-19-2A (fc′ 83·67 MPa push-in)
1HNM-19-2B (fc′ 83·67 MPa push-in)
1 1HNM-19-2C (fc′ 85·12 MPa push-in)
Normalised bond stress
0·8
2C
0·6
2B
0·4
2A
0·2
0
0 0·2 0·4 0·6 0·8 1 1·2
Normalised displacement
0 Confining reinforcement
1500 1000 500 0 500 1000 1500
Concrete strain: micro strain The influence of different confinement bar diameters
on local bond behaviour of deformed bars was investi-
Fig. 9. Concrete strains (gauges 1 and 2 at bond area and 3 gated in series M2 of Tables 2 and 5. The vertical and
at the edge) horizontal steel reinforcement shown in Fig.1 repre-
sents the extra confining reinforcement for tested speci-
men. The selected different vertical bar diameters were
250 ranged from 0.3 to 0.6 of the tested bar diameter. Table
5 presents the measured values of slip, load and bond
200 strength at maximum load. All of the tested concrete
Compression load: kN
0·6
1
4
0·4
f′c 85 MPa
0·2
0
0 0·2 0·4 0·6 0·8 1 1·2
Normalised displacement
25 and 35 mm diameter bars efficiently. In addition, the bar. The bond strength of the 20 mm diameter bar is
failure mode for specimens with extra confinement was greater than the tensile capacity of the bar cross-section
characterised by pulling out the bar from concrete area. Therefore, the bar is broken during testing and
rather than the sudden splitting behaviour for speci- this curve does not demonstrate the entire bond behav-
mens with no confinement. Therefore, high-strength iour. The ascending slope of the curve for a 20 mm
concrete needs extra steel to reach an adequate level of diameter bar is much steeper than for the 25 and
bond energy and ductility. The confinement reinforce- 35 mm diameter bars. Further comparison between the
ment of high-strength concrete is considered adequate, area under the curve shows that the area under the
when the diameter of the confinement bar is from 0.3 curve for the bar with a diameter of 35 mm is less than
to 0.6 of the tested bar. for the bar diameter of 25 mm. Hence, the experiment
results show that the bond resistance for the smaller
Bar diameter diameter is higher than that for the larger diameter bar.
The bond test results of the 20, 25 and 35 mm In general, the results of this series agree with the find-
8
diameter bars are shown in series M3 of Tables 2 and ings of Eligehausen et al. , using a similar test set-up for
5. The effect of varying bar diameter on the bond normal-strength concrete. However, the bond strength
strength is illustrated in Fig. 12. All curves in this values are different for each concrete strength level. The
figure are normalised with respect to maximum bond sudden drop of the stress level at the beginning of the
stress and maximum displacement of a 25 mm diameter descending section of the bond stress–displacement
1·2
Bar dia. 20 mm 3HNM-12-3 (Bar dia. 35 mm, f′c 87·45 MPa
0·8
0·6
Bar dia. 25 mm
0·4
Bar dia. 35 mm
0·2
0
0 0·2 0·4 0·6 0·8 1 1·2
Normalised displacement
curve is attributed to the characteristics of the high- comparison of the normalised bond stress–displace-
strength concrete. ment response for the three specimens tested under
different rates of loading for a tested bar diameter of
Bar spacing 35 mm. Although at the initial stage of loading there
The influence of different lateral bar spacing on local was a noticeable difference for the specimen with rate
bond behaviour was investigated in series M5 of Tables of loading of 1.51 mm/min the bond–displacement
3 and 6. The lateral bar spacing was taken as 3.5 db for curves were similar. The result indicated that the bond
all the tested specimens as shown in the plan view of strength is approximately the same under different rates
Fig. 1. However, this spacing was changed in four of loading for a tested bar of 35 mm as presented in
specimens during this investigation to examine the ef- series M6 of Table 6.
fect of the lateral spacing on the bond behaviour. Two
specimens were tested with bar diameter of 25 mm and
lateral spacing of 25 and 50 mm and the other two Concrete strength
specimens were tested with bar diameter of 35 mm and The influence of the concrete compressive strength
bar spacing of 35 and 70 mm. on the bond behaviour was investigated in series M4 of
In the case of bar diameter of 25 mm there was no Tables 3 and 6. In principle, the results of this series of
significant difference between the two in the ascending tests agree with the previous study for normal concrete
portion, while in the descending portion there was a 8
strengths of 30 and 55 MPa. The main difference be-
small difference. The bond strength for specimen with tween high-strength concrete and normal-strength con-
bar spacing of 25 mm was about 20% less than for a crete is the instantaneous drop of the curve at the
specimen with 50 mm bar spacing. beginning of the descending branch of the curves, as a
The test results for the specimen with bar diameter result of losing adhesion. This brittle behaviour is well
of 35 mm show that the increase in bar spacing had illustrated in series M4 of tests especially for concrete
more influence on the bond resistance of the initial part with higher strength. The results of all tests in this
of the bond stress–slip relationship than on the bond series confirmed the nonlinear brittle behaviour of the
strength. The bond strength is improved with the in- bond for high-strength concrete. In the case of high-
crease of lateral bar spacing. The result of observation strength concrete the capacity of bond strength is high-
and comparison between bond strength for this series er than the normal; however, the impact of the instanta-
of tests showed a possible difference of 20% in the neous drop in the bond stress for high-strength concrete
bond strength due to the lateral bar spacing. must be recognised. The bond strength is strongly de-
pendent on concrete strength and this parameter has a
Rate of loading direct effect on bond behaviour. A comparison of nor-
This section presents the experimental results from malised bond stress with regard to the maximum load
the testing of three specimens tested under different of specimen with compressive strength of 94.96 MPa to
displacement rates of 75, 1.51 and 0.0151 mm/min as other specimens, with different concrete strengths for a
shown in series M6 of Tables 3 and 6. Fig. 13 shows a 25 mm diameter bar is shown in Fig. 14.
1·2
Curve 1: Specimen 6HNM-6-1 with rate of loading 75·0000 mm/min & f′c 89·00 MPa
Curve 2: Specimen 6HNM-6-2 with rate of loading 0·0151 mm/min & f′c 78·00 MPa
Curve 3: Specimen 6HNM-6-3 with rate of loading 1·5100 mm/min & f′c 87·45 MPa
1
3 2 1
Normalised bond stress
0·8
0·6
0·4
0·2
0
0 0·2 0·4 0·6 0·8 1 1·2
Normalised displacement
0·2 2
0
0 0·2 0·4 0·6 0·8 1 1·2
Normalised displacement