5kVA OFF-GRID MPPT BASED SOLAR INVERTER

TECHNICAL SPECIFICATIONS
Nominal Inverter Capacity 5 kVA/4000W
Nominal Battery Voltage 96 V
Maximum Battery 10A±1A
Charging Current from
AC
PV Open Circuit Voltage <160V & 40A (5000Wp)
& Current (Maximum [Recommended Vmp=122V±1, PV Open circuit Voltage<160V]
Panel Capacity)
Overload 110% for 30 sec., 150% for 5 sec., 200% for 2 sec. (Three retries
before permanent shutdown and requires manual reset)
Input AC Voltage 120V AC-290V AC, Single Phase (Line, Neutral Earth)
Mains input frequency 45 to 55Hz
Inverter efficiency >=90% peak efficiency
THD <3%, with linear load
Load power factor 0.8
Inverter Output voltage 230V±2%,
Protections Battery Over Voltage, Battery Under voltage, Output Over load,
Output short circuit, Battery reverse polarity (optional),
PV Reverse polarity (Optional), AC mains Out of range,
Over Temperature.

Features True Sine wave DSP based Inverter design with MOSFET
Technology.
High Efficiency and accurate MPPT algorithm,
User friendly Display & Control,
AC mains auto Bypass,
Three stage Battery Charging through AC mains
Two stage Battery charging in Solarmode (MPPT based bulk
charging and float charging)
Rugged Construction and Quiet Operation with Fan forced
cooling.
Battery type supported Lead Acid Tubular, VRLA,
Circuit Breaker AC Mains Input with 16A (class C) Input MCB, Inverter Output
with 16A (class C) Output MCB
& Manual Bypass Switch
Operating Temperature -10° C to 50° C without derating
Unit Dimensions 590mm Depth X 630mm Height X 295mm Width
Enclosure Free standing with wheel arrangements
Weight 65kg
Metering& Display 16X2 LCD for AC Mains Input Voltage, Inverter Output Voltage,
Mains Charging Current, Solar Charging, Total Load on Inverter,
Overload, Temperature, System Tripped condition.
Audible Alarm Built-in buzzer operates on fault conditions
Cooling Fan Forced cooling
Protection Class IP-21
Finish Gray White with Saffron Red
Priority Charging Solar over AC mains
Sizing of PV Panel and For 100Ah--maximum charging current <15A (Panel
Battery Capacity 250WX4X2); 150Ah--maximum charging current <22 (Panel
250WX4X3); 200Ah--maximum charging current <40A (Panel
250WX4X5 set)

Note 1: For extended battery life full panel capacity should not be connected if minimum
20% load is not guaranteed during day time.

Note 2: No single load (inductive or motor load) should be connected more than 25% of the
rated capacity.

Remarks: PV Open circuit Voltage up should be maintained below 160V DC