Masonry section design:

Created on: 22/12/2022 7:54:50 PM

MASONRY UNIT COMPRESSIVE STRENGTH:


SABS 0164 - 1992 Part I - Tables 3a) & 3b)

Nominal strength = 14MPa.


Non-modular hollow grouted brick, aspect ratio of 0.9 with 70% solid material
Masonry unit embedded in a 10mm thick, Class II mortar.
Characteristic compressive strength, fk = 6.38MPa fk=6.38MPa
Grout strength should be at least 6.38MPa

CHECK MOMENT CAPACITY:


SABS 0164 - 1992 Part II - §7.2.4.2.1

Compression failure Tension failure


2.5MPa 2.5MPa

x : 85mm
x : 198mm

48kN
d : 395mm

z : 353mm
z : 296mm

21kN

Mr : 15kNm Mr : 7kNm

Use 2 x 5.6mm bars, fy =485MPa As=33mm²


Tension failure, Mr = 7.33kNm > Mu = 5kNm. OK

CHECK SHEAR CAPACITY:


SABS 0164 - 1992 Part II - §6.2.4.1.1 & §8.2.3

Shear resistance, Vr = 13.82kN > Vu = 8.35kN. OK

CHECK LOCAL BOND CAPACITY:


SABS 0164 - 1992 Part II - §6.2.7

Bond resistance exceeds bond stress, 1.07MPa > 0.6MPa. OK

CHECK LIMITING DIMENSIONS AND LATERAL STABILITY:


SABS 0164 - 1992 Part II - §7.2.3.3

Simply supported beams, limiting span to depth ratio = 20


Actual span to depth ratio = 5.57 < 20 OK
Span = 2000mm < 6000mm, beam is laterally stable. OK