Split Case Fire Pump Selection Criteria NFPA Limits


Pump Mo de l: 8x6 x14F-S Rat e d Flo w 1000 US gpm 140% He ad o f Rat e d He ad 308 psi
No m. Spe e d: 2 950 rpm Rat e d He ad 2 2 0 psi 6 5% He ad at 150% Flo w 143 psi
Marke t : List e d Fire Pump Imp. Dia 13.399 in Flo w at 150% 1500 US gpm
Appro val/List ing: FM/UL Po we r Re quire d at Dut y 194 hp He ad at 150% 196 psi
Rat e d Efficie ncy 6 6 .1 % Po we r Re q at 150% 2 31 hp
Fluid Wat e r Efficie ncy at 150% 7 4.1 %
T e mpe rat ure 85 ºF Max BHP 2 7 7 hp
Sp. Gravit y 1.000 Clo se d Valve He ad 2 42 psi

140% He ad o f Rat e d He ad 308PSI

Typical Performance Curve is shown. Fire Pumps are tested to ANSI/HI 14.6 acceptance grade 1U.
Rated Duty Point is guaranteed within the following tolerances: Flow 0% to + 10%, Head 0% to + 6%.
NO OTHER POINTS ARE GUARANTEED. PLEASE CONSULT FACTORY IF NEEDED.

Pe rfo rmance Curve Dat a


Flo w (US gpm) He ad (psi) Efficie ncy (%) Po we r Re quire d (hp) NPSHr (ft )
0 2 42 0 0 9
2 50 2 37 40.4 134 9
500 2 33 49 154 9
7 50 228 57 .5 17 4 9
1000 220 6 6 .1 194 9
1500 196 7 4.1 2 31 9.97
2 340 139 7 1.6 264 16 .8