EXAMINATION NO. 16

TECHNICAL EXAMINATION QUESTION SHEETS

CATEGORY Mechanical (HVAC)


GRADE Level - 1

CONTENTS :

1. Design <10points>
2. Installation (1) <10points>
3. Installation (2) <10points>

TIME SCHEDULE :

9:00 to 11:00

NOTE :
1. Check this Examination question sheets and confirm the category and grade
are proper for those which you are going to take.

2. This Examination question sheets consists of 07 sheets.


Confirm you have all the sheets.
Inform to Observer immediately when you do not have all the sheets.

3. Write your examinee's NO. onto this cover and all the answer sheets
at first.
If missing, it will be considered no answer written.

4 All the question sheets should be given back to the Observer after finish.

5 No examinees will be allowed to leave the examination centre before 30 min.


after starting of the examination.

EXAMINEE'S NO.

Date : 16 May 2015

1/13
L-1 No. 16/ 16 May 2015

Level - 1 Mechanical (HVAC)


No.
Compulsory Design

< Question 1 > ( 6 points )

Figures mentioned below shows flow-chart and psychrometric chart on cooling mode of air
conditioning. Please answer the following questions of (1) through (5).

Figure - 1 ② RA

OA ① ③ ④ SA

Cooling coil Fan

Figure - 2 20.0

11.0 ①
8.0

[Kcal/kg] ②

HL
13 20 33 [℃]
5 5

[ Calculation conditions to get capacity required ]


a. Air conditioned floor area is 400 m2, occupancy rate by people is 0.2 person/m2,
and OA volume required is 25 m3/hr.person. ( 14.7 cfm/person )
b. Indoor sensible cooling load is 23,000 kcal/hr ( 91,271.36 B.T.U./hr ) while air conditioned.
c. Specific heat under constant pressure of air is 0.24 kcal/kg.°C, density of air is 1.2 kg/m3
d. Ignore heat gain from fan and duct system.

(1) Please get OA volume ( m3/hr ) or ( cfm )

400 m2 x 0.2 P /m2 x 25 m3 /hr.P = 2,000 m3/hr

(2) Get SA volume ( m3/hr ) or ( cfm )

23,000 / [ 0.24 x 1.2 x ( 20 – 13 )] = 11,408 m3 /hr

Page 2 of 13
L-1 No. 16/ 16 May 2015

(3) Get enthalpy ( kcal/kg ) or ( B.T.U./kg ) at mixing point of OA and RA


( at point in Figure - 1 & 2 )

Enthalpy == ( 11.0 x ( SA - OA ) + 20.0 x OA ) / SA


= ( 11.0 x ( 11,408 - 2,000 ) + 20.0 x 2,000 ) / 11,408
= 12.58 kcal/kg

(4) Get OA cooling load ( kcal/hr ) or ( B.T.U./hr )

1.2 x OA x ( ① - ② )
= 1.2 x 2,000 x ( 20.0 - 11.0 ) = 21,600 kcal/hr

(5) Get cooling capacity required ( kcal/hr ) or ( B.T.U./hr )

1.2 x SA x ( ③ - ④ )
= 1.2 x 11,408 x ( 12.58 - 8.0 ) = 62,698 kcal/hr

Page 3 of 13
L-1 No. 16/16 May 2015

Level-1 Mechanical (HVAC)


No
Compulsory Design

<Question 2> (4 points)

30.0 m
WATER LEVEL 2.8 m

3.6 m
10.0 m 10.0 m PUMP CENTRELINE

1.0 m
PUMP
COOLING TOWER
60 m

50 m

PIPE SIZE = 100 mm dia.

15.0 m
CHILLER
20.0 m

Shown above is a simple cooling water system diagram consisting of a cooling tower
circulating pump, interconnecting pipework and accessories.

Given data : Cooling water flow rate 1,000 L / min


Friction rate 40 mmAq / m
Pressure loss for chiller 8 mAq
Pressure loss for cooling tower 1 mAq
Equivalent length of valves and fittings
Gate valve 1.4 m
Y-Strainer 1.5 m
Check valve 14.0 m
Flexible connection 0.5 m
Elbow 1.2 m

Q-1 What is the static head of pump suction side? ( 0.5 point )

<Answer> 3.6 m

Q-2 What is the static head of pump discharge side? ( 0.5 point )

<Answer> 3.6 m + 2.8 m = 6.4 m

Q-3 What is the actual head of pump ? ( 0.5 point )

<Answer> 6.4 - 3.6 = 2.8 m

Page 4 of 13
L-1 No. 16/16 May 2015

Q-4 Calculate the design pump head (mAq) using a factor of safety of 10%.
( 2.5 point )
<Answer>
Total
Equiv.
Equiv.
S/N Item Qty Lgth
Lgth
(m) (m)
a) Loss for Pipe, Valves, Fittings (1 point)
Straight pipe 195 195.0
Gate valve 4 1.4 5.6
Y-Strainer 1 1.5 1.5
Check valve 1 14.0 14.0
Flexible connection 4 0.5 2.0
Elbow 5 1.2 6.0

Total Equivalent Length, m = 224.1


Pipe friction rate, mmAq/m = 40.0
Total Friction Loss for Pipe, valves & ftg, mAq = 8.964

b) Loss for equipment (0.5 point)


Loss for Chiller, mAq = 8.00
Loss for cooling tower, mAq = 1.00
Total friction loss for equipment, mAq = 9.00

c) Total Friction Loss for equipment,pipe, valves & fittings, mAq (0.5
point) = 17.964
d) Actual Pump Head, mAq (0.5 point ) = 2.80

Total Pump Head, mAq = 20.764


Safety factor, 10% = 2.08

Design Pump Head, mAq = 22.84

Page 5 of 13
Level - 1 Mechanical (HVAC)
No.
Compulsory Installation 1

< Question 1 > (1.5 Point)


Install method of left figures are not correct, draw correct ones on right side.

1. pipe connectiom around water tank Answer

Sample)
2. pipe connectiom

3. duct connection to fan

4. duct connection to louver

Louver Louver
L-1 No. 16 / 16 May 2015

Level - 1 Mechanical (HVAC)


No.
Compulsory Installation 1

< Question 2 > (5 Point)


Air flow drawing of AHU is as below
Given pressure drop of each section
return air duct A-B 38 mmAq Pre Filter D 10 mmAq
Supply air duct G-H 20 mmAq Middle Filter E 25 mmAq
Air Plenum C 2 mmAq Cooling Coil F 15 mmAq

Question

1. Calculate static pressure on drain hole


(1 point)
Answer -(38+2+10+25+15 )= -90 mmAq

2. Draw condensation water level and dimension of height at 3 staus on trap drawing below
in case drain water is in trap already. (3 points)

Fan Stop Fan Start Runnung Fan Running and Drain Out

Pagge 7 of 13
L-1 No. 16 / 16 May 2015

Answer

Fan Stop Fan Start Runnung Fan Running and Drain Out

3. Calculate minimun height H of trap if h is not 65 mm (1 point)

Answer 90+45= 135 mm

Pagge 8 of 13
L-1 No. 16/16 May 2015

Level - 1 Mechanical (HVAC)


No.
Compulsory Installation 1

< Question 3 > < 3.5 points >

Choose the alphabets and put the answers in the Function columns below.

Valves Function

Y-strainer f

Isolation valves c

Flexible joints a

Regulating valve b

Motorized modulation valve d

Drain point e

Air Vent g

a- To isolate equipment vibration from chilled water pipe

b- To manually set the chilled water flowrate

c- To isolate the piping system for maintenance / replacement and operation

d- To control the chilled water flowrate during equipment start/stop

e- To drain off chilled water

f- To collect debris in the chilled water pipe from damaging the equipment
coil
g- To release air trapped in the pipework

Page 9 of 13
L-1 No. 16/16 May 2015

Level - 1 Mechanical (HVAC)Thermal storage tank


No.
Compulsory Installation - 2

<Question 1> (8 points)
a). Figures show a closed system in which recirculating water is not exposed to the atmosphere.
This system is always required as expansion tank to operation system pressure by allowing
the water to expand when the temperature rise.
Please complete the piping schematic in the figures for both the direct return piping system
and reverse return piping system. (4points)

[ Fig. 1 ] Direct Return Closed piping system

E.T

F.C.U

Heat Exchanger

Pump

[ Fig. 2 ] Reverse Return Closed piping system

E.T

F.C.U

Heat Exchanger

Pump

b). Please state one each of advantage and disadovantage of Reverse Return Piping System
as conposed to Direct Return Piping Systen. (4points)
[Answer colume]
1). Advantage (2points)

2). Disadvantage (2points)

Page 10 of 13
L-1 No. 16/16 May 2015

Page 11 of 13
L-1 No.16/16 May 2015

Level - 1 Mechanical (HVAC)Thermal storage tank


No.
Compulsory Installation - 2

<Question 1> (8 points)
a). Figures show a closed system in which recirculating water is not exposed to the atmosphere.
This system is always required as expansion tank to operation system pressure by allowing
the water to expand when the temperature rise.
Please complete the piping schematic in the figures for both the direct return piping system
and reverse return piping system. (4points)

[ Fig. 1 ] Direct Return Closed piping system

E.T

F.C.U

Heat Exchanger

Pump

[ Fig. 2 ] Reverse Return Closed piping system

E.T

F.C.U

Heat Exchanger

Pump

b). Please state one each of advantage and disadovantage of Reverse Return Piping System
as conposed to Direct Return Piping Systen. (4 points)
[Answer colume]
1). Advantage (2 point)
Reverse Return Piping System is easier for regulating the water flow rates.

The supply and return main pipe line carry the water in the same direction.

2). Disadvantage (2 point)


Piping cost is increased
more installation space required

Page 12 of 13
L-1 No. 16 / 16 May 2015

Level - 1 Mechanical (HVAC)


NO.
Compulsory Installation 2

< Question 2> (2 points )


During the constuction of open type expansion water tank, list down 4 important
points to check

Answer ;

a) level of the tank in relation to system.


b). type of construction (concrete, fiberglass, metal.)
c). safe access and maintenance space
d). ball valve and sensor requirement
e). inlet,outlet,drain provision
f). tank support details

Page 13 of 13