Professional Documents
Culture Documents
IDS816 Installer Manual
IDS816 Installer Manual
EP
IT
I NH
IDS
AL
EC
Y
URIT
S
IDS816
IDS816
Installer Guide to Wiring and
Keypad Programming
1. Contents
Figures
Figure 1: Connection Diagram without Tamper per Zone ..... 6
Figure 2: Tamper per Zone Connection ................................ 7
Figure 3: Zone Doubling Connection..................................... 8
Figure 4: Resistors used for Tamper per Zone or Zone ..........
Doubling ................................................................. 9
Figure 5: Programmable Output Configuration ..................... 9
Figure 6: Fire Detect Output Sequence .............................. 34
Tables
3
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
For correct operation the IDS816 must be used in conjunction with the
specified transformer/battery combination and appropriate peripheral
sensors and signalling devices.
DIG
EP
IT
I NH
IDS
AL
EC
Y
S
URIT
4
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
5
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
6
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
7
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
12K 4K7
Red Purple
7. Programmable Outputs
A relay board must be used when any device requiring a high current is
connected to a programmable output. The output circuitry of a
programmable output consists of a 12 volt source with a 56Ω series
resistor. Current sink is via a 1000Ω resistor to negative. The output
circuitry is shown in Figure 5.
Should the need arise to return the panel to factory default, utilise the
hardware reset switch (see Figure 1).
The panel can be defaulted by removing both battery and AC power
from the panel, and then reapplying the power while depressing the
reset switch. Factory default values will be restored to all locations
and all attached keypads I.D’s will be defaulted
10
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
1. Remove power to the keypad and the restore power while holding
down the [1] and [3] keys simultaneously for three seconds.
2. All the keypad LEDs will flash ON and OFF together. Wait for five
seconds and then press the [#] hash key to allocate a new I.D
to the defaulted keypad. Keypad I.Ds are allocated incrementally.
14. E ven t L o g
11
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
16.1 Introduction
The panel can be programmed via either a keypad or via the up/
download software. Programming the panel by means of a LED
keypad is explained below:
Zone 1 1
Zone 2 2
Zone 3 4
Zone 4 8
12
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
13
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
will flash. Press the [!] star key and a long beep will
confirm entry into program mode.
17.2 Programming Standard Locations
1. Ensure the panel is in program mode - the READY indicator will
be flashing.
2. Enter the [LOCATION NUMBER] of the program location that you
wish to view or change.
3. Press the [!] star key. The READY indicator will continue
flashing and the AWAY indicator will illuminate.
4. The zone LED’s will display the data stored in the program
location in binary format.
5. Enter the [NEW DATA] followed by the [!] star key. A long beep
will indicate a valid entry and the AWAY indicator will extinguish.
6. If you do not wish to change the data press the [#] key.
The READY indicator will continue flashing and the AWAY
indicator will extinguish
7. Repeat steps 2 - 5 untill all the necessary locations have been
programmed.
8. Press the [#] hash key to exit program mode.
9. The READY indicator will stop flashing and the panel will return to
the standby mode.
An Example
Location 40 on page 26 of this manual provides us with a good
example of a bitmapped location which will help explain the
programming method employed for such locations.
Location 40 allows the installer to select up to twelve trouble
conditions which can be displayed and reported. By default only AC
fail trouble and low battery trouble are enabled. If we enter program
mode and then view the contents of Location 40 we will note that the
[1] LED and [5] LED will be illuminated. All other zone LED indicators
will be extinguished. To enable the Comms Fail Trouble Display
(indicated by zone 2 LED) press the 2 key followed by the [!] star key.
A long beep will indicate a valid entry and the 2 zone LED indicator will
illuminate indicating the enabling of the Comms Fail Trouble Display.
Continue selection (or deselection) of the desired trouble conditions.
Once a final selection has been made enter the [!] star key again to
enter the selection. The AWAY indicator will extinguish and a long
beep will indicate acceptance of a valid data entry.
15
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
Value Action
0 Will reset all locations to the factory default values. All user
codes will also be defaulted: (Master User Code 1234.)
Will default the master user code to 1234 and also default the
1
master user code properties.
16
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
Table 5 (page 18) Provides a complete list of the different zone types
together with a description of their characteristics.
17
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
18
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
19
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
Tamper by Zone
Individual zones may be enabled for tamper by zone. See page 7
Figure 2, for connection details. This feature is not available if zone
doubling is enabled. (See Figure 3, page 8 and Location 38 page 24)
Cross Zoning
This feature is useful for reducing false alarms. Violating zones with
the cross zone property enabled will not immediately generate an
alarm. The Cross Zone Delay Timer is started. See Location 36.
Depending on the value programmed into location 37 (Cross Zone Trip
Count) the zone (or any other zone with cross zone option enabled)
must trip the number of times programmed into location 37 before an
alarm is generated. An alarm will also be generated should the zone
remain violated for the entire delay period.
Swinger Shutdown
During a single arm cycle if the number of alarm violations generated
by a swinger zone equals the shutdown count (Location 33) the control
panel will automatically bypass the that zone.The swinger shutdown
counter is reset either when the system is disarmed and re-armed or
automatically when the 24 hour self test report is generated. See
Sublocation 5 of Locations 109 and110 [Partition Setup]
Note: For the following locations a two digit hexadecimal code must
be programmed. To disable a reporting code a double zero
(00) must be entered.
The code transmitted when the zone is violated during an arm cycle or
if a panic or 24 Hour Zone is violated.
20
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
The zone restoral code is transmitted when the zone has returned to
the unviolated condition after triggering an alarm.
A zone bypass code will be reported when the panel is armed with a
zone bypassed.
The zone shut down code will be reported if the system is armed and a
zone is automatically bypassed as a result of multiple violations of that
zone.
Two digits must be programmed for each zone. The first digit
references the programmable output number e.g. output 1 to 5. The
second digit sets the output action. Refer to Table below for a list of
actions. Refer to Section 17.6.4 for a detailed description for
Programming Programmable Ouputs.
21
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
The zone loop response is the period of time for which the zone must
remain violated before a violation is registered. By default a Fixed
Zone Loop Response of 100ms is used. See option 4 of location 38.
LOCATION 35 Reserved
22
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
If the panel is armed and the total number of cross zone violations
reaches this count within the time period programmed into location 36,
an alarm condition will be registered. Program a value from [0] to [15].
A [0] will disable this location. Program zones as cross zones in Sub
Location 2 of locations [1 - 16]. A single cross zone violated
continuously for the time specified in Location 36 will also register an
alarm condition.
23
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
LE D ON / OFF Action
A user assi gned to any parti ti on may cancel the
ON *
si ren.
1
Only a user assi gned to the parti ti on that tri ggered
OFF
the si ren may cancel the si ren
ON Enables keypad trouble beep.
2
OFF * D i sables keypad trouble beep
ON Enables telephone li ne moni tori ng.
3
OFF * D i sables telephone li ne moni tori ng.
Reserved
4
Reserved
ON Enables keypad beep on communi cati on.
5
OFF * D i sables keypad beep on communi cati on.
ON * Enables keypad Fi re, Medi cal and Pani c keys .
6
OFF D i sables keypad Fi re, Medi cal and Pani c keys
Enables the di splay of bypassed and stay zones
ON *
when armed i n the stay mode.
7
D i sables the di splay of bypassed and stay zones
OFF
when armed i n the stay mode.
ON Enables the si ren delay.
8
OFF * D i sables the si ren delay.
Enables zone doubli ng (All expanded / keypads
ON
zones i gnored)
9
D i sables zone doubli ng (expansi on / keypad zones
OFF *
can be used to expand the system to si xteen zones.)
ON * Enable Box Tamper
10
OFF D i sable Box Tamper
ON * Enable Si ren Tamper
11
OFF D i sable Si ren Tamper
ON * Enable 485 D evi ce Tamper
12
OFF D i sable 485 D evi ce Tamper
ON Enable Si lent D edi cated Pani c Zone
13
OFF * D i sable Si lent D edi cated Pani c Zone
24
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
When the AC power fails, the panel will wait for this period of time
before reporting the mains failure. The same time period applies before
the restoral event is reported and logged.
This delay eliminates unnecessary reporting if the AC power is
removed for a short time period. Provided the back up battery is in
good condition, short AC power failures will not affect the functioning of
the alarm system.Select the appropriate value from the table above.
25
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
ON/
LE D Action
OFF
ON * Enable AC fail trouble display
1
OFF Disable AC fail trouble display
ON Enable Comms fail trouble display
2
OFF * Disable Comms fail trouble display
ON Enable phone line trouble display
3
OFF * Disable phone line trouble display
ON Enable siren tamper trouble display
4
OFF * Disable siren tamper trouble display
ON * Enable low battery detection trouble display
5
OFF Disable low battery detection trouble display
ON Enable clock loss trouble display
6
OFF * Disable clock loss trouble display
ON Enable engineer's reset trouble display
7
OFF * Disable engineers reset trouble display
ON Enable box tamper trouble display
8
OFF * Disable box tamper trouble display
ON Reserved
9
OFF * Reserved
ON Enable 485 device trouble display
10
OFF * Disable 485 device trouble display
ON Enable bus trouble display
11
OFF * Disable bus trouble display
ON Enable Aux. 12V trouble display
12
OFF * Disable Aux. 12V trouble display
The siren time out period is the period of time for which the siren will
sound after an audible alarm condition is registered. Select the
appropriate time period from the table above.
27
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
Note: Program this function individually per keypad. After this time
period if there is no keypad activity the backlighting will
extinguish.
28
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
29
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
LOCATION 61 RF Jamming RC
This reporting code will be reported when the RF PIR battery voltage
drops below 4V.
This reporting code will be reported when the RF PIR battery voltage
rises above 4V for 1 hour.
LOCATION 66 Reserved
LOCATION 67 Reserved
30
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
This reporting code will be reported when the supply voltage to the
Wired Expansion Module rises above 12V for 1 second.
There are five programmable outputs on the IDS816 alarm panel and a
further two programmable outputs on the Wired Zone Expander
module. When selecting outputs, programmable outputs on the
IDS816 alarm panel are addressed from ‘1’ to ‘5’. outputs on the Wired
Zone Expander are addressed as ‘6’ and ‘7’. Please refer to the table
below.
31
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
When the output action of an event is programmable there are 4
permitted output actions which can be selected. These are listed
below.
32
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
33
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
L o c. Function Output
95 Fire Sensor Power Programmable Output Disabled
96 Dual Reporting Programmable Output Disabled
Enter a two digit value of the current day of the month. Valid range 01 -
31.
34
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
Enter which day of the week Daylight Saving returns to standard time.
This location is used for setting the Daylight Saving offset. Enter the
number of minutes the clock will offset - Valid range 0 - 250.
35
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
36
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
The value programmed into this location will determine the duration of
time between Auto Tests.
LOCATION 113 Auto Test Time
Enter the time when the auto test will be reported. The format is
“hhmm” based on a 24 hour clock.
EXAMPLE:
If a value of [7] was programmed into location 112 and [1400] was
programmed into this location, the auto test would be sent weekly at
2:00pm.
37
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
Note: Entering [0] into this location will disable the dialler.
The value entered into location 116 selects the primary communicator
format. Select from the table above the value appropriate to the
required format. During communication the green LED on the PCB will
illuminate indicating that the panel has taken the telephone off- hook.
If programmed accordingly (see location 38), the keypad will beep
after receiving a handshake from the base station. This indicates a
successful transmission of data.
38
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
NOTES ON CONTACT I.D.
If the panel has been programmed to use the Contact I.D format it will
not be necessary to program individual reporting codes. All codes are
reported by default. Provision is made to disable the reporting of
certain groups of codes. See location 118 and 120. Table 11 contains
a list of standard (default) Contact I.D reporting codes.
Any event that relates to a specific zone, or to a specific user, will
have the relevant zone/user number attached to the end of the
Contact I.D reporting code.
39
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
Location 118 and 120 are used to either enable or disable the reporting
of groups of events via the communicator. This is especially useful
when using Contact I.D or SIA formats. Instead of having to individually
disable multiple locations it is possible to disable groups of reporting
codes. These locations are bitmapped.
40
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
LE D ON / OFF Action
ON Enable Close Reporting Code
1
OFF Disable Close Reporting Code
ON Enable Stay Close Reporting Code
2
OFF Disable Stay Close Reporting Code
ON Enable Open Reporting Code
3
OFF Disable Open Reporting Code
ON Enable Cancel Reporting Code
4
OFF Disable Cancel Reporting Code
ON * Enable Alarm Reporting Code
5
OFF Disable Alarm Reporting Code
ON Enable Restore Reporting Code
6
OFF Disable Restore Reporting Code
ON Enable Bypass Reporting Code
7
OFF Disable Bypass Reporting Code
ON Enable Force Reporting Code
8
OFF Disable Force Reporting Code
ON Enable Tamper Reporting Code
9
OFF Disable Tamper Reporting Code
ON Enable Tamper Restore Reporting Code
10
OFF Disable Tamper Restore Reporting Code
ON Enable Shutdown Reporting Code
11
OFF Disable Shutdown Reporting Code
ON Enable Shutdown Restore Reporting Code
12
OFF Disable Shutdown Restore Reporting Code
ON * Enable AC Fail Reporting Code
13
OFF Disable AC Fail Reporting Code
ON * Enable AC Restore Reporting Code
14
OFF Disable AC Restore Reporting Code
ON * Enable Low Battery Reporting Code
15
OFF Disable Low Battery Reporting Code
ON * Enable Battery Restore Reporting Code
16
OFF Disable Battery Restore Reporting Code
41
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
LE D ON / OFF Action
ON * Enable Test Report Reporting Code
1
OFF Disable Test Report Reporting Code
ON Enable Download Reporting Code
2
OFF Disable Download Reporting Code
ON * Enable Siren Fuse Trouble Reporting Code
3
OFF Disable Siren Fuse Trouble Reporting Code
ON * Enable Aux. 12V Trouble Reporting Code
4
OFF Disable Aux. 12V Trouble Reporting Code
ON Enable Keypad Fuse Trouble Reporting Code
5
OFF Disable Keypad Fuse Trouble Reporting Code
ON Enable 485 Device Tamper Reporting Code
6
OFF Disable 485 Device Tamper Reporting Code
ON Enable 485 Bus Tamper Reporting Code
7
OFF Disable 485 Bus Tamper Reporting Code
ON * Enable Box Tamper Reporting Code
8
OFF Disable Box Tamper Reporting Code
ON * Enable Dedicated Panic Reporting Code
9
OFF Disable Dedicated panic Reporting Code
ON Enable Phone Line Restoral Reporting Code
10
OFF Disable Phone Line Restoral Reporting Code
ON * Enable Duress Reporting Code
11
OFF Disable Duress Reporting Code
ON * Enable Keypad Panic Reporting Code
12
OFF Disable Keypad Panic Reporting Code
ON * Enable Keypad Fire Reporting Code
13
OFF Disable Keypad Fire Reporting Code
ON * Enable Keypad Medical Reporting Code
14
OFF Disable Keypad Medical Reporting Code
ON * Enable Keypad Lockout Reporting Code
15
OFF Disable Keypad Lockout Reporting Code
ON Enable Access Reporting Code
16
OFF Disable Access Reporting Code
42
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
Loc
Group Reporting Code / Disable 3
120
ON Enable RF Jamming
1
OFF Disable RF Jamming
ON Enable RF Jamming Restore
2
OFF Disable RF Jamming Restore
ON Enable RF Supervision Failure
3
OFF Disable RF Supervision Failure
ON Enable RF Passive Low Battery
4
OFF Disable RF Passive Low Battery
ON Enable RF Passive Battery Restore
5
OFF Disable RF Passive Battery Restore
ON Enable RF Receiver Low Battery
6
OFF Disable RF Receiver Low Battery
ON Enable RF Receiver Battery Restore
7
OFF Disable RF Receiver Battery Restore
ON Enable Wired Expansion Low Battery
8
OFF Disable Wires Expansion Low Battery
ON Enable Wired Expansion Battery Restore
9
OFF Disable Wired Expansion battery Restore
NOTES ON PROGRAMMING TELEPHONE NUMBERS:
For the telephone number locations a [0] value is used as a termination
digit. It is important therefore that any zeros (0) in the telephone
number itself be entered as a [10]. All hexadecimal values are entered
using the mode key.
Enter numbers consecutively with no other key presses between each
digit. [See Table 3 on page 13]
LE D ON / OFF Action
ON * Enable Fax Defeat
1
OFF Disable Fax Defeat
ON * Enable Manual Pickup
2
OFF Disable Manual Pickup
ON * Enable Auto Pickup
3
OFF Disable Auto Pickup
ON Enable Callback
4
OFF * Disable Callback
This location determines the number of rings before the panel picks up
the telephone line. In the event that the panel picks up the phone and
no valid download log on sequence is received by the panel, the call
will be terminated by the panel.
44
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
45
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
Quick Arm:
This option allows the user to arm the panel by holding down the [1]
key for two seconds until the keypad beeps.
Force Arm:
With this option enabled the panel will arm with violated zones e.g. an
open window. When the panel arms, any violated zone is bypassed. If
bypassed zones restore during the arm cycle, the zone is
automatically re-activated.
Engineer Reset:
If enabled this option prevents arming the panel after an alarm
condition has occured. The panel can only be armed after the engineer
has entered a valid installer code. A trouble condition will be displayed
on the keypad.
47
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
ON /
LE D Action
OFF
Enable Automatic Re-enabling of Shutdown Zones at the
ON
Time of the Dialer test.
1
Disable Automatic Re-enabling of Shutdown Zones at the
OFF *
Time of the Dialer test.
ON Enable Bypassing of Common Zones
2
OFF * Disable Bypassing of Common Zones
ON Enable Delay Before Communications
3
OFF * Disable Delay Before Communications
ON Enable Keypad Lockout
4
OFF * Disable Keypad Lockout
ON Enable User Phone Access
5
OFF * Disable User Phone Access
ON Enable Silent Keypad Panic
6
OFF * Disable Silent Keypad Panics
The exit delay will begin after the entry of a valid user code. During this
period it will be possible to violate entry/exit and follower zones without
causing an alarm condition thus allowing exit from the premises. elect
the appropriate exit delay period from the table above.
48
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
This entry delay begins after the violation of a primary entry/exit zone.
During this period it is permissible to violate follower zones without
causing an alarm condition provided that an entry/exit zone was
violated first. If a follower zone is violated without a prior entry/exit zone
violation, it will be treated as an instant zone. If an instant zone is
violated during this period an alarm condition will immediately be
registered. Select the appropriate value for the primary entry delay
from the table.
49
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
This sublocation stores the time that the partition will auto disarm. The
format of data entered into this location is “hhmm” based on a 24 hour
clock. For example: To auto-disarm at 11:35 am, enter 1135.
This location selects the delay period for the keypad buzzer warning
which is initiated before the panel autoarms. At the completion of the
Auto Arm Delay the panel will arm. A valid user code entered during
the delay period will cancel the autoarm.
Sublocation 14 Reserved
Sublocation 15 Reserved
51
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
S ub- Default
E ven t Output
Loc Action
21 Close Programmable Output 3 Set High
22 Stay Close Programmable Output Disabled
23 Open Programmable Output 3 S et L o w
24 Cancel Programmable Output Disabled
25 Alarm Restoral Programmable Output Disabled
26 Bypass Prorammable Output Disabled
27 Forced Arm Prorammable Output Disabled
28 Zone Tamper Prorammable Ouput Disabled
29 Zone Tamper Restoral Prorammable Output Disabled
30 Zone Shutdown Programmable Output Disabled
31 Zone Shutdown Restoral Prorammable Output Disabled
32 Keypad Panic Prorammable Output 1 Pulse High
33 Keypad Fire Prorammable Output Disabled
34 Keypad Medical Prorammable Output Disabled
35 Keypad Lockout Prorammable Output Disabled
36 Duress Programmable Output 1 Pulse High
37 Verifies Alarm Prorammabe Output Disabled
38 Burglary Prorammable Output 2 Pulse High
39 Panic Prorammable Output 1 Pulse High
40 Fire Prorammable Output Disabled
41 Tamper Zone Prorammable Output Disabled
52
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
S ub-
E ven t Output
Loc
42 Siren Programmable Output Disabled
43 Strobe Programmable Output Disabled
44 Chime Programmable Output Disabled
LE D Output
1 Panel - Prog Output 1
2 Panel - Prog Output 2
3 Panel - Prog Output 3
4 Panel - Prog Output 4
5 Panel - Prog Output 5
6 Wired Zone Expander - Programmable Output 1
7 Wired Zone Expander - Programmable Output 2
The IDS 816 provides for 32 user codes. These locations allow the
installer to configure the user code properties.
53
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
54
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
LE D User Option
1 Master user
2 Duress code
3 Arm to disarm code (maids code)
4 Global Arm / Disarm
Note: If the system is armed using the quick arm key the system
will report a close by user 35. If the system is armed by
means of a keyswitch or non-latching remote receiver
connected to an arm disarm zone the system will report a
close by user 34.
55
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
57
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
Location Keypad ID
400 Keypad "1"
401 Keypad "2"
402 Keypad "3"
403 Keypad "4"
404 Keypad "5"
405 Keypad "6"
406 Keypad "7"
407 Keypad "8"
ON /
LE D Action
OFF
The Keypad will timeout back to its default partition after it
ON * has been used to view another partition
1
The keypad will not timeout and will continue to show current
OFF
partition information
ON Keypad sleep mode enabled
2
OFF * Keypad sleep mode disabled
ON Enable Keypad Zone
3
OFF * Disable Keypad Zone
ON Enable Global Keypad Status
4
OFF * Disable Global Keypad Status
Value Action
10 Disable Reset Switch
Any other value Enable Reset Switch
59
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
Note: If RF Zone added to Zone number which is already used as a
Wired Zone the RF Zone will function in parallel with Wired
Zone. If the Wired Zone is unused terminate it with a 3k3
resistor.
60
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
61
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
63
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
64
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00
IDS816 INSTALLER MANUAL
65
IDS816 INSTALLER MANUAL NO. 700-283-02B ISSUED NOV 2004 VER 2.00