Oxygen PSA Plant Specifications Required for Papua New Guinea

Mt. Hagen Hospital

Mt Hagen, Western Higghland Provincve, Papua New Guinea.


Designated Hospital, PNG Phone: +675 541 1200 https://www.whhs.gov.pg/
Flow of Oxygen PSA Plant
Requested (Nm3/h) around 20 Nm3/h
PSA type: Containerized or Skid
Mounted Containerized
Require Booster Compressor? Yes, at a minimum output pressure of 150 Bar
If "yes" to booster compressor - At a minimal of 17 Nm3/h
Flow required (Nm3/h)
Located in highlands at at an elevation of 1,677m,
Altitude https://en.wikipedia.org/wiki/Mount_Hagen
Humidity averages 83% according to some reports.
https://www.timeanddate.com/weather/papua-new-
Relative Humidity guinea/mount-hagen/climate
Power Supply 3 Phase - Voltage
(V): 240/415 VAC
Power Supply – Frequency (Hz): 50
Require Voltage Stabilizer?1 Yes
Require soft-start / VFD
Package? Yes
Uninterrupted Power Supply
(UPS) for PLC and Alarms ? Yes
Backup Manifold required? High pressure cylinder filling manifold
Require connection to existing
piping network? No
Language for user manual,
operation/ maintenance
instructions English
Number of staff to be trained: 5
Location for training (virtual/in
person): In person
Training scope required Operation (Intro)
Safety / Testing Protocols
Cleaning/Maintenance (Intro)
Cleaning routines of the PSA plant considering the electrical
safety precautions
Cleaning routines for the filters, if applicable (i.e. reusable)
Testing of alarms
Testing of operating pressures
Testing of oxygen concentration

1
The voltage stabilizer is asked for quotation separately and may also be procured by the client locally. The
inability to supply the voltage stabilizer will not affect the evaluation of the offering.

1
Frequency of the recommended maintenance routines
Safety precautions on management of oxygen
Advanced maintenance tasks required that shall be carried out
by a third-party
Medical Oxygen as a therapeutic product will require training on
the elements of quality control and regulatory requirements.
Additional scope of training (if Additionally with respect to Good Manufacturing Practice
non-standard)2 (GMP).
Maintenance and Services
period (X years): 5 years standard
Warranty required, (years): 5 years standard
Any other Equipment supply Generator: diesel, 3phase 240/415VAC 50Hz with outdoor
required3 enclosure and included fuel tank, and no less than 100KW Prime.

Lae Hospital

Designated Hospital, PNG ANGAU Hospital, Lae, PNG


Flow of Oxygen PSA Plant around 20 Nm3/h
Requested (CM/h)
PSA type: Containerized or Containerized
Skid Mounted
Require Booster Compressor? Yes, at a minimum output pressure of 150 Bar
If "yes" to booster compressor At a minimal of 17 Nm3/h
- Flow required (CM/h)
Altitude about 20m above sea level
Relative Humidity No, humidity can reach 89-90% (coastal area, consider the
salinity conditions in selecting coating of equipment and filters)
Power Supply 3 Phase - 240/415 VAC
Voltage (V):
Power Supply – Frequency 50
(Hz):
Require Voltage Stabilizer? No
Require soft-start / VFD Yes
Package?
Uninterrupted Power Supply Yes
(UPS) for PLC and Alarms ?
Backup Manifold required? High pressure cylinder filling manifold
Require connection to existing No
piping network?
Language for user manual, English
operation/ maintenance
instructions

2
For the additional training scope, it is nice to cover but not compulsory
3
The diesel generator is asked for quotation separately and may also be procured by the client locally. The
inability to diesel generator will not affect the evaluation of the offering

2
Number of staff to be trained: 5
Location for training (virtual/in In person
person):
Training scope required Operation (Intro)
Safety / Testing Protocols
Cleaning/Maintenance (Intro)
Cleaning routines of the PSA plant considering the electrical
safety precautions
Cleaning routines for the filters, if applicable (i.e. reusable)
Testing of alarms
Testing of operating pressures
Testing of oxygen concentration
Frequency of the recommended maintenance routines
Safety precautions on management of oxygen
Advanced maintenance tasks required that shall be carried out by
a third-party
Additional scope of training (if Medical Oxygen as a therapeutic product will require training on
non-standard)4 the elements of quality control and regulatory requirements.
Additionally with respect to Good Manufacturing Practice (GMP).
Maintenance and Services 5 years standard
period (X years):
Warranty required (years): 5 years standard
Any other Equipment supply Generator: diesel, 3phase 240/415VAC 50Hz with outdoor
required5 enclosure and included fuel tank, and no less than 100KW Prime.

4
For the additional training scope, it is nice to cover but not compulsory
5
The diesel generator is asked for quotation separately and may also be procured by the client locally. The
inability to diesel generator will not affect the evaluation of the offering