Professional Documents
Culture Documents
Harmonics: Noor Mohamed.A
Harmonics: Noor Mohamed.A
Harmonics
Harmonic is an electric voltage or current that the cause the power quality problems. Due to high
harmonics the equipment or machines may malfunction to fail to operate. Major source for harmonics
is power electronic equipment like UPS, VFD, medical equipment, Arc furnace, Battery Chargers etc.,
When a sinusoidal waveform is deviated to other waveforms, then it contains a harmonic. It causes the
voltage deviations and creates distortion in the power system, which causes many problems by the loads
it contains of linear loads and non – linear loads.
Figure 1 Harmonics Injection
From the above figure, the fundamental frequency waveform is affected by the third, fifth and seventh
harmonic and it leads to non-sinusoidal waveform. From this point, the lower order harmonic is severe
than the higher order harmonic, because the magnitude of current is higher in the lower order harmonic
especially odd harmonic.
Why odd harmonic is higher than even?
When the even (second) harmonic is present in the system, the positive & negative cycle harmonic
current is compensated each other (considering the half cycle of fundamental current). So, impact of
even harmonics is almost neglected without using any filter and all. When the odd (third) harmonic is
present in the system, the one positive cycle & one negative cycle harmonic current compensate each
other. The balance one cycle of harmonic current will affect the system. In this case, the harmonic filter
is needed to compensate harmonic current component.
Figure 2 Waveform of odd harmonic Figure 3 Waveform of even harmonic
For power system studies consulting and corporate training requirements, reach out us – Contact us.
https://powerprojectsindia.com
NOOR MOHAMED.A
For power system studies consulting and corporate training requirements, reach out us – Contact us.
https://powerprojectsindia.com
NOOR MOHAMED.A
neglected by using small filters but eliminating of lower order harmonic is difficult one because it needs
higher capacity of filter. But cost wise the 6-pulse converter is economical compare to 12 pulse
converters (no. of switch requirement is high compare to 6 pulse converter and switching losses also
high). So mostly 6 pulse converters used in the application
Figure 5 Lower order harmonic by using 6-pulse converter
From the figure 5 & 6, the lower order harmonic in the 6-pulse converter is distorted the sine wave very
poorly compare to 12-pulse converter. Magnitude of particular harmonic in the system is decided by
the below formula,
Magnitude of harmonic= Fundamental / Harmonic order.
i.e. Magnitude of h5= 1/5=20%; Magnitude of h17= 1/17=5.88%
The above result also confirms, the lower order harmonic is more dominant compare to higher order
harmonic component in the system.
Sequence of harmonics
The above figure represents three sequence components. Those are
i. Positive sequence (R= 0o, Y= -120o, B= 120o)
ii. Negative sequence (R= 0o, Y= -240o, B= 240o)
iii. Zero sequence (R= 0o, Y= 0o, B= 0o)
The harmonic order is also represented by the sequence components. The below table explains how
each harmonic order represented in the sequence components.
For power system studies consulting and corporate training requirements, reach out us – Contact us.
https://powerprojectsindia.com
NOOR MOHAMED.A
For power system studies consulting and corporate training requirements, reach out us – Contact us.
https://powerprojectsindia.com