STRUCTURAL CALCULATION REPORT FOR


Two Storey Residential Row House
(Prefab)

DOCUMENT NAME:
Date: 11 April 2022

Rev Type Engineer Reviewed Approved Description

Page: 1 / 30
Doc. Name:
Residential Row House
Date:

REVISION LOG

REV DATE DESCRIPTION MAJOR REASON FOR CHANGE

Page: 2 / 30
Doc. Name:
Residential Row House
Date:

CONTENTS
1. General Information ........................................................................................... 4

2. Load Cases ....................................................................................................... 6

3. Lateral Load ..................................................................................................... 12

4. Steel Result ..................................................................................................... 16

5. Concrete Design Result ................................................................................... 30

Page: 3 / 30
Doc. Name:
Residential Row House
Date:

1. General Information
(1) Project Information : Ayala

(2) Structure Name : (1.0) Follow through with the correction of


(3) Site Location : project information
(4) Purpose of Building :

(5) Building Scale :

(6) Structure Type :

(1) Country Code : NSCP Standards

(2) National Annex : s. 2015

(3) Steel Design : AISC360M-10 (LRFD)

(4) Concrete : ACI 318M-14

(5) Loading

- Wind Load : ASCE7-10

- Seismic Load : UBC 1997

- Crane Load : NONE

(6) Reference Code

Cover thickness type: Clear Cover

Member Type Default Cover(m) Remark


Column 0.040
Beam 0.040
Wall 0.040
Slab 0.040
Plate 0.040
Brace 0.040
Flat Slab 0.040
Foundation 0.040
The Concrete Default Design Cover

Page: 4 / 30
Doc. Name:
Residential Row House
Date:
Yield Tensile Modulus of Weight Poisson's
Code Material Strength Strength Elasticity Density Ratio Remark
Fy(kN/m2) Fu(kN/m2) Es(kN/m2) ρ(kN/m3) α
ASTM A36 248211 399896 199948024 77.091 0.300
Steel Strengths By Steel Grades

Name Section Material Remark


1SC1 170x170x3.0 A36
1SC2 170x170x3.0 A36
2SC2 170x170x3.0 A36
Steel Column List

No information of Steel Sub Column List exists to print table.

Name Section Material Remark


2SG1 160x55x3 A36
2SG2 160x110x3 A36
RSG1 160x110x3 A36
RSG2 160x55x3 A36
Steel Beam List

No information of Steel Sub Beam List exists to print table.

(2) Provide summary tabulation of specification


as well for
a.) bolts, connectors, plates
b.)purlins,
c.) ALC panels to be used
d.) Wall footing, thickening slab details

Page: 5 / 30
Doc. Name:
Residential Row House
Date:

2. Load Cases

No. Combination Description Remark


1 LCB1_1 1.40D+1.00NX
2 LCB1_2 1.40D-1.00NX
3 LCB2_1 1.40D+1.00NY
8.) Specify
4 LCB2_2 1.40D-1.00NY
5 LCB3 1.40D Loading values
6 LCB4_1 1.20D+1.60L+1.00NX considered for DL
7 LCB4_4 1.20D+1.60L-1.00NX LL
8 LCB5_1 1.20D+1.60L+1.00NY
9 LCB5_4 1.20D+1.60L-1.00NY
10 LCB6 1.20D+1.60L
11 LCB13_1 1.20D+1.00L+1.00NX
12 LCB13_4 1.20D+1.00L-1.00NX
13 LCB14_1 1.20D+1.00L+1.00NY
14 LCB14_4 1.20D+1.00L-1.00NY
15 LCB15 1.20D+1.00L
16 LCB16_1 1.20D+0.50WX+1.00NX
17 LCB16_2 1.20D+0.50WX-1.00NX
18 LCB16_3 1.20D-0.50WX+1.00NX
19 LCB16_4 1.20D-0.50WX-1.00NX
20 LCB17_1 1.20D+0.50WY+1.00NY
21 LCB17_2 1.20D+0.50WY-1.00NY
22 LCB17_3 1.20D-0.50WY+1.00NY
23 LCB17_4 1.20D-0.50WY-1.00NY
24 LCB18_1 1.20D+1.00NX
25 LCB18_2 1.20D-1.00NX
26 LCB19_1 1.20D+1.00NY
27 LCB19_2 1.20D-1.00NY
28 LCB20 1.20D
1.20D+1.00L+1.00WX+
29 LCB35_1
1.00NX
1.20D+1.00L+1.00WX-
30 LCB35_4
1.00NX
1.20D+1.00L-
31 LCB35_5
1.00WX+1.00NX
1.20D+1.00L-1.00WX-
32 LCB35_8
1.00NX
1.20D+1.00L+1.00WY+
33 LCB38_1
1.00NY
1.20D+1.00L+1.00WY-
34 LCB38_4
1.00NY
1.20D+1.00L-
35 LCB38_5
1.00WY+1.00NY
1.20D+1.00L-1.00WY-
36 LCB38_8
1.00NY
1.20D+1.00L+1.00EQ+1
37 LCB55_1
.00NX

Page: 6 / 30
Doc. Name:
Residential Row House
Date:
1.20D+1.00L+1.00EQ-
38 LCB55_4
1.00NX
1.20D+1.00L-
39 LCB55_5
1.00EQ+1.00NX
1.20D+1.00L-1.00EQ-
40 LCB55_8
1.00NX
1.20D+1.00L+1.00EQ+1
41 LCB56_1
.00NY
1.20D+1.00L+1.00EQ-
42 LCB56_4
1.00NY
1.20D+1.00L-
43 LCB56_5
1.00EQ+1.00NY
1.20D+1.00L-1.00EQ-
44 LCB56_8
1.00NY
45 LCB57_1 1.20D+1.00L+1.00EQ
46 LCB57_2 1.20D+1.00L-1.00EQ
47 LCB66_1 0.90D+1.00WX+1.00NX
48 LCB66_2 0.90D+1.00WX-1.00NX
49 LCB66_3 0.90D-1.00WX+1.00NX
50 LCB66_4 0.90D-1.00WX-1.00NX
51 LCB67_1 0.90D+1.00WY+1.00NY
52 LCB67_2 0.90D+1.00WY-1.00NY
53 LCB67_3 0.90D-1.00WY+1.00NY
54 LCB67_4 0.90D-1.00WY-1.00NY
55 LCB68_1 0.90D+1.00NX
56 LCB68_2 0.90D-1.00NX
57 LCB69_1 0.90D+1.00NY
58 LCB69_2 0.90D-1.00NY
59 LCB70 0.90D
60 LCB76_1 0.90D+1.00EQ+1.00NX
61 LCB76_2 0.90D+1.00EQ-1.00NX
62 LCB76_3 0.90D-1.00EQ+1.00NX
63 LCB76_4 0.90D-1.00EQ-1.00NX
64 LCB77_1 0.90D+1.00EQ+1.00NY
65 LCB77_2 0.90D+1.00EQ-1.00NY
66 LCB77_3 0.90D-1.00EQ+1.00NY
67 LCB77_4 0.90D-1.00EQ-1.00NY
68 LCB78_1 0.90D+1.00EQ
69 LCB78_2 0.90D-1.00EQ
70 STL_EN_STR Steel Strength Envelope
Steel Load Combination for Strength

No. Combination Description Remark


1 svLCB1_1 1.00D+1.00NX
2 svLCB1_2 1.00D-1.00NX
3 svLCB2_1 1.00D+1.00NY
4 svLCB2_2 1.00D-1.00NY

Page: 7 / 30
Doc. Name:
Residential Row House
Date:
5 svLCB3 1.00D
6 svLCB4_1 1.00D+1.00L+1.00NX
7 svLCB4_4 1.00D+1.00L-1.00NX
8 svLCB5_1 1.00D+1.00L+1.00NY
9 svLCB5_4 1.00D+1.00L-1.00NY
10 svLCB6 1.00D+1.00L
11 svLCB7_1 1.00D+1.00NX
12 svLCB7_4 1.00D-1.00NX
13 svLCB8_1 1.00D+1.00NY
14 svLCB8_4 1.00D-1.00NY
15 svLCB16_1 1.00D+0.75L+1.00NX
16 svLCB16_4 1.00D+0.75L-1.00NX
17 svLCB17_1 1.00D+0.75L+1.00NY
18 svLCB17_4 1.00D+0.75L-1.00NY
19 svLCB18 1.00D+0.75L
20 svLCB25_1 1.00D+0.60WX+1.00NX
21 svLCB25_2 1.00D+0.60WX-1.00NX
22 svLCB25_3 1.00D-0.60WX+1.00NX
23 svLCB25_4 1.00D-0.60WX-1.00NX
24 svLCB26_1 1.00D+0.60WY+1.00NY
25 svLCB26_2 1.00D+0.60WY-1.00NY
26 svLCB26_3 1.00D-0.60WY+1.00NY
27 svLCB26_4 1.00D-0.60WY-1.00NY
28 svLCB35_1 1.00D+0.70EQ+1.00NX
29 svLCB35_2 1.00D+0.70EQ-1.00NX
30 svLCB35_3 1.00D-0.70EQ+1.00NX
31 svLCB35_4 1.00D-0.70EQ-1.00NX
32 svLCB36_1 1.00D+0.70EQ+1.00NY
33 svLCB36_2 1.00D+0.70EQ-1.00NY
34 svLCB36_3 1.00D-0.70EQ+1.00NY
35 svLCB36_4 1.00D-0.70EQ-1.00NY
36 svLCB37_1 1.00D+0.70EQ
37 svLCB37_2 1.00D-0.70EQ
1.00D+0.75L+0.45WX+
38 svLCB46_1
1.00NX
1.00D+0.75L+0.45WX-
39 svLCB46_4
1.00NX
1.00D+0.75L-
40 svLCB46_5
0.45WX+1.00NX
1.00D+0.75L-0.45WX-
41 svLCB46_8
1.00NX
1.00D+0.75L+0.45WY+
42 svLCB47_1
1.00NY
1.00D+0.75L+0.45WY-
43 svLCB47_4
1.00NY
1.00D+0.75L-
44 svLCB47_5
0.45WY+1.00NY
1.00D+0.75L-0.45WY-
45 svLCB47_8
1.00NY

Page: 8 / 30
Doc. Name:
Residential Row House
Date:
46 svLCB58_1 1.00D+0.75L+0.45WY
47 svLCB58_2 1.00D+0.75L-0.45WY
1.00D+0.75L+0.53EQ+1
48 svLCB67_1
.00NX
1.00D+0.75L+0.53EQ-
49 svLCB67_4
1.00NX
1.00D+0.75L-
50 svLCB67_5
0.53EQ+1.00NX
1.00D+0.75L-0.53EQ-
51 svLCB67_8
1.00NX
1.00D+0.75L+0.53EQ+1
52 svLCB68_1
.00NY
1.00D+0.75L+0.53EQ-
53 svLCB68_4
1.00NY
1.00D+0.75L-
54 svLCB68_5
0.53EQ+1.00NY
1.00D+0.75L-0.53EQ-
55 svLCB68_8
1.00NY
56 svLCB69_1 1.00D+0.75L+0.53EQ
57 svLCB69_2 1.00D+0.75L-0.53EQ
58 svLCB78_1 0.60D+0.60WX+1.00NX
59 svLCB78_2 0.60D+0.60WX-1.00NX
60 svLCB78_3 0.60D-0.60WX+1.00NX
61 svLCB78_4 0.60D-0.60WX-1.00NX
62 svLCB79_1 0.60D+0.60WY+1.00NY
63 svLCB79_2 0.60D+0.60WY-1.00NY
64 svLCB79_3 0.60D-0.60WY+1.00NY
65 svLCB79_4 0.60D-0.60WY-1.00NY
66 svLCB80_1 0.60D+1.00NX
67 svLCB80_2 0.60D-1.00NX
68 svLCB81_1 0.60D+1.00NY
69 svLCB81_2 0.60D-1.00NY
70 svLCB82 0.60D
71 svLCB88_1 0.60D+0.70EQ+1.00NX
72 svLCB88_2 0.60D+0.70EQ-1.00NX
73 svLCB88_3 0.60D-0.70EQ+1.00NX
74 svLCB88_4 0.60D-0.70EQ-1.00NX
75 svLCB89_1 0.60D+0.70EQ+1.00NY
76 svLCB89_2 0.60D+0.70EQ-1.00NY
77 svLCB89_3 0.60D-0.70EQ+1.00NY
78 svLCB89_4 0.60D-0.70EQ-1.00NY
79 svLCB90_1 0.60D+0.70EQ
80 svLCB90_2 0.60D-0.70EQ
81 ftLCB1_1 1.00L+1.00NX
82 ftLCB1_2 1.00L-1.00NX
83 ftLCB2_1 1.00L+1.00NY
84 ftLCB2_2 1.00L-1.00NY
85 ftLCB3 1.00L
86 STL_EN_SER Steel Serviceability

Page: 9 / 30
Doc. Name:
Residential Row House
Date:
Envelope
87 STL_EN_FATG Steel Fatigue Envelope
Steel Load Combination for Serviceability

No. Combination Description Remark


1 LCB1 1.40D
2 LCB2 1.20D+1.60L
3 LCB5 1.20D+1.00L
4 LCB6_1 1.20D+0.50WX
5 LCB6_2 1.20D-0.50WX
6 LCB7_1 1.20D+0.50WY
7 LCB7_2 1.20D-0.50WY
8 LCB8 1.20D
9 LCB17_1 1.20D+1.00L+1.00WX
10 LCB17_2 1.20D+1.00L-1.00WX
11 LCB20_1 1.20D+1.00L+1.00WY
12 LCB20_2 1.20D+1.00L-1.00WY
13 LCB29_1 1.20D+1.00L+1.00EQ
14 LCB29_2 1.20D+1.00L-1.00EQ
15 LCB34_1 0.90D+1.00WX
16 LCB34_2 0.90D-1.00WX
17 LCB35_1 0.90D+1.00WY
18 LCB35_2 0.90D-1.00WY
19 LCB36 0.90D
20 LCB40_1 0.90D+1.00EQ
21 LCB40_2 0.90D-1.00EQ
22 RC_EN_STR RC Strength Envelope
RC Load Combination for Strength

No. Combination Description Remark


1 svLCB1 1.00D
2 svLCB2 1.00D+1.00L
3 svLCB6 1.00D+0.75L
4 svLCB9_1 1.00D+0.60WX
5 svLCB9_2 1.00D-0.60WX
6 svLCB10_1 1.00D+0.60WY
7 svLCB10_2 1.00D-0.60WY
8 svLCB15_1 1.00D+0.70EQ
9 svLCB15_2 1.00D-0.70EQ
10 svLCB20_1 1.00D+0.75L+0.45WX
11 svLCB20_2 1.00D+0.75L-0.45WX

Page: 10 / 30
Doc. Name:
Residential Row House
Date:
12 svLCB23_1 1.00D+0.75L+0.45WY
13 svLCB23_2 1.00D+0.75L-0.45WY
14 svLCB38_1 1.00D+0.75L+0.53EQ
15 svLCB38_2 1.00D+0.75L-0.53EQ
16 svLCB53_1 0.60D+0.60WX
17 svLCB53_2 0.60D-0.60WX
18 svLCB54_1 0.60D+0.60WY
19 svLCB54_2 0.60D-0.60WY
20 svLCB55 0.60D
21 svLCB59_1 0.60D+0.70EQ
22 svLCB59_2 0.60D-0.70EQ
RC Serviceability
23 RC_EN_SER
Envelope
RC Load Combination for Serviceability

Page: 11 / 30
Doc. Name:
Residential Row House
Date:

3. Lateral Load

Wind Function Report: ASCE7-10(Building)-1

1. Basic Input Data

Design Code : ASCE7-10


Average Roof Height(ft) : 17.72
Basic Wind Speed, V0(mile/h) : 185.00
Exposure Category :B
Directionality Factor : 0.85
Structural Rigidity : Rigid

2. Gust Factor

G (Major, a) : 0.88
G (Ortho, a+90) : 0.86

3. Topographic Effect

Not Considered

4. Equation for Wind Load

Wind Force
Pressure
Velocity Pressure at Design Height
Velocity Pressure at Mean Roof
Height
Gradient Height (m)
Power Law Eponent

5. Story Related Parameters

5.1. Major, a

5.1.1. Windward

Level qz
Set Story Cpe Kz Kzt
(ft) (ksi)
T1 Roof 17.72 0.80 0.60 1.00 44.89
T1 2F 8.28 0.80 0.57 1.00 42.80
T1 1F 0.00 0.80 0.57 1.00 42.80
5.1.2. Leeward

Page: 12 / 30
Doc. Name:
Residential Row House
Date:
Level qz
Set Story Cpe Kz Kzt
(ft) (ksi)
T1 Roof 17.72 -0.50 0.60 1.00 44.89
T1 2F 8.28 -0.50 0.60 1.00 44.89
T1 1F 0.00 -0.50 0.60 1.00 44.89
5.2. Ortho, a+90

5.2.1. Windward

Level qz
Set Story Cpe Kz Kzt
(ft) (ksi)
T1 Roof 17.72 0.80 0.60 1.00 44.89
T1 2F 8.28 0.80 0.57 1.00 42.80
T1 1F 0.00 0.80 0.57 1.00 42.80
5.2.2. Leeward

Level qz
Set Story Cpe Kz Kzt
(ft) (ksi)
T1 Roof 17.72 -0.50 0.60 1.00 44.89
T1 2F 8.28 -0.50 0.60 1.00 44.89
T1 1F 0.00 -0.50 0.60 1.00 44.89

Overturnin
Pressure(k Loaded Loaded Wind Story Story g
Story
N/m2) H(m) B(m) Force(kN) Force(kN) Shear(kN) Moment(k
N.m)
Roof 1.990 1.438 5.300 15.165 15.165 0.000 0.000
2F 1.920 2.700 5.300 27.475 27.475 15.165 43.600
G.L 0.000 1.263 0.000 0.000 0.000 42.640 151.266
Story Shear Force Table by Wind Load Data (Wind Load-1-[0])

Overturnin
Pressure(k Loaded Loaded Wind Story Story g
Story
N/m2) H(m) B(m) Force(kN) Force(kN) Shear(kN) Moment(k
N.m)
Roof 2.412 1.438 16.000 55.476 55.476 0.000 0.000
2F 2.343 2.700 16.000 101.220 101.220 55.476 159.492
G.L 0.000 1.263 0.000 0.000 0.000 156.695 555.147
Story Shear Force Table by Wind Load Data (Wind Load-1-[90])

Page: 13 / 30
Doc. Name:
Residential Row House
Date:
Seismic Function Report: UBC 1997(Static)-1

1. Input Data & Formula

Design Code : UBC 1997


Soil Profile Type : Se
Seismic Zone :4
Importance Factor : 1.0
Ductility Coefficient, R (Major Direction) : 4.5

2. Design Spectral Acceleration Parameters

Seismic Zone Factor : 0.40


Seismic Source Type :C
Closest Distance to Known Seismic Source : 50.00
Period Coefficient : 1.30

3. Fundamental Period

Major Direction
Approximate Fundamental Period, Ta : 0.302
Analytical Period : Not Considered
Fundamental Period, T : 0.302

4. Seismic Base Shear

Major Direction

Na : 1.000

Nv : 1.000

Ca = Na x Ca : 0.360

Cv = Nv x Cv : 0.960

: 0.706 W

: 0.200 W

: 0.040 W

(for Seismic Zone 4) : 0.071 W

: 0.071 W

: 0.200 W

Page: 14 / 30
Doc. Name:
Residential Row House
Date:

Overturning Total
Seismic Story Story
Story Weight(kN) Moment(kN. Torsion(kN.
Force(kN) Force(kN) Shear(kN)
m) m)
Roof 164.957 51.959 51.959 0.000 0.000 0.000
2F 359.798 52.992 52.992 51.959 149.381 0.000
G.L 0.000 0.000 0.000 104.951 414.382 0.000
Story Shear Force Table by Seismic Load Data (Static Seismic Load-1)

Overturning Total
Seismic Story Story
Story Weight(kN) Moment(kN. Torsion(kN.
Force(kN) Force(kN) Shear(kN)
m) m)
Roof 164.957 51.959 51.959 0.000 0.000 0.000
2F 359.798 52.992 52.992 51.959 149.381 0.000
G.L 0.000 0.000 0.000 104.951 414.382 0.000
Story Shear Force Table by Seismic Load Data (Static Seismic Load-1(Ortho.))

Page: 15 / 30
Doc. Name:
Residential Row House
Date:

4. Steel Result
(1) Steel Member Design Philosophy

Steel Member Design is done in nGen as per steel design code :

- Design Code : AISC360M-10 (LRFD)

- National Annex : None

Load
Design Group Member Section Design Ratio Status
Combination
1SC2 Column-17 170x170x3.0 LCB56_1 0.005 OK
1SC1 Column-23 170x170x3.0 LCB5_4 0.051 OK
2SC2 Column-42 170x170x3.0 LCB55_8 0.002 OK
RSG2 Beam-41 160x55x3 LCB1_1 0.007 OK
RSG1 Beam-53 160x110x3 LCB1_2 0.004 OK
2SG1 Beam-138 160x55x3 LCB5_4 0.026 OK
2SG2 Beam-142 160x110x3 LCB1_1 0.001 OK
Steel Combined Ratio Result Summary Table

(1) Design Group: 1SC2

Steel Member Design Summary Report AISC360M-10 (LRFD) [N, mm]

A. Design Case: Envelope Design Case

B. Member Information

a. Member Name 3 A 2.00e+003 mm2


- 1SC2 - Column-11 [87]
3
170

b. Material Asy 9.66e+002 mm2


- A36 (ASTM) [1] z
Asz 9.66e+002 mm2
- Fy = 248.21 MPa
c. Section y Iy 9.32e+006 mm4
170
- 170x170x3.0 [2] Iz 9.32e+006 mm4
d. Member Length
- L = 2.525 m Sy 1.10e+005 mm3
- Ly = 2.525 m, Lz = 2.525 m Sz 1.10e+005 mm3
- Lb = 2.525 m (at 0.00L, 0.00 m)
e. Effective Length Factor Zy 1.26e+005 mm3
- Ky = 0.752, Kz = 0.672 Zz 1.26e+005 mm3
f. Member Parameters
- B1y = 1.000, B1z = 1.000 ry 6.82e+001 mm
- B2y = 1.000, B2z = 1.000 rz 6.82e+001 mm
- Cb = 1.891
- Cv = 1.000
g. Seismic Provision: Considered
- Seismic Load Resisting System: SMF

C. Check Slenderness Ratio

Page: 16 / 30
Doc. Name:
Residential Row House
Date:
KL/r = 27.829 < 200.000 ( OK )

D. Check Combined Ratio(at 0.00L, 0.00 m)

Combination: LCB38_1 (1.20D+1.00L+1.00WY+1.00NY)


Axial -1.56 kN / -351.05 kN = 0.004 < 1.000 OK(1)
0.00 kN m / 20.06 kN m = 0.000 < 1.000
. . OK(1)
Moment
0.04 kN.m / 20.06 kN.m = 0.002 < 1.000 OK(1)
Combined 0.004 < 1.000 OK(1)

E. Check Shear Capacity(at 0.00L, 0.00 m)

Combination: LCB38_1 (1.20D+1.00L+1.00WY+1.00NY)


Shear 0.24 kN / 129.48 kN = 0.002 < 1.000 OK(1)

F. Check Deflection(at 0.00L, 0.00 m)

Combination: svLCB6 (1.00D+1.00L)


Deflection 0.00 mm / 7.01 mm (L/360) = 0.000 < 1.000 OK

G. Check Fatigue

Do not check because checked off Fatigue check option.

Page: 17 / 30
Doc. Name:
Residential Row House
Date:
(2) Design Group: 1SC1

Steel Member Design Summary Report AISC360M-10 (LRFD) [N, mm]

A. Design Case: Envelope Design Case

B. Member Information

a. Member Name 3 A 2.00e+003 mm2


- 1SC1 - Column-21 [133]

3
170
b. Material Asy 9.66e+002 mm2
- A36 (ASTM) [1] z
Asz 9.66e+002 mm2
- Fy = 248.21 MPa
c. Section y Iy 9.32e+006 mm4
170
- 170x170x3.0 [2] Iz 9.32e+006 mm4
d. Member Length
- L = 2.525 m Sy 1.10e+005 mm3
- Ly = 0.316 m, Lz = 0.316 m Sz 1.10e+005 mm3
- Lb = 0.316 m (at 1.00L, 2.53 m)
e. Effective Length Factor Zy 1.26e+005 mm3
- Ky = 0.799, Kz = 0.795 Zz 1.26e+005 mm3
f. Member Parameters
- B1y = 1.000, B1z = 1.000 ry 6.82e+001 mm
- B2y = 1.000, B2z = 1.000 rz 6.82e+001 mm
- Cb = 2.179
- Cv = 1.000
g. Seismic Provision: Considered
- Seismic Load Resisting System: SMF

C. Check Slenderness Ratio

KL/r = 3.696 < 200.000 ( OK )

D. Check Combined Ratio(at 1.00L, 2.53 m)

Combination: LCB5_4 (1.20D+1.60L-1.00NY)


Axial -3.72 kN / -362.64 kN = 0.010 < 1.000 OK(1)
-0.53 kN m / -20.06 kN m = 0.027 < 1.000
. . OK(1)
Moment
0.39 kN.m / 20.06 kN.m = 0.020 < 1.000 OK(1)
Combined 0.051 < 1.000 OK(1)

E. Check Shear Capacity(at 1.00L, 2.53 m)

Combination: LCB4_4 (1.20D+1.60L-1.00NX)


Shear 1.24 kN / 129.48 kN = 0.010 < 1.000 OK(1)

F. Check Deflection(at 0.00L, 0.00 m)

Combination: svLCB6 (1.00D+1.00L)


Deflection 0.00 mm / 7.01 mm (L/360) = 0.000 < 1.000 OK

Page: 18 / 30
Doc. Name:
Residential Row House
Date:
G. Check Fatigue

Do not check because checked off Fatigue check option.

Page: 19 / 30
Doc. Name:
Residential Row House
Date:
(3) Design Group: 2SC2

Steel Member Design Summary Report AISC360M-10 (LRFD) [N, mm]

A. Design Case: Envelope Design Case

B. Member Information

a. Member Name 3 A 2.00e+003 mm2


- 2SC2 - Column-39 [162]

3
170
b. Material Asy 9.66e+002 mm2
- A36 (ASTM) [1] z
Asz 9.66e+002 mm2
- Fy = 248.21 MPa
c. Section y Iy 9.32e+006 mm4
170
- 170x170x3.0 [2] Iz 9.32e+006 mm4
d. Member Length
- L = 2.875 m Sy 1.10e+005 mm3
- Ly = 2.875 m, Lz = 2.875 m Sz 1.10e+005 mm3
- Lb = 2.875 m (at 0.00L, 0.00 m)
e. Effective Length Factor Zy 1.26e+005 mm3
- Ky = 0.683, Kz = 0.561 Zz 1.26e+005 mm3
f. Member Parameters
- B1y = 1.000, B1z = 1.000 ry 6.82e+001 mm
- B2y = 1.000, B2z = 1.000 rz 6.82e+001 mm
- Cb = 2.219
- Cv = 1.000
g. Seismic Provision: Considered
- Seismic Load Resisting System: SMF

C. Check Slenderness Ratio

KL/r = 28.784 < 200.000 ( OK )

D. Check Combined Ratio(at 0.00L, 0.00 m)

Combination: LCB55_8 (1.20D+1.00L-1.00EQ-1.00NX)


Axial -0.34 kN / -350.24 kN = 0.001 < 1.000 OK(1)
0.02 kN m / 20.06 kN m = 0.001 < 1.000
. . OK(1)
Moment
-0.01 kN.m / -20.06 kN.m = 0.000 < 1.000 OK(1)
Combined 0.002 < 1.000 OK(1)

E. Check Shear Capacity(at 0.00L, 0.00 m)

Combination: LCB38_1 (1.20D+1.00L+1.00WY+1.00NY)


Shear 0.11 kN / 129.48 kN = 0.001 < 1.000 OK(1)

F. Check Deflection(at 0.00L, 0.00 m)

Combination: svLCB6 (1.00D+1.00L)


Deflection 0.00 mm / 7.99 mm (L/360) = 0.000 < 1.000 OK

Page: 20 / 30
Doc. Name:
Residential Row House
Date:
G. Check Fatigue

Do not check because checked off Fatigue check option.

Page: 21 / 30
Doc. Name:
Residential Row House
Date:
(1) Design Group: RSG2

Steel Member Design Summary Report AISC360M-10 (LRFD) [N, mm]

A. Design Case: Envelope Design Case

B. Member Information

a. Member Name 55
A 7.92e+002 mm2
- RSG2 - Beam-1 [1]

3
b. Material Asy 4.80e+002 mm2
z

160
- A36 (ASTM) [1] Asz 3.30e+002 mm2
- Fy = 248.21 MPa 3
c. Section y Iy 2.95e+006 mm4

3
- 160x55x3 [1] 55
Iz 2.14e+005 mm4
d. Member Length
- L = 1.200 m Sy 3.68e+004 mm3
- Ly = 1.200 m, Lz = 1.200 m Sz 5.01e+003 mm3
- Lb = 1.200 m (at 0.00L, 0.00 m)
e. Effective Length Factor Zy 4.37e+004 mm3
- Ky = 0.786, Kz = 0.500 Zz 8.79e+003 mm3
f. Member Parameters
- B1y = 1.000, B1z = 1.000 ry 6.10e+001 mm
- B2y = 1.000, B2z = 1.000 rz 1.64e+001 mm
- Cb = 1.043
- Cv = 1.000
g. Seismic Provision: Considered
- Seismic Load Resisting System: SMF

C. Check Slenderness Ratio

L/r = 73.060 < 300.000 ( OK )

D. Check Combined Ratio(at 0.00L, 0.00 m)

Combination: LCB1_2 (1.40D-1.00NX)


Axial 0.00 kN / 176.93 kN = 0.000 < 1.000 OK(1)
-0.02 kN m / -9.13 kN m = 0.002 < 1.000
. . OK(1)
Moment
0.00 kN m / 1.46 kN m = 0.000 < 1.000
. . OK(1)
Combined 0.002 < 1.000 OK(1)

E. Check Shear Capacity(at 0.00L, 0.00 m)

Combination: LCB1_2 (1.40D-1.00NX)


Shear -0.44 kN / -64.34 kN = 0.007 < 1.000 OK(1)

F. Check Deflection(at 0.25L, 0.30 m)

Combination: svLCB18 (1.00D+0.75L)


Deflection 0.00 mm / 3.33 mm (L/360) = 0.000 < 1.000 OK

Page: 22 / 30
Doc. Name:
Residential Row House
Date:
G. Check Fatigue

Do not check because checked off Fatigue check option.

Page: 23 / 30
Doc. Name:
Residential Row House
Date:
(2) Design Group: RSG1

Steel Member Design Summary Report AISC360M-10 (LRFD) [N, mm]

A. Design Case: Envelope Design Case

B. Member Information

a. Member Name 55
A 1.58e+003 mm2
- RSG1 - Beam-3 [3]

3
b. Material Asy 9.60e+002 mm2
5.1
- A36 (ASTM) [1] z
Asz 6.60e+002 mm2

160
- Fy = 248.21 MPa
c. Section y3
Iy 5.89e+006 mm4

3
55
- 160x110x3 [9] Iz 7.78e+005 mm4
d. Member Length
- L = 1.200 m Sy 7.37e+004 mm3
- Ly = 1.200 m, Lz = 1.200 m Sz 1.35e+004 mm3
- Lb = 1.200 m (at 0.75L, 0.90 m)
e. Effective Length Factor Zy 8.74e+004 mm3
- Ky = 0.568, Kz = 0.500 Zz 2.36e+004 mm3
f. Member Parameters
- B1y = 1.000, B1z = 1.000 ry 6.10e+001 mm
- B2y = 1.000, B2z = 1.000 rz 2.22e+001 mm
- Cb = 1.009
- Cv = 1.000
g. Seismic Provision: Considered
- Seismic Load Resisting System: SMF

C. Check Slenderness Ratio

L/r = 54.139 < 300.000 ( OK )

D. Check Combined Ratio(at 0.75L, 0.90 m)

Combination: LCB1_2 (1.40D-1.00NX)


Axial 0.00 kN / 353.85 kN = 0.000 < 1.000 OK(1)
-0.02 kN m / -19.31 kN m = 0.001 < 1.000
. . OK(1)
Moment
0.00 kN.m / 3.91 kN.m = 0.000 < 1.000 OK(1)
Combined 0.001 < 1.000 OK(1)

E. Check Shear Capacity(at 0.75L, 0.90 m)

Combination: LCB1_2 (1.40D-1.00NX)


Shear -0.45 kN / -128.67 kN = 0.003 < 1.000 OK(1)

F. Check Deflection(at 0.00L, 0.00 m)

Combination: ftLCB3 (1.00L)


Deflection 0.00 mm / 3.33 mm (L/360) = 0.000 < 1.000 OK

Page: 24 / 30
Doc. Name:
Residential Row House
Date:
G. Check Fatigue

Do not check because checked off Fatigue check option.

Page: 25 / 30
Doc. Name:
Residential Row House
Date:
(3) Design Group: 2SG2

Steel Member Design Summary Report AISC360M-10 (LRFD) [N, mm]

A. Design Case: Envelope Design Case

B. Member Information

a. Member Name 55
A 1.58e+003 mm2
- 2SG2 - Beam-97 [187]

3
b. Material Asy 9.60e+002 mm2
5.1
- A36 (ASTM) [1] z
Asz 6.60e+002 mm2

160
- Fy = 248.21 MPa
c. Section y3
Iy 5.89e+006 mm4

3
55
- 160x110x3 [9] Iz 7.78e+005 mm4
d. Member Length
- L = 1.200 m Sy 7.37e+004 mm3
- Ly = 1.200 m, Lz = 0.300 m Sz 1.35e+004 mm3
- Lb = 0.300 m (at 0.75L, 0.90 m)
e. Effective Length Factor Zy 8.74e+004 mm3
- Ky = 0.608, Kz = 0.500 Zz 2.36e+004 mm3
f. Member Parameters
- B1y = 1.000, B1z = 1.000 ry 6.10e+001 mm
- B2y = 1.000, B2z = 1.000 rz 2.22e+001 mm
- Cb = 3.000
- Cv = 1.000
g. Seismic Provision: Considered
- Seismic Load Resisting System: SMF

C. Check Slenderness Ratio

L/r = 19.673 < 300.000 ( OK )

D. Check Combined Ratio(at 0.75L, 0.90 m)

Combination: LCB55_8 (1.20D+1.00L-1.00EQ-1.00NX)


Axial 0.00 kN / 353.85 kN = 0.000 < 1.000 OK(1)
-0.00 kN m / -19.52 kN m = 0.000 < 1.000
. . OK(1)
Moment
0.00 kN.m / 3.91 kN.m = 0.000 < 1.000 OK(1)
Combined 0.000 < 1.000 OK(1)

E. Check Shear Capacity(at 0.75L, 0.90 m)

Combination: LCB55_8 (1.20D+1.00L-1.00EQ-1.00NX)


Shear -0.04 kN / -128.67 kN = 0.000 < 1.000 OK(1)

F. Check Deflection(at 0.13L, 0.15 m)

Combination: svLCB18 (1.00D+0.75L)


Deflection 0.00 mm / 3.33 mm (L/360) = 0.000 < 1.000 OK

Page: 26 / 30
Doc. Name:
Residential Row House
Date:
G. Check Fatigue

Do not check because checked off Fatigue check option.

Page: 27 / 30
Doc. Name:
Residential Row House
Date:
(4) Design Group: 2SG1

Steel Member Design Summary Report AISC360M-10 (LRFD) [N, mm]

A. Design Case: Envelope Design Case

B. Member Information

a. Member Name 55
A 7.92e+002 mm2
- 2SG1 - Beam-95 [185]

3
b. Material Asy 4.80e+002 mm2
z

160
- A36 (ASTM) [1] Asz 3.30e+002 mm2
- Fy = 248.21 MPa 3
c. Section y Iy 2.95e+006 mm4

3
- 160x55x3 [1] 55
Iz 2.14e+005 mm4
d. Member Length
- L = 1.200 m Sy 3.68e+004 mm3
- Ly = 1.200 m, Lz = 1.200 m Sz 5.01e+003 mm3
- Lb = 1.200 m (at 0.75L, 0.90 m)
e. Effective Length Factor Zy 4.37e+004 mm3
- Ky = 0.871, Kz = 0.500 Zz 8.79e+003 mm3
f. Member Parameters
- B1y = 1.000, B1z = 1.000 ry 6.10e+001 mm
- B2y = 1.000, B2z = 1.000 rz 1.64e+001 mm
- Cb = 1.397
- Cv = 1.000
g. Seismic Provision: Considered
- Seismic Load Resisting System: SMF

C. Check Slenderness Ratio

L/r = 73.060 < 300.000 ( OK )

D. Check Combined Ratio(at 0.75L, 0.90 m)

Combination: LCB4_4 (1.20D+1.60L-1.00NX)


Axial 0.00 kN / 176.93 kN = 0.000 < 1.000 OK(1)
-0.00 kN m / -9.76 kN m = 0.000 < 1.000
. . OK(1)
Moment
0.00 kN.m / 1.46 kN.m = 0.000 < 1.000 OK(1)
Combined 0.000 < 1.000 OK(1)

E. Check Shear Capacity(at 0.75L, 0.90 m)

Combination: LCB4_4 (1.20D+1.60L-1.00NX)


Shear -0.02 kN / -64.34 kN = 0.000 < 1.000 OK(1)

F. Check Deflection(at 0.25L, 0.30 m)

Combination: svLCB18 (1.00D+0.75L)


Deflection 0.00 mm / 3.33 mm (L/360) = 0.000 < 1.000 OK

Page: 28 / 30
Doc. Name:
Residential Row House
Date:
G. Check Fatigue

Do not check because checked off Fatigue check option.

6.) Lacking detailed design


calculation
for base plates and anchor bolts
7.) Provide checking calculations
for ALC walls behaviour, bending

Page: 29 / 30
Doc. Name:
Residential Row House
Date:

5. Concrete Design Result

Page: 30 / 30
Project Job Ref.

Section Sheet no./rev.


1
Calc. by Date Chk'd by Date App'd by Date
04/04/2022

FOUNDATION ANALYSIS & DESIGN (ACI318)


In accordance with ACI318-14
Tedds calculation version 3.2.09

FOOTING ANALYSIS
Length of foundation; Lx = 1000 mm
Width of foundation; Ly = 800 mm
Foundation area; A = Lx  Ly = 0.800 m2
Depth of foundation; h = 400 mm 5.) Provide Design
Depth of soil over foundation; hsoil = 800 mm
Density of concrete; conc = 24.5 kN/m3 calculation
1
for WF1, WF2, WF3.
which was recently
revised and label
design group accordingly
800
400

y
75.8 kN/m2 75.8 kN/m2

Wall no.1 details


Width of wall; ly1 = 150 mm
position in y-axis; y1 = 400 mm
Soil properties
Net allowable bearing pressure; qallow_Net = 80 kN/m2
Density of soil; soil = 18.0 kN/m3
Angle of internal friction; b = 30.0 deg
Design base friction angle; bb = 30.0 deg
Coefficient of base friction; tan(bb) = 0.577
Self weight; Fswt = h  conc = 9.8 kN/m2
Soil weight; Fsoil = hsoil  soil = 14.4 kN/m2
Project Job Ref.

Section Sheet no./rev.


2
Calc. by Date Chk'd by Date App'd by Date
04/04/2022

Wall no.1 loads per linear meter


Dead load in z; FDz1 = 36.0 kN
Live load in z; FLz1 = 5.0 kN
Live roof load in z; FLrz1 = 2.0 kN
Footing analysis for soil and stability
Load combinations per ASCE 7-16
1.0D (0.681)
1.0D + 1.0L (0.743)
1.0D + 1.0Lr (0.706)
1.0D + 1.0S (0.681)
1.0D + 1.0R (0.681)
1.0D + 0.75L + 0.75Lr (0.746)
1.0D + 0.75L + 0.75S (0.727)
1.0D + 0.75L + 0.75R (0.727)

Combination 6 results: 1.0D + 0.75L + 0.75Lr


Forces on foundation per linear meter
Force in z-axis; Fdz = D  A  (Fswt + Fsoil) + D  FDz1 + L  FLz1 + Lr  FLrz1 = 60.6 kN

Moments on foundation per linear meter


Moment in y-axis, about y is 0; Mdy = D  (A  (Fswt + Fsoil)  Ly / 2) + D  (FDz1  y1) + L  (FLz1  y1) + Lr 
(FLrz1  y1) = 24.2 kNm

Uplift verification
Vertical force; Fdz = 60.6 kN
PASS - Foundation is not subject to uplift
Stability against sliding
Resistance due to base friction; FRFriction = max(Fdz, 0 kN)  tan(bb) = 35 kN

Bearing resistance
Eccentricity of base reaction
Eccentricity of base reaction in y-axis; edy = Mdy / Fdz - Ly / 2 = 0 mm
Strip base pressures
q1 = Fdz  (1 - 6  edy / Ly) / (Ly  1000 mm) = 75.8 kN/m2
q2 = Fdz  (1 + 6  edy / Ly) / (Ly  1000 mm) = 75.8 kN/m2
Minimum base pressure; qmin = min(q1,q2) = 75.8 kN/m2
Maximum base pressure; qmax = max(q1,q2) = 75.8 kN/m2
Allowable bearing capacity
Allowable bearing capacity; qallow = qallow_Net + (h + hsoil)  soil = 101.6 kN/m2
qmax / qallow = 0.746
PASS - Allowable bearing capacity exceeds design base pressure

FOOTING DESIGN (ACI318)


In accordance with ACI318-14
Project Job Ref.

Section Sheet no./rev.


3
Calc. by Date Chk'd by Date App'd by Date
04/04/2022

Material details
Compressive strength of concrete; f’c = 21 MPa
Yield strength of reinforcement; fy = 280 MPa
Cover to reinforcement; cnom = 75 mm
Concrete type; Normal weight
Concrete modification factor;  = 1.00
Wall type; Concrete

Analysis and design of concrete footing


Load combinations per ASCE 7-16
1.4D (0.049)
1.2D + 1.6L + 0.5Lr (0.051)
1.2D + 1.6L + 0.5S (0.050)
1.2D + 1.6L + 0.5R (0.050)
1.2D + 1.0L + 1.6Lr (0.050)
1.2D + 1.0L + 1.6S (0.047)
1.2D + 1.0L + 1.6R (0.047)

Combination 2 results: 1.2D + 1.6L + 0.5Lr


Forces on foundation per linear meter
Ultimate force in z-axis; Fuz = D  A  (Fswt + Fsoil) + D  FDz1 + L  FLz1 + Lr  FLrz1 = 75.4 kN

Moments on foundation per linear meter


Ultimate moment in y-axis, about y is 0; Muy = D  (A  (Fswt + Fsoil)  Ly / 2) + D  (FDz1  y1) + L  (FLz1  y1) + Lr 
(FLrz1  y1) = 30.2 kNm

Eccentricity of base reaction


Eccentricity of base reaction in y-axis; euy = Muy / Fuz - Ly / 2 = 0 mm
Strip base pressures
qu1 = Fuz  (1 - 6  euy / Ly) / (Ly  1000 mm) = 94.3 kN/m2
qu2 = Fuz  (1 + 6  euy / Ly) / (Ly  1000 mm) = 94.3 kN/m2
Minimum ultimate base pressure; qumin = min(qu1,qu2) = 94.3 kN/m2
Maximum ultimate base pressure; qumax = max(qu1,qu2) = 94.3 kN/m2
Shear diagram (kN)
26.1

0.4 0-0.4
0

-26.1
Project Job Ref.

Section Sheet no./rev.


4
Calc. by Date Chk'd by Date App'd by Date
04/04/2022

Moment diagram (kNm)


3.4

0 0

5.2

Moment design, y direction, positive moment


Ultimate bending moment; Mu.y.max = 3.4 kNm
Tension reinforcement provided; No.4 bars at 150 c/c bottom
Area of tension reinforcement provided; Asy.bot.prov = 860 mm2
Minimum area of reinforcement (7.6.1.1); As.min = 0.0020  Lx  h = 800 mm2
PASS - Area of reinforcement provided exceeds minimum
Maximum spacing of reinforcement (7.7.2.3); smax = min(3  h, 457 mm) = 457 mm
PASS - Maximum permissible reinforcement spacing exceeds actual spacing
Depth to tension reinforcement; d = h - cnom - y.bot / 2 = 319 mm
Depth of compression block; a = Asy.bot.prov  fy / (0.85  f'c  Lx) = 13 mm
Neutral axis factor; 1 = 0.85
Depth to neutral axis; c = a / 1 = 16 mm
Strain in tensile reinforcement (7.3.3.1); t = 0.003  d / c - 0.003 = 0.05722
PASS - Tensile strain exceeds minimum required, 0.004
Nominal moment capacity; Mn = Asy.bot.prov  fy  (d - a / 2) = 75.1 kNm
Flexural strength reduction factor; f = min(max(0.65 + (t - 0.002)  (250 / 3), 0.65), 0.9) = 0.900
Design moment capacity; Mn = f  Mn = 67.6 kNm
Mu.y.max / Mn = 0.051
PASS - Design moment capacity exceeds ultimate moment load
One-way shear design, y direction
Ultimate shear force; Vu.y = 0.4 kN
Depth to reinforcement; dv = h - cnom - y.bot / 2 = 319 mm
Shear strength reduction factor; v = 0.75
Nominal shear capacity (Eq. 22.5.5.1); Vn = 0.17    (f'c  1 MPa)  Lx  dv = 248.2 kN
Design shear capacity; Vn = v  Vn = 186.2 kN
Vu.y / Vn = 0.002
PASS - Design shear capacity exceeds ultimate shear load
Project Job Ref.

Section Sheet no./rev.


5
Calc. by Date Chk'd by Date App'd by Date
04/04/2022

No.4 bars at 150 c/c bottom

1
Project Job Ref.

Section Sheet no./rev.


1
Calc. by Date Chk'd by Date App'd by Date
04/04/2022

FOUNDATION ANALYSIS & DESIGN (ACI318)


In accordance with ACI318-14
Tedds calculation version 3.2.09

FOOTING ANALYSIS
Length of foundation; Lx = 1000 mm
Width of foundation; Ly = 800 mm
Foundation area; A = Lx  Ly = 0.800 m2
Depth of foundation; h = 400 mm
Depth of soil over foundation; hsoil = 800 mm
Density of concrete; conc = 24.5 kN/m3

1
800
400

y
91.9 kN/m2 55 kN/m 2

Wall no.1 details


Width of wall; ly1 = 150 mm
position in y-axis; y1 = 350 mm
Soil properties
Net allowable bearing pressure; qallow_Net = 80 kN/m2
Density of soil; soil = 18.0 kN/m3
Angle of internal friction; b = 30.0 deg
Design base friction angle; bb = 30.0 deg
Coefficient of base friction; tan(bb) = 0.577
Self weight; Fswt = h  conc = 9.8 kN/m2
Soil weight; Fsoil = hsoil  soil = 14.4 kN/m2
Project Job Ref.

Section Sheet no./rev.


2
Calc. by Date Chk'd by Date App'd by Date
04/04/2022

Wall no.1 loads per linear meter


Dead load in z; FDz1 = 36.0 kN
Live load in z; FLz1 = 2.5 kN
Live roof load in z; FLrz1 = 2.0 kN
Footing analysis for soil and stability
Load combinations per ASCE 7-16
1.0D (0.847)
1.0D + 1.0L (0.889)
1.0D + 1.0Lr (0.881)
1.0D + 1.0S (0.847)
1.0D + 1.0R (0.847)
1.0D + 0.75L + 0.75Lr (0.904)
1.0D + 0.75L + 0.75S (0.879)
1.0D + 0.75L + 0.75R (0.879)

Combination 6 results: 1.0D + 0.75L + 0.75Lr


Forces on foundation per linear meter
Force in z-axis; Fdz = D  A  (Fswt + Fsoil) + D  FDz1 + L  FLz1 + Lr  FLrz1 = 58.7 kN

Moments on foundation per linear meter


Moment in y-axis, about y is 0; Mdy = D  (A  (Fswt + Fsoil)  Ly / 2) + D  (FDz1  y1) + L  (FLz1  y1) + Lr 
(FLrz1  y1) = 21.5 kNm

Uplift verification
Vertical force; Fdz = 58.7 kN
PASS - Foundation is not subject to uplift
Stability against sliding
Resistance due to base friction; FRFriction = max(Fdz, 0 kN)  tan(bb) = 33.9 kN

Bearing resistance
Eccentricity of base reaction
Eccentricity of base reaction in y-axis; edy = Mdy / Fdz - Ly / 2 = -34 mm
Strip base pressures
q1 = Fdz  (1 - 6  edy / Ly) / (Ly  1000 mm) = 91.9 kN/m2
q2 = Fdz  (1 + 6  edy / Ly) / (Ly  1000 mm) = 55 kN/m2
Minimum base pressure; qmin = min(q1,q2) = 55 kN/m2
Maximum base pressure; qmax = max(q1,q2) = 91.9 kN/m2
Allowable bearing capacity
Allowable bearing capacity; qallow = qallow_Net + (h + hsoil)  soil = 101.6 kN/m2
qmax / qallow = 0.904
PASS - Allowable bearing capacity exceeds design base pressure

FOOTING DESIGN (ACI318)


In accordance with ACI318-14
Project Job Ref.

Section Sheet no./rev.


3
Calc. by Date Chk'd by Date App'd by Date
04/04/2022

Material details
Compressive strength of concrete; f’c = 21 MPa
Yield strength of reinforcement; fy = 280 MPa
Cover to reinforcement; cnom = 75 mm
Concrete type; Normal weight
Concrete modification factor;  = 1.00
Wall type; Concrete

Analysis and design of concrete footing


Load combinations per ASCE 7-16
1.4D (0.049)
1.2D + 1.6L + 0.5Lr (0.047)
1.2D + 1.6L + 0.5S (0.046)
1.2D + 1.6L + 0.5R (0.046)
1.2D + 1.0L + 1.6Lr (0.047)
1.2D + 1.0L + 1.6S (0.044)
1.2D + 1.0L + 1.6R (0.044)

Combination 1 results: 1.4D


Forces on foundation per linear meter
Ultimate force in z-axis; Fuz = D  A  (Fswt + Fsoil) + D  FDz1 = 77.5 kN

Moments on foundation per linear meter


Ultimate moment in y-axis, about y is 0; Muy = D  (A  (Fswt + Fsoil)  Ly / 2) + D  (FDz1  y1) = 28.5 kNm

Eccentricity of base reaction


Eccentricity of base reaction in y-axis; euy = Muy / Fuz - Ly / 2 = -33 mm
Strip base pressures
qu1 = Fuz  (1 - 6  euy / Ly) / (Ly  1000 mm) = 120.5 kN/m2
qu2 = Fuz  (1 + 6  euy / Ly) / (Ly  1000 mm) = 73.3 kN/m2
Minimum ultimate base pressure; qumin = min(qu1,qu2) = 73.3 kN/m2
Maximum ultimate base pressure; qumax = max(qu1,qu2) = 120.5 kN/m2
Shear diagram (kN)
26.7

0.0 0
-2.3
0

-23.7
Project Job Ref.

Section Sheet no./rev.


4
Calc. by Date Chk'd by Date App'd by Date
04/04/2022

Moment diagram (kNm)


3.3

0 0

4.9

Moment design, y direction, positive moment


Ultimate bending moment; Mu.y.max = 3.3 kNm
Tension reinforcement provided; No.4 bars at 150 c/c bottom
Area of tension reinforcement provided; Asy.bot.prov = 860 mm2
Minimum area of reinforcement (7.6.1.1); As.min = 0.0020  Lx  h = 800 mm2
PASS - Area of reinforcement provided exceeds minimum
Maximum spacing of reinforcement (7.7.2.3); smax = min(3  h, 457 mm) = 457 mm
PASS - Maximum permissible reinforcement spacing exceeds actual spacing
Depth to tension reinforcement; d = h - cnom - y.bot / 2 = 319 mm
Depth of compression block; a = Asy.bot.prov  fy / (0.85  f'c  Lx) = 13 mm
Neutral axis factor; 1 = 0.85
Depth to neutral axis; c = a / 1 = 16 mm
Strain in tensile reinforcement (7.3.3.1); t = 0.003  d / c - 0.003 = 0.05722
PASS - Tensile strain exceeds minimum required, 0.004
Nominal moment capacity; Mn = Asy.bot.prov  fy  (d - a / 2) = 75.1 kNm
Flexural strength reduction factor; f = min(max(0.65 + (t - 0.002)  (250 / 3), 0.65), 0.9) = 0.900
Design moment capacity; Mn = f  Mn = 67.6 kNm
Mu.y.max / Mn = 0.049
PASS - Design moment capacity exceeds ultimate moment load
One-way shear design, y direction
Ultimate shear force; Vu.y = 2.3 kN
Depth to reinforcement; dv = h - cnom - y.bot / 2 = 319 mm
Shear strength reduction factor; v = 0.75
Nominal shear capacity (Eq. 22.5.5.1); Vn = 0.17    (f'c  1 MPa)  Lx  dv = 248.2 kN
Design shear capacity; Vn = v  Vn = 186.2 kN
Vu.y / Vn = 0.012
PASS - Design shear capacity exceeds ultimate shear load
Project Job Ref.

Section Sheet no./rev.


5
Calc. by Date Chk'd by Date App'd by Date
04/04/2022

No.4 bars at 150 c/c bottom

1
(4) Trasfer these plans and layout before
the detailed calculation page for easy reviewing
of design group location for reference.
4) Where is 1SC1 and 1SC2 located?
Provide plan reflecting 1SC2,1SC1. Only
2SC2 is reflected on Plan
5.) Provide layouts and plans for the SOG and WF

You might also like