enclosures and shall conform to the require- rivets, and other mechanical fasteners shall

ments of 510.3. Enclosure


openings not penetrate duct walls. Clearance of any
required to reach access panels in the ducts shall comply with Section 507.2.
ductwork shall be large enough for the 510.6.2 All ducts shall be protected on the
removal of the access panel. exterior by paint or other suitable weather
protective coating or shall be constructed of
510.4 Listed Grease Ducts. Listed grease ducts non-corrosive stainless steel. Ductwork
shall be installed in accordance with the terms of the subject to corrosion shall have minimal
listing and the manufacturer's instructions. contact with the building surface.

510.5 Other Grease Ducts. Other grease ducts 5'l 0.7 lnterior lnstallations.
shall comply with the requirements of this section.
510.7.1 ln all buildings more than one story in
510.5.1 Materials. Ducts shall be constructed of height, and in one-story puildings where the roof
and supported by carbon steel not less than ceiling assembly is required to have a fire resis-
0.054 inch (1.37 mm) (No. 16 MSG) in thickness tance rating, the ducts shall be enclosed in a
or stainless steel not less than 0.043 inch (1.09 continuous enclosure extending from the lowest
mm) (No. 18 MSG) in thickness. fire rated ceiling or floor above the hood,
through any concealed spaces, to or through the
510.5.2 lnstallation. roof so as to maintain the integrity of the fire
separations required by the applicable Building
510.5.2.1 All seams, joints, penetrations, Code provisions. The enclosure shall be sealed
and duct to hood collar connections shall around the duct at the point of penetration of the
have a liquid tight continuous external weld. lowest fire rated ceiling or floor above the hood
Exception No. 1: Duct to hood collar in order to maintain the fire resistance rating of
connections as shown in Figure 52 shall the enclosure and shall be vented to the exterior
be permitted. of the building through weather protected
openings.
Exception No. 2: Penetrations shall be Exception: The continuous enclosure
permitted to be sealed by other listed provisions shall not be required where a
devices that are tested to be grease field applied grease duct enclosure or a
tight and are evaluated under the same factory built grease duct enclosure (see
conditions of fire severity as the hood or Section 507.2.3) is protected with a listed
' enclosure of listed grease extractors duct through penetration protection system
and whose presence does not detract equivalent to the fire resistance rating of
from the hood's or duct's structural the assembly being penetrated, and the
integrity. materials are installed in accordance with
the conditions of their listings and the
Exception No. 3: lnternal welding shall manufacturers' instructions and are
be permitted, provided the joint is acceptable to the Authority Having
formed or ground smooth and is readily Jurisdiction.
accessible for inspection.
510.7.2The enclosure required in Section 510.7.1 ,
510.5.2.2 Overlapping duct connections of shall conforms to Sections 510.7.2.1 through
either the telescoping or the bell type shall 510.7.2.3.
be used for welded field joints, not butt-weld
connections. The inside duct section shall 510.7.2.1 lf the building is less than four stories
always be uphill of the outside duct section. in height, the enclosure wall shall have a fire
The difference between inside dimensions resistance rating of not less than one (1) hour.
of overlapping sections shall not exceed
ll4inch (6.4 mm). The overlap. shall n$ 510.7.2.2|f the building is four stories or more in
exceed two (2) inches (50.8 mm). (See height, the enclosure wall shall have a fire
Figure 5-3.) resistance rating of not less than two (2) hours.

51 0.6 Exterior lnstallations. 510.7.2.3 Clearance from the duct or the


exhaust fan to the interior surface of enclosures
510.6.1 The exterior portion of the ductwork of combustible construction shall be not less
shall be verticalwherever possible and shall than eighteen (18) inches (457 mm), and
be installed and adequately supported on clearance from the duct to the interior surface of
the exterior of a building. Bolts, screws, enclosures of noncombustible or limited

86 2012 PHILIPPINE MECHANICAL ENGINEERING CODE