COOLING LOAD CALCULATION SHEET
Q, STRUCTURAL HEAT GAIN: Q = U*A*(T Thermal conductivity
2
U; Thermal conductivity [w/m2/°C] Walls 0.16 [w/m /°C]
2
Ceiling 0.16 [w/m /°C]
2
Floor 0.22 [w/m /°C]
2
Glass 1.4 [w/m /°C] ∆T °C
Ti; Ski Park temperature -3 °C
To, Ambient temperature 45 °C 48 °C
To1, Temperature inside mall 26 °C 19 °C
Page 1 Sheet1
INTERNAL HEAT GAIN TOTAL 477.94
*
ASHRAE F30.4 Table 1
2
Snow area 5600 m
qR = (Sys. losses)(qF + qC + qSR + qHL)
Page 2 Sheet1
qR = refrigeration requirement
qF = snow chilling
qC = concrete chilling load
qSR = refrigeration to cool secondary coolant
qHL = building and pumping heat load
qF= 9.09 kw
qC= 72.30417 kw
qSR= 6.210069 kw
qHR= 78.4 kw
qR= 166.0042 kw
w/m2
Convection 6.2 34720
Radiation 1.2 6720
Condensation 0.5 2800
Ground conduction 3.4 19040
Headers 2.7 15120
78.4 kw
Selected 166 kw
Note Maximum capacitty required during the 5 days pull down
Normal opearion 12 % EXTRA
Sensible Heat
Q(s)=0.29 x R x ∆t where:
Q(s) is the sensible heat load in kcal/h.
3
R is the fresh air rate in m /h.
∆t is the difference in outdoor and indoor temperature in °C
Latent Heat
Q(L)=720 x R x ΔH where:
Q(L) is the Latent heat load in kcal/h.
R is the fresh air rate in m3/h.
ΔH is the absolute difference in outdoor and indoor humidity in kg/kg.
Page 3 Sheet1
3
Air Flow 20000 m /h
Page 4 Sheet1
Page 5 Sheet1
Page 6 Sheet1
9.09 864000
1
Page 7 Sheet1