<<Contents>> <<Index>>

General EJA430E
Specifications Gauge Pressure Transmitter

GS 01C31E01-01EN [Style: S2]

The high performance gauge pressure transmitter


EJA430E features single crystal silicon resonant
sensor and is suitable to measure liquid, gas, or
steam pressure. The EJA430E outputs a 4 to 20 mA
DC signal corresponding to the measured pressure.
It also features quick response, remote setup and
monitoring via BRAIN or HART communications and
self-diagnostics. FOUNDATION Fieldbus, PROFIBUS
PA and 1 to 5 V DC with HART (Low Power) protocol
types are also available.
EJA-E series models in their standard configuration,
with the exception of the Fieldbus, PROFIBUS and
Low Power types, are certified as complying with SIL
2 for safety requirement.

 STANDARD SPECIFICATIONS
Refer to GS 01C31T02-01EN for Fieldbus
communication type and GS 01C31T04-01EN for
PROFIBUS PA communication type for the items
marked with “◊.”
□ PERFORMANCE SPECIFICATIONS
□ SPAN AND RANGE LIMITS Zero-based calibrated span, linear output, wetted
parts material code ‘S’ and silicone oil, unless
Measurement psi bar kgf/cm2 otherwise mentioned.
MPa
Span/Range (/D1) (/D3) (/D4) For Fieldbus and PROFIBUS PA communication
Span
5 to 500 20 to 2000
0.05 to 5 0.05 to 5 types, use calibrated range instead of span in the
kPa inH2O following specifications.
H −400
−100 to Specification Conformance
Range to 2000 −1 to 5 −1 to 5
500 kPa EJA-E series ensures specification conformance to at
inH2O
least ±3σ.
Span 0.03to 3.5 4.3 to 500 0.3 to 35 0.3 to 35
A Reference Accuracy of Calibrated Span
−14.5 to
Range −0.1 to 3.5
500
−1 to 35 −1 to 35 (includes the effects of terminal-based linearity,
hysteresis, and repeatability)
Span 0.14 to 16 20 to 2300 1.4 to 160 1.4 to 160
B −14.5 to Measurement span H
Range −0.1 to 16 −1 to 160 −1 to 160
2300
Reference X ≤ span ±0.055% of Span
accuracy X > span ±(0.01+0.0063 URL/span)% of Span
X 70 kPa (280 inH2O)
URL
500 kPa (2000 inH2O)
(upper range limit)

Measurement span A B
Reference X ≤ span ±0.055% of Span
accuracy X > span ±(0.01+0.0045 URL/span)% of Span
X 0.35 MPa (50 psi) 1.6 MPa (230 psi)
URL
3.5 MPa (500 psi) 16 MPa (2300 psi)
(upper range limit)

Yokogawa Electric Corporation GS 01C31E01-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright June 2012
Tel.: 81-422-52-5690 Fax.: 81-422-52-2018 20th Edition Feb. 2022
<<Contents>> <<Index>> 2
[When /HAC is specified] □ FUNCTIONAL SPECIFICATIONS
Measurement span H Output “◊”
For 4 to 20 mA HART / BRAIN
Reference X ≤ span ±0.04% of Span
accuracy X > span (Output signal code D and J)
±(0.005+0.0049 URL/span)% of Span
Two wire 4 to 20 mA DC output with digital
X 70 kPa (280 inH2O) communications, linear or square root programmable.
URL BRAIN or HART FSK protocol are superimposed on
500 kPa (2000 inH2O)
(upper range limit) the 4 to 20 mA signal.
Output range: 3.6 mA to 21.6 mA
Measurement span A B
Output limits conforming to NAMUR NE43 can be
pre-set by option code C2 or C3.
Reference X ≤ span ±0.04% of Span
accuracy X > span For 1 to 5 V HART
±(0.005+0.0035 URL/span)% of Span
(Output signal code Q)
X 0.35 MPa (50 psi) 1.6 MPa (230 psi) Three or four wire low power 1 to 5 V DC output with
URL HART, linear or square root programmable. HART
3.5 MPa (500 psi) 16 MPa (2300 psi)
(upper range limit) protocol are superimposed on the 1 to 5 V DC signal.
Ambient Temperature Effects per 28°C (50°F) Output range: 0.9 V to 5.4 V DC
Change Failure Alarm
For 4 to 20 mA HART / BRAIN
Capsule Effect (Output signal code D and J)
H ±(0.083% Span + 0.02% URL) Output status at CPU failure and hardware error;
A and B ±(0.083% Span + 0.014% URL) Up-scale: 110%, 21.6 mA DC or more (standard)
Down-scale: −5%, 3.2 mA DC or less
Stability (All normal operating condition)
For 1 to 5 V HART (Output signal code Q)
±0.1% of URL per 10 years
Analog output status at CPU failure and hardware
Power Supply Effects(Output signal code D and J) error;
±0.005 % per Volt (from 21.6 to 32 V DC, 350Ω) Up-scale: 110%, 5.4 V DC or more (standard)
Vibration Effects Down-scale: −5%, 0.8 V DC or less
Amplifier housing code 1 and 3: Damping Time Constant (1st order)
Less than 0.1% of URL when tested per the Amplifier’s damping time constant is adjustable from
requirements of IEC60770-1 field or pipeline 0.00 to 100.00 s by software and added to response
with high vibration level (10-60 Hz, 0.21 mm time.
displacement/60-2000 Hz 3 g) Note: For BRAIN protocol type, when the software
Amplifier housing code 2: damping is set to less than 0.5 s, communication
Less than ±0.1% of URL when tested per the may occasionally be unavailble during the
requirements of IEC60770-1 field with general operation, especially while output changes
application or pipeline with low vibration level (10-60 dynamically. The default setting of damping
ensures stable communication.
Hz 0.15mm displacement /60-500 Hz 2g)
Mounting Position Effects Update Period “◊”
Rotation in diaphragm plane has no effect. Tilting Pressure: 45 ms
up to 90 degree will cause zero shift up to 0.4 kPa Zero Adjustment Limits
(1.6 inH2O) which can be corrected by the zero Zero can be fully elevated or suppressed, within the
adjustment. lower and upper range limits of the capsule.
Response Time (All capsules) “◊” External Zero Adjustment
90 ms External zero is continuously adjustable with
150 ms for H capsule with Wetted Parts Material 0.01% incremental resolution of span. Re-range
code H, M, T, A, D, B and W. can be done locally using the digital indicator with
When software damping is set to zero and including rangesetting switch.
dead time of 45 ms (nominal) Integral Indicator (LCD display) “◊”
5-digit numerical display, 6-digit unit display and bar
graph.
The indicator is configurable to display one or up to
three of the following variables periodically.;
pressure in %, scaled pressure, measured pressure.
See also “Factory Setting”.
Local Parameter Setting
(Output signal code D, J and Q)
Parameter configuration by the external zero
adjustment screw and push button (Integral indicator
code E) offers easy and quick setup for parameters
of Loop test, Tag number, Unit, LRV, URV, Damping,
Output mode (linear/square root), Display out 1, and
Re-range by applying actual pressure (LRV/URV)
and Device Information.

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN Nov. 20, 2019-00
<<Contents>> <<Index>> 3
Burst Pressure Limits Minimum Pressure Limit
69 MPa (10,000 psi) for wetted parts material S and See graph below
L.
47 MPa (6,800 psi) for wetted parts material other
than S and L. 100(14.5) Atmospheric
Self Diagnostics pressure
Working
CPU failure, hardware failure, configuration error, pressure
and over-range error for pressure and capsule kPa abs
temperature. (psi abs)
User-configurable process high/low alarm for
Applicable range
pressure is also available.
10(1.4)
Signal Characterizer
(Output signal code D, J and Q)
User-configurable 10-segment signal characterizer
for 4 to 20 mA output. 2.7(0.38)
SIL Certification
EJA-E series transmitters except Fieldbus,
PROFIBUS PA and 1-5V DC with HART (Low Power) 1(0.14)
-40 0 40 80 120
communication types are certified in compliance with
(-40) (32) (104) (176) (248)
the following standards;
IEC 61508: 2010; Process temperature °C (°F)
Functional Safety of Electrical/electronic/ F01E.ai

programmable electronic related systems; SIL 2 Figure 1. Working Pressure and Process Temperature
capability for single transmitter use, SIL 3 capability
for dual transmitter use. Supply & Load Requirements
Reliability Data different depending on hardware and (Output signal code D and J. Optional features
software revision. or approval codes may affect electrical
For details, refer to Functional Safety Data Sheet. requirements.)
(Document number: TI 01C25A05-01EN or TI With 24 V DC supply, up to a 550Ω load can be
01C25A05-21EN for option code SLT ) used. See graph below.
The document can be downloaded from the website
of Yokogawa.
(Website address: https://www.yokogawa.com/
solutions/products-platforms/field-instruments/)
600
□ NORMAL OPERATING CONDITION E-10.5
R=
(Optional features or approval codes may External 0.0244 Digital
affect limits.) load Communication
resistance range
Ambient Temperature Limits BRAIN and HART
−40 to 85°C (−40 to 185°F)
250
−30 to 80°C (−22 to 176°F) with LCD display
Process Temperature Limits
−40 to 120°C (−40 to 248°F) R (Ω)
Ambient Humidity Limits
0 to 100% RH
10.5 16.6 25.2 42
Maximum Over Pressure Power supply voltage E (V DC)
F02E.ai
Capsule Pressure
Figure 2. Relationship Between Power Supply
H and A 16 MPa (2300 psi)
Voltage and External Load Resistance
B 25 MPa (3600 psi)*
(Output signal code D and J)
*: 24 MPa (3400 psi) for Wetted Parts Material code
H, M, T, A, D and B.
Supply Voltage “◊”
Working Pressure Limits (Silicone oil) For 4 to 20 mA HART / BRAIN
Maximum Pressure Limits (Output signal code D and J)
10.5 to 42 V DC for general use and flameproof type.
Capsule Pressure 10.5 to 32 V DC for lightning protector
H 500 kPa (2000 inH2O) (option code /A.)
A 3.5 MPa (500 psi) 10.5 to 30 V DC for intrinsically safe, type n, or non-
B 16 MPa (2300 psi) incendive type.
Minimum voltage limited at 16.6 V DC for digital
communications, BRAIN and HART

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN Nov. 20, 2019-00
<<Contents>> <<Index>> 4
For 1 to 5 V HART (Output signal code Q) Non-wetted Parts Materials
Power supply : Bolting
9 to 28 V DC for general use and flame proof type. B7 carbon steel, 316L SST or 660 SST
Power Consumption :
0.96 mA to 3 mA, 27 mW Housing
• Low copper cast aluminum alloy
Load for 4 to 20 mA HART / BRAIN • Low copper cast aluminum alloy with corrosion
(Output signal code D and J) resistance properties (copper content ≤ 0.03%,
0 to 1290Ω for operation iron content ≤ 0.15%) (optional)
250 to 600Ω for digital communication • ASTM CF-8M Stainless steel (optional)
Output Load for 1 to 5 V HART Coating of housing
(Output signal code Q) [for aluminum housing]
1 MΩ or greater (meter input impedance) Polyester resin powder coating
Note that with three-wire connection, the cable length Mint-green paint (Munsell 5.6BG 3.3/2.9 or its
may affect the measurement accuracy of the output equivalent)
signal. [for option code /P or /X2]
Communication Requirements “◊” Epoxy and polyurethane resin solvent coating
(Approval codes may affect electrical requirements.) Degrees of protection
BRAIN IP66/IP67, Type 4X
Communication distance Cover O-rings
Up to 2 km (1.25 miles) when using CEV Buna-N, fluoro-rubber (optional)
polyethylene-insulated PVC-sheathed cables. Name plate and tag
Communication distance varies depending on type of 316 SST
cable used.
Fill fluid
Load capacitance Silicone, Fluorinated oil (optional)
0.22 µF or less
Weight
Load inductance [Installation code 7, 8 and 9]
3.3 mH or less 2.8 kg(6.2 lb) for wetted parts material code S and
Input impedance of communicating device L, without integral indicator, mounting bracket, and
10 kΩ or more at 2.4 kHz. process connector.
EMC Conformity Standards Add 1.5 kg (3.3lb) for Amplifier housing code 2.
EN 61326-1 Class A, Table2 Connections
EN 61326-2-3 Refer to “MODEL AND SUFFIX CODES.”
EN 61326-2-5 (for fieldbus) Process connection of cover flange: IEC61518
European Pressure Equipment Directive
2014/68/EU < Related Instruments>
Sound Engineering Practice FieldMate Versatile Device Management Wizard:
EU RoHS Directive Refer to GS 01R01A01-01E.
EN IEC 63000 BRAIN TERMINAL: Refer to GS 01C00A11-00E
Power Distributor: Refer to GS 01B04T01-02E or
Safety Requirement Standards GS 01B04T02-02E
EN 61010-1, C22.2 No.61010-1
• Installation category: I
(Anticipated transient overvoltage 330 V) < Reference >
• Pollution degree: 2 • ; Registered trademark of Yokogawa
• Indoor/Outdoor use Electric Corporation.
• FieldMate; Registered trademark of Yokogawa
□ PHYSICAL SPECIFICATIONS Electric Corporation.
• Teflon; Trademark of E.I. DuPont de Nemours &
Wetted Parts Materials Co.
Diaphragm, cover flange, process connector, • Hastelloy; Trademark of Haynes International Inc.
capsule gasket, and vent/drain plug • HART®: Registered trademark of FieldComm
Refer to “MODEL AND SUFFIX CODES.” Group.
Process connector gasket • FOUNDATION Fieldbus; Trademark of FieldComm
PTFE Teflon Group.
Fluorinated rubber for option code N2 and N3 • PROFIBUS; Registered trademark of Profibus
Nutzerorganisation e.v., Karlsruhe, Germany.
Other company names and product names used in
this material are registered trademarks or trademarks
of their respective owners.

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN July 1, 2021-00
<<Contents>> <<Index>> 5
 MODEL AND SUFFIX CODES
Model Suffix Codes Description
EJA430E ............................... Gauge pressure transmitter
Output signal -D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
-J . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol)*1
-F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol, refer to
GS 01C31T02-01EN)
-G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to
GS 01C31T04-01EN)
-Q . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Low Power, 1 to 5 V DC with digital communication (HART 7 protocol)
Measurement H . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 to 500 kPa (20 to 2000 inH2O)
span (capsule) A . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.03 to 3.5 MPa (4.3 to 500 psi)
B . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.14 to 16 MPa (20 to 2300 psi)
Wetted parts  . . . . . . . . . . . . . . . . . . . . . . . . . Refer to “Wetted Parts Material” Table.
material *2
Process connections 0 . . . . . . . . . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
See the table in the next1 . . . . . . . . . . . . . . . . . . . . . . with Rc1/4 female process connector
page for the codes for a 2 . . . . . . . . . . . . . . . . . . . . . . with Rc1/2 female process connector
diaphragm seal system. 3 . . . . . . . . . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . . . . . . . . . with 1/2 NPT female process connector
► 5 . . . . . . . . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts materia J . . . . . . . . . . . . . . . . . . . B7 carbon steel
G . . . . . . . . . . . . . . . . . . . 316L SST
C . . . . . . . . . . . . . . . . . . . 660 SST
Installation -3 . . . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection down side
-7 . . . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection down side
-8 . . . . . . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . . . . . . Horizontal piping and left side high pressure
-B . . . . . . . . . . . . . . . . . Bottom Process Connection, left side high pressure*3
-U . . . . . . . . . . . . . . . . . Universal flange*3
Amplifier housing 1 . . . . . . . . . . . . . . Cast aluminum alloy
3 . . . . . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties *4
2 . . . . . . . . . . . . . . ASTM CF-8M stainless steel *5
Electrical connection 0 . . . . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . . . . G1/2 female, two electrical connections and a blind plug *6
7 . . . . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug *6
9 . . . . . . . . . . . M20 female, two electrical connections and a blind plug *6
A . . . . . . . . . . . G1/2 female, two electrical connections and a 316 SST blind plug
C . . . . . . . . . . . 1/2 NPT female, two electrical connections and a 316 SST blind plug
D . . . . . . . . . . . M20 female, two electrical connections and a 316 SST blind plug
Integral indicator D . . . . . . . . Digital indicator *7
E . . . . . . . . Digital indicator with the range setting switch (push button) *8
► N . . . . . . . . (None)
Mounting bracket ► B . . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . . 304 SST or SCS13A 2-inch pipe mounting, L type (for vertical piping)
J . . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . . 316 SST or SCS14A 2-inch pipe mounting, L type (for vertical piping)
M . . . . . . 316 SST or SCS14A 2-inch pipe mounting (for bottom process connection
type)
N . . . . . . (None)
Optional Codes / Optional specification

The “►” marks indicate the most typical selection for each specification.
*1: HART 5 or HART 7 is selectable. Specify upon ordering.
*2: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage
to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm
and the fill fluid can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium
hypochlorite, and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the
wetted parts material.
*3: Applicable only for Wetted parts material code S.
*4: Not applicable for electrical connection code 0, 5, 7, 9 and A.
*5: Not applicable for electrical connection code 0, 5, 7 and 9.
*6: Material of a blind plug; aluminum alloy for code 5 and 9, and SUS304 for code 7.
*7: Not applicable for output signal code G.
*8: Not applicable for output signal code F.

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN June 1, 2017-00
<<Contents>> <<Index>> 6
Table. Wetted Parts Materials
Wetted parts Cover flange and process
Capsule Capsule gasket Vent/Drain plug
material code connector
Hastelloy C-276 (Diaphragm)
*2
S# ASTM CF-8M *1*8 Teflon-coated 316L SST 316 SST
F316L SST, 316L SST (Others)
Hastelloy C-276 *2 (Diaphragm)
L# ASTM CF-3M *7*8 Teflon-coated 316L SST 316L SST
F316L SST, 316L SST (Others)
H# ASTM CF-8M *1*8 Hastelloy C-276 *2 PTFE Teflon 316 SST
M# ASTM CF-8M *1*8 Monel PTFE Teflon 316 SST
T ASTM CF-8M *1*8 Tantalum PTFE Teflon 316 SST
A# Hastelloy C-276 equivalent *3 Hastelloy C-276 *2 PTFE Teflon Hastelloy C-276 *2
D Hastelloy C-276 equivalent *3 Tantalum PTFE Teflon Hastelloy C-276 *2
B# Monel equivalent *4 Monel PTFE Teflon Monel
W# Super Duplex SST equivalent *5 Hastelloy C-276 *2 PTFE Teflon Super Duplex SST *6
*1: Cast version of 316 SST. Equivalent to SCS14A.
*2: Hastelloy C-276 or ASTM N10276.
*3: Indicated material is equivalent to ASTM CW-12MW.
*4: Indicated material is equivalent to ASTM M35-2.
*5: Indicated material is equivalent to ASTM A995 Grade5A.
*6: ASTM S32750 or EN 10272 1.4410.
*7: Cast version of 316L SST. Equivalent to SCS16A.
*8: Intergranular corrosion test passed according to ASTM A262 Practice E.
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR0175/ISO 15156.
Please refer to the latest standards for details. Selected materials also conform to NACE MR0103.

[Process Connections Code for Diaphragm Seal System]


The table below shows the codes dedicated for the combination with a diaphragm seal system. They are only
available when the transmitter is ordered in combination with a diaphragm seal system. Please also refer to GS
01C25W01-01EN.

Process Connections Code High Pressure Side Low Pressure Side


B With C80F, C82F or C70S diaphragm seal Open to atmosphere
With C80F or C82F diaphragm seal for high
G Open to atmosphere
vacuum use
80F, C82F, and C70S stands for C80FW or C80FE remote mount flanged diaphragm seal, C82FA inner diaphragm adapter
connection seal, C82FD inner diaphragm flanged seal, and C70SW or C70SE remote mount hygienic diaphragm seal respectively.

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN July 1, 2021-00
<<Contents>> <<Index>> 7
 OPTIONAL SPECIFICATIONS (For Explosion Protected type) “◊”
For other agency approvals and marine approvals, please refer to GS 01C25A20-01EN.
Please select appropriate equipment in accordance with the laws and regulations of the relevant country/region, when
it is used in a location where explosive atmospheres may be present.

Item Description Code


Factory Mutual FM Explosionproof Approval *1
(FM) Applicable Standard: FM3600, FM3615, FM3810, NEMA 250, ANSI/UL 61010-1, ANSI/UL 61010-2-30
Explosionproof for Class I, Division 1, Groups B, C and D, Dust-ignitionproof for Class II/III, Division 1,
FF1
Groups E, F and G, in Hazardous locations, indoors and outdoors (Enclosure: Type 4X)
“FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.”
Temperature class: T6, Amb. Temp.: –40 to 60°C (–40 to 140°F)
FM Intrinsically safe Approval *1*3
Applicable Standard: ‌FM 3600, FM 3610, FM 3611, FM 3810, ANSI/ISA-60079-0, ANSI/ISA-60079-11,
ANSI/ISA-61010-1, NEMA 250
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
Groups E, F & G and Class III, Division 1, Class I, Zone 0, in Hazardous Locations, AEx ia IIC
Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2, FS1
Groups F & G, Class I, Zone 2, Group IIC, in Hazardous Locations
Enclosure: Type 4X, Temp. Class: T4, Amb. Temp.: –60 to 60°C (–75 to 140°F)
Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G] Vmax=30 V, Imax=200 mA, Pmax=1 W, Ci=6 nF, Li=0 µH
[Groups C, D, E, F and G] Vmax=30 V, Imax=225 mA, Pmax=1 W, Ci=6 nF, Li=0 µH
Combined FF1 and FS1 *1*3 FU1
ATEX ATEX Flameproof Approval *1
Applicable Standard: EN IEC 60079-0, EN 60079-1, EN 60079-31
Certificate: KEMA 07ATEX0109 X
II 2 G Ex db IIC T6...T4 Gb, II 2 D Ex tb IIIC T85°C Db
Degree of protection: IP66/IP67
KF22
Amb. Temp. (Tamb) for gas-proof :
T4; –50 to 75°C (–58 to 167°F), T5; –50 to 80°C (–58 to 176°F), T6; –50 to 75°C (–58 to 167°F)
Process Temp. for gas-proof (Tp):
T4; –50 to 120°C (–58 to 248°F), T5; –50 to 100°C (–58 to 212°F), T6; –50 to 85°C (–58 to 185°F)
Max. surface Temp. for dust-proof: T85°C (Tamb: –30 to 75°C, Tp: –30 to 85°C) *2
ATEX Intrinsically safe Approval *1*3
Applicable Standard: EN IEC 60079-0, EN 60079-11
Certificate: DEKRA 11ATEX0228 X
II 1 G Ex ia IIC T4 Ga, II 2 D Ex ia IIIC T85°C T100°C T120°C Db
Degree of protection: IP66/IP67
KS21
Amb. Temp. (Tamb) for EPL Ga: –50 to 60°C (–58 to 140°F)
Maximum Process Temp. (Tp) for EPL Ga:120°C
Electrical data: Ui=30 V, Ii=200 mA, Pi=0.9 W, Ci=27.6 nF, Li=0 µH
Amb. Temp. for EPL Db: –30 to 60°C *2
Max. surface Temp. for EPL Db: T85°C (Tp: 80°C), T100°C (Tp: 100°C), T120°C (Tp: 120°C)
Multiple types of protection (KF22, KS21 or Intrinsically safe Ex ic) *1*3
Applicable Standard: EN IEC 60079-0, EN 60079-11
KU22
II 3 G Ex ic IIC T4 Gc, Amb. Temp.: –30 to 60°C (–22 to 140°F) *2
Ui=30 V, Ci=27.6 nF, Li=0 μH

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN July 1, 2021-00
<<Contents>> <<Index>> 8
Item Description Code
Canadian CSA Explosionproof Approval *1
Standards Certificate: 2014354
Association Applicable Standard: C22.2 No. 25, C22.2 No. 30, CAN/CSA-C22.2 No. 94,
(CSA) CAN/CSA-C22.2 No. 61010-1, CAN/CSA-C22.2 No. 61010-2-030, CAN/CSA-C22.2 No. 60079-0,
CAN/CSA-C22.2 No. 60079-1, CAN/CSA-C22.2 No. 60529
Explosion-proof for Class I, Groups B, C and D.
Dustignition-proof for Class II/III, Groups E, F and G.
When installed in Division 2, “SEAL NOT REQUIRED” Enclosure: Type 4X,
Temp. Code: T6...T4 CF1
Ex d IIC T6...T4 Enclosure: IP66/IP67
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6 *2
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA-12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
CSA Intrinsically safe Approval *1*3
Certificate: 1606623
[For Division System]
Applicable Standard: C22.2 No.0, C22.2 No.94, C22.2 No.157, C22.2 No.213, C22.2 No.61010-1,
C22.2 No.61010-2-030
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G,
Class III, Division 1, Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division 2,
Groups F & G, Class III, Division 1
Enclosure: Type 4X, Temp. Code: T4 Amb. Temp.: –50 to 60°C(–58 to 140°F) *2
Electrical Parameters: [Intrinsically Safe] Vmax=30V, Imax=200mA, Pmax=0.9W, Ci=10nF, Li=0 µH
[Nonincendive] Vmax=30V, Ci=10nF, Li=0 µH
CS1
[For Zone System]
Applicable Standard: CAN/CSA-C22.2 60079-0, CAN/CSA-E60079-11, CAN/CSA-E60079-15,
CAN/CSA-C22.2 No.60529
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP66/IP67
Amb. Temp.: –50 to 60°C(–58 to 140°F) *2, Max. Process Temp.: 120°C(248°F)
Electrical Parameters: [Ex ia] Ui=30V, Ii=200mA, Pi=0.9W, Ci=10nF, Li=0 µH
[Ex nL] Ui=30V, Ci=10nF, Li=0 µH
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA-12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
Combined CF1 and CS1 *1*3 CU1
IECEx IECEx Flameproof Approval *1
Applicable Standard: IEC 60079-0, IEC60079-1
Certificate: IECEx CSA 07.0008
Flameproof for Zone 1, Ex d IIC T6...T4 Gb Enclosure: IP66/IP67 SF2
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6
IECEx Intrinsically safe and Flameproof Approval *1*3
Intrinsically safe Ex ia
Certificate: IECEx DEK 11.0081X
Applicable Standard: IEC 60079-0, IEC 60079-11
Ex ia IIC T4 Ga Enclosure: IP66/IP67
Amb. Temp.: –50 to 60 °C(–58 to 140 °F), Max. Process Temp.: 120 °C(248 °F)
Electrical Parameters: Ui=30 V, Ii=200 mA, Pi=0.9 W, Ci=27.6 nF, Li=0 μH
Intrinsically safe Ex ic
Certificate: IECEx DEK 13.0061X
Applicable Standard: IEC 60079-0, IEC 60079-11
SU21
Ex ic IIC T4 Gc IP code: IP66
Amb. Temp.: –30 to 60°C(–22 to 140°F) *2, Max. Process Temp.: 120°C(248°F)
Electrical Parameters: Ui=30V,Ci=27.6 nF, Li=0 μH
Flameproof
Certificate: IECEx CSA 07.0008
Applicable Standard: IEC 60079-0, IEC60079-1
Flameproof for Zone 1, Ex d IIC T6...T4 Gb Enclosure: IP66/IP67
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN Feb. 1, 2022-00
<<Contents>> <<Index>> 9
Item Description Code
IECEx IECEx Flameproof Approval *1
Applicable Standard: IEC 60079-0, IEC 60079-1, IEC 60079-31
Certificate: IECEx DEK 14.0046X
Enclosure: IP66/IP67
Ex db IIC T6...T4 Gb, Ex tb IIIC T85°C Db
Amb. Temp. (Tamb) for gas-proof : SF22
T4; –50 to 75°C (–58 to 167°F), T5; –50 to 80°C (–58 to 176°F), T6; –50 to 75°C (–58 to 167°F)
Process Temp. for gas-proof (Tp):
T4; –50 to 120°C (–58 to 248°F), T5; –50 to 100°C (–58 to 212°F),
T6; –50 to 85°C (–58 to 185°F)
Max. surface Temp. for dust-proof: T85°C (Tamb: –30 to 75°C, Tp: –30 to 85°C) *2
IECEx Intrinsically safe and SF22 *1*3
Intrinsically safe Ex ia
Certificate: IECEx DEK 11.0081X
Applicable Standard: IEC 60079-0, IEC 60079-11
Ex ia IIC T4 Ga Enclosure: IP66/IP67
Amb. Temp.: –50 to 60°C (–58 to 140°F), Max. Process Temp.: 120°C (248°F)
Electrical Parameters: Ui=30V, Ii=200mA, Pi=0.9W, Ci=27.6nF, Li=0 μH
Intrinsically safe Ex ic SU22
Certificate: IECEx DEK 13.0061X
Applicable Standard: IEC 60079-0, IEC 60079-11
Ex ic IIC T4 Gc IP code: IP66
Amb. Temp.: –30 to 60°C (–22 to 140°F) *2, Max. Process Temp.: 120°C (248°F)
Electrical Parameters: Ui=30V,Ci=27.6 nF, Li=0 μH
Flameproof
Refer to SF22
*1: Applicable for Electrical connection code 2, 4, 7, 9, C and D.
*2: Lower limit of temperature is –15°C (5°F) when /HE is specified.
*3: Not applicable for output signal code Q.

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN Feb. 1, 2022-00
<<Contents>> <<Index>> 10
 OPTIONAL SPECIFICATIONS
Item Description Code
High accuracy type *1*21*29 High accuracy HAC
Painting Color change Amplifier cover only*2 P
Amplifier cover and terminal cover, Munsell 7.5 R4/14 PR
Coating change Anti-corrosion coating*3 X2
316 SST exterior parts 316 SST zero-adjustment screw and setscrews*4 HC
Fluoro-rubber O-ring All O-rings of amplifier housing. Lower limit of ambient temperature: –15°C (5°F) HE
Lightning protector Transmitter power supply voltage: 10.5 to 32 V DC ( 10.5 to 30 V DC for intrinsically safe type,
9 to 32 V DC for Fieldbus communication type.)
A
Allowable current: Max. 6000 A ( 1×40 µs ), Repeating 1000 A ( 1×40 µs ) 100 times
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Oil-prohibited use*5*29 Degrease cleansing treatment K1
Degrease cleansing treatment with fluorinated oilfilled capsule.
K2
Operating temperature −20 to 80°C (−4 to 176°F)
Oil-prohibited use with Degrease cleansing and dehydrating treatment K5
dehydrating treatment*5*29 Degrease cleansing and dehydrating treatment with fluorinated oilfilled capsule.
K6
Operating temperature −20 to 80°C (−4 to 176°F)
Capsule fill fluid*29 Flourinated oil filled in capsule
K3
Operating temperature −20 to 80°C (−4 to 176°F)
Calibration units*6 P calibration (psi unit) D1
bar calibration (bar unit) (See Table for Span and Range Limits.) D3
M calibration (kgf/cm2 unit) D4
Plug option*24*25*29 Long vent*7: Total length: 119 mm (standard: 34 mm); Total length when combining with
U1
optional code K1, K2, K5, and K6: 130 mm. Material: 316 SST U1.
Without vent and drain plugs UN
Gold-plated capsule gasket*8*29 Gold-plated 316L SST capsule gasket. Without drain and vent plugs. GS
Gold-plated diaphragm*9*29 Surface of isolating diaphragms are gold plated, effective Gold plate thickness: 3 μm A1
for hydrogen permeation. Gold plate thickness: 10 μm A2
Output limits and failure Failure alarm down-scale : Output status at CPU failure and hardware error is −5%, 3.2mA DC
C1
operation*10 or less for 4 to 20 mA output type, and −5%, 0.8V DC or less for 1 to 5 V output type.
Failure alarm down-scale: Output status at CPU
NAMUR NE43 Compliant C2
failure and hardware error is −5%, 3.2 mA DC or less.
Output signal limits:
3.8 mA to 20.5 mA *22 Failure alarm up-scale: Output status at CPU
C3
failure and hardware error is 110%, 21.6 mA or more.
Body option*11*29 Right side high pressure, without drain and vent plugs N1
Terminal N1 and Process connection, based on IEC61518 with female thread on both sides of cover
Side N2
flange, with blind kidney flanges on back
L H N2, and Material certificate for cover flange, diaphragm, capsule body, and blind kidney flange N3
F03E.ai

Wired tag plate 316 SST tag plate wired onto transmitter N4
Data configuration at factory*12 Software damping, Descriptor,
Data configuration for HART communication type CA
Message
Data configuration for BRAIN communication type Software damping CB
Material certificate*13*29 Cover flange *14 M01
Cover flange, Process connector *15 M11
Cover flange, Diaphragm, Capsule body*14*30 MA1
Cover flange, Process connector, Diaphragm, Capsule body*15*26 MC1
Cover flange, Bolt and Nut for cover flange, Diaphragm, Capsule body, Vent and Drain plug,
MG1
Vent screw, Capsule gasket*14*23*25
Cover flange, Process connector, Bolt and nut for cover flange, Bolt for process connector,
MH1
Diaphragm, Capsule body, Vent and Drain plug, Vent screw, Capsule gasket*15*23*25
Pressure test/ Test Pressure: 500 kPa (2000 inH2O)*17 T11
Leak test certificate*16*29 Nitrogen Gas*20
Test Pressure: 3.5 MPa (500 psi)*18 T01
Retention time: one minute
Test Pressure: 16 MPa (2300 psi)*19 T12
Parameter list*27 List of setting and adjustment parameters YP
Functional safety(SIL)*28 Low temperature expansion of functional safety Amb.Temp.: −55 to 85°C SLT

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN Nov. 20, 2019-00
<<Contents>> <<Index>> 11
*1: Applicable for wetted parts material code S or L. Not applicable for /A2.
*2: Not applicable for amplifier housing code 2 and 3.
*3: Not applicable with color change option. Not applicable for amplifier housing code 2.
*4: 316 or 316L SST. The specification is included in amplifier code 2.
*5: Applicable for wetted parts material code S, M, H and T.
*6: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by option codes D1,
D3, and D4.
*7: Applicable for vertical impulse piping type (installation code 3 or 7) and wetted parts material code S, M, H and T.
*8: Applicable for wetted parts material code S; process connection code 0 and 5; and installation code 8 and 9.
Not applicable for option code U1, N2, N3 and M11. No PTFE is used for wetted parts.
*9: Applicable for wetted parts material code S or L. /A2 is not applicable with FM approval.
*10: Applicable for output signal codes D and J. The hardware error indicates faulty amplifier or capsule.
*11: Applicable for wetted parts material code S, M, H and T.; process connection codes 3, 4, and 5; installation code 9; and
mounting bracket code N. Process connection faces on the other side of zero adjustment screw.
*12: Also see ‘Ordering Information’.
*13: Material traceability certification, per EN 10204 3.1B.
*14: Applicable for process connections code 0 and 5.
*15: Applicable for process connections code 1, 2, 3, and 4.
*16: The unit on the certificate is always Pa unit regardless of selection of option code D1, D3 or D4.
*17: Applicable for capsule code H.
*18: Applicable for capsule code A.
*19: Applicable for capsule code B.
*20: Dry nitrogen gas is used for oil-prohibited use (option codes K1, K2, K5, and K6).
*21: Not applicable for output signal code Q.
*22: The 1 to 5 V voltage output corresponding to 4 to 20 mA current output is applied to output signal code Q which is non-
compliant to NAMUR NE43.
*23: Not applicable with plug option code UN.
*24: Not applicable for installation code -U.
*25: Not applicable with option code N1, N2, N3 and GS.
*26: Applicable for option code UN and N1.
*27: Applicable for output signal code D and J.
*28: Not applicable for output signal code F, G, Q, process connections code for diaphragm seal system.
*29: Not applicable with process connections code for diaphragm seal system B and G.
*30: Applicable for option code UN, N1, and GS.

 OPTIONAL SPECIFICATIONS (FOR DIAPHRAGM SEAL SYSTEM)


The table below shows the code dedicated for the combination with a diaphragm seal system. It is only available when
the transmitter is ordered in combination with a diaphragm seal system. Please also refer to GS 01C25W01-01EN

Item Descriptions Code


Capsule fill fluid Fluorinated oil filled in capsule Operating temperature −20 to 80°C (−4 to 176°F) K13
Material certificate Bolt and nut for cover flange M51

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN Mar. 30, 2020-00
<<Contents>> <<Index>> 12
 DIMENSIONS
Unit: mm (approx.inch)

● Vertical Impulse Piping Type


Wetted Parts Material Code S, L

Electrical connection
for code 5, 9, A, and D.
Process connector downside

6(0.24)
(Installation code 7)

242(9.53) 110(4.33)

(2.13)
175(6.89)

54
12 39
97 129(5.08) 2-inch pipe
(3.82) (0.47) (1.54) (O.D. 60.5 mm)
Mounting bracket External indicator Vent/Drain plugs*5 Process connector upside
(L-type,optional) Conduit connection (Installation code 6)
(2.05)

(optional)
52

Integral indicator Process connection


(optional)
97(3.82)
223(8.78)

67(2.64)

(1.61)
ø78(3.07)

138(5.43)*2
95(3.74)

ø70(2.76)

41
(1.61)
67(2.64)

223(8.78)
41

97(3.82)
Process
Conduit connector
Process connection connection (optional)
27
Zero adjustment High Low

(2.05)
pressure (1.06) pressure

52
Ground terminal side*1 side*1
Open to atmosphere
ø10(0.39) F04E.ai

● Horizontal Impulse Piping Type (Installation code 9)


Wetted Parts Material Code S, L
External indicator 89(3.50) 67 Conduit connection 110(4.33)
Conduit connection Zero
(2.64) adjustment 12 39
(optional) 95(3.74) Integral indicator (0.47) (1.54)
(optional)
54
ø78(3.07)

(2.76)

(2.13)
ø70

6
175(6.89)
145(5.71)

129(5.08)

(0.24)
Vent plug, Ground
Dran plug*3*5 terminal

Electrical connection Vent plug*3*5


for code 5, 9, A, and D. Drain plug*3*5 Open to atmosphere
124(4.88)

41 ø5(0.20)
Process connection 27(1.06)
(1.61) Low
High
pressure pressure
115(4.53) Process connector
(1.63)

side*1
41.3

side*1
(optional)
(1.85)
47

Mounting bracket 2-inch pipe


(Flat-type,optional) (O.D. 60.5 mm)
65*2
(2.56) F05E.ai

*1: When Installation code 2, 3, or 8 is selected, high and low pressure side on the above figure are reversed.
(i.e. High pressure side is on the right side.)
*2: When option code K1, K2, K5, or K6 is selected, add 15 mm (0.59 inch) to the value in the figure.
*3: Not available when option code GS is specified.
*4: When electrical connection code 7 or C is selected, a blind plug is protruded up to 8 mm (0.31 inch) from the conduit connection.
*5: When option code UN is specified, Vent/Drain holes and plugs are not applicable.

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN Nov. 20, 2019-00
<<Contents>> <<Index>> 13
Unit: mm (approx.inch)

● Vertical Impulse Piping Type


Wetted Parts Material Code: H, M, T, A, D, B, W

Electrical connection
for code 5, 9, A, and D.
Process connector downside

6(0.24)
(Installation code 7)
256(10.10) 110(4.33)
194(7.64)

(2.13)
12*5 39

54
97 143(5.63) 2-inch pipe
(3.82) (0.47) (1.54)
(O.D. 60.5 mm)
External indicator
Mounting bracket Conduit connection Process connector upside
(2.05)

(L-type,optional) (optional)
52

Process connection (Installation code 6)


Integral indicator Vent/Drain
(optional) plugs*4
102(4.02)
234(9.21)

72(2.83)

(1.81)
148(5.83)*2
ø78(3.07)

46
(3.74)

(2.76)
ø70
95
(1.81)

234(9.21)
72(2.83)
46

102(4.02)
Conduit
connection High 27 Low
Process connection pressure pressure
Zero adjustment side*1 (1.06)

(2.05)
Ground terminal side*1

52
Process connector
(optional) Open to atmosphere
ø10(0.39)
F06E.ai

● Horizontal Impulse Piping Type (Installation code 9)


Wetted Parts Material Code: H, M, T, A, D, B, W
Conduit connection
External indicator 94(3.70) 72(2.83) 110(4.33)
Conduit connection Zero
(optional) 95(3.75) adjustment 12*5 39
Integral indicator
(optional) (0.47) (1.54)
54
ø78(3.07)

(2.13)
6
(2.76)
ø70

(0.24)
159(6.26)

143(5.63)
194(7.64)

Ground terminal
Electrical connection
for code 5, 9, A, and D. Vent plug*4

Drain plug*4 Open to atmosphere


124(4.88)

46 Process connection ø5(0.20)


(1.81) 54
Process connector (2.13)
125(4.92)
(optional)
(1.63)

2-inch pipe
41.3

(1.85)

(O.D. 60.5 mm)


47

Mounting bracket
(Flat-type,optional)
67*2
(2.64) F07E.ai

*1: When Installation code 2, 3, or 8 is selected, high and low pressure side on the above figure are reversed.
(i.e. High pressure side is on the right side.)
*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm (0.59 inch) to the value in the figure.
*3: When electrical connection code 7 or C is selected, a blind plug is protruded up to 8 mm (0.31 inch) from the conduit connection.
*4: When option code UN is specified, Vent/Drain holes and plugs are not applicable.
*5: When measurement span code H is selected, 9 mm (0.35 inch) for installation code 6, 7 and 9, or 15 mm (0.59 inch) for
installation code 2, 3 and 8.

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN July 1, 2021-00
<<Contents>> <<Index>> 14
Unit: mm (approx.inch)

● Universal Flange (INSTALLATION CODE ‘U’)


58 67 110(4.33)
External indicator (2.28) (2.64)
Conduit connection Conduit connection 12 39
95(3.74) Zero
(optional) Integral indicator adjustment (0.47) (1.54)
54 (optional)

ø78(3.07)
(2.13)
6

(2.76)
ø70
145(5.71)

(0.24)

129(5.08)
175(6.89)
Ground terminal

Electrical connection

(1.63)
41.3
for code 5, 9, A, and D.
Open to atmosphere
Drain plug ø10(0.39)
41 Process connection 65*1
Vent plug Open to atmosphere
(1.61) (2.56) ø5(0.2)
115(4.53) High Low
Process connector pressure pressure
Drain plug (optional) side side
F08E.ai

*1: When Option code K1, K2, K5, or K6 is selected, add 15 mm (0.59 inch) to the value.
*2: When electrical connection code 7 or C is selected, a blind plug is protruded up to 8 mm (0.31 inch) from the conduit connection.

● Bottom Process Connection (Installation code B)


54
(2.13) 95(3.74) 188(7.40)
6
Integral indicator
(0.24) 73 110(4.33)
(optional) Zero
(2.87) adjustment 12 39
Conduit connection (0.47) (1.54)
Electrical connection
ø78(3.07)

for code 5, 9, A, and D.


(2.76)
ø70

109(4.29)
159(6.26)

Extenal indicator
Conduit connection
(optional)
Ground terminal

Vent plug*3
Mounting bracket*1
(2.36)

High Low
60

(optional) pressure pressure


side side

2-inch pipe Process connector 27


(O.D. 60.5 mm) (optional) (1.06) Open to
atmosphere
Process connection 65 129 ø10(0.39)
(2.56) (5.08)

41.3
(1.63) F09E.ai

*1: A transmitter with SST housing is not applicable for mounting to horizontal 2-inch pipe.
*2: When electrical connection code 7 or C is selected, a blind plug is protruded up to 8 mm (0.31 inch) from the conduit connection.
*3: When option code UN is specified, Vent holes and plugs are not applicable.

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN Nov. 20, 2019-00
<<Contents>> <<Index>> 15

● Terminal Configuration ● Terminal Wiring for 4 to 20 mA output,


FOUNDATION Fieldbus and PROFIBUS PA
communication types
+ 1
Power supply and output terminals
SUPPLY – 2

CHECK + 3
– 2
External indicator (ammeter) terminals*1*2

Ground terminal

*1: When using an external indicator or check meter, the internal


resistance must be 10 Ω or less.
*2: Not available for FOUNDATION Fieldbus and PROFIBUS PA
Terminal 1 Terminal 3 communication types.
Terminal 2
● Terminal Wiring for 1 to 5 V output
+ 1
Power supply terminals
SUPPLY – 2

VOUT + 3 1 to 5 V DC with HART communication


– 2 terminals
Ground terminal

Three or four wire connection. For four wire connection, both supply
and signal lines use SUPPLY - terminal.
F10E.ai

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN Nov. 7, 2016-00
<<Contents>> <<Index>> 16

< Ordering Information > “◊” < Factory Setting > “◊”
Specify the following when ordering
Tag number As specified in order
1. Model, suffix codes, and option codes
2. Calibration range and units Software
‘2.00 s’ or as specified in order
1) Calibration range can be specified with range damping *1
value specifications up to 5 digits (excluding Calibration range
As specified in order
any decimal point) for low or high range limits lower range value
within the range of -32000 to 32000. When Calibration range
reverse range is designated, specify Lower upper range As specified in order
Range Value(LRV) as greater than Upper Range value
Value(URV.) Selected from mmH2O, mmH2O(68°F),
2) Specify only one unit from the table, ‘Factory mmAq*2, mmWG*2, mmHg, Pa, hPa*2,
Calibration range kPa, MPa, mbar, bar, gf/cm2,
Settings’ when shipped.’
units kgf/cm2, inH2O, inH2O(68°F), inHg, ftH2O,
3. Display scale and units (for transmitters equipped ftH2O(68°F) or psi. (Only one unit can be
with integral indicator only) specified)
Specify either 0 to 100 % or engineering unit scale Designated value specified in order.
and ‘Range and Unit’ for engineering units scale: Display setting
(%, or user scaled value.)
Scale range can be specified with range limit
specifications up to 5 digits (excluding any decimal *1: To specify this item at factory, option code CA or
point) for low or high range limits within the range CB is required.
of -32000 to 32000. The unit display consists of *2: Not available for HART protocol type.
6-digit, therefore, if the specified unit is longer than
7 characters excluding ‘/’, the first 6 characters will < Material Cross Reference >
be displayed on the unit display.
4. HART PROTOCOL ASTM JIS
When output signal code is “J”, specify the HART 316 SUS316
protocol revision “5” or “7”. F316 SUSF316
5. TAG NO (if required) 316L SUS316L
Specified characters (up to 16 characters for F316L SUSF316L
BRAIN, 22 characters for HART, or 16 characters
304 SUS304
for /N4 tag) are engraved on the stainless steel tag
plate fixed on the housing. F304 SUSF304
6. SOFTWARE TAG (for HART only. if required) 660 SUH660
Specified characters (up to 32 characters) are set B7 SNB7
as “Tag” (the first 8 characters) and “Long tag”*1 CF-8M SCS14A
(32 characters) in the amplifier memory. Use
alphanumeric capital letters.
When the “SOFTWARE TAG” is not specified, <Information on EU WEEE Directive>
specified “TAG NO” is set as “Tag” (the first 8 EU WEEE (Waste Electrical and Electronic Equipment)
characters) and “Long tag”*1 (22 characters) in the Directive is only valid in the EU.
amplifier memory. This instrument is intended to be sold and used only
*1: applicable only when HART 7 is selected. as a part of equipment which is excluded from WEEE
7. Other factory configurations (if required) Directive, such as large-scale stationary industrial
Specifying option code CA or CB will allow further tools, a large-scale fixed installation and so on, and,
configuration at factory. Following are configurable therefore, subjected to the exclusion from the scope
items and setting range. of the WEEE Directive. The instrument should be
[/CA : For HART communication type] disposed of in accordance with local and national
1) Descriptor (up to 16 characters) legislation/regulations.
2) Message (up to 30 characters)
3) Software damping in second (0.00 to 100.00)
[/CB : For BRAIN communication type]
1) Software damping in second (0.00 to 100.00)

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 01C31E01-01EN April 10, 2018-00
Subject to change without notice.