11kV Switchgear Schemes

You might also like

Download as ppsx, pdf, or txt
Download as ppsx, pdf, or txt
You are on page 1of 17

11kV SWITCHGEAR

Revision Number. 0
Contents
1. 11kV Switchgear Video
2. 11kV Switchgear SLD
3. CB schematic Drawing
4. 11kV Switchgear Control Circuit
a. Outgoing Feeder Panel
b. TR Incomer Panel
c. Bus Tie Panel
d. Measuring Panel

Global Top Energy Solution Provider 2


OUTGOING FEEDER

OUTGOING FEEDER

TR INCOMER FEEDER

OUTGOING FEEDER

OUTGOING FEEDER
2. 11kV SWITCHGEAR SLD

OUTGOING FEEDER

MEASURING FEEDER

BUS TIE PANEL

MEASURING FEEDER

OUTGOING FEEDER

OUTGOING FEEDER

OUTGOING FEEDER

TR INCOMER FEEDER
Global Top Energy Solution Provider
3
3. CB SCHEMATIC DRAWING

Global Top Energy Solution Provider 4


4. 11kV Switchgear Control/Alarm Circuit

A. Closing/Opening via discrepancy switch


LOCAL LOCAL
LOCAL CLOSING (CB OPENING
CLOSING (CB IN SERVICE)
IN TEST)

Global Top Energy Solution Provider 5


4. 11kV Switchgear Control/Alarm Circuit

B. Closing/Opening Circuit via BCU


BCU CLOSING BCU
(CB in OPENING
SERVICE)

Global Top Energy Solution Provider 6


4. 11kV Switchgear Control/Alarm Circuit
A. OUTGOING FEEDER CLOSE LOGIC (SOFT-
WARE)

SOFTWARE INTERLOCKS:
1. PROTECTION NOT LOCK-OUT
2. NO PROTECTION TRIPS
3. VCB IN SERVICE
4. BUS ES OPEN AND LINE ES ARE OPEN
5. TCS ARE HEALTHY
6. SPRING IS CHARGED

Global Top Energy Solution Provider 7


4. 11kV Switchgear Control/Alarm Circuit
A. TR INCOMER CLOSE LOGIC (SOFTWARE)
SOFTWARE INTERLOCKS:
1. PROTECTION NOT LOCK-OUT
2. NO PROTECTION TRIPS
3. VCB IN SERVICE
4. BUS ES OPEN AND “NO
UNDERVOLTAGE AND NO
OVERVOLTAGE IN BUS BAR”
5. TR ES ARE OPEN
6. TCS ARE HEALTHY
7. SPRING IS CHARGED
8. SYNCHRONIZATION OK
9. 33KV TR PROTECTION NOT LOCK-OUT
10. 33KV TR CB CLOSE
11. 33KV TR ES OPEN
HARDWIRE INTERLOCK:
1. 33KV PROTECTION RELAY NOT FAULTY

Global Top Energy Solution Provider 8


4. 11kV Switchgear Control/Alarm Circuit

A. BUS TIE CLOSE LOGIC (SOFTWARE)

SOFTWARE INTERLOCKS:
1. PROTECTION NOT LOCK-OUT
2. NO PROTECTION TRIPS
3. VCB IN SERVICE
4. BUS ES 1 and 2 ARE OPEN
5. NO UNDERVOLTAGE AND NO
OVERVOLTAGE IN BUS BAR
6. TCS ARE HEALTHY
7. SPRING IS CHARGED
8. SYNCHRONIZATION OK
Global Top Energy Solution Provider 9
4. 11kV Switchgear Control/Alarm Circuit

B. OUTGOING FEEDER BCU Opening Logic (SOFTWARE)

Global Top Energy Solution Provider 10


4. 11kV Switchgear Control/Alarm Circuit

B. TR INCOMER / BUS TIE BCU Opening Logic (SOFTWARE)

Global Top Energy Solution Provider 11


4. 11kV Switchgear Control/Alarm Circuit

C. Outgoing / Bus Tie Protection Trip Circuit PROTECTION


TRIP

Global Top Energy Solution Provider 12


4. 11kV Switchgear Control/Alarm Circuit
1. 33kV TR
C. TR Incomer Protection Trip Circuit PROTECTION
1. PROTECTION
TRIP
TRIP

Global Top Energy Solution Provider 13


4. 11kV Switchgear Control/Alarm Circuit

C. Outgoing / Bus Tie /TR Inc Protection Trip CircuitPROTECTION


TRIP

Global Top Energy Solution Provider 14


4. 11kV Switchgear Control/Alarm Circuit

C. Outgoing/TR Inc / Bus Tie Common alarm

Global Top Energy Solution Provider 15


4. 11kV Switchgear Control/Alarm Circuit

C. Measuring Panel

BUS ES
OV BUS ES
OV
BUS ES OV

UV UV
UV

Global Top Energy Solution Provider 16


Global Top Energy Solution Provider

THANK YOU!