ENVIROMUX-STSP-xx Pipe Sensor

Installation Manual
The ENVIROMUX-STSP-xx (xx= cable length ordered) is an outdoor temperature sensor
designed to work in combination with a NTI SERIMUX-S-x Secure SSH Console Serial Switch
or ENVIROMUX-SEMS-16 Server Environment Monitoring Switch to measure the surface
temperature when mounted on a thin-walled steel, copper, or aluminum pipe. The
ENVIROMUX-STSP-xx is a water-tight temperature sensor designed for self-centering and
easy to install.

Features include:
• Mount to the outside of a thin-walled steel, copper, or aluminum pipe (up to 1/4" thick
wall).

• Copper contact transmits surface temperature to thermal sensor.

• Weatherproof enclosure designed to IP67 specifications.

• Applications from -40°F to 185°F (-40°C to 85°C).

• Accurate to within ±1.0°F (±0.5°C).

• Response time: <1 minute for temperature changes of ±2°F.

• High resistance to external influences on the cable due to digital output signal.

• Re-calibration is not necessary after initial set-up.

• MTBF: 1,942,123 hrs.

• Self centering mounting bracket available for 1-3" diameter pipe, and 3-6.5" diameter pipe (included).

o Includes adjustable cable ties to secure mounting bracket to pipe.

• Available lengths for attached CAT5e cable: 1/10/50/100/200/400/600/800/1000 feet.

• Powered by ENVIROMUX-SEMS-16 or SERIMUX-S-x.

• Regulatory approvals: CE, RoHS.

• Compatible with NTI ENVIROMUX-SEMS-16 and SERIMUX-S-x only.


Installation
Before installing the sensor, make sure the pipe surface where the sensor will make contact is clean and free of oil, dirt,
or grease.

1. Install cable ties around the pipe and leave loose.

Apply cable ties


loosely to the pipe

2. Slide the sensor mounting bracket first under one cable tie and tighten so it is snug.
3. Slide the second cable tie onto the second mounting bracket and snug the cable tie.

Lower mounting
Slide mounting
bracket
bracket under
cable tie

CAT5e cable
4. Align the ENVIROMUX-STSP-xx with the pipe, tighten the cable ties and trim. A sensor mounted crooked on the pipe may not
provide accurate readings.

TIE STRAP

SENSOR
PIPE MOUNTED CROOKED

Sensor case runs


parallel with the
pipe

5. Plug the cable into an available “RJ45-SENSORS” port on a SERIMUX-S-x or ENVIROMUX-SEMS-16.

REAR VIEW OF ENVIROMUX-SEMS-16


DIGITAL IN AUX
1 2 3 4 5 6 7 8 BEACON SIREN AUX PWR
RJ45 SENSORS + 12V + 12V + 12V + 12V + 12V + 12V + 12V + 12V +1 2V +1 2V +1 2V

OUTPUT RELAYS OUT


CONSOLE
1 2 3 4

NTI
R

NETWORK TECHNOLOGIES INC 1275 Danner Dr, Aurora, OH 44202 Tel:330-562-7070 www.n etworktechinc.com IN ETHERNET

RJ45-male
connector
CAT5e cable from ENVIROMUX-STSP-xx
(up to 1,000 feet)

Rear View of SERIMUX-S-16DP


PWR 1 PWR 2 AC INPUT

NTI
100-240VAC 16 15 14 13 12 11 10 9 R
NETWORK 1275 Danner Dr Tel:330-562-7070
RJ45 SENSORS
15W TECHNOLOGIES Auror a, OH 44202 Fax:330-562-1999
INCORPORATED www.networ ktechinc.com

P P
W W CONSOLE
R R
1 2 RESET

2A,250V 2A,250V 8 7 6 5 4 3 2 1 ETHERNET 1 ETHERNET 2

RJ45-male
connector
CAT5e cable from ENVIROMUX-STSP-xx
(up to 1,000 feet)

6. Follow the instructions that came with the SERIMUX-S-x or ENVIROMUX-SEMS-16 for configuring and monitoring the
temperature readings provided by the ENVIROMUX-STSP-xx.

The ENVIROMUX-STPS-xx Sensor unit can be wrapped with insulation if desired after it has been installed and checked for
operation.
Warranty Information