Medium Voltage Products

TJO 7
Outdoor voltage transformers

The TJO 7 single-pole insulated voltage transformers


are cast in outdoor epoxy resin and are designed mainly
for insulation voltages up to 40.5 kV. Insulation voltages
different from the above are to be the subject of an
agreement between the manufacturer and the customer.
Alternative insulation voltages are available to special
order. Standard transformers incorporate an overvoltage
factor of 1.9 Un/8 hrs.

Description Parameters
One outlet of the primary winding, including its terminal, is Rated primary voltages 1)
[kV] 20:√3; 22:√3; 27:√3; 30:√3;
insulated from earth at the rated insulation value. The other 33:√3; 35:√3
outlet of the primary winding, together with its terminal, is Rated secondary voltages 1) 2)
[V] 100:√3; 110:√3
earthed during operation. Most transformers are equipped Rated voltages for open-delta [V] 100:3; 110:3
with two secondary windings, the first is either for measure- connection 1)

ment or protection purposes, the other is for connection into Rated frequency [Hz] 50; 60
an open-delta configuration in a three-phase system. One Highest voltage for equipment [kV] up to 40.5
terminal of each secondar winding and one of the open-delta Rated power-frequency withstand [kV] up to 95
connected terminals must be earthed during the transformer voltage (r.m.s.), 1 min.
operation. Rated lightning impulse withstand [kV] up to 200
The secondary windings are led out into a cast-type second- voltage (peak)
ary terminal board covered with a sealed plastic cover. Max. rated burden/classes [VA/cl] 50/0.2; 150/0.5; 250/1
– measurement winding
The transformer body is fixed by four screws, the bolted Max. rated burden/classes [VA/cl] up to 200/3P or 6P
earthing clamp is located on the transformer base plate. For – residual winding
ease of handling and assembly the transformer is supplied 1)
Other voltages can also be supplied on request.
with four suspension lugs fixed to the base plate. 2)
Accuracy classes 0.2; 0.5; 1 (measurement winding) or 3P; 6P (protection winding).

By special order, the transformer can also be supplied with a


primary winding designed for two different primary voltages
(with secondary side changeover switch).

The transformers are designed and manufactured to conform


with the requirements and recommendations of the following
standards: IEC, EN, VDE, ANSI, BS, GOST, ČSN and PN-EN.
Dimensions
340 250
M12 weight: 52-55 kg
creepage distance: 1250 mm

(40)

680
90

3405PL402-W1-en. Edition 12.2010


M8

5
N

55
10 170
220
450
SECONDARY CLAMPS
2 WINDING EXECUTION
M6
N da dn
15 4xØ12,2

a1 a2 n
190
3 WINDING EXECUTION
M6
N da dn

1a 1n 2a 2n
310 15

Labelling of the voltage transformer outlets


A (M) N (O) A (M) N (O) A (M) B (N) A (M) B (N)

a n a1 a2 n a b a1 a2 b
(m) (o) (m1) (m2) (o) (m) (n) (m1) (m2) (n)

a) Single-pole insulated b) Single-pole insulated c) Double-pole insulated d) Double-pole insulated


transformer transformer with a tap transformer transformer with a tap

A (M) N (O) A (M) N (O) A (M) N (O)

1a 1n 2a 2n a n da dn a1 a2 n da1 da2 dn
(1m) (1o) (2m) (2o) (m) (o) (r) (s) (m1) (m2) (o) (r1) (r2) (s)

e) Single-pole insulated transformer with f) Single-pole insulated transformer with g) Single-pole insulated transformer with two
two secondary windings two secondary windings, with one being secondary, tapped, windings, one of which
the auxiliary (residual) winding is the auxiliary (residual) winding

For more information please contact: We reserve the right to make technical changes or modify the contents of this
document without prior notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB Sp. z o.o. does not accept any responsibility
ABB Sp. z o.o. whatsoever for potential errors or possible lack of information in this document.
Branch in Przasnysz We reserve all rights in this document and in the subject matter and illustrations
59 Leszno Str. contained therein. Any reproduction, disclosure to third parties or utilization of its
06-300 Przasnysz contents – in whole or in parts – is forbidden without prior written consent of
ABB Sp. z o.o.
Phone: +48 29 75 33 000
Fax: +48 29 75 33 327 © Copyright 2010 ABB
All rights reserved
www.abb.pl

You might also like