4 RELAYS + 8 BINARY INPUTS MODULE

† Thybus port
In order to extend I/O capability, the Pro_N relays can be cus-
tomized through external auxiliary MRI modules.
• 4 output relays.
• 8 binary inputs.
• 5 user assignable LEDs.

The MRI module do not need external auxiliary supply. It is fed


directly by Thybus port.
The Thybus link must be carried out by means shielded cable
with RJ45 connectors.

Pro_N MRI
THYBUS INTPUT THYBUS OUTPUT
ETHERNET

A1 ≅ D1 52
IN1
UAUX 51
A2 54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 50 K1 5
IN2
49 6
48 7
THYBUS

E1 IN3
47 11
K2
OUTPUT RELAYS

43
BINARY INPUTS

IN4
12
42 13
BLOCK OUT
BLOCK IN

BLOUT-
A17 A15 OUTPUT INPUT 41
RUN
BUS

IN5 16
ON

BLOUT+ K3
40
4
2
3

A18 A16
1

MODULO 4 RELE' + 8 INGRESSI DIGITALI


4 RELAYS + 8 BINARY INPUTS MODULE 15
35 14
IN6
34
33 K4 22
A19
BINARY INPUTS

IN1 FRONT PANEL IN7 21


A20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27
32 20
RS232

A21 31
IN2 IN8
A22 30
3

MRI - Flyer - 10 - 2010


SPECIF IC AT IONS
GENERAL † Environmental conditions
Ambient temperature -25...+70 °C
† Mechanical data Storage temperature -40...+85 °C
Mounting DIN rail Relative humidity 10...95 %
Dimensions 9 modules Atmospheric pressure 70...110 kPa
Mass 0.3 kg
† Certifications
† Insulation tests Product standard for measuring relays EN 50263
Reference standards EN 60255-5 CE conformity
High voltage test 50 Hz 2 kV 60 s • EMC Directive 89/336/EEC
Impulse voltage withstand (1.2/50 μs) 5 kV • Low Voltage Directive 73/23/EEC
Insulation resistance >100 MΩ Type tests IEC 60255-6

† Voltage dip and interruption † Thybus link


Reference standards EN 61000-4-29 Type shielded patch cable, RJ45 / RJ45, direct
Category 5
† EMC tests for interference immunity Max length of the Pro-N/ MRI link 2m
1 MHz damped oscillatory wave EN 60255-22-1 1 kV-2.5 kV
Electrostatic discharge EN 60255-22-2 8 kV INPUT CIRCUITS
Fast transient burst (5/50 ns) EN 60255-22-4 4 kV
Conducted radio-frequency fields EN 60255-22-6 10 V † Binary inputs
Radiated radio-frequency fields EN 60255-4-3 10 V/m Quantity 8
High energy pulse EN 61000-4-5 2 kV Type dry inputs
Magnetic field 50 Hz EN 61000-4-8 1 kA/m Max permissible voltage 19...265 Vac/19...300 Vdc
Damped oscillatory wave EN 61000-4-12 2.5 kV Max consumption, energized 3 mA
Ring wave EN 61000-4-12 2 kV
Conducted common mode (0...150 kHz) EN 61000-4-16 10 V OUTPUT CIRCUITS

† Emission † Output relays K1...K4


Reference standards EN 61000-6-4 (ex EN 50081-2) Quantity 4
Conducted emission 0.15...30 MHz Class A Type of contacts changeover (SPDT, type C)
Radiated emission 30...1000 MHz Class A Nominal current 8A
Nominal voltage/max switching voltage 250 Vac/400 Vac
† Climatic tests Breaking capacity:
Reference standards IEC 60068-x, ENEL R CLI 01, CEI 50 • Direct current (L/R = 40 ms) 30 VA
• Alternating current (λ = 0,4) 40 W
† Mechanical tests Make 1000 W/VA
Reference standards EN 60255-21-1, 21-2, 21-3 Short duration current (0,5 s) 30 A

† Safety requirements † LEDs


Reference standards EN 61010-1 Quantity 8
Pollution degree 3 • ON (green) 1
Reference voltage 250 V • Bus (yellow) 1
Overvoltage III • Run (green) 1
Pulse voltage 5 kV • Allocatable (red) 5

DIMENSIONS
158.5 56

54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28
45
90

OUTPUT INPUT
RUN
BUS
ON

4
2
3

5
1

MODULO 4 RELE' + 8 INGRESSI DIGITALI


4 RELAYS + 8 BINARY INPUTS MODULE

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27

60

2 MRI - Flyer - 10 - 2010


† Threshold settings
The trigger inputs can be set using jumper plug (jumper X1...X8) Inputs Threshold Threshold
Jumper Jumper
to 15 V or 55 V. (Terminals) (V) (V)
The default setting for activation threshold for all inputs is 15 V.
IN1 (51-52) X1 ON 15 X1 OFF 55
If the setting must be changed, the jumpers must be placed on
the base card, accessible after opening the case.
IN2 (49-50) X2 ON 15 X2 OFF 55
The instructions below must be performed in sequence:
• Disconnect the ThyBus connectors, IN3 (47-48) X3 ON 15 X3 OFF 55
• Remove the case and put the electronics on a static plan (to
open the case just unhook the four mounting tabs) IN4 (42-43) X4 ON 15 X4 OFF 55
• Place the jumper (see table)
• Reassemble the case IN5 (40-41) X5 ON 15 X5 OFF 55

IN6 (34-35) X6 ON 15 X6 OFF 55

IN7 (32-33) X7 ON 15 X7 OFF 55

IN8 (30-31) X8 ON 15 X8 OFF 55

mounting tabs

Jumpers

X5
X1

X8
X2
X3 X4 X6

MRI - Flyer - 10 - 2010 3


Headquarters: 20139 Milano - Piazza Mistral, 7 - Tel. +39 02 574 957 01 ra - Fax +39 02 574 037 63
Factory: 35127 Padova - Z.I. Sud - Via dell’Artigianato, 48 - Tel. +39 049 894 770 1 ra - Fax +39 049 870 139 0

www.thytronic.it thytronic@thytronic.it www.pro-n.it