Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Doc NO.

• PH-IMS-SP08-WI02-FR02
REVISION / ISSUE:01/01
DATE:1/03/2018
Centrifugal Pump Performance Report
Page | 1 OF 1

Model: NT 125/400 Client: Power House Machine Code: 1P063CSE0093 Report No.PPR ( 9) / 2019

Maximum pressure : 5.5 Bar Driver: Electrical Motor Date of Inspection: 7/2/2019

Motor power: 70 KW Ambient temp : 19 °C Max Flow: 64155 BPD Work Order No. Requested

Bearing temp M.Seal Temp


Frequency Current °C °C pump Suction Discharge Discharge
Speed Suction pressure Flow Duration
temp Temp Temp pressure
R.p.m Bar rate BPD minute
HZ Amp MF MR PF PR Front Rear °C °C °C Bar

1485 50 82 38 N/A 72 66 29.6 N/A 27 27 28 0.2 5 30000 30


1485 50 82 43 N/A 78 77 31 N/A 29 29 29 0.2 5 30000 30

VIBRATION RECORDS
Velocity Value (mm/s)
point direction type 5 bar
C X Velocity 4.34
C Y Velocity 4.51
C Z Velocity 5.76
D X Velocity 4.34
D Y Velocity 3.54
D Z Velocity 3.86
A X @Base Velocity 5.05
A Y @Base Velocity 6.94
A Z @Base Velocity 3.87
B X Velocity 7.12
B Y Velocity 7.3
B Z Velocity 5.09
Evaluation:
1. The pump does not achieve its flow rate according to the performance curve.
2. The vibration Values of pump and Motor are not in acceptance limits.
3. Grease Leakage from Rear Bearing of pump.
4. Minor Water Leakage from Rear Bearing of pump.
5. No Protections for Pump and Motor.
6. Pump and motor need to clean and paint.
7. No Petro lift certification.
8. No Glands on Control Box of Motor.

Result:
Action
Inspected By Q C DEP Reviewed By Witnessed By
Name: Moaz Yousef Gaber Name: Mohamed wageh Name:
Signature: Moaz Yousef Signature: Mohamed wageh DEP. Mechanical
Date : 7/2/2019 Date : 7/2/2019 Date :