ReiriOffice Touch (DCPF04)

Setup Procedures

ASEAN Oceania Training Centre 1


Introduction

The objective of this sharing session is to let everyone have a


basic understanding on the ReiriOffice Touch Setup.

ASEAN Oceania Training Centre 2


ReiriOffice Touch (DCPF04)
1. Preparation

ASEAN Oceania Training Centre 3


1.1.1 Check List DCPF04 : Preparation

ReiriOffice Touch DCPA01 USB A-USB C cable Power adaptor


DCPF04

• Controls up to 64 • Power cable • AC-DC Power


• Touch screen tablet indoor units. adaptor
• 2 USB 2.0 Type-A • X7A DIII-net
ports. connector port
• 2 RS485, 6 pins • X1A power supply
block connectors. port
• 1 LAN port • A[+]|B[-] Modbus
communication port
• 1 USB Type-C port

ASEAN Oceania Training Centre 4


1.2 DCPA01 Dip Switches DCPF01 : Preparation

DS1 ITEM OFF ON ADD DS2-1 DS2-2 DS2-3 DS2-4


1 Unused - - 0 OFF OFF OFF OFF
2 Communication speed 9600 bps 19200 bps 1 OFF OFF OFF ON
3 Stop Bit 1 2 2 OFF OFF ON OFF
4 Parity check Even Odd

ASEAN Oceania Training Centre 5


1.3 Group address setting for VRV indoor units DCPF04 : Preparation

BRC1E Series

1 2 3

ASEAN Oceania Training Centre 6


ReiriOffice Touch (DCPF04)
2. Overview

ASEAN Oceania Training Centre 7


2.1.5 ReiriOffice Touch Overview DCPF04 : Setup
One DCPA01 can control
USB Type-C connector, a total of 64 indoor units To X37A
Power supply
5V DC input X1A

10 CUs
D1[+] D1[-] X7A
To OUT/D unit
RS485 F1 | F2
LAN cable
DCPF04 A[+] B[-]
ReiriOffice Touch

To IN/D unit
F1 | F2
Modbus TCP/IP
Router LAN cable

Internet WAGO I/O System


ASEAN Oceania Training Centre 8
2. DCPF04 - ReiriOffice Touch Reiri Overview
ReiriOffice Touch Add 1 X1A
To X37A
5V DC D1[+] D1[-] Power supply
(Port 1) To IN/D
input X7A
To OUT/D unit
unit F1 | F2

200m
F1 | F2
10 CUs
D2[+] D2[-]
(Port 2) A[+] B[-] Max 64 indoor units
DCPF04 1st card

200m RS485
USB Type-A USB Type-A
LAN cable

(Port 4) (Port 3) Add 2


Max 64 indoor
10 CUs units
3rd card

(Total 256 indoor units)


Add 1 To X37A
X1A
Power supply
Smart meters IAQ sensors To OUT/D unit
To IN/D
(Max 30) (Max 30) X7A unit F1 | F2
F1 | F2

Modbus 10 CUs
TCP/IP 2nd card
A[+] B[-] Max 64 indoor units
LAN
Router cable

Add 2
Max 64 indoor
10 CUs
units
WAGO I/O System D-Mobile adaptor 4th card
Internet
(10 nodes) (Max 50) ASEAN Oceania Training Centre 9
2.1.7 ReiriOffice Touch Overview DCPF04 : Preparation

A B C D E F
- + - +

LABEL DESCRIPTION
A USB Type A port (2.0)
USB Type A port (2.0) - the priority port is indicated
B
by a round sticker
C Micro SD card port
D LAN Port (1 GbE Speed LAN)
E RS485, 6 pin terminal block connectors
F USB Type C connector, 5V DC power input
ASEAN Oceania Training Centre 10
2.1.8 ReiriOffice Touch Overview DCPF04 : Preparation

E D2 D1

A B C D E F - + - +

- + - +

Polarity as shown
on the sticker.
LABEL DESCRIPTION
The priority port is indicated
A USB Type A port (2.0) by a round sticker.
USB Type A port (2.0) - the priority port is indicated Note:
B
by a round sticker
• Cable type: Twisted pair cables
C Micro SD card port • Cable thickness: 0.25mm2 to 0.75mm2
D LAN Port (1 GbE Speed LAN) • When using a shielded cable, connect only
E RS485, 6 pin terminal block connectors one end of it to the ground.
• The maximum wiring distance must be kept at
F USB Type C connector, 5V DC power input 200m
ASEAN Oceania Training Centre 11
ReiriOffice Touch (DCPF04)
3. Reiri Setup Tool
(Setup Workflow)

ASEAN Oceania Training Centre 12


3.1 Setup Workflow DCPF04 : Setup Workflow

STEP 1 STEP 6
Download Reiri Setup Tool App Setup Activator User Account

STEP 2
STEP 7
Open Reiri Setup Tool App and connect to
Activate Reiri Controller
the Reiri Controller

STEP 3 STEP 8
Set up an admin account for ReiriOffice Activate / Deactivate / Delete
Touch Optional Functions

STEP 4 STEP 9
Set Reiri Controller information and Add devices to Reiri Controller for
activate cloud connection monitoring and controlling.

STEP 5 STEP 10
Set Time and Date for Reiri Controller Edit the management points attributes

ASEAN Oceania Training Centre 13


3.2 Download Reiri setup tool DCPF04 : Setup Workflow

B. A. Connect your phone


to the same network
as the ReiriOffice
Touch.

B. Download Reiri Setup


tool from Google Play
A. or App Store. Open
the app and tap agree
to the terms of
service.

ASEAN Oceania Training Centre 14


3.2.1 Find the controller DCPF04 : Setup Workflow

AOTC

A. Tap Find controller to refresh the A.


controller list.

B. Tap on the controller details to login. B.

NOTE
• The Smartphone that is
running the Reiri Setup Tool
must be connected to the
same network as the
ReirOffice Touch.

ASEAN Oceania Training Centre 15


3.2.2 Setup Admin Account DCPF04 : Setup Workflow

AOTC

C. For first time login, use the


following login credentials.
Username: setup
Password: C.
Next, press Login to continue.

NOTE
• Once a user account is
being created, this setup
account will be removed.

ASEAN Oceania Training Centre 16


3.2.3 Setup Admin Account DCPF04 : Setup Workflow

F.
D.
E.

D. Tap on User Account


Management.
E. Tap on Add User
Account to create an
account for service F. The Password must be minimum
engineer. 10 characters and must contain
at least 2 of the following
characters.
• 1 Uppercase character
• 1 Lowercase character
• 1 Numeric character
• 1 Special characters
(excluding / , “ ‘ ;)
ASEAN Oceania Training Centre 17
3.2.4 Setup Admin Account DCPF04 : Setup Workflow

G. Choose Admin as User Class


H. Press Save to save the account.
I. Repeat steps F to H to create
another account for client.
J. H.
J. Press Back to go back to main
H. menu.

NOTE
G. • Create 2 admin accounts, one
for the client and one for the
service engineer to perform
setup and act as a backup in
case if the client forgets their
login credentials the engineer
can use its account to recover
the data.

ASEAN Oceania Training Centre 18


3.2.5 Setup Admin Account DCPF04 : Setup Workflow

K. Tap on Logout
L. Login to the admin account that you
had created for Service Engineer.

L.

K.

ASEAN Oceania Training Centre 19


3.3 Cloud Connection DCPF04 : Optional Settings

A. Tap on Controller Settings.


B. Swipe the slider to the right to activate
the Cloud Connection.
C.
C. Tap Back to return to main menu.

A.
B.

ASEAN Oceania Training Centre 20


3.3.1 Cloud Connection DCPF04 : Optional Settings
Local
C. Reboot the
controller to apply
the changes made. LAN cable
D. After Reboot, the
user will be able to
DCPF04
access remotely via
Router ReiriOffice Touch
ReiriOffice app.

Remote D.
Internet

Cloud
C.

ASEAN Oceania Training Centre 21


3.4 Controller information settings DCPF04 : Setup Workflow

A. Select Controller Settings.


B. Go to Controller Information Settings.
C. Provide a Controller Name for the
ReiriOffice Touch, the Project Floor Size
and Project Location. This helps in the
identification and finding of the Reiri
A. controller in group control.

B. C.

ASEAN Oceania Training Centre 22


3.5 Time and Date DCPF04 : Setup Workflow

A. Performing Time & Date


setting is necessary to
ensure that the schedule
runs at the pre-set date and
time.

B. B. Internet Time
Synchronization is ON as
C. default.
A.
C. Tap on Asia/Singapore to
change your Time zone.

NOTE
• Internet access must always be
available for auto time
synchronization.

ASEAN Oceania Training Centre 23


3.5.1 Time and Date DCPF04 : Setup Workflow

D. If no internet is available, set


the time manually by keying in
E. the
• Time
• Date
D.
• Time Zone
E. Select your respective
Timezone.

ASEAN Oceania Training Centre 24


3.6 Activate Optional Function DCPF04 : Setup Workflow

A. Select Activate Optional


Function.
B. Activating Setup Activator User
Account is required in order to
activate ReiriOffice Touch and
Reiri Option Software.

B.

A.

ASEAN Oceania Training Centre 25


3.6.1 Setup Activator User Account DCPF04 : Setup Workflow

C. The Username and Password is obtainable from Daikin Sales Office.


D. Tap Hide Activator User Account after the Username and Password are input.

D. Activates ReiriOffice Touch with


Username and Password
Daikin Affiliate

C.
Login to Reiri Option
Distribute the created
Management System to
Username and Password
create an activator user
to the activator.
account.
Activator
(Installer)

NOTE
• The Username and Password is one-time issued and tagged to the installer. It
shall be used by that installer repeatedly to activate other controllers or options for
the all sites/projects.

ASEAN Oceania Training Centre 26


3.7 Activate Controller DCPF04 : Setup Workflow

A. Once Activate Controller is tapped and activated, ReriOffice Touch


can be used in conjunction with ReriOffice App.

A.

ASEAN Oceania Training Centre 27


3.8 Scan Option Key QR code DCPF04 : Setup Workflow

A. Tap Scan Option Key QR


code and the smartphone
will be re-directed to the
camera function.
B. Position the QR code
within the focal point of the
camera screen to scan it.
A. B. C. The License key is use for
manual entry in instances
whereby the QR code
scanner cannot work
properly.

C.
ASEAN Oceania Training Centre 28
3.9 Scan Option Key QR code DCPF04 : Setup Workflow

NOTE D.
• There are 2 scenarios where the
Licence key cannot be tapped. First,
if the Reiri controller already have C. Upon succession, the License key will be
the same option installed and displayed in the List of Options Available.
second, if the option is not Next, tap on the License key.
supported by that Reiri controller.
D. A confirmation dialogue will be prompted,
tap on OK to confirm. E.
E. The activated option will show its Model
name in the Activated Options.
C.

ASEAN Oceania Training Centre 29


3.9.1 Option Key Manual Entry DCPF04 : Setup Workflow
C. Option Key Manual Entry is only use if QR code
cannot work. To use this option, tap on Option
Key Manual Entry.
D. Input the License key and tap Submit.

D.

C.

ASEAN Oceania Training Centre 30


3.9.2 Deactivate Options DCPF04 : Setup Workflow

A. Any options that has been activated


will be shown beneath Activated
B. Options.

B. To remove any activated options, tap


on the option model name
(eg.DCPN003).

C. Tap Ok when being prompted.

D. Tap Ok again to confirm the


deactivation.

C.

A.
D.
ASEAN Oceania Training Centre 31
3.9.3 Removal of Options DCPF04 : Setup Workflow

E.

D. The License key of the deactivated option is displayed in


the List of options available.

E. To fully removed the deactivated option from the


ReiriOffice Touch, tap on the License key and swiped it to
the left.

NOTE
• Removal of any options is only recommended if it has been mistakenly activated
D. on the wrong Reiri controller or when the existing Reiri controller needs to be
replaced.

ASEAN Oceania Training Centre 32


3.10 Device Connection Settings DCPF04 : Setup Workflow
A. Tap Device Connection Settings. This
function connects devices to ReiriOffice
Touch.
B. The List of devices that can be connected
to ReiriOffice Touch includes:
B. • DCPA01
• DTA116A51
• IAQ sensors
A. • Smart Meter
• WAGO / IO
• iTC (ReiriOffice only)
• iTM (ReiriOffice only)
• Reiri Controllers
• D-Mobile
• Z-Wave (ReiriHome)
• DAMA module

NOTE
• Reboot the Reiri once the device
connection settings are done.
ASEAN Oceania Training Centre 33
3.11 DCPA01 DCPF04 : Setup Workflow
Add 1 To X37A
X1A
Power supply

To OUT/D unit To IN/D


X7A F1 | F2 unit F1 | F2
10 CUs

A[+] B[-] 1st card Max 64 indoor units

Add 2
Max 64 indoor
10 CUs units
3rd card
RS485 port (Total 256 indoor units)
Add 1 To X37A
X1A
Power supply
To IN/D
To OUT/D unit
X7A unit F1 | F2
F1 | F2
10 CUs

A[+] B[-] 2nd card Max 64 indoor units

Add 2

Max 64 indoor
10 CUs
units
4th card
ASEAN Oceania Training Centre 34
3.11.1 DCPA01 DCPF04 : Setup Workflow
Add 1 Add 2

1st card 3rd card

Add 1 Add 2

RS485 port
2nd card 4th card

ASEAN Oceania Training Centre 35


3.11.2 DTA116A51 DCPF04 : Setup Workflow
Add 1

1st card

Add 2

[D1+] [D1-] 3rd card


For IAQ sensors (Port 1)
and Smart Power
Add 1
meter
[D2+] [D2-]
(Port 2)

NOTE 2nd card

DTA116A51 does not come with the Add 2


following features.
• PPD function
• Remote controller prohibition
• HRV control 4th card

ASEAN Oceania Training Centre 36


3.12 IAQ Sensor DCPF04 : Setup
Add 1

Add 2

RS485 USB
converter
[D1+] [D1-]
(Port 1)
Add 1

Add 30 Add 2 Add 1 [A+] [B-] [A+] [B-] [D2+] [D2-]


(Port 4) (Port 3) (Port 2)
Smart
meters

Add 2

Add Add Add IAQ


30 2 1 sensors
ASEAN Oceania Training Centre 37
3.12.1 Smart Meter DCPF04 : Setup Workflow
Add 1

Add 2

RS485 USB
converter
[D1+] [D1-]
(Port 1)
Add 1

Add 30 Add 2 Add 1 [A+] [B-] [A+] [B-] [D2+] [D2-]


(Port 4) (Port 3) (Port 2)
Smart
meters

Add 2

Add Add Add IAQ


30 2 1 sensors
ASEAN Oceania Training Centre 38
3.12.2 WAGO I/O DCPF04 : Setup Workflow
Add 1

Add 2

[D1+] [D1-]
(Port 1)
Add 1

[D2+] [D2-]
(Port 2)

Add 2

ASEAN Oceania Training Centre 39


3.13 Reiri Controller DCPF04 : Setup Workflow
A. ReiriOffice Touch can be used as a floor
controller to monitor and control the VRV
indoor units at their own individual floor.

A.
D.
C. Go to Reiri Controller setting
and enter the User and
Password of the Service Class
Account that was created by the B. The ReriOffice
ReiriOffice administrator. D. administrator
creates a Service
User Class
account for each
192.168.1.179 ReiriOffice Touch.
D.
B.
C.
D. This allows the users on each
respective floor to monitor and control
the VRV indoor units from their own
ReiriOffice Touch

ASEAN Oceania Training Centre 40


3.14 D-Mobile DCPF04 : Setup Workflow

A. Swipe the slider to the right to activate the


connection with D-mobile.

A.

D-Mobile adaptor (Max 50)

NOTE
• The D-mobile has to be paired to the client’s network first using WPS (Wi-
Fi Protected Setup) method or D-Mobile App.
• D-mobile has to be connected to the same network as ReiriOffice Touch

ASEAN Oceania Training Centre 41


3.16 Reboot Reiri DCPF04 : Setup Workflow

A. Reboot controller is to force the


controller to restart. This is to apply the
settings or configurations changes
made to the Reiri controllers.

A.

ASEAN Oceania Training Centre 42


3.17 Point Settings DCPF04 : Setup Workflow

A. Point Settings allows you to


customize the point attributes to use
the data correctly.

A.

ASEAN Oceania Training Centre 43


ReiriOffice Touch
4. Reiri Setup Tool
(Optional Settings)

ASEAN Oceania Training Centre 44


4.1 User Account Management DCPF04 : Optional Settings

A. Tap on User Account


Management to perform
account settings.

A. B. Tap on Add User Account to


add a user.

B.

ASEAN Oceania Training Centre 45


4.1.1 Add Admin User Class Account DCPF04 : Optional Settings

C. Fill up the field accordingly


• Username
• Password
• Select user class of
Admin or Service

NOTE
• Admin User Class has full access right.
• Service User Class access right to the management
points can be selectively assigned by Admin User
Class.
C.

ASEAN Oceania Training Centre 46


4.1.2 Add Service User Class Account DCPF04 : Optional Settings

D.

NOTE
• When ReiriOffice Touch is used as a floor controller, ReiriOffice administrator
registers a Service Class Account for each ReiriOffice Touch to allow the monitoring
and control of each individual floor’s AC equipment and management points.
ASEAN Oceania Training Centre 47
4.1.3 Add Service User Class Account DCPF04 : Optional Settings

D. Tap on the Pont Name to select or unselect


the point.
E. Tap on Save to save and confirm the changes.
F. E. F. Tap back to exit.

D.
PM2.5 Value PM2.5 Value

CO2 Concentration Value CO2 Concentration Value

NOTE
• Admin User Class can assign management points to
Service User Class.
• Maximum 80 accounts can be created.
ASEAN Oceania Training Centre 48
4.1.4 Modify Service User Account DCPF04 : Optional Settings

H.
I.
G.
G. Tap on Modify service User
Account to edit existing Service
User Class.
H. Tap on the username that you
want to modify.
I. Add or remove the points by
tapping the Point name to select
or unselect.

ASEAN Oceania Training Centre 49


4.1.5 Delete User Account DCPF04 : Optional Settings

J. Tap on Delete User Account to remove


created accounts.
K. Tap on the username of the account
that you want to delete.

K. Equal Rights

User Class: User Class:


Admin Admin

NOTE
J. • Admin User Class accounts share
equal rights to
• Add / Delete Admin user class
accounts.
• Add / Edit / Delete Service user
class accounts

ASEAN Oceania Training Centre 50


4.1.6 Delete User Account DCPF04 : Optional Settings

L. Confirm the request when


prompted.
M. Tap OK once account is deleted.

L. M.

ASEAN Oceania Training Centre 51


4.1.7 Change Password DCPF04 : Optional Settings

B.

C.
A. Tap on Change
Password
B. Enter the new Password
and re-enters it again to C. Tap on OK once.
confirm.
A.

ASEAN Oceania Training Centre 52


4.2 Network Settings DCPF04 : Optional Settings

A. Click on Controller Settings.


B. Select Network Settings.

A.

B.

ASEAN Oceania Training Centre 53


4.2 Network Settings DCPF04 : Optional Settings

B. Wired – If DCPF04 is linked to the


wireless router with a LAN cable.

DCPF04
ReiriOffice Touch
B.
LAN cable

Internet

NOTE
• Connection Type and Connection Mode are set at Wired and Auto respectively by default hence no changes is
required unless other settings options is preferred.

ASEAN Oceania Training Centre 54


4.2.1 Network Settings DCPF04 : Optional Settings

C. WiFi – If DCPF04 is linked to the wireless router


wirelessly (i.e no LAN cable).
D. Key in the SSID and Password of the Wi-Fi network
if Wi-Fi is selected as connection type.

C.

DCPF04
ReiriOffice Touch

D.

Internet

ASEAN Oceania Training Centre 55


4.2.2 Network Settings DCPF04 : Optional Settings

E. Auto – IP address is auto assigned to


the Reiri controller by the wireless
router.
F. Static – IP address is manually
assigned and fixed.
G. Key in the parameters of the Wi-Fi
network if Static is selected as
F. connection mode.
E.

G.

ASEAN Oceania Training Centre 56


4.2.3 Email Server Settings DCPF04 : Optional Settings

A. Email Server Settings is necessary if client


requires an email notification on the system
fault.
B. Key in the required email server parameters.
B. • URL [SMTP@gmail.com]
• Port [587]
• Domain [gmail.com]
• Username
• Password
C. Key in the required Sender information.
A. • Sender Name
C. • Sender Email

NOTE
• Recipient email is set on the ReiriOffice App.
• Turn ON Less secure app access.
ASEAN Oceania Training Centre 57
4.3 Bill Header Settings DCPF04 : Optional Settings

A. Bill Header Settings - To


upload the company logo
which will be displayed as
the bill header (B.).
B. Tap on Choose file to upload
B. a picture.

A.

ASEAN Oceania Training Centre 58


4.3.1 Bill Header Settings DCPF04 : Optional Settings

C. C. Uploaded logo is shown on


the top left corner of the bill.
1.

NOTE
• Only logo image in PNG format is
accepted.
2. • Input the information of the
tenant (1.) and owner (2.) using
the ReiriOffice app.
ASEAN Oceania Training Centre 59
4.3.2 PPD Settings DCPF04 : Optional Settings

A. PPD Settings: Performs PPD


calculation in accordance with PPD
grouping setup.
Tap on PPD Settings
B. Select Main Power Type: Select the
appropriate power type based on the
power supply symbol as stated on the
indoor unit model.

B.

A.

ASEAN Oceania Training Centre 60


4.3.3 PPD Settings DCPF04 : Optional Settings

A. Tap on Select Main Power Type to


display the list of power supply
symbol.
B. Select the matching power supply
symbol as stated in the equipment list
of the indoor units.
B.

A.

ASEAN Oceania Training Centre 61


4.3.4 PPD Settings DCPF04 : Optional Settings

C. Next, proceed to select the model


and capacity for the indoor units.
D. Tap on Select Model.
E. A list on indoor unit model is shown,
choose the matching model based
on the indoor units’ equipment list.

C. E.

D.
NOTE
• Model and Capacity of indoor
units are auto detected and then
autofill. When autofill doesn’t
work, entry the field information
manually.
ASEAN Oceania Training Centre 62
4.3.5 PPD Settings DCPF04 : Optional Settings
F. Tap on Select Capacity
G. A list of the capacity is shown,
choose the matching model based
on the indoor units’ equipment list.
G.

F.

NOTE
• After setting the model and capacity for
one indoor unit, the system will
automatically scan the rest of the indoor
units with the same model and capacity
to perform auto input. This reduces the
time taken to repeat the same input.
ASEAN Oceania Training Centre 63
4.3.6 PPD Settings DCPF04 : Optional Settings

I. Group Name: Enter a group


name for the new group.
IDU power measured: If indoor
units’ power consumption is
H. measured with a KWH meter,
this option must be activated
too.

H. Tap on “+” to add Meter List: Display all the KWH


new group. I. meters that are connected to the
ReiriOffice Touch. Select only
the ones that are measuring the
same PPD group, this includes
the KWH meter for the indoor
units (IDU) too.
IDU list: Display all the Indoor
Units. Select only the ones that
are in the same PPD group.

ASEAN Oceania Training Centre 64


4.3.7 PPD Settings DCPF04 : Optional Settings

GROUP 1 (1) GROUP 2


D1[+]D2[-] Port 2

(3)
D1[+]D2[-] Port 1

(3)
(2)
AC-dcpa1: (1)
1-00001 AC-dcpa2:
1-00001 (2)
(4)
AC-dcpa1: (3)
1-00002 AC-dcpa2:
1-00002 (4)
ASEAN Oceania Training Centre 65
4.3.8 PPD Settings DCPF04 : Optional Settings

K. Tap on Start PPD


J. Calculation to start the
PPD calculation.

K.
J. After the PPD group is
being saved successfully,
proceed to start the PPD
calculation. Tap on
Stopped to change the
calculating state.

ASEAN Oceania Training Centre 66


4.3.9 PPD Settings DCPF04 : Optional Settings

B. This option allows a quick view


of the current PPD calculation
status

B.

ASEAN Oceania Training Centre 67


4.4 Reboot Reiri DCPF04 : Optional Settings

IP:192.168.1.70

DCPF04
ReiriOffice Touch
LAN cable

A. Reboot controller is to
force the controller to
restart. This is to
apply the settings or
configurations
changes made to the
Reiri controllers.

Wireless Router
SSID: AOTC
Password: 123
IP: 192.168.1.1 Internet A.

ASEAN Oceania Training Centre 68