Professional Documents
Culture Documents
IS 16481-2016 Fibers
IS 16481-2016 Fibers
Indian Standard
ICS 59.060.20;91.100.40
© BIS 2016
FOREWORD
This Indian Standard was adopted by the Bureau of Indian Standards, after the draft finalized by the Technical
Textiles for Build Tech Sectional Committee had been approved by the Textile Division Council.
To support current high gross domestic product growth in India, proper growth of infrastructural is very essential.
From residential and commercial complexes, to surface transport and aviation, special economic zones or
entertainment and hospitality industry, concrete structures are a must and have to be built up at a faster pace and
preserved for its serviceability over longer periods. For durability concerns, plastic shrinkage cracks as well as
the drying shrinkage and temperature cracks in concrete structures need attention of the structural engineers,
builders, consultants and regulatory authorities.
Infrastructure is the backbone of development of any country which needs strong and durable constructions,
which can serve with minimum maintenance over a long period. But traditional concrete is brittle enough, and
needs to improve for ductile performance. The weakness of concrete in tension can be overcome to some extent
by the inclusion of a sufficient volume of fibres. The use of synthetic fibres also alters the behaviour of the cement
based matrix after it has cracked. Synthetic fibres are added to cement based matrix to reduce plastic shrinkage
cracking and also to reduce shrinkage and temperature cracking. The fibres may be used in concrete over steel
deck construction as well as to reduce fire damage in concrete.
Synthetic micro-fibres are used as secondary reinforcement in infrastructural construction. With its use, durability
of structure can be increased. Therefore, use of synthetic fibres such as polyester, nylon and polypropylene in
construction needs no emphasis.
The hot and humid climatic conditions prevalent in India, and sometimes saline water use in construction, leads to
rapid deterioration of traditional concrete structures, which generally lack certain fundamental properties such as
flexural toughness and resistance to moisture and water absorption, that results in corrosion of steel reinforcement
leading to premature failure of structures. Fibre reinforced concrete has many advantages such as improved
tensile and flexural strength and toughness, crack resistance, minimized drying shrinkage cracks, reduced seepage
of water; higher fatigue life; more ductility, increased abrasion and impact resistance; etc. It also tends to improve
concrete towards homogeneous behavior. In case of spray concrete or shotcrete, rebound loss can be reduced
using fibres.
For the effective use of fibres in hardened concrete,
a) fibre content by volume shall be adequate.
b) fibre length shall be optimal.
c) fibres shall have optimal aspect ratio in relation to method of dosing and mixing.
Though synthetic fibres are most commonly used in cast-in-situ concrete, their use in shotcrete and precast products
is growing. Adding synthetic fibres to shotcrete can reduce rebound and material waste, permit thicker layers per
pass, reduce sagging, and inhibit plastic shrinkage cracking. Precast manufacturers use synthetic fibres in their
products to facilitate handling at early age, help reduce concrete breakage during handling, and save on labour.
They also report fewer shrinkage cracks when using the fibres. Some precast manufacturers use synthetic fibres in
unusually shaped precast products, such as planters and urns, instead of wire reinforcing. If not carefully placed,
wire reinforcing in these products is sometimes exposed when the products are removed from the forms.
The composition of the Committee responsible for the formulation of this standard is given in Annex P.
For the purpose of deciding whether a particular requirement of this standard is complied with, the final value,
observed or calculated, expressing the result of a test or analysis, shall be rounded off in accordance with IS 2 : 1960
Rules for rounding off numerical values (revised). The number of significant places retained in the rounded off
value should be the same as that of the specified value in this standard.
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
Indian Standard
TEXTILES SYNTHETIC MICRO-FIBRES FOR USE IN
CEMENT BASED MATRIX SPECIFICATION
1 SCOPE may lead to cracking, internal warping, and external
deflection, before the concrete is subjected to any kind
This standard prescribes physical, application and
of loading.
functional requirements for synthetic micro fibers such
as polyester, nylon and polypropylene fibres, etc, for 3.8 Elongation of the Fibre Elongation of the fibre
use in cement based matrix for secondary reinforcement is defined as the ratio of the length change of the fibre
in construction works such as concrete roads and to the initial length expressed as a percentage.
pavements, industrial and commercial floorings, NOTE The length change should be measured on the fibre
residential and commercial buildings, bridges and itself.
elevated structures, water retaining structures and dams,
ports and under sea concrete structures, plaster, 3.9 Equivalent Diameter Equivalent diameter is the
shotcrete, precast, mortar, etc. diameter of a circle with an area equal to the mean cross-
sectional area of the fibre. For circular fibres, the
2 REFERENCES equivalent diameter is equal to the diameter of the fibres.
The standards listed in Annex A contain provisions, NOTE The equivalent diameter shall be calculated as given
in Annex J.
which through reference in this text, constitute
provisions of this standard. At the time of publication, 3.10 Fibre Dispersion Opening and distribution or
the editions indicated were valid. All standards are scattering of bundle of fibres uniformly
subject to revision and parties to agreements based on and homogeneously in a cement based matrix such that
this standard are encouraged to investigate the almost no bundles, agglomeration of fibres, clustering
possibility of applying the most recent editions of the of fibres or bunches of fibres are visible in the cement
standards indicated in Annex A. based matrix after dispersion.
1
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
3.17 Modulus of Fibres The modulus is the ratio synthetic fibres such as polyester, polypropylene and
of stress to strain. It is expressed in Mpa. nylon used for secondary reinforcement of concrete.
However, the type of most commonly used synthetic
3.17.1 Modulus of Fibres, Initial The slope of the
fibres and general range of their physical properties
initial straight portion of a stress-strain curve. It is
and the fibre content in concrete applications is
expressed in Mpa.
described in Annex B for information of the users.
3.17.2 Modulus of Fibres, Secant The ratio of change
4.2 The synthetic fibres used for secondary
in stress to change in strain between the points of zero
reinforcement in concrete shall comply with the
stress and breaking stress. It is expressed in Mpa.
requirements given in 4.3 to 4.8 and the physical,
3.17.3 Modulus of Fibres, Tangent The ratio of application and functional requirements as given in
change in stress to change in strain derived from the Tables 1, 2 and 3.
tangent to any point on a stress-strain curve. It is
expressed in Mpa. 4.3 General
3.18 Permeability The coefficient representing the Only virgin synthetic fibres (monofilament/
rate at which water is transmitted through a saturated multifilament in case of polyester and nylon and
specimen of concrete under an externally maintained monofilament/fibrillated in case of polypropylene) of
hydraulic gradient. cut length 6 mm to 25 mm, inert to concrete
environment shall be used as secondary reinforcement
3.19 Precast Concrete products cast at a site remote in cement based matrix and no recycled material shall
from the final installation. be permitted. Fibres shall be well dispersed in the
3.20 Shrinkage and Temperature Cracking cement based matrix so as to have uniform functional
Shrinkage moisture and temperature change causing properties. Fibres shall be identified as per the
cracking in tension due to a change in length or volume. confirmatory tests specified in IS 667.
3.21 Specific Gravity The ratio of the density of a 4.3.1 The user shall obtain a certificate from the fibre
polymer (fibre) to the density of water at 27 ± 2°C. manufacturer along with a test report including that the
fibre used is virgin fibre for every lot of fibre purchased.
3.22 Synthetic Fibres Straight or deformed pieces The iso-phthalic acid (IPA) content for polyester virgin
of extruded, orientated and cut material which are fibre shall be zero when tested as per method prescribed
suitable to be homogeneously mixed into concrete or in Annex C. The polymer content of the virgin polymer
mortar for use for secondary reinforcement in concrete shall be minimum 97 percent and other additives such
for various constructional applications. Synthetic fibres as oxidation and UV stabilizers shall not be more than
are fibres manufactured from polymer based materials 3 percent and the same shall be validated by a certificate
such as polypropylene, nylon, polyester and carbon, etc. from the polymer supplier for each lot.
3.23 Tenacity Breaking force of a fibre divided by NOTES
its linear density. 1 The PP and nylon are not recycled.
2 If required by the customer, fibres of cut length more than
3.24 Tensile Strength Stress corresponding to the 25 mm are permitted.
maximum force a fibre can resist. The tensile strength
is calculated by dividing the maximum force a fibre 4.4 Resistance to Alkalis
can resist by the mean cross-sectional area of the fibre
Synthetic fibres shall retain at least 90 percent of their
prior to loading.
original breaking strength when tested by the method
3.25 Ultimate Elongation of the Fibre Maximum prescribed in Annex D.
ratio of the length change of the fibre to the initial length
expressed as a percentage. 4.5 Resistance to Acids
3.26 Water Absorptive Capacity Mass of water Synthetic fibres shall retain at least 90 percent of their
that is absorbed by unit mass of the fibre expressed as original breaking strength when tested by the method
a percentage of the mass of the fibre, under specified prescribed in Annex E.
conditions and after a specified time.
4.6 Resistance to Ageing
4 REQUIREMENTS The test specimen of synthetic fibres in the form of a
sheet (see G-3) when subjected to ageing at 70 ± 2°C
4.1 Types of Synthetic Fibres Used in Secondary
for 168 h by the procedure described in IS 7016 (Part 8)
Reinforcement of Concrete
shall retain at least 90 percent of their original tensile
4.1.1 This standard mainly covers requirements for strength.
2
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
NOTE For testing fibres of length less than 10 mm, manufacture shall provide a skein from which fibres of the required length can
be taken for testing tensile strength.
NOTES
1 The gain percent in Table 3 shall be calculated by the formula:
( V2 − V1 ) × 100
Gain percent = V2
where
V1 = value of each parameter for the control sample of cement based matrix, and
V2 = value of each parameter for the fibre reinforced cement based matrix sample.
2 For preparation of test specimen for above functional property of cement based matrix, the manufacture shall declare the optimum
dosage percent of the fibre to be used in cement based matrix. However, in general, fibres are added from 0.06 to 0.3 percent by volume
depending upon the type of fibre and the end use for which concrete is used.
3 Method for preparing reference concrete for evaluating the drying shrinkage gain percent is specified in Annex N.
3
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
6 SAMPLING
Table 4 Scale of Sampling
6.1 Lot (Clause 7.1)
All fibre bags or pouches containing same type of fibre Sl Number of Fibre Sample Sub- Permissible No.
and of same length and diameter dispatched to a buyer No. Pouches in the Lot Size Sample of Defective
against one dispatch note shall constitute a lot. Size Pouches
(1) (2) (3) (4) (5)
6.2 The conformity of the lot to the requirements of
i) Up to 1 200 2 1 0
this standard shall be determined on the basis of the
ii) 1 201 to 3 200 3 1 0
tests carried out on the samples selected from it. iii) 3 201 to 10 000 5 2 0
6.3 The fibres from the bags or pouches selected from iv) 10 001 to 35 000 8 2 1
the lot shall be tested for various requirements specified v) 35 001 to 150 000 13 3 1
in 4.1 to 4.8 and Tables 1 to 3. Any fibre bag or pouch vi) 150 001 to 500 000 20 3 2
failing to meet one or more of the corresponding vii) 500 001 and above 32 5 2
4
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
ANNEX A
(Clause 2)
LIST OF REFERRED INDIAN STANDARDS
ANNEX B
(Clause 4.1.1)
TYPES OF SYNTHETIC FIBRES USED IN SECONDARY REINFORCEMENT OF CONCRETE
5
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
ANNEX C
(Clause 4.3.1)
METHOD OF TEST FOR ISOPHTHALIC ACID CONTENT OF THE VIRGIN POLYESTER FIBRE
C-1 PRINCIPLE intraocculat pressure, irritation of mucous membrane,
conjunctiva. If contacted with skin and eyes cause
This method is applicable to measure isophthalic acid
irritation. Seek medical advice, if inhaled.
content in polyethylene terephthalate sample. The
polymer sample is digested in benzyl alcohol, C-3.6 Use leather hand gloves while handling hot
depolymerized then esterified to dibenzyl isophthalate, apparatus and equipments.
dibenzyl terephthalate and glycols. Isopropyl titanate
is added as a depolymerization catalyst. The sample is C-4 APPARTUS
analyzed by gas chromatography and the peak areas of C-4.1 Gas Chromatograph (GC), with flame
the two esters are used to estimate the weight percentage ionization detector.
dimethyl isophthalate using an internal standard.
C-4.2 Capillary Column, 60 m length and 0.53 mm
C-2 POTENTIAL ENVIORMENT ISSUE ID MXT ® - 1.
C-2.1 In case of spillage, it can lead to pollution near C-4.3 Dispensette or Pipette, 2 ml, 5 ml and 10 ml.
the workplace area and environment hazard. After
C-4.4 Volumetric Flask, 100 ml, 500 ml.
analysis sample is disposed as per laid down procedure.
C-2.2 Hydrogen, nitrogen and instrument air are used C-4.5 Beaker
during analysis. The hydrogen gas has no adverse C-4.6 Funnel
ecological effects are expected. Hydrogen does not
contain any Class I or Class II ozone depleting C-4.7 50 ml Flask
chemicals. However, hydrogen is explosive. Gaseous C-4.8 Heating Mental, to maintain temperature of
nitrogen is an inert non-flammable gas. High 250°C.
concentration in air may cause deficiency of oxygen
with the risk of unconsciousness and death. Chloroform C-4.9 AR Grade Dimethyl Isopthalate (DMI)
in high concentration in air can kill most animals in
few minutes. C-4.10 AR Grade Benzyl Alcohol
6
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
titnate digest it for 2 h. Allow it to cool up to room of 2 percent standard IPA solution. If value of 2.0
temperature then make the volume to 500 ml by percent standard IPA solution is varying in the range
carefully rinsing the flask by isopropyl alcohol. of 0.01 percent, then there is no need for change in
Dimethyl suburate will get converted into dibenzyl response factor. If there is deviation in value then rerun
suburate (DBS). Mark the stock solution as DBS per standard solution for response factor (see C-5.3).
2ml ≈ X·XXXX mg. Weight 0.2 ± 0.02 g of chips into the round bottom
flask. Add 2 ml of benzyl alcohol. Add 3 drops of
C-5.2 Stock Dimethyl Isopthalate (DMI) Solution isopropyl titanate. Digest the solution for 1 h. Allow it
Take 0.2 ± 0.01 g of dimethyl isopthalate (DMI). Add to cool up to room temperature. Add 10 ml of
40 ml of benzyl alcohol and 6 to 7 drops of isopropyl chloroform. Add 2 ml of internal standard solution that
titnate digest it for 2 h. Allow it to cool up to room is solution prepared in C-5.1 and shake vigorously.
temperature then make the volume to 100 ml by Inject 1 µl of sample solution into gas chromatograph.
carefully rinsing the flask by isopropyl alcohol. This
will be converted to dibenzyl isopthalate (DBI). Mark C-8 CHROMATOGRAPH SETTINGS
the stock solution as DBI per 2 ml ≈ X·XXXX mg. Injector temperature : 300°C
C-5.3 Standard Solution for Response Factor Detector temperature : 320°C
Oven temperature : 270°C
Take 2 ml of solution prepared in C-5.1 and 2 ml of
solution prepared in C-5.2. Add 10 ml of chloroform. Gas flow rates
Nitrogen : 20 psig
C-5.4 Two Percent Standard IPA Stock Solution
Hydrogen : 30 ± 10 ml/min
Weigh out accurately 0.200 ± 0.005 g of pure DMI Air : 300 ± 20 ml/min
powder into round bottom flask, add 30 ml of benzyl
Attenuation :4
alcohol and 3 drops of isopropyl titante, reflux the
solution for 5 h reagent and dilute to 100 g by isopropyl Range :1
alcohol, calculate actual DMI concentration by C-9 CALCULATION
considering its purity and label the flask with actual
weight taken. Consider this weight during calculation A1 × W2
of IPA by GC. Response factor (RF) =
A2 × W1
C-5.5 Two Percent Standard IPA Solution for where
GC Injection
A1 = area of dibenzyl suburate (DBS) (Internal
Take 2.0 ml IPA stock solution and add 2 ml internal standard) solution;
standard (see C-5.1) and further add 10 ml of
W1 = weight of DBS in solution, in mg;
chloroform, same bottle to be labelled as 2.0 percent
IPA. Inject 1 µl in GC. A2 = area of DBI in standard solution; and
W2 = weight of DBI in standard solution, in mg.
C-6 CALIBRATION FOR PERFORMANCE
CHECK TWICE /MONTH STANDARD CHIPS RF × Internal standard, mg ×
C-7 ANALYTICAL PROCEDURE Isophthalic = Area of IPA in sample × 100
acid, percent Weight of sample, in mg ×
Inject 1 µl of standard solution for response factor Area of internal standard
(see C-5.3) and calculate response factor. Inject 1 µl in sample
7
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
ANNEX D
(Clause 4.4)
DETERMINATION OF RESISTANCE OF FIBRES TO ALKALIS
ANNEX E
(Clause 4.5)
DETERMINATION OF RESISTANCE OF FIBRES TO ACIDS
E-1 MATERIALS solution after 28 days, wash, dry and condition it
for 24 h at 27 ± 2°C and 65 ± 2 percent relative
E-1.1 Sample of synthetic fibres weighing about 100 g.
humidity.
E-1.2 Solution of hydrochloric acid of pH 4 to 5.
E-2.5 Find out the breaking strength of the 30
E-2 PROCEDURE individual fibres from the test specimen according to
IS 235 (see Note). Calculate the average breaking
E-2.1 Prepare 2 specimens of fibre each weighing about strength for the test specimen. Similarly find out the
20 g. breaking strength of 30 individual fibres from the
E-2.2 Prepare a solution of hydrochloric acid of pH 4 control sample and then calculate the average breaking
to 5. strength of the control specimen.
NOTE For testing fibres of length less than 10 mm,
E-2.3 Keep one specimen as test specimens and manufacture shall provide a skein from which fibres of the
submerge it in the above solution (see E-2.2) in a glass required length can be taken for testing tensile strength
container maintained at pH of 4 to 5 and temperature
of 30 ± 2°C. Cover the solution properly and maintain E-2.6 Calculate the percentage breaking strength
the temperature at 30 ± 2°C for 28 days. Keep the retained as follows:
remaining specimen separately as blank in the standard
atmosphere of 27 ± 2°C temperature and 65 ± 2 percent Test specimen breaking
relative humidity as control sample. Breaking strength = strength (Average)
×100
retained in percent Control specimen breaking
E-2.4 Remove the test specimen from the alkaline strength (Average)
8
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
ANNEX F
(Clause 4.7)
DETERMINATION OF RESISTANCE OF FIBRES TO ULTRA VIOLET LIGHT
F-1 TEST SPECIMENS F-3.2.1 Te type of fluorescent UV lamp, the timing of
the UV exposure and the temperature of condensation
The test specimens for tensile strength shall be taken
shall be as specified in F-2.
from the sample as specified in IS 235.
F-3.3 Determine the average tensile strength of at least
F-2 TEST CONDITIONS 30 individual fibres for each specimen separately for
F-2.1 The test shall be carried out with fluorescent all the six specimens separately as the tensile strength
UV-B lamp (see IS 7903). after UV exposure as given in F-3.2.
F-2.2 The duration of the test shall be 144 h (that is 6 F-3.4 Determine the percent retention of original tensile
days). strength for each specimen as follows:
ANNEX G
(Clause 4.8)
DETERMINATION OF WATER ABSORPTIVE CAPACITY
G-1 PRINCIPLE G-2.3 Dish, for containing the wire gauze with the test
piece attached, of sufficient volume to allow a water
The water absorptive capacity is a measure of the
depth of 20 mm.
amount of water held within a test piece after specified
times of immersion and vertical drainage. For practical G-2.4 Suitable Weighing Glass, with cover.
reasons, the drainage time is quite short. This is
G-2.5 Balance, capable of determining mass to an
especially important, if very volatile liquids are used,
accuracy of 0.01 g.
in which case an assessment of evaporation loss may
be necessary. G-2.6 Stop Watch
G-2 APPARATUS G-2.7 Reagent Grade Water, see IS 1070.
G-2.1 Wire Gauze Test Piece Support, of at least G-3 PREPARATION AND CONDITIONING OF
120×120 mm, with a metal frame. The gauze shall be TEST SPECIMENS
made from a stainless steel test sieve of 2 mm nominal
mesh size [see IS 460 (Part 2)]. G-3.1 Prepare five test specimens in the form of a
uniform wadding or sheet of fibres each of size
G-2.2 Clips, to hold the test piece on the gauze. 100 ± 1 mm × 100 ± 1 mm.
9
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
G-3.2 Condition the test specimens in a standard G-4.6 Remove all clips except one at corner.
atmosphere of 27 ± 2 °C temperature and 65 ± 2 percent
G-4.7 Hang freely and vertically to drain for 120 ± 3 s.
relative humidity for 24 h in accordance with IS 6359.
NOTE The water shall be left long enough to equilibrate
G-4.8 Take the test specimen off the gauze without
with the conditioning atmosphere. squeezing the water from it, place it in the weighing
glass with cover and weigh it.
G-4 PROCEDURE
G-4.9 Repeat G-4.1 to G-4.8 with the remaining four
G-4.1 Carry out the test in the standard atmosphere test specimens.
of 27 ± 2 °C temperature and 65 ± 2 percent relative
NOTE Use fresh conditioned water for each test
humidity. specimen.
G-4.2 Weigh the test specimen to an accuracy
G-5 EXPRESSION OF TEST RESULTS
of 0.01 g, using the balance (see G-2.5) and the
weighing glass with cover (see G-2.4). G-5.1 Calculate the water absorptive capacity (WAC),
in percent, of each test specimen by the formula:
G-4.3 Place the test specimen on the stainless steel
gauze (see G-2.1) fastening it at the edges with the clips
mn − mk
(see G-2.2). WAC = × 100
mk
G-4.4 Place the gauze with the attached test specimen
where
approximately 20 mm below the liquid surface in the
dish (see G-2.3) and start the stop watch (see G-2.6). mk = mass of the dry test specimen, in g; and
Introduce the gauze obliquely in order to avoid trapping mn = mass of the test specimen and the absorbed
air bubbles. liquid at the end of the test, in g.
G-4.5 After 60 ± 1 s, remove the gauze test specimen G-5.2 Report the average water absorptive capacity of
support and test specimen. the five test specimens.
ANNEX H
[Table 1, Sl No. (iii)]
DETERMINATION OF SPECIFIC GRAVITY
H-1 Take a specimen of weighing about 1 g of fibres 4m
from the sample and find out its mass (m) accurately to Specific gravity of fibre =
πd 2 l n
the nearest mg. Count the total number of fibres (n) in
the test specimen. H-4 For triangular cross-section fibres, calculate the
H-2 Let l be the mean fibre length, in cm, correct to specific gravity of the fibre by the formula:
two decimal places as determined by the procedure m
Specific gravity
described in IS 235 and d be the mean fibre diameter, = = 0.433a2×l
of the fibre a × sin 60 × a/2 × l
in cm, correct to two decimal places as determined in
IS 6919. where
H-3 For circular cross-section fibres, calculate the a = side of the equilateral triangle of cross-
specific gravity of the fibre by the formula: section of the fibre.
10
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
ANNEX J
[Table 1, Sl No. (vi) and (vii)]
DETERMINATION OF MELTING AND GLASS TRANSITION TEMPERATURES
11
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
techniques for size reduction often introduce thermal to erase previous thermal history.
effects because of friction or orientation or both, and NOTE In some cases it is possible that the preliminary
thereby change the thermal history of the specimen. thermal cycle will interfere with the transition of interest,
causing an incorrect transition or eliminating a transition. Where
J-4.2 Molded or Pelleted Specimens it has been shown that this effect is present, omit the preliminary
thermal cycle.
Cut the specimens with a microtome, razor blade,
hypodermic punch, paper punch, or cork borer (size J-6.1.4 Hold the temperature for 5 min (see J-6.1.3).
No. 2 or 3) or other appropriate means to appropriate J-6.1.5 Cool to at least 50°C below the peak
size, in thickness or diameter and length that will best crystallization temperature at a rate of 10°C/min and
fit the specimen container, as in J-3.1.5 and will record the cooling curve.
approximately meet the desired weight in the
subsequent procedure. J-6.1.6 Hold the temperature for 5 min.
J-6.1.7 Repeat the heating at a rate of 10°C/min and
J-4.3 Film or Sheet Specimens
record the heating curve.
For films thicker than 40 µm (see J-4.2). Fur thinner
J-6.1.8 Measure the melting temperatures on the curve
films, cut slivers to fit in the specimen capsules or punch
(that is melting extrapolated onset temperature, melting
disks, if the circular specimen capsules are used.
extrapolated end temperature and melting peak
J-4.4 Use any shape or form listed in J-4.1 to J-4.3 temperature.
except when conducting referee tests that shall be
performed on films as specified in J-4.3. J-6.2 Glass Transition Temperature
J-6.2.1 The purge gas shall be used during testing. The
J-5 CALIBRATION
flow rate of the gas shall be the same as used in the
J-5.1 The purge gas shall be used during calibration. calibration.
J-5.2 Calibrate the DSC temperature signal using a J-6.2.2 Use a specimen mass appropriate for the
heating rate of 10°C/min. material to be tested. In most cases, a 10 to 20 mg
specimen mass is satisfactory. Weigh the specimen to
J-5.3 Calibrate the DSC heat flow signal using heating
an accuracy of ±10 µg.
rate of 10°C/min.
J-6.2.3 Perform and record a preliminary thermal cycle
J-5.4 Some instruments allow for the temperature and
by heating the sample at a rate of 20°C/min from at
heat flow calibration to be performed simultaneously.
least 50°C below to 30°C above the melting
In such cases, use the same heating rate for this method
temperature to erase previous thermal history.
(10°C/min) and follow the manufacturers instruction.
J-6.2.4 Hold the temperature for 5 min.
J-6 PROCEDURE
J-6.2.5 Quench cool to at least 50°C below the
J-6.1 Melting Temperature transition temperature of interest.
J-6.1.1 The purge gas shall be used during testing. The J-6.2.6 Hold the temperature for 5 min.
flow rate of the gas shall be the same as used in the
J-6.2.7 Repeat heating at a rate of 20°C/min and record
calibration (10°C/min).
the heating curve until all desired transitions have been
J-6.1.2 Use a specimen mass appropriate for the completed.
material to be tested, In most cases, a 5 mg specimen
J-6.2.8 The glass transition is more pronounced at faster
mass is satisfactory. Avoid overloading. Weigh the
heating rates. A heating rate of 20°C/min is used for
specimen to an accuracy of ±10µg.
Tg measurements. The instrument shall be calibrated
J-6.1.2.1 Intimate thermal contact between the pan and at this heating rate. If both first and second-order
specimen is essential for reproducible results. Crimp a transition (Tm and Tg, respectively) arc to be
metal cover against the pan with the sample sandwiched determined in the same run, use procedure J-6.1 and
in between to ensure good heat transfer. Take care to determine results from the second heating step
ensure flat pan bottoms. (see G-6.1.7).
J-6.1.3 Perform and record a preliminary thermal cycle J-6.2.9 Measure Tg (extrapolated onset temperature,
by heating the sample at a rate of 10°C/min from at midpoint temperature and extrapolated end
least 50°C below to 30°C above the melting temperature temperature)
12
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
ANNEX K
[Table 1, Sl No. (viii)]
DETERMINATION OF INTRINSIC VISCOSITY
K-3.13 Wiley Mill Grinder, with 20 mesh stainless K-7.2 Place a TFE fluorocarbon plastic-coated stirring
steel screen. bar into the flask and add approximately 25 ml of
solvent. Prepare one flask without any sample present.
K-3.14 Drying Oven Cap the flasks.
13
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
K-7.3 Place the flasks in steel beakers and place on a past the calibration marks.
magnetic hot plate which has been preheated to 110°C.
K-7.9 Record the flow time and repeat the measurement
Heat the flasks for 15 min while stirring. Remove flasks
three more times. Average these results unless the range
and inspect for undissolved PET, PA or PP. If a sample
in time exceeds 0.2 s. in which case make additional
does not dissolve completely, extend the stirring time
measurements until four within a range of 0.2 s are
for up to 30 more min while inspecting the sample at
obtained for averaging. Measure the solvent flow time
10 min intervals. If the sample fails to dissolve
in the same manner as the flow time of the solution
completely at this time, this procedure is not applicable.
samples.
K-7.4 When the samples have completely dissolved,
K-7.10 During the measurements, record the bath
remove the flasks from the hot plate and allow them to
temperature to the nearest 0.01°C. Ensure that the
cool to approximately room temperature. Remove the
range in temperature does not exceed 0.01°C.
stirring bars with a magnetic retriever and wash the
bar with fresh solvent letting the wash solvent fall back K-7.11 When measurements are completed, remove the
into the volumetric flask. Add additional solvent to a viscometer from the bath and carefully pour the
level about 1cm below the 50 ml mark. Place the flasks solution from the viscometer into a safety disposal
in the constant temperature bath preset at 30 ± 0.01°C. container.
Allow the flasks to sit for 10 min to reach the bath
temperature. Invert the stoppered flasks to wash down K-8 CALCULATION
solvent droplets adhering to the flask walls above the K-8.1 Determine the inherent viscosity as follows:
polymer solution and add sufficient solvent to raise the
liquid level up to the 50 ml mark. (l n × ηr )
ηmin =
K-7.5 Pour the solution in to a clean dry, Cannon- C
Ubbelohde viscometer by passing it through a funnel
and filter screen into the top of the larger viscometer where
tube. Fill the viscometer to a level between the level ηmin = inherent viscosity at 30°C and at a polymer
lines on the large reservoir bulb at the bottom of the concentration of 0.5 g/d (dimensions of
larger tube. Remove the funnel and place the viscometer inherent viscosity are dl/g);
in the constant temperature bath preset at 30 ± 0.01°C.
ηr = relative viscosity (t/t0);
Allow at least 15 min for the temperature of the solution
in the viscometer to reach equilibrium. t = average solution flow time, in s;
t0 = average solvent flow time, in s; and
K-7.6 Using suction from an aspirator, draw the
solution through the capillary to a level above the top C = polymer solution concentration, in g/dl.
calibration mark. Regulate the level by capping the K-8.2 Calculate the intrinsic viscosity η from a single
breather tube with one rubber-gloved finger and measurement of the relative viscosity by the Billmeyer
carefully applying suction to the top of the capillary relationship:
tube. Use care to prevent splashing or bubble formation.
A valve in the aspirator line has been found to be useful η = 0.25 (ηr 1 + 3 lnηr)/C
to control the suction.
K-9 REPORT
K-7.7 Let the sample solution or solvent flow back
Report the following information:
down the capillary tube by removing the suction from
the top of the capillary tube and by removing the finger a) Sample identification and description;
from the top of the breather tube. The first flow is a b) Sample mass;
rinse to wet the capillary bulb and finally equilibrate c) Percent of inert material;
the sample solution to the bath temperature.
d) Sample dissolution time and temperature;
K-7.8 After the solution has drained out of the capillary, e) Average solvent flow time;
repeat K-7.6 and K-7.7 and time the period required f) Average solution flow time;
for the liquid to fall back from the higher calibration
g) Average viscometer bath temperature;
mark to lower calibration mark above the capillary. Use
the electric timer for this measurement. The bottom of h) Inherent viscosity (three significant places);
the meniscus of the liquid surface is used for and
determining the times at which the liquid surface flows j) Intrinsic viscosity
14
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
ANNEX L
[Table 2, Sl No. (i)]
DETERMINATION OF EQUIVALENT FIBRE DIAMETER
L-1 FIBRE WITH CIRCULAR CROSS- weigh it accurately to the nearest mg. Count the number
SECTION of total fibres in the sample and find out the average
mass of individual fibre by dividing the mass of sample
L-1.1 For fibres with a diameter less than 0.3 mm, the
by the total number of fibres in it. Measure the length
diameter shall be measured using optical microscope.
of 50 fibres accurately and calculate average fibre
30 individual fibres diameter shall be measured and
length. The average mass, mf in g, and the average
then mean fibre diameter shall be calculated.
(developed) length, ld in mm, of the fibre shall be
L-1.2 For fibres with a diameter greater than 0.3 mm, determined to an accuracy of 0.001 g and 0.01 mm,
the diameter of the fibre shall be measured with a respectively. The equivalent fibre diameter shall be
micrometer to a precision of 0.001 mm. 30 individual computed from the mass and the developed length using
fibres diameter shall be measured and then mean fibre the following formula with the nominal density of the
diameter shall be calculated. fibre, ρ, in g/cm3:
ANNEX M
[Table 2, Sl No. (iii)]
DETERMINATION OF ASPECT RATIO OF FIBRES
M-1 From the equivalent fibre diameter as determined by the procedures described in L-2.1, determine the aspect
ratio by the formula:
15
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
ANNEX N
(Table 3, Note 3)
PREPARATION OF REFERENCE CEMENT BASED MATRIX TO BE USED FOR EVALUATING
SYNTHETIC FIBRES FOR REINFORCEMENT IN CEMENT BASED CONSTRUCTIONS
N-1 GENERAL index together not more than 30 percent. The aggregates
shall be from hard rocks, such as basalt or granite.
The composition and characteristics of reference
cement based matrix for construction used to evaluate N-3.1.2 Fine aggregate shall be the sand conforming
the performance of synthetic fibres under standard to Zone II as defined in IS 383, with a maximum
laboratory conditions. of 3 percent of the material passing through the 75
micron sieve.
N-2 REQUIREMENTS OF REFERENCE
CEMENT BASED MATRIX FOR N-3.1.3 The aggregate grading, measured according to
CONSTRUCTION IS 2386 (Part 1) shall conform to IS 383.
The reference concretes shall be designed to meet a Water for mixing in concrete and for curing shall
prescribed flexural strength, as defined in Table 4. conform to the requirements of IS 456 (see 5).
N-3.3 Cement
Table 4 Parameters of Reference Cement Based
Matrix for Construction Ordinary Portland cement 53 grade conforming
(Clause N-2.1) to IS 12269 shall be used.
16
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
f) For the matrix with fibres, care shall be taken reporting the average flexural strength.
to ensure that the fibres are evenly distributed
throughout the mix. N-6 REPORT
The following information shall be recorded for the
N-5 STRENGTH EVALUATION
reference concrete:
N-5.1 Compressive strength shall be determined using
a) Origin and particle size distribution of coarse
150 mm×150 mm×150 mm cubes at the age of 28 days,
and fine aggregates, and brand and type of
for both the concrete mixes without and with fibres.
cement and admixtures used;
N-5.2 If the reduction in compressive strength of the b) Mix composition including dry aggregates and
matrix with fibres is found to be more than 5 percent admixtures, in kg/m³, and details of mixing
than that of the matrix without fibres, the reference matrix procedure;
shall be checked for cohesiveness, air entrainment and c) Fibre type and properties described according
voids, and the reference mix may be corrected, if to this standard /norm/guide;
necessary. Normally, statistically significant reduction d) Workability and compressive strength, of the
in compressive strength, indicates inappropriate mix plain and fibre cement based matrix
proportion, and needs revision of the aggregate grading. e) Date and time of casting and testing of
N-5.3 Six prismatic 150 mm×150 mm×550 mm (or specimens;
even longer) specimens, made from a reference matrix f) Drying shrinkage as per IS 1199; and
without incorporating fibres will be tested for flexural g) Flexural strength to the nearest 0.05 MPa
strength after 28 days under third-point loading (at one (average of specimens) for the plain cement
third span) on a 450 mm span as per IS 516, for based matrix.
17
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
IS 16481 : 2016
ANNEX P
(Foreword)
COMMITTEE COMPOSITION
Technical Textiles for Build Tech Sectional Committee, TXD 34
Organization Representative(s)
Indian Institute of Technology, New Delhi PROF B. BHATTACHARJEE (Chairman)
E.I. Dupont India Private Ltd, Gurgaon SHRI MANISH BANSAL
SHRI ATANU ACHARYA (Alternate)
FICCI, New Delhi SHRI CHETAN BIJESURE
SHRI SURESH KANNAN (Alternate)
Reliance Industries Ltd, New Delhi SHRI M. S. VERMA
SHRI RAJIV GAURI (Alternate)
All India Flat Tape Manufacture Association, New Delhi SHRI K. S. ARORA
SHRI SANJAY JAIN (Alternate)
Bekaert Industries Private Ltd, Pune SHRI GANESH CHAUDHARI
SHRI NAVNEET NARAYAN (Alternate)
Building Materials and Technology Promotion DR SHAILESH KUMAR AGRAWAL
Council, New Delhi SHRI J. K. PRASAD (Alternate)
Business Co-ordination House, New Delhi SHRI SAMIR GUPTA
SHRIMATI RITIKA GUPTA (Alternate)
Central Building Research Institute, Roorkee SHRI S. K. SINGH
Central Road Research Institute, New Delhi REPRESENTATIVE
CSIR-Structural Engineering Research Centre, Chennai SHRIMATI SMITHA GOPINATH
SHRI V. RAMESH KUMAR (Alternate)
Delkon Textiles Private Ltd, Faridabad SHRI VIKAS SINGHAL
SHRI G. S. SINGHAL (Alternate)
DSC Group, New Delhi COL M. K. SOOTA
Indian Technical Textile Association, Mumbai SHRIMATI SHASHI SINGH
Larson & Turbro Ltd, New Delhi REPRESENTATIVE
Nina Concrete System Pvt. Limited, Mumbai SHRI RAKESH GUPTA
SHRI KAUSHAL PARIKH (Alternate)
Office of Textile Commissioner, Mumbai SHRI AJAY PANDIT
SHRI M. BALUCHAMY (Alternate)
Oriental Infrastructure Limited, COL A. K. BHASIN
PEC University of Technology, Chandigarh DR S. K. SINGH
DR P. K. GUPTA (Alternate)
Plastindia Foundation, Mumbai SHRI SURENDER CHOUDHARY
SHRI L. K. SINGH (Alternate)
Raina Industries Private Ltd, Mumbai DR MOHIT RAINA
Shapoorji Pallanji & Co Limited, Nagpur SHRI MANOJ KAWALKAR
SHRI HEMANT GOPINATH JOSHI (Alternate)
Synthetic & Art Silk Mills Research Association, Mumbai SHRI RAVI PRAKASH SINGH
SHRI PREMNATH SURWASE (Alternate)
Textile Committee, New Delhi SHRI P ANKAJ MALIK
SHRI V. SAKSENA (Alternate)
In personal capacity (36 Old Sneh Nagar, Wardha Road, SHRI L. K. JAIN
Nagpur 440 015)
BIS Directorate General S HRI P RABHAKAR R AI , Scientist E and Head (TXD)
[Representing Director General (Ex-officio)]
Member Secretary
SHRI J. K. GUPTA
Scientist C (TXD), BIS
18
Free Standard provided by BIS via BSB Edge Private Limited to Dinesh Gaikwad -
Panvel(dineshgaikwad.1739@rediffmail.com) 185.221.69.47 [for non-commercial use only].
BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods
and attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publications), BIS.
Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of
BIS Catalogue and Standards : Monthly Additions.
This Indian Standard has been developed from Doc No.: TXD 34 (1145).