STRUCTURAL DRAWINGS

FOR
THREE AND HALF STOREY RESISDENCE
OWNER : DAW JIT TOO MAR ZAW
LOCATION : CORNER OF 65 & 118-A STREETS, MANDALAY

MATT MYANMAR
PROJECT NO. - Z00122
CLIENT - DAW JIT TUU MAR ZAW
RELEASED DATE - JUNE/2022 Design and Construction Company Limited.
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


DRAWING LIST f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
NO SHEET NO. DRAWING TITLE fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
01. S-PLO.01 PILE LAYOUT PLAN @ LVL. -03'-08" 2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
02. S-PDT.01 PILING DETAILS
03. S-GN-DT01 GENERAL DESIGN SPECIFICATIONS
04. S-GN-DT02 MATERIAL SPECIFICATION & GENERAL NOTE FOR REINFORCEMENT
05. S-GN-DT03 GENERAL NOTE
06. S-GN-DT04 SPLICE DETAILING & CONCRETE PROTECTION FOR REINFORCEMENT
07. S-GN-DT05 ANCHORAGE DETAILING & STEEL CUT OFF POINT FOR BEAM
08. S-GN-DT06 SPLICE DETAILING (FOR BEAM) PROJECT :
THREE AND HALF STOREY
09. S-GN-DT07 - STIRRUP SCHEDULE FOR TYPICAL (FLOOR) MAIN BEAM RESISDENCE
- STEEL CUT OFF POINT SIGN FOR DIFFERENT BAR QUANTITIES [CORNER OF 65TH & 110A STREET]
- TYPICAL BEAM SECTION DETAILS WITH TORSION BARS
10. S-GN-DT08 SPLICE DETAIL FOR COLUMN BLOCK NO.
11. S-GN-DT09 TYPICAL BEAM DETAILS & GENERAL DETAIL FOR PIPE SLEEVE PENETRATION LOT NO.
12. S-GN-DT10 GENERAL DETAILS - 1 TOWNSHIP CHAN MYA THARSI, MANDALAY

13. S-GN-DT11 GENERAL DETAILS - 2


SUBJECT :
14. S-FM.01 PILE CAP LAYOUT PLAN @ LVL. 00'-00" DRAWING LIST

15. S-FM.02 RETAINING WALL LAYOUT PLAN


16. S-FM.03 GROUND FLOOR LAYOUT PLAN @ LVL. +02'-06" SCALE : SHEET NO :
17. S-FM.04 FIRST FLOOR LAYOUT PLAN @ LVL. +15'-00" DATE : JUNE/2022 S-DL01

18. S-FM.05 SECOND FLOOR LAYOUT PLAN @ LVL. +27'-00" REVISION NO ( - ) DATE ( - )
19. S-FM.06 THIRD FLOOR LAYOUT PLAN @ LVL. +38'-06" REVISION NO ( - ) DATE ( - )
20. S-FM.07 ROOF FLOOR LAYOUT PLAN @ LVL. +50'-00"
OWNER :
21. S-FM.08 ROOF TOP LAYOUT PLAN @ LVL. +61'-06"
22. S-FM.09 PART PLAN OF STAIR CASE
23. S-FM.10 PART PLAN OF FIRST FLOOR (STEEL BEAM FRAMING PLAN & CONNECTION LAYOUT PLAN) DAW JIT TOO MAR ZAW

24. S-SCD.01 STEEL CONNECTION DETAILS - 1


25. S-SCD.02 STEEL CONNECTION DETAILS - 2 (BASE PLATE CONNECTION)
26. S-RBD.01 R.C DETAIL FOR BEAM - 1 L.C :
27. S-RBD.02 R.C DETAIL FOR BEAM - 2
28. S-RBD.03 R.C DETAIL FOR BEAM - 3
29. S-RBD.04 R.C DETAIL FOR BEAM - 4
30. S-RBD.05 R.C DETAIL FOR BEAM - 5
31. S-RBD.06 R.C DETAIL FOR BEAM - 6
R.S.E / P.E (CONSTRUCTION) :
32. S-RBD.07 R.C DETAIL FOR BEAM - 7
33. S-RSD.01 R.C DETAIL FOR SLAB & STAIR - 1
34. S-RSD.02 R.C DETAIL FOR SLAB & STAIR - 2
35. S-RSD.03 R.C DETAIL FOR SLAB & STAIR - 3
36. S-RCD.01 R.C DETAIL FOR COLUMN - 1
37. S-RCD.02 R.C DETAIL FOR COLUMN - 2 R.S.E / P.E (STRUCTURE) :
38. S-PC.01 R.C DETAIL FOR PILE CAP - 1
39 S-PC.02 R.C DETAIL FOR PILE CAP - 2
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


1 2 3 4 5 f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
58'-6" CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
12' 17'-3" 17'-3" 12'

1PC1 2PC1A 2PC1A 1PC1 1PC1

1'-9"

1'-9"

1'-9"

1'-9"

1'-9"
C

1'-9"

1'-9"

1'-9"

1'-9"

1'-9"
1'-9" 1'-9" 1'-9" 6' 1'-9" 1'-9" 6' 1'-9" 1'-9" 1'-9" 1'-9" 1'-9"

PROJECT :
THREE AND HALF STOREY
RESISDENCE
[CORNER OF 65TH & 110A STREET]
17'-3"

3'-6"
1'-9" 1'-9" 1'-9" 6' 1'-9" 1'-9" 6' 1'-9" 1'-9" 1'-9" BLOCK NO.
LOT NO.
1'-9"

1'-9"

1'-9"

1'-9"
TOWNSHIP CHAN MYA THARSI, MANDALAY

1'-9" 1'-9"
34'-6"

B SUBJECT :
6'

6'

6'

6'

1'-9"
PILE LAYOUT PLAN @ LVL. -03'-08"
1'-9"

1'-9"

1'-9"

1'-9"
SCALE : AS SHOWN SHEET NO :

6'
2PC1A 4PC1 4PC1 2PC1
DATE : JUNE/2022 S-PLO.01
17'-3"

1'-9"
REVISION NO ( - ) DATE ( - )
2PC1
REVISION NO ( - ) DATE ( - )

OWNER :
1'-9" 1'-9" 1'-9" 6' 1'-9" 1'-9" 6' 1'-9" 1'-9" 6' 1'-9"
1'-9"
1'-9"

1'-9"

1'-9"
A
1'-9"
1'-9"

1'-9"

1'-9"
DAW JIT TOO MAR ZAW
1PC1 2PC1 2PC1 2PC1

NOTE:
1. ALL PILE CUT OFF LVL. TO BE -03.667' UNLESS STATED OTHERWISE.
1. ALL PILE CAPS TO BE 48" THICK UNLESS STATED OTHERWISE. L.C :
PILE LAYOUT PLAN @ LVL. -03'-08" 2. ALL PILE CAP TOP LEVEL = 00'-00".
GENERAL NOTE FOR MINI-BORED PILE
1. CONCRETE USED SHALL BE G30(4350PSI) FOR ALL PILES.
1 Scale: 1/8"=1"-0"
PILE CENTER TO CENTER SPACING = 6'
PILE CENTER TO EDGE DISTANCE = 21"
2. CONCRETE COVER TO THE NEAREST REINFORCEMENT SHALL BE 3". ALL DIMENSION ARE TO BE CHECKED AND VERIFIED ON SITE.
3. THE BASE OF THE PILE SHALL BE THOROUGHLY CLEAN, SOUND AND FREE FROM LOOSE SAND DEPOSIT, LAITANCE, SILT PRIOR TO CONCRETING. THE CONTRACTOR SHALL
CLEAN. THE BASE USING AIR LIFT AND/OR OTHER APPROVED METHOD. ALL PILES BASES SHALL BE POST GROUTED AS PER SPECIFICATIONS, IF THE PRELIMINARY PILE LOAD TEST
REQUIRED.
4. MINIMUM REINFORCEMENT LAP SHALL BE 48 TIMES THE BAR DIAMETER.
5. ALL LOAD TESTS ON PILES MUST COMPLY WITH REQUIREMENTS DETAILED IN TECHNICAL SPECIFICATIONS. REINFORCEMENT SCHEDULE FOR PILES R.S.E / P.E (CONSTRUCTION) :
6. LENGTH OF REINFORCING BARS INDICATED ON THE DRAWING ARE STRAIGHT LENGTH ONLY.
7. THE PILE SHALL NOT DEVIATE FROM VERTICAL BY MORE THAN 1 IN, AND SHALL BE MEASURED ON SITE USING A PLUMB LINE AT GROUND LEVEL AND RECHECKED AT THE PILE SIZE ESTIMATED PILE LENGTH PILE REINFORCEMENT
CUT-OFF LEVEL. THE CROSS-SECTIONAL DIMENSION OF THE PILE IS NOT TO BE LESS THAN SPECIFIED. CHECK THE AUGER WIDTH AS REQUIRED AND RECORD FOR EACH PILE TO (DIA. IN) FROM STREET LEVEL(FT) MAIN REIN. SPIRAL LINKS
ENSURE THE SPECIFIED DIAMETER IS ACHIEVED, ALLOW A TOLERANCE OF 5% ON THE AUGER WIDTH.THE PERMISSIBLE TOLERANCE IN THE TRUE CUT-OFF LEVEL WILL BE PLUS OR
MINUS 1", UPON FINAL DRAWING. TOP 6' T10-4IN
24 40 10T20
8. REINFORCING BARS YIELD STRENGTH SHALL BE HRB500(72500PSI). OTHERS T10-6IN
11. PILE LOAD TEST REQUIREMENTS
(a) WORKING PILE LOAD TEST IS TO BE CARRIED OUT FROM GROUND LEVEL.
(b) PILE IS TESTED TO 2.0 TIMES WORKING LOAD. FINAL LOAD TEST ARE LISTED IN TABLE A. TOTAL NUMBER OF PILES 28 NOS
(c) THE ALLOWABLE MAXIMUM SETTLEMENT MEASURED AT THE PILE TOP UNDER FULL TEST LOAD SHALL NOT LARGER THAN 1". R.S.E / P.E (STRUCTURE) :
(d) THE PILE LOADING TEST IS TO BE PERFORMED BY MEANS OF JACK WHICH IT'S REACTION FROM TENSION PILES. ESTIMATED PILE LENGTH 40FT
(e) THE TEST LOAD SHOULD BE APPLIED IN 2 EQUAL INCREMENTS UP TO THE DESIGN PILE WORKING LOAD, THEN RELEASED AND REAPPLIED IN 4 EQUAL INCREMENTS UP TO
THE PILE TEST LOAD (TWICE OF THE MAX. WORKING LOAD) UNDER WORKING LOAD AND MAINTAINED FOR A LEAST 72 HOURS BEFORE REMOVAL. PILE SIZE Ø24"
(f) THE LOAD AT EACH INCREMENTAL STAGE SHOULD BE HELD FOR A PERIOD OF 10 MINUTES OR LONGER UNTIL THE RATE OF SETTLEMENT IS LESS THAN 0.01"/HR. FOR EACH
STAGE THE LOAD OF INCREMENT OF LOAD SHOULD BE APPLIED AS SMOOTHLY AND EXPEDITIOUSLY AS POSSIBLE. PILE ALLOWABLE LOAD 75TONS(SAFETY FACTOR 2)
(g) THE TEST LOAD SHOULD BE MEASURED NY A CALIBRATED LOAD MEASURING DEVICE AND ALSO BY A CALIBRATED PRESSURE GAUGE IN THE HYDRAULIC SYSTEM.
(h) LOADING TEST PROPOSAL SHALL BE PREPARED BY CONTRACTOR AND SUBMITTED TO ENGINEER FOR APPROVAL PRIOR TO TESTING WORKS. PILE WORKING LOAD 150TONS
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
PILE CAP TOP LEVEL (00') f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
2' fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

10T20

F.T.L
T10-4IN
SPIRAL LINKS
MAIN REINFORCEMENT 10T20
SPIRAL LINKS T10-4IN
PILE CUT OFF LEVEL (-03.667')
PILE CAP BASE LEVEL (-04') SECTION 1-1
PROJECT :
THREE AND HALF STOREY
RESISDENCE
2' [CORNER OF 65TH & 110A STREET]

BLOCK NO.

1 LOT NO.
T10-4IN

3xPILE DIAMETER
TOWNSHIP CHAN MYA THARSI, MANDALAY
10T20

6'
T10-6IN SUBJECT :
40FT FROM LVL. 00'

SPIRAL LINKS PILING DETAILS


MAIN REINFORCEMENT 10T20
ESTIMATE PILE LENGTH

SPIRAL LINKS T10-6IN


1
SECTION 2-2 SCALE : 2"=1" SHEET NO :
DATE : JUNE/2022 S-PDT.01
REVISION NO ( - ) DATE ( - )
REVISION NO ( - ) DATE ( - )

OWNER :
2
DAW JIT TOO MAR ZAW

L.C :
T10-6IN

R.S.E / P.E (CONSTRUCTION) :

R.S.E / P.E (STRUCTURE) :

PILE BASE LEVEL (-40')

PILE SECTION DETAIL


GENERAL DESIGN SPECIFICATION NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


DESIGN SPECIS WIND WIND COEFFICIENTS WIND SPEED (MPH) 80.000
f'c = 3000psi(G20.69) FOR BEAM & SLAB
SPECIFICATIONS BUILDING CODES IBC 2006 EXPOSURE TYPE B f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
LOCAL BUILDING CODES MNBC 2020, MNBC, YCDC TOPOGRAPHICAL FACTOR, Kzt 1.000 AND ALL CAST-IN REBAR
MINIMUM DESIGN LOAD ASCE 7-10 0.850 2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
GUST FACTOR
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
CONCRETE FRAME DESIGN ACI 318-14 DIRECTIONALLY FACTOR, Kd 0.850
STEEL FRAME DESIGN
STRUCTURAL WELDING DESIGN
COLD FORMED FRAME DESIGN
DETAILING ACI DETAILING MANUAL - MNL-66(20)
APPLIED SOFTWARES SUPER STRUCTURE ETABS 2019
SUB STRUCTURE TEKLA TEDDS 2021
DRAWING AUTOCAD 2022 PROJECT :
THREE AND HALF STOREY
LOADING DEAD LOAD 4.5" CLAY BRICK WALL 55 PSF RESISDENCE
9" CLAY BRICK WALL 100 PSF [CORNER OF 65TH & 110A STREET]

FINISH LOAD 25 PSF


LIVE LOAD STAIR 100 PSF BLOCK NO.
GYM & BEAUTY SALON 100 PSF LOT NO.
DINNING ROOM 100 PSF
TOWNSHIP CHAN MYA THARSI, MANDALAY

ROOF GARDEN 100 PSF


80 SUBJECT :
CORRIDOR PSF
MAID ROOM 80 PSF GENERAL DESIGN SPECIFICATIONS

STUDY ROOM 60 PSF


VERANDAH 60 PSF SCALE : SHEET NO :
LIVING ROOM 60 PSF DATE : JUNE/2022 S-GN-DT01
STAFF ROOM 60 PSF
REVISION NO ( - ) DATE ( - )
MASTER BED ROOM 40 PSF
KITCHEN 40 PSF REVISION NO ( - ) DATE ( - )
ROOF TOP SLAB 40 PSF OWNER :
WAREHOUSE(LIGHT) 125 PSF
ROOF LIVE 20 PSF
QUAKE DIRECTION & ECCENTRICITY X DIRECTION DAW JIT TOO MAR ZAW

FACTORS RESPONSE MODIFICATION (R) 8.0


OCCUPANCY IMPORTANCE (I) 1
1.20
SEISMIC COEFFICIENTS 0.2 SEC SPECTRAL ACCEL (Ss) L.C :
1 SEC SPECTRAL ACCEL (S1) 0.70
6
LONG-PERIOD TRANSITION PERIOD
SITE CLASS E
SITE COEFFICIENT (Fa) 0.900
SITE COEFFICIENT (Fv) 2.400
R.S.E / P.E (CONSTRUCTION) :
QUAKE DIRECTION & ECCENTRICITY Y DIRECTION
FACTORS RESPONSE MODIFICATION (R) 8.0
OCCUPANCY IMPORTANCE (I) 1
1.20
SEISMIC COEFFICIENTS 0.2 SEC SPECTRAL ACCEL (Ss)

1 SEC SPECTRAL ACCEL (S1) 0.70


6 R.S.E / P.E (STRUCTURE) :
LONG-PERIOD TRANSITION PERIOD
SITE CLASS E
SITE COEFFICIENT (Fa) 0.900
SITE COEFFICIENT (Fv) 2.400
NOTE:
MATERIAL SPECIFICATIONS & TEST METHODS
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
f'c = 3000psi(G20.69) FOR BEAM & SLAB
CEMENTITIOUS MATERIALS PORTLAND CEMENT ASTM C150 f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AGGREGATES NORMALWEIGHT ASTM C33 AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
WATER - ASTM C1602

WELDING REINFORCING BARS AWS D1.4

DEFORMED REINFORCEMENT CARBON STEEL ASTM A615

PLAIN REINFORCEMENT CARBON STEEL ASTM A615

HEADED SHEAR STUD REINFORCEMENT HEADED STUDS AND HEAED STUD ASSEMBLIES ASTM A1044 PROJECT :
THREE AND HALF STOREY
MAKING AND CURING CONCRETE TEST SPECIMENS IN THE FIELD C31 RESISDENCE
TEST METHOD FOR COMPRESSIVE STRENGTH OF CYLINDRICAL [CORNER OF 65TH & 110A STREET]
C39
CONCRETE SPECIMENS
READY-MIXED CONCRETE C 94 BLOCK NO.
TEST METHOD FOR COMPRESSIVE STRENGTH OF HYDRAULIC CEMENT
C 109 LOT NO.
MOTORS
ADMIXTURES WATER REDUCTION AND SETTING TIME MODIFICATION ASTM C494 TOWNSHIP CHAN MYA THARSI, MANDALAY

SUBJECT : MATERIAL SPECIFICATION &


PRODUCING FLOWING CONCRETE ASTM C1017 GENERAL NOTE FOR
REINFORCEMENT
AIR-ENTRAINING ADMIXTURES ASTM C260
SCALE : SHEET NO :
DATE : JUNE/2022
GENERAL NOTES FOR REINFORCED CONCRETE S-GN-DT02

REVISION NO ( - ) DATE ( - )
STANDARD REINFORCING BARS NOMINAL MAXIMUM SIZE OF COARSE AGGREGATE
REVISION NO ( - ) DATE ( - )
< 51 (THE NARROWEST DIMENSION BETWEEN SIDES OF FORMS)
DESIGNATION NOMINAL DIAMETER NOMINAL AREA WEIGHT
OWNER :
< 31 (THE DEPTH OF SLABS)
d(aggregate)
MM IN MM2 IN2 KG/M LB/FT < 3/4( (THE MINIMUM CLEAR SPACING BETWEEN INDIVIDUAL REINFORCING BARS
6 6 0.24 28.27 0.04 0.22 1.61 OR WIRES, BUNDLES O FBARS) DAW JIT TOO MAR ZAW

8 8 50.27 0.08 0.40 2.86


10 10 0.39 78.54 0.12 0.62 4.46
12 12 0.47 113.10 0.18 0.89 6.42 L.C :
14 14 0.55 153.90 0.24 1.21 8.75
16 16 0.00 201.10 0.31 1.58 11.43
18 18 0.71 254.00 0.39 2.00 14.47
20 20 0.79 314.20 0.49 2.47 17.87
22 22 0.87 380.10 0.59 2.98 21.55
R.S.E / P.E (CONSTRUCTION) :
25 25 0.98 490.90 0.76 3.85 27.85
28 28 1.10 615.00 0.95 4.83 34.94
32 32 1.26 804.00 1.25 6.31 45.64
36 36 1.42 1018.00 1.58 7.99 57.79

40 40 1.58 1257.00 1.95 9.87 71.39


R.S.E / P.E (STRUCTURE) :
50 50 1.97 1964.00 3.04 15.42 111.53
NOTE:
GENERAL NOTES:
SLUMP LIMITS: PROPORTION AND DESIGN MIXES TO RESULT IN CONCRETE SLUMP
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
1. THESE NOTES APPLY TO ALL DRAWINGS. AT POINT OF PLACEMENT AS FOLLOWS: f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
2. ALL STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE ARCHITECTURAL. 1. RAMPS. AND SLOPING SURFACE: NOT MORE THAN 3IN. fy = 58000psi(HRB400) For ALL REINFORCING BARS
PLUMBING,ELECTRICAL,MECHANICAL AND OTHER SERVICES DRAWINGS. ALL CHASES,CHAMFERS, 2. WALLS. COLUMNS, BEAMS AND SLABS: NOT MORE THAN 4IN. AND ALL CAST-IN REBAR
3. REINFORCED FOUNDATION SYSTEMS: NOT MORE THAN 3IN. 2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
POCKETS,OPENINGS,FIXINGS TO BE BUILT-IN FOR OTHER TRADES ,ETC.SHALL BE PROVIDED IN CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
4. CONCRETE CONTAINING HRWR ADMIXTURE (SUPERPLASTICIZER):
THE LOCATION AND TO THE SIZES SHOWN ON THE DRAWINGS OR AS REQUIRED.THE CONTRACTOR NOT MORE THAN 8IN AFTER ADDITION OF HRWR TO
SHALL CHECK ALL DRAWINGS AND VERIFY LEVELS AND DIMENSIONS IN ADVANCE OF THE WORK SITE VERIFIED 2IN to 3IN SLUMP CONCRETE.
AND REPORT ANY DISCREPANCIES TO THE ENGINEER IMMEDIATELY. 5. OTHER CONCRETE: NOTE MORE THAN 4IN.
3. UNLESS NOTED OTHERWISE ALL LEVELS REFER TO TOP OF STRUCTURAL CONCRETE. CONSTRUCTION TOLERANCES:
4. THE CONTRACTOR SHALL OBTAIN THE ENGINEER'S APPROVAL TO ALL EXCAVATIONS BEFORE PLACING STANDARD TOLERANCES FOR CONCRETE CONSTRUCTION AND
ANY BLINDING LAYER OR REINFORCEMENT. MATERIALS" ACl 117-81 WITH FOOTNOTE DELETED REFERRING TO
5. ALL CONCRETE WORKS SHALL CONFORM WITH MYANMAR NATIONAL CODE AND ACI STANDARD. BUILDINGS OVER 100feet(30m)IN HEIGHT. TOLERANCE GIVEN IN ACI 117
6. CONCRETE GRADES NOTE: FROM TABLE OF STRENGTH,CONTRACTOR SHALL USE HIGHER STRENGTH BETWEEN CUBE AND CYLINDER. SHALL APPLY THROUGHOUT THE FULL HEIGHT OF THE BUILDING. PROJECT :
THREE AND HALF STOREY
RESISDENCE
CYLINDER STRENGTH EQUIVALENT CUBE STRENGTH [CORNER OF 65TH & 110A STREET]
GRADE ELEMENT
AT 28DAYS AT 28DAYS
ALL BEAMS, SLABS, AND WEARING SLABS. BLOCK NO.
20.6/26.4 MIX 3000psi 3846psi
ALL SUPERSTRUCTURE BEAMS AND SLABS OR STRUCTURES AS TO NOTED ON DRAWINGS.
LOT NO.
20.6/26.4 MIX 3000psi 3846psi ALL COLUMNS, WALLS AND PILE CAPS OR STRUCTURES AS NOTED ON DRAWINGS. TOWNSHIP CHAN MYA THARSI, MANDALAY

SUBJECT :
7. HIGH TENSILE STEEL BARS SHALL BE HOT ROLLED DEFORMED AND CONFORMED WITH ASTM A615-617 AND HAVE A GUARANTEE YIELD STRESS GENERAL NOTE
OF 50000PSI AND TENSILE STRENGTH OF 70000PSI FOR HRB400, APPLICABLE TO T10 ~ T18 REBARS.
8. UNLESS NOTED OTHERWISE IN THE DRAWINGS THE CONCRETE COVER TO THE OUTERMOST
SURFACE OF THE STEEL REINFORCEMENT (STIRRUPS,TIES OR SPIRALS IF TRANSVERSE REINFORCEMENT ENCLOSE MAIN BARS; SCALE : SHEET NO :
OUTERMOST LAYER OF BARS IF MORE THAN ONE LAYER IS USED WITHOUT STIRRUPS OR TIES;METAL END FITTING OR DATE : JUNE/2022 S-GN-DT03
DUCT ON POST TENSIONED PRESTRESSING STEEL) SHALL BE OF THAT LISTED BELOW.
REVISION NO ( - ) DATE ( - )
9. ALL DIMENSIONS ARE IN INCHES AND LEVELS IN FEETS.
10.ABBREVIATIONS:- REVISION NO ( - ) DATE ( - )
T1 1ST LAYER AT TOP B.O.W BOTTOM OF WALL U.N.O. UNLESS NOTED OTHERWISE
OWNER :
B1 1ST LAYER AT BOTTOM T.O.B TOP OF BEAM F.F.L. FLOOR FINISH LEVEL
T2 2ND INNER LAYER AT BOTTOM M.H MEASURED HORIZONTALLY S.F.L. STRUCTURAL FINISH LEVEL
B2 2ND INNER LAYER AT BOTTOM M.V MEASURED VERTICALLY RC REINFORCED CONCRETE
DAW JIT TOO MAR ZAW
A.R ALTERNATELY REVERSED N.T.S. NOT TO SCALE PT POST TENSIONED
A.S ALTERNATELY STAGGERED F.T.L. FULL TENSION LAP CL CENTRELINE
A.P ALTERNATELY PLACED F.C.L. FULL COMPRESSION LAP EQ EQUAL
F.F FAR FACE F.T.A. FULL TENSION ANCHORAGE THK THICK CONCRETE fc'=3000 PSI FOR CYLINDER STRENGTH
F.C.A. FULL COMPRESSION ANCHORAGE TYP TYPICAL L.C :
N.F NEAR FACE fcu =3846 PSI. FOR CUBE STRENGTH
S.H.A. STANDARD HOOK ANCHORAGE MAX MAXIMUN LAP & ANCHORAGE LENGTH
E.F EACH FACE REBAR fy=HRB400 (fy = 58000 psi)
B.F BOTH FACE S.S. SINGLE STIPPUP MIN MINMUM
FULL TENSION FULL COMPRESSION FULL TENSION FULL COMPRESSION STANDARD HOOK
E.W EACH WAY D.S. DOUBLE STIPPUP @ AT BAR
LAP(IN) LAP(IN) ANCHORAGE(IN) LAP(IN) ANCHORAGE(IN)
B.W BOTH WAY T.S. TRIPLE STIPPUP
F.R.R FIRE RESISTANCE RATING R.L. REDUCED LEVEL T10 14.5 13 14.5 13 8
11. BAR MARKS INDICATE THE TYPE AND SIZE OF REINFORCEMENT e.g.T10-4IN
T12 17.5 17.5 R.S.E / P.E (CONSTRUCTION) :
15.5 15.5 10
T10 4IN
T16 23 21 23 21 13

HIGH TENSILE STEEL BAR BAR SPACING 26 26


T18 24.5 24.5 17
12. BARS TO BE BENT IN ACCORDANCE WITH ACI 318 UNLESS NOTED OTHERWISE.
T20 36 26.5 36 26.5 27.5
13. ALL BEAMS ARE SHOWN THUS WIDTH x DEPTH(BxD). R.S.E / P.E (STRUCTURE) :

FOR TOP BARS SPLICE LENGTH MULTIPLY BY 1.3


WHEN BOTTOM REBAR LAP SPLICE LOCATION BEYOND 1/4 CLEAR SPAN
OF BEAM FROM SUPPORT FACE TO MID-SPAN MULTIPLY BY 1.3
NOTE:
DESIGN SPECIFICATION
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
f'c = 3000PSI FOR CYLINDER STRENGTH (fcu=3846PSI FOR CUBE STRENGTH) FOR BEAM, SLAB, COLUMN & FOOTING f'c = 3000psi(G20.69) FOR BEAM & SLAB
fy = 58000psi (HRB400) FOR ALL f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

STANDARD HOOK (FOR MAIN BARS) STANDARD HOOK (FOR STIRRUPS AND TIES)
3in
4 d ≥2 1/2 " b
b 135° 6d
b ,3inm
r in. PROJECT :
D db r r r THREE AND HALF STOREY

STANDARD HOOK
RESISDENCE

ANCHORAGE
[CORNER OF 65TH & 110A STREET]
db
BLOCK NO.
D = 2r 12db D = 2r
LOT NO.
TOWNSHIP CHAN MYA THARSI, MANDALAY

SUBJECT :
D = MINIMUN INSIDE DIAMETER OF BEND SPLICE DETAILING &
CONCRETE PROTECTION FOR
= 6db FOR 18MM THROUGH 25MM REINFORCEMENT
= 8db FOR 30MM,32MM AND 35MM db db
= 10db FOR 45MM AND 60MM SCALE : SHEET NO :
D = MINIMUN INSIDE DIAMETER OF BEND DATE : JUNE/2022 S-GN-DT04
= 4d FOR 16MM AND SMALLER REVISION NO ( - ) DATE ( - )
b
= 6d FOR 18MM,20MM
COVER b REVISION NO ( - ) DATE ( - )
* PROVIDE A CLREA COVER OF 1.5" FOR BEAMS, 0.75" FOR SLABS AND 3" FOR FOOTING , IF NOT OTHERWISE METIONED.
OWNER :

SPLICE
DAW JIT TOO MAR ZAW

NOTE: L.C :
SPLICE LENGTH
a) REFER TO DETAIL ON DRAWINGS FOR THE LOCATIONS WHERE THESE LAP AND ANCHORAGE LENGTHS ARE TO BE APPLIED.
SPLICE IN TENSION (PLAIN BARS)
b) FOR TENSION LAP AND TENSION BOND VALUES LISTED ABOVE SHALL BE MULTIPLIED BY 1.3 FOR
HORIZONTAL REINFORCEMENT PLACED WHEN THERE IS MORE THAN 300 mm(12 inches) THICK OF FRESH
CONCRETE IS CAST BELOW THE HORIZONTAL REINFORCEMENT.
SPLICE LENGTH c) STAGGERED TENSION LAP IS ALLOWED WHEN 50% OR LESS OF THE TOTAL REINFORCEMENT IS SPLICED
SPLICE IN TENSION (DEFORMED BARS) WITHIN THE REQUIRED LAP LENGTH ONLY ON LOCATIONS AND CONDITIONS INDICATED ON DRAWINGS.
d) NUMBERS IN PARENTHESES ARE TO BE USED FOR SLABS AND WALLS WHERE CLEAR CONCRETE COVER R.S.E / P.E (CONSTRUCTION) :
TO REINFORCEMENT IS LESS THAN BAR DIAMETER.
SPLICE LENGTH e) LAP OR ANCHORAGE LENGTH OF INDIVIDUAL BARS WITHIN A BUNDLE IN TENSION OR COMPRESSION,
TO BE 1.2 TIMES FOR THREE-BAR BUNDLE AND 1.3 TIMES FOR FOUR-BAR BUNDLE IN RESPECT
SPLICE IN COMPRESSION (BOTH PLAIN AND DEFORMED)
TO THE LAP ANCHORAGE LENGTHS SPECIFIED ABOVE.
f) FOR STANDARD HOOK ANCHORAGE LENGTH VALUES LISTED ABOVE SHALL BE MULTIPLIED
BY 1.43 FOR BARS HAVING SIDE COVER LESS THAN 63.5mm(2-1/2inches) OR BARS HAVING COVER ON BAR
EXTENSION BEYOND HOOK OF LESS THAN 51mm(2 inches). R.S.E / P.E (STRUCTURE) :
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

2h 2h 2h

h
Link 1 Link 2 Link 3

[2''] [2''] [2''] EXTRA BARS AS SHOWN IN BEAM SCHEDULE


PROJECT :
THREE AND HALF STOREY
RESISDENCE
STIRRUPS SCHEDULE TYPICAL FLOOR BEAM(U.O.S) [CORNER OF 65TH & 110A STREET]
BEAM SIZE STIRRUP DIAMETER DISTANCE (LINK 1,3) LINK 1,3 LINK 2
SLOPE FOR DIFFERENT BEAM DEPTH
Sr.no
(IN x IN) (MM) (IN) (IN) (IN)
BLOCK NO.
1 12x16 10 32 4 6
2 4 6 LOT NO.
12x18 10 36
TOWNSHIP CHAN MYA THARSI, MANDALAY

SUBJECT :
STIRRUP SCHEDULE FOR TYPICAL
(FLOOR) MAIN BEAM
2h
THIS SIGN IS TO SHOW CUT OFF POINT ONLY,
BUT NOT TO DO AS SHOWN. ALL OF WHICH ARE IN THE SAME LAYER. SCALE : SHEET NO :
DATE : JUNE/2022 S-GN-DT07
2"

h
2" 2"
COLUMN REVISION NO ( - ) DATE ( - )
COLUMN
2" EXTRA BARS AS SHOWN IN BEAM SCHEDULE REVISION NO ( - ) DATE ( - )

OWNER :
SLOPE FOR DIFFERENT BEAM DEPTH
DAW JIT TOO MAR ZAW

STEEL CUT OFF POINT SIGN DIFFERENT BAR QUANTITIES IN THE SAME LAYER
L.C :

HORIZONTAL TORSION LAYER


REQUIRED BAR DIAMETER 25mmØ SPACER BAR
CLOSED STIRRUPS MAIN STEELS
(3x2) 1-25mmØ R.S.E / P.E (CONSTRUCTION) :
TORSION STEELS
MAIN STEELS VERTICAL TORSION LAYER 25mmØ SPACER BAR

STEELS POSITION DETAIL TORSION STEEL REFERENCE DETAIL FOR TWO-LAYPE MAIN BARS
BEAM COVER=40mm BEAM COVER=40mm

TYPICAL BEAM SECTION DETAIL WITH TORTION BARS R.S.E / P.E (STRUCTURE) :
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
TIE BAR @ CALCULATED SPACING( REFER COLUMN SCHEDULE) NOTES FOR COLUMN DETAL
TIE BAR @ 4" c/c

SPLICE LENGTH
TENSION
LARGER OF X OR Y

50% LAPPING, ALTERNATE Lo> CLEAR SPAN/6

20" PROJECT :
Se (REFER COLUMN SCHEDULE) THREE AND HALF STOREY
Se RESISDENCE
[CORNER OF 65TH & 110A STREET]
MAIN BAR
8 x LONGITUDINAL BAR DIAMETER
So
So BLOCK NO.
24 x TIE BAR DIAMETER
Lo

LOT NO.
FLOOR LEVEL So≤ 0.5 x (SMALLER OF X OR Y)
TOWNSHIP CHAN MYA THARSI, MANDALAY

6" SUBJECT :
So
GIVEN SPACING REFER COLUMN SCHEDULE SPLICE DETAIL FOR COLUMN
Lo

So
So SCALE : SHEET NO :
DATE : JUNE/2022 S-GN-DT08
X
FLOOR TO FLOOR HEGHT

TIE BAR @ CALCULATED SPACING REVISION NO ( - ) DATE ( - )


( REFER COLUMN SCHEDULE)
REVISION NO ( - ) DATE ( - )
MAIN BAR

Y
OWNER :
TIE BAR @ 4" c/c

SECTION A-A
L1

TENSION 50% LAPPING, ALTERNATE DAW JIT TOO MAR ZAW


SPLICE LENGTH

TIE BAR @ CALCULATED SPACING


( FROM COLUMN SCHEDULE)
Se (REFER COLUMN SCHEDULE) L.C :
Se
A A
VERTICAL REBAR REFER COLUMN SCHEDULE
So
So
Lo

FLOOR LEVEL
NOTE: R.S.E / P.E (CONSTRUCTION) :
-COLUMN CLEAR COVER 3IN FOR THE CONCRETE CAST AGAINST
AND PERMANENTLY EXPOSED TO EARTH. OTHERWISE 1.5IN UOS.
-COLUMN MAIN STEEL MUST BE SPLICED ONLY IN MIDDLE HALF OF COLUMN HEIGHT.
-SPLICED LENGTHS ARE TO BE USED ACCORDING TO DESIGN SECTIONS.
-NUMBER OF TIES AND SPACING IN DISTANCE L0 AND L1 ARE SHOWN IN COLUMN SCHEDULE.
COLUMN TYPICAL DETAILS -135° HOOK MUST BE USED AT THE END OF ALL TIE BARS.
-TIE SPACING IN THE SPLICE LENGTH AT THE MIDDLE HALF OF THE COLUMN HEIGHT IS 4IN c/c.
-DO NOT SPLICE MORE THAN 50% OF THE TOTAL COLUMN LONGITUDINAL STEEL ANY WHERE.
R.S.E / P.E (STRUCTURE) :
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


L1/3 0R L2/3 L1/3 0R L2/3 L2/3 0R L3/3 L2/3 0R L3/3 L3/3 0R L4 OR F.T.A. f'c = 3000psi(G20.69) FOR BEAM & SLAB
WHICHEVER IS GREATER WHICHEVER IS GREATER WHICHEVER IS GREATER WHICHEVER IS GREATER WHICHEVER IS GREATER f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
2H 0R 0.25L1 2H 0R 0.25L1 2H 0R 0.25L2 2H 0R 0.25L2 2H 0R 0.25L3 2H 0R 0.25 L4 fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
WHICHEVER IS GREATER (Links 2) WHICHEVER IS GREATER WHICHEVER IS GREATER (Links 2) WHICHEVER IS GREATER WHICHEVER IS GREATER (Links 2) WHICHEVER IS GREATER 2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
(Links 1) (Links 3) (Links 1) (Links 3) (Links 1) (Links 3)
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
a b c a b c a b c a b

BEAM DEPTH
F.T.A.

BC

(H)
F.T.A.

d e g f d e g 2" f d e g 2" f d g e
2" 2" 2" STIRRUPS(TYP.) 2" 2"
PROJECT :
L1/8 L2/8 L2/8 L3/8 THREE AND HALF STOREY
RESISDENCE
[CORNER OF 65TH & 110A STREET]

BLOCK NO.
L1 L2 L3 L4
LOT NO.
TYPICAL CONTINUOUS BEAM DETAIL
TOWNSHIP CHAN MYA THARSI, MANDALAY

SUBJECT : TYPICAL BEAM DETAILS &


GENERAL DETAIL FOR PIPE SLEEVES
PENETRATION
L/3 L/3
SCALE : SHEET NO :
2d (NO PIPE SLEEVE
2H 0R 0.25L 2H 0R 0.25L SHALL BE ALLOWED JUNE/2022
2-EXTRA STIRRUPS EACH DATE : S-GN-DT09
WHICHEVER IS GREATER (Links 2) WHICHEVER IS GREATER WITHIN THIS ZONE (TYP.)
(Links 1) (Links 3) 2d SIDE OF SLEEVE REVISION NO ( - ) DATE ( - )
SCHED. 40 G. I. PIPE SLEEVE 2d
a b c BEAM DEPTH REVISION NO ( - ) DATE ( - )
TOP
F.T.A.

F.T.A.

TOP BARS

d
BARS
OWNER :
(H)
F.T.A.

F.T.A.

d
DAW JIT TOO MAR ZAW
d e g f
D/S
STIRRUPS STIRRUPS 20"
BOT. BARS (TYP.)
L/8 L/8
FACE OF SUPPORT EXTRA BARS
4d(MIN.) E.F. (TYP.) L.C :
L/4 L/2 L/4
LIMIT L0CATION
OF PIPE SLEEVE
L L

TYPICAL SIMPLE BEAM DETAIL LOCATION OF PIPE SLEEVE THRU BEAM


WALL LENGTH
NOTES:
R.S.E / P.E (CONSTRUCTION) :
1. SEEK STRUCT'L ENGINEER'S APPROVAL
FOR PIPE SLEEVES W/ DIAMETERS BIGGER
a b THAN THE MAXIMUM STIPULATED.
a b 2xTA
2. PIPE SLEEVES SHALL BE LOCATED WITHIIN
TENSION ZONES OF BEAMS.
2xTA

CA 3. NO PIPE SLEEVE SHALL BE ALLOWED AT


d e
CA

TWICE THE BEAM DEPTH(2d)FROM THE SUPPORT.


d e R.S.E / P.E (STRUCTURE) :
L
L
4. PIPE SLEEVE MAX DIAMETER IS: (LEAST
GOVERNS
A)1/5 OF BEAM DEPTH
TYPICAL CANTILEVER BEAM DETAIL B)4"
NOTE:

≤SLAB THK
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:

≥2"
0.3LX 0.3LY f'c = 3000psi(G20.69) FOR BEAM & SLAB
0.15 LX F.T.A f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
MIN120 fy = 58000psi(HRB400) For ALL REINFORCING BARS

≤50
AND ALL CAST-IN REBAR
0.15 LY SLAB THICKNESS 2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
SLAB DROP ACROSS MAIN SPAN
1 F.T.A

≤SLAB THK
10

10"
MIN120
LX LY LX LY
1.5h
WHEN SLAB DROP ≤50 SLAB DROP ≥SLAB THICKNESS TA

SLAB DROP OVER BEAM SLAB DROP ACROSS MAIN SPAN PROJECT :
THREE AND HALF STOREY
RESISDENCE
MIN 0.3( L1 OR L2)OR LAP
REINF ARRANGEMENT IN SLAB DROP [CORNER OF 65TH & 110A STREET]

SPAN L1
SPAN L2 SPAN L3 BLOCK NO.
SPAN L1 SPAN L2
MIN 0.25 L1 OR LAP MIN 0.3( L1 OR L2)OR LAP MIN 0.3( L2 OR L3)OR LAP
(NOT LESS THAN 45 DIA) WHICHEVER IS GREATER WHICHEVER IS GREATER LAP T2 LEFT HAND 'L' BAR . LAP LOT NO.
(NOT LESS THAN 45 DIA) (NOT LESS THAN 45 DIA)
WHICHEVER IS GREATER
(NOT LESS THAN 45 DIA) T1 LEFT HAND T1 MID-SPAN BAR.
EXTEND LAP LENGTH CRANK OVER BEAM TOP
'U' BAR
T1 T2
LAP LAP T1 LAP
T2
BOTTOM REIN SEE
T1 LAP INTO BEAM T2 8" 14" STEEL AS SHOWN T1 T2 RIGHT HAND BAR TOWNSHIP CHAN MYA THARSI, MANDALAY
SCHEDULES
SUBJECT :

t
t
t>=8" B1 B2 GENERAL DETAIL - 1
B2 B2
B1 BOTTOM REINF SEE 2" 2"
B1 BOTTOM REINF SEE 2" LAP B1 B2
2" SCHEDULES SCHEDULES
L1 L4 SCALE : SHEET NO :
L1 TYPICAL SOLID SLAB BALCONY CANTILEVER SLAB DATE : JUNE/2022 S-GN-DT10
NOT TO SCALE
REVISION NO ( - ) DATE ( - )
45DIA
REVISION NO ( - ) DATE ( - )
MAIN BARS
OWNER :
45DIA

45DIA
NOTE:
45DIA DAW JIT TOO MAR ZAW
45DIA

1.ALL REPLACEMENT AND DIAGONAL BARS SHOULD


EXTEND AN ANCHORAGE LENGTH BEYOND THE EDGE OF
DISTRIBUTION THE HOLE.
BARS
2.HOLES LARGER THAN 36IN IN ANY DIRECTION ARE
DETAILED ON THE DRAWINGS.
HOLE < 6IN. HOLE >6IN.&<18IN. L.C :
HOLE < 18IN.&<36 IN.
NOT TO SCALE NOT TO SCALE NOT TO SCALE

CUT BARS INTERUPTED BY HOLE.PROVIDE PROVIDE TRIMMER BARS AS PREVIOUS DETAIL IN


TRIMMER BARS OF SAME DIA .TYPE & ADDITION PROVIDE DIAGONAL TRIMMER OF SAME DIA,
NUMBER AS CUT BARS TYPE & NUMBER AS PREVIOUS DETAIL TRIMMERS.

R.S.E / P.E (CONSTRUCTION) :


T 10-8"

SPAN L1 SPAN L2
1.5L1 OR 0.3L2 OR 100 DIA
TOP REINF AS SHOWN
ON FLOOR PLANS OR LAP 0.25L 0.5L 0.25L
SCHEDULES T1 T2 T2
t

4" THK LEAN B2 R.S.E / P.E (STRUCTURE) :


CONC BOTTOM REINF SEE B1 L
LAP BOTTOM REINF SEE
6" THK WELL SCHEDULES SCHEDULES
R C BEAM 2" 2"
COMPACTED L3 L4
HARDCORE LAP LOCATION

TYPICAL MASS CONCRETE STEPS CANTILEVER SLAB


NOT TO SCALE
NOTE:
L1 L2 L3 1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
END BAY INTERNAL BAY INTERNAL BAY U-BARS OF THE SAME f'c = 3000psi(G20.69) FOR BEAM & SLAB
DIAMETER AS THE BARS f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
DISTRIBUTION TOP DISTRIBUTION TOP ON TO WHICH THEY LAP fy = 58000psi(HRB400) For ALL REINFORCING BARS
BAR X-DIRECTION L1/3 L1/3 L1/3 L2/3 L2/3 L2/3 L3/3 BAR X-DIRECTION TYPICAL
REINFORCEMENT KEY AND ALL CAST-IN REBAR
(TYPICAL) (TYPICAL)

REINFORCEMENT

REINFORCEMENT
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN

(TYP)
24"

24"
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
(TYP)
TEMPORARY OPENING

L1/3
24"MIN. 24"MIN. LAP DISTRIBUTION TOP
BAR Y-DIRECTION
LAP 24"MIN.

24"MIN.
END BAY

(TYPICAL) PERMANENT OPENING


L1/3
L1

LAP
L1/3

LAP
0.2L1
L TRIMMERS

0.1 L2
REINFORCEMENT PROJECT :
L2/3

LAP
0.1 L2 THREE AND HALF STOREY
INTERNAL BAY

0.1 L3 NOTE: RESISDENCE


LAP [CORNER OF 65TH & 110A STREET]
L2/3

LAP 1.TRIMMERS ARE FIXED TO TEMPORARY OPENING (BOXOUT)DIMENSINS.


L2

0.2 L2 LAP 2.REINFORCEMENT TERMINATES AT PERMANENT OPENING.IF PERMANENT


24"MIN. 0.2 L1 OPENING IS OMITTED THEN.
REINFORCEMENT IS CONTINUOUS THROUGHOUT UNO. BLOCK NO.
L2/3

LAP
0.2 L2 LOT NO.

0.1 L3
DISTRIBUTION TOP
INTERNAL BAY
L3/3

LAP
BAR Y-DIRECTION FLOOR OPENING DETAILS TOWNSHIP CHAN MYA THARSI, MANDALAY

(TYPICAL) NOT TO SCALE SUBJECT :


L3

GENERAL DETAIL - 2
LAP

24"MIN.
SCALE : SHEET NO :
BARS MAY BE DISPLACED NO ADDITIONAL
NOTE: REFT NECESSARY JUNE/2022
1. DISTRIBUTION BARS SHOULD BE LAPPED, ANCHORED & SPLICE SIMILAR TO ORDINARY TOP BAR & DATE : S-GN-DT11
TRIMMER BARS
BOTTOM BAR REQUIREMENT FOR R.C. SLABS.
2. LAP SPLICE FOR TOP /BOTTOM BAR SHOULD BE LOCATED AS INDICATED ON REVISION NO ( - ) DATE ( - )
PLAN ABOVE 30 X DIAMETER 0F REBAR FOR CCMPRESSION BAR AND 40 x DIAMETER

t
FOR TENSION BAR. REVISION NO ( - ) DATE ( - )
LAP U-BARS OF THE SAME LAP
DIAMETER AS THE BARS OWNER :
TYPICAL SLAB LAYOUT OF DISTRIBUTION BARS
ON TO WHICH THEY LAP TYPICAL
NOT TO SCALE
b TRIMMING OF HOLES IN SLAB
NOTE: NOT TO SCALE DAW JIT TOO MAR ZAW
(TOP) 2-16mm0(IF t<12IN)
b=12IN IF t<12IN.
2-18mm0(IF t>=12IN) b=20IN IF t>=12IN.
tDROP

24"(TYP.)
SLAB
THICKNESS L TO MATCH L.C :

24"(TYP.)

BEAM
R8mm0 @4IN (IF t<12IN)
12mm0 @4IN (IF t>=12IN) 2-16mm0(IF t<12IN)
ADJACENT TOP BARS
(BOTTOM) 2-18mm0(IF t>=12IN)

L
FOLD AT SUNK SLAB
REFER TO BAR TABLE
NOT TO SCALE
R.S.E / P.E (CONSTRUCTION) :
FLOOR OPENING(L) ADD BARS
LESS THAN 10" 2-12mm0 T&B
L=>10"<20" 2-16mm0 T&B
L=>20"<40" 3-16mm0 T&B
NOTE:
1.FOR OPENING LESS THAN 8"x8".SLAB REBARS TO BE ADJUSTED
AROUND OPENING.
2.FOR OPENINGS GREATER THAN 40"x40".REFER TO SLAB PLANS. R.S.E / P.E (STRUCTURE) :
3.LOCATION OF OPENINGS TO THE APPROVAL OF THE ENGINEER.
4.EQUIVALENT OPENINGS AREA SHALL APPLY THE DETAILS SHOWN ABOVE.
5.EQUIVALENT OPENINGS AREA SHALL INCLUDE RECTANGLE,TRIANGLE AND
POLYGON SHAPE.
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

1 2 3 4 5

58'-6"
12' 17'-3" 17'-3" 12'

PROJECT :
THREE AND HALF STOREY
1PC1 2PC1A 2PC1A 1PC1 1PC1 RESISDENCE
[CORNER OF 65TH & 110A STREET]

1'

1'

1'

1'

1'
C

3'-6"

3'-6"

3'-6"

3'-6"
2'-6"

2'-6"

2'-6"

2'-6"

2'-6"
C1 C2 C3 C4 C5
1' 2'-6" 4'-11" 4'-7" 4'-9" 4'-9" 1'-11" 1'-7" 1'-11" 1'-7" BLOCK NO.
3'-6" 9'-6" 3'-6" 3'-6"
9'-6"
LOT NO.
TOWNSHIP CHAN MYA THARSI, MANDALAY
17'-3"

SUBJECT :
3'-6" 9'-6" 9'-6" 3'-6" PILE CAP LAYOUT PLAN
1' 2'-6" 5' 4'-6" 4'-9" 4'-9" 1'-11" 1'-7" @LVL. +00'-00"

SCALE : AS SHOWN SHEET NO :


3'-6"
5'

5'

5'

5'
B1 B2 B3 B4 1'-11" 1'-7" DATE : JUNE/2022 S-FM.01
34'-6"

9'-6"

9'-6"

9'-6"

9'-6"
B REVISION NO ( - ) DATE ( - )
4'-6"

4'-6"

4'-6"

4'-6"
B5 REVISION NO ( - ) DATE ( - )

9'-6"
2PC1A 4PC1 4PC1 2PC1 OWNER :
17'-3"

DAW JIT TOO MAR ZAW


2PC1

3'-6" 9'-6" 9'-6" 9'-6"


1' 2'-6" 4'-11" 4'-7" 4'-9" 4'-9" 5'-1" 4'-5"

A1 A2 A3 A4 L.C :
1'-7" 1'-11"

1'-7" 1'-11"

1'-7" 1'-11"
2'
3'-6"

3'-6"

3'-6"
A
1'-6"

1PC1 2PC1 2PC1 2PC1

PILE CAP LAYOUT PLAN @ LVL. 00'-00"


1 Scale: 1/8"=1"-0"
R.S.E / P.E (CONSTRUCTION) :

NOTE:
1. ALL PILE CAPS TO BE 48" THICK UNLESS STATED OTHERWISE.
2. ALL PILE CAP TOP LEVEL = 00'-00".
PILE CENTER TO CENTER SPACING = 6'
PILE CENTER TO EDGE DISTANCE = 21"
ALL DIMENSION ARE TO BE CHECKED AND VERIFIED ON SITE.
R.S.E / P.E (STRUCTURE) :
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

1 2 3 4 5
B A

58'-6"
12' 17'-3" 17'-3" 12'

PROJECT :
THREE AND HALF STOREY
RESISDENCE
C5 [CORNER OF 65TH & 110A STREET]
C
C1 C2 C3 C4
BLOCK NO.
LOT NO.
TOWNSHIP CHAN MYA THARSI, MANDALAY
17'-3"

SUBJECT :
RETAINING WALL LAYOUT PLAN

SCALE : AS SHOWN SHEET NO :


B1 B2 B3 B4 DATE : JUNE/2022 S-FM.02
34'-6"

B REVISION NO ( - ) DATE ( - )

B5 REVISION NO ( - ) DATE ( - )

OWNER :
17'-3"

DAW JIT TOO MAR ZAW

A1 A2 A3 L.C :
A
A4

RETAINING WALL SECTION RETAINING WALL SECTION


3" LEAN CONC: RETAINIING WALL LAYOUT PLAN 3" LEAN CONC:
PLINTH LVL.
+2'-6"
6" SAND FILLING 1 Scale: 1/8"=1"-0"
PLINTH LVL.
+1'-6"
6" SAND FILLING
R.S.E / P.E (CONSTRUCTION) :

6" HARD CORE 6" HARD CORE


N.G.L N.G.L
+0'-00" WELL COMPACTED +0'-00" WELL COMPACTED
SUB BASE SUB BASE

9" RETAINING WALL 9" RETAINING WALL

3" LEAN CONC: 3" LEAN CONC: R.S.E / P.E (STRUCTURE) :


BASE 6" HARD CORE BASE 6" HARD CORE
-3'-00" -3'-00"
WELL COMPACTED WELL COMPACTED
SUB BASE SUB BASE
SECTION A-A SECTION A-A
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

1 2 3 4 5

58'-6"
12' 17'-3" 17'-3" 12'

6'-2" 5'-10" PROJECT :


THREE AND HALF STOREY
C2 RESISDENCE
C1 GMB4 T.L +1.5' GMB2 C3 GMB2 C4 GMB4 C5 [CORNER OF 65TH & 110A STREET]
C
LS1
5'-10"

8.25'
BLOCK NO.
GB1 T.L +1.5' LOT NO.
GMB1 T.L +1.5'

TOWNSHIP CHAN MYA THARSI, MANDALAY


17'-3"

SUBJECT :
GB1 T.L +1.5'

GMB3

GMB2

GMB2

GMB1
GROUND FLOOR LAYOUT PLAN
@ LVL. +02'-06"

SCALE : AS SHOWN SHEET NO :


B1 B2 GMB2 B3 GMB2 B4 GMB5 DATE : JUNE/2022 S-FM.03
34'-6"

B UP
REVISION NO ( - ) DATE ( - )
GMB5 T.L +1.5'

B5 REVISION NO ( - ) DATE ( - )

OWNER :
T.L +1.5'

GMB3

GMB2

GMB2
17'-3"

GMB1

DAW JIT TOO MAR ZAW

B2
GM
T.L +1.5'

A1 GMB5 T.L +1.5' A2 GMB2 A3 GMB2 A4 L.C :


A
2'-3"

GCB2
GCB1

GCB1

1'-10"
3'-6"

2"
SC1
SEE DETAILS AT SC1 STEEL
COLUMN BASE PLATE
CONNECTION

GROUND FLOOR LAYOUT PLAN @ LVL. +02'-06"


1 Scale: 1/8"=1"-0"
R.S.E / P.E (CONSTRUCTION) :

NOTE:
ALL R.C. BEAM TOP LEVEL TO BE +2.5' UNLESS OTHERWISE STATED.

R.S.E / P.E (STRUCTURE) :


NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

1 2 3 4 5

58'-6" 5'-6"
12' 17'-3" 17'-3" 12'

PROJECT :
THREE AND HALF STOREY
C2 RESISDENCE
C1 FMB7 FMB2 C3 FMB2 C4 FMB4 C5 FCB2 [CORNER OF 65TH & 110A STREET]
C
LS1 BLOCK NO.
21'
LOT NO.
TOWNSHIP CHAN MYA THARSI, MANDALAY
17'-3"

S2 S2 S1 S1
SUBJECT :
FMB2

FMB3

FMB3

FMB3

FMB1

FB1
FIRST FLOOR LAYOUT PLAN
@ LVL. +15'-00"

SCALE : AS SHOWN SHEET NO :


B1 FMB6 B2 FMB3 B3 FMB3 B4 FMB5 FCB3 DATE : JUNE/2022 S-FM.04
34'-6"

B UP
REVISION NO ( - ) DATE ( - )

FB1
S1 S1 REVISION NO ( - ) DATE ( - )

5'-9"
B5
FMB4 FCB2
OWNER :
CS1
FMB3

FMB3

FMB3
S1 S2 S2
17'-3"

FMB2

9"
DAW JIT TOO MAR ZAW

FCB1
S1

SFB1
FB2
3'-10"

S1 S1
A1 A2 FMB2 A3 FMB2 A4 FCB1 L.C :
FB2

FMB2
A
FCB2

FCB2
2'-3"

SFB1
S1 S1

FB1 SC1
6'-3" 5'-9" SFB1
SEE DETAIL AT
PART PLAN OF
FFL

FIRST FLOOR LAYOUT PLAN @ LVL. +15'-00"


1 Scale: 1/8"=1"-0"
R.S.E / P.E (CONSTRUCTION) :

NOTE:
ALL R.C. BEAM & SLAB TOP LEVEL TO BE +15' UNLESS OTHERWISE STATED.

R.S.E / P.E (STRUCTURE) :


NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

1 2 3 4 5

58'-6"
12' 17'-3" 17'-3" 12' 5'-6"

7'-10" PROJECT :
THREE AND HALF STOREY
C2 RESISDENCE
C1 SMB6 SMB2 C3 SMB2 C4 SMB4 C5 SCB3 [CORNER OF 65TH & 110A STREET]
C
LS1
S1
BLOCK NO.

SB3

7'-9"
26.67'
32.75'
26.5' LOT NO.

S1 SB4 TOWNSHIP CHAN MYA THARSI, MANDALAY


17'-3"

S1 S2 S1
SUBJECT :
SMB2

SMB3

SMB3

SMB3

SMB1
26.83'

SB3
SECOND FLOOR LAYOUT PLAN
@ LVL. +27'-00"
SB4

9'-6"
T.L 26.83'

S1 SCALE : AS SHOWN SHEET NO :


4'-8"

SB3
UP B2 26.83' S1
B1 SMB6 SMB3 B3 SMB3 B4 SMB5 DATE : JUNE/2022 S-FM.05
34'-6"

B REVISION NO ( - ) DATE ( - )
S1 S1 S1

5'-9"
B5 REVISION NO ( - ) DATE ( - )
S1 SB1 SB1 SMB4 SCB3
OWNER :
1'-9.5" 2'

9"
S1 S1 CS1
S1 S1
SMB3

SMB3
SB4 SB2 SCB4
17'-3"

SB4 SB4
SMB2

SB2
T.L +26.5'
DAW JIT TOO MAR ZAW
S1 S1

SCB1
SB3

SB3

26.83' S1 S1 S1
8'-8"

S1 SMB9 S1

7'-6"
26.67' 26.67' 26.5'
26.67'
A2 A3 L.C :
A1 SMB6 T.L +26.67' SMB7 T.L +26.67' T.L +26.67' SMB8 A4 SCB2 T.L +26.5'
A
SCB4
SCB5

SCB5

S1 S1 S1
SCB3

SCB3

SCB3
3'-6"

3'-6"
S1 S1 S1 S1 26.5'
26.67' 26.67' 26.67'

SB3 SB3 SB3 SB3 SB3 SB3 SCB5


5'-7" 3'-10" 3'-9" 12'-6"

SECOND FLOOR LAYOUT PLAN @ LVL. +27'-00"


1 Scale: 1/8"=1"-0"
R.S.E / P.E (CONSTRUCTION) :

NOTE:
ALL R.C. BEAM & SLAB TOP LEVEL TO BE +27' UNLESS OTHERWISE STATED.

R.S.E / P.E (STRUCTURE) :


NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

1 2 3 4 5

58'-6"
12' 17'-3" 17'-3" 12' 4'-6"

9'-2" 8'-1" 4' PROJECT :


THREE AND HALF STOREY
C2 RESISDENCE
C1 TMB5 TMB2 C3 TMB2 C4 TMB3 T.L38' C5 TCB3 T.L38'
[CORNER OF 65TH & 110A STREET]
C
LS1 38.167' BLOCK NO.
S1
44.25'
38.33' LOT NO.

TB2
S1 TOWNSHIP CHAN MYA THARSI, MANDALAY
TB3 T.L38.33' S1
17'-3"

S2

TMB1 T.L 38'


SUBJECT :

T.L 38'
TMB2

TMB1

TMB1
38'
4'-4.5"

TMB1
THIRD FLOOR LAYOUT PLAN
S1
@ LVL. +38'-06"

TB3
38.167'
TB3 38'
S1
SCALE : AS SHOWN SHEET NO :
4'-10"

38.33'
UP S1
LS1
B1 B2 TMB1 B3 TMB1 B4 TMB3 T.L38' DATE : JUNE/2022 S-FM.06
34'-6"

B REVISION NO ( - ) DATE ( - )
TMB5 S1

5'-9"
S1 38' B5 REVISION NO ( - ) DATE ( - )
S1
TMB3 T.L38' TCB3 T.L38'
TB2 OWNER :

TCB5 T.L 38'


TCB2 T.L 38'
3'-3"

S1 S1

TMB1
TMB2

TMB1

TMB1
S2
17'-3"

TB3 38' 38'

6'
DAW JIT TOO MAR ZAW
TB3 T.L38' TCB5 T.L38'
S1

TCB5 T.L 38'


8'-6"

T.L 38'
S1 S1
38'

TB3

6'
A1 TMB5 A2 TMB2 A3 TMB2 A4 TCB1 T.L38' L.C :
A

TCB5 T.L 38'


TB3 T.L 38'
S1
TCB2
TCB2
TCB4

TCB2
3'-6"

S1 S1 S1

3'
38'

TB1 TB1 TB1 TCB2 T.L38'


6' 6' 4'

THIRD FLOOR LAYOUT PLAN @ LVL. +38'-06"


1 Scale: 1/8"=1"-0"
R.S.E / P.E (CONSTRUCTION) :

NOTE:
ALL R.C. BEAM & SLAB TOP LEVEL TO BE +38.5' UNLESS OTHERWISE STATED.

R.S.E / P.E (STRUCTURE) :


NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

1 2 3 4 5

58'-6"
12' 17'-3" 17'-3" 12'

5'-6" 11'-9" 4'-6" PROJECT :


THREE AND HALF STOREY
C2 RESISDENCE
C1 RMB4 RMB2 C3 RMB2 T.L49.5' C4 RCB4 T.L49.5' [CORNER OF 65TH & 110A STREET]
C
LS1
S1 BLOCK NO.
44.25'
49.67' LOT NO.
RB2 TOWNSHIP CHAN MYA THARSI, MANDALAY

RMB2 T.L49.5'
S1

T.L49.5'
17'-3"

S2
SUBJECT :
RMB6

RMB5
S1

RB3
49.5'

RMB5
49.5' ROOF FLOOR LAYOUT PLAN

RB2
@ LVL. +50'-00"
10'

S1
SCALE : AS SHOWN SHEET NO :
LS1 DN B2
B1 RMB1 B3 RMB1 T.L49.5' B4 RCB2 T.L49.5' DATE : JUNE/2022 S-FM.07
34'-6"

B REVISION NO ( - ) DATE ( - )
RMB3
REVISION NO ( - ) DATE ( - )

OWNER :

T.L49.5'

RB2 T.L49.5'
RMB5
RMB6

RMB5

S2 S1
17'-3"

RMB2
S1 S2 49.5' 49.5'
DAW JIT TOO MAR ZAW

A1 A2 RMB2 A3 RMB2 T.L49.5' A4 RCB4 T.L49.5' L.C :


RMB4
A

RCB4 T.L49.5'

RCB5
S1
RCB3

RCB1

RCB1

T.L49.5'
3'-6"

3'-6"
S1 S1 S1 49.5' 49.5'
RCB5
RB1 RB1 RB2 T.L49.5' T.L49.5'

ROOF FLOOR LAYOUT PLAN @ LVL. +50'-00"


1 Scale: 1/8"=1"-0"
R.S.E / P.E (CONSTRUCTION) :

NOTE:
ALL R.C. BEAM & SLAB TOP LEVEL TO BE +50' UNLESS OTHERWISE STATED.

R.S.E / P.E (STRUCTURE) :


NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

1 2 3 4 5

58'-6"
12' 17'-3" 17'-3" 12'

5'-6" PROJECT :
THREE AND HALF STOREY
RTB2 C2 RESISDENCE
C1 RTB1 C3 [CORNER OF 65TH & 110A STREET]
C
BLOCK NO.
LOT NO.
TOWNSHIP CHAN MYA THARSI, MANDALAY
RTB1

RTB1

RTB1
CS1
17'-3"

S1 S2 SUBJECT :
ROOF TOP LAYOUT PLAN
@ LVL. +61'-06"

SCALE : AS SHOWN SHEET NO :


B1 RTB2 B2 RTB1 B3 DATE : JUNE/2022 S-FM.08
34'-6"

B REVISION NO ( - ) DATE ( - )

5'-9"
S1 CS1 REVISION NO ( - ) DATE ( - )
RSB1 OWNER :
RTB1

RTB1

RTB1
17'-3"

S1 S2

5'
DAW JIT TOO MAR ZAW
RSB1
3'-10"

CS1

6'-6"
S2

A1 RTB2 A2 RTB2 A3 L.C :


A
3'-6"

3'-6"
CS1 CS1

ROOF TOP LAYOUT PLAN @ LVL. +61'-06"


1 Scale: 1/8"=1"-0"
R.S.E / P.E (CONSTRUCTION) :

NOTE:
ALL R.C. BEAM & SLAB TOP LEVEL TO BE +61.5' UNLESS OTHERWISE STATED.

R.S.E / P.E (STRUCTURE) :


NOTE:

1 2 1 2 1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
12' f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
12' fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
C1 LB1 C2 C1 LB1 C2 2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
C C CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

LS1 LS1

5'-6"
5'
8.25' 21'

PROJECT :
17'-3"

17'-3"
THREE AND HALF STOREY

SS1

SS1

SS1

SS1
RESISDENCE
[CORNER OF 65TH & 110A STREET]

BLOCK NO.
LOT NO.
TOWNSHIP CHAN MYA THARSI, MANDALAY

B1 B2 B1 B2
FMB6 SUBJECT :
B UP B UP PART PLAN OF STAIR CASE
GMB5
3
PART PLAN OF STAIR CASE AT LEVEL +8.25' PART PLAN OF STAIR CASE AT LEVEL +21' SCALE : 16"=1" SHEET NO :
DATE : JUNE/2022 S-FM.09
REVISION NO ( - ) DATE ( - )
REVISION NO ( - ) DATE ( - )
1 2 1 2 OWNER :
12' 12'

C1 LB2 C2 C1 LB2 C2 DAW JIT TOO MAR ZAW


C C

LS1 LS1

5'-6"
5'-6"

L.C :
32.75' 44.25'

17'-3"
17'-3"

SS1

SS1
SS1

SS1

R.S.E / P.E (CONSTRUCTION) :

UP UP LS1
2'-3"
2'-3"

B1 LS1 27' B2 B1 B2
38.5'
B B
R.S.E / P.E (STRUCTURE) :
SMB6 TMB5
PART PLAN OF STAIR CASE AT LEVEL +32.75' PART PLAN OF STAIR CASE AT LEVEL +44.25'
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
5 5 f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

FCB2
FCB2

B5 CS1 B5 4 CS1

PROJECT :

FCB1
THREE AND HALF STOREY
RESISDENCE

FCB1

SFB1

SFB1
[CORNER OF 65TH & 110A STREET]

BLOCK NO.
A4 A4
LOT NO.
FCB1 FCB1
A A
TOWNSHIP CHAN MYA THARSI, MANDALAY

4
SFB1

SUBJECT :

SFB1
PART PLAN OF FIRST FLOOR
2 3 (STEEL BEAM FRAMING PLAN &
SFB1 CONNECTION LAYOUT PLAN)
SC1 SFB1 SC1 1
3
SCALE : 16"=1" SHEET NO :
DATE : JUNE/2022 S-FM.10
PART PLAN OF FIRST FLOOR (STEEL BEAM LAYOUT PLAN) PART PLAN OF FIRST FLOOR (CONNECTION LAYOUT PLAN)
REVISION NO ( - ) DATE ( - )
REVISION NO ( - ) DATE ( - )
STEEL COLUMN & BEAM SCHEDULE FOR HOT ROLLED SECTION
OWNER :

tf
bf
JIS SS400 Fy 36,000 PSI
Fu 58,000 PSI I SECTION h
2 bf
MARK SIZE H(MM) B(MM) Tw(MM) Tf (MM) SECTIONAL AREA(CM ) UNIT MASS (KG/M) tw
tw DAW JIT TOO MAR ZAW
tf

h
SC1 250x125x6x9 250 125 6 9 37 29.6
SFB1 250x125x6x9 250 125 6 9 37 29.6

L.C :

R.S.E / P.E (CONSTRUCTION) :

R.S.E / P.E (STRUCTURE) :


NOTE:
1. SC1 250x125x6x9 COLUMN & SFB1 250x125x6x9 BEAM FLANGE MOMENT CONNECTION
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
f'c = 3000psi(G20.69) FOR BEAM & SLAB

1.25"
4/16 SS400
16MM THK; PLATE
2.75" SS400 f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
4/16 PL 0.63x5 1/4x14.34
16MM THK; PLATE
Hole type (connector):Standard (STD) 4/16 1.25" 1.25" PL 0.63x5 1/4x14.34 fy = 58000psi(HRB400) For ALL REINFORCING BARS
Bolts:M16 G_8_8 3/16 4/16

1.25"
AND ALL CAST-IN REBAR

1"

2.8543"
4/16 2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
4/16 CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

14.34"
1.25"
2.75"
4/16
5"

6.6339"
14.34"
4/16 4/16
10" SFB1
H250X125 SFB1 4/16
H250X125

2.8543"
1.25"
SC1
H250X125 5.25"

1"
5.25"
SC1
H250X125

TOP VIEW SIDE VIEW FRONT VIEW PLATE DETAIL

PROJECT :
2. SC1 250x125x6x9 COLUMN & SFB1 250x125x6x9 BEAM WEB SHEAR CONNECTION THREE AND HALF STOREY
RESISDENCE
4/16 [CORNER OF 65TH & 110A STREET]
4/16 Hole type (beam):Standard (STD) 2.3425" 2"

1.5"

1.5"
1.5"
Hole type (connector):Standard 1.5" 1.5"
(STD) 6Bolts:M16 G_8_8 BLOCK NO.

2.57"
1.5" 2" 1.5"

2x2.35 in=4.7

2x2.35 in=4.7
9.1338"
LOT NO.

7.7"

7.7"
10"

0.7169"
TOWNSHIP CHAN MYA THARSI, MANDALAY
SFB1
H250X125 SFB1 0.394 in
SC1 5" H250X125 SUBJECT :
H250X125 SS400 SS400
SC1 10MM THK; PLATE 10MM THK; PLATE STEEL CONNECTION DETAILS - 1
H250X125 PL 0.394x5x7.7 PL 0.394x5x7.7

3
SCALE : 4 "=1' SHEET NO :
TOP VIEW SIDE VIEW FRONT VIEW PLATE DETAIL
DATE : JUNE/2022 S-SCD.01

REVISION NO ( - ) DATE ( - )
3. SFB1 250x125x6x9 GIRDER & SFB1 250x125x6x9 BEAM SHEAR CONNECTION
REVISION NO ( - ) DATE ( - )
1.5" 3/16
2.35" 3/16 OWNER :
0.75"

1.5"
2.57"
1.5"
2x2.35 in=4.7

1.5"
7.7"

2.57"

7.7"
DAW JIT TOO MAR ZAW
2.35 in
SFB1 SFB1 0.256 in
H250X125 SFB1 3.85"
H250X125 Hole type (beam):Standard (STD) 3.85"
H250X125
SS400 Hole type (connector):Standard (STD)
6.5 MM THK; PLATE 3Bolts:M16 G_8_8 SS400
SFB1 PL 0.256x3.85x7.7 6.5 MM THK; PLATE
H250X125 PL 0.256x3.85x7.7 L.C :

TOP VIEW SIDE VIEW FRONT VIEW PLATE DETAIL

4. SFB1 250x125x6x9 GIRDER & CONCRETE COLUMN OR BEAM SHEAR CONNECTION


6T16 CAST-IN
ANCHOR REBAR
R.S.E / P.E (CONSTRUCTION) :
5/16 SS400 1.5"
5/16 20 MM THK; PLATE

1.5"
GMS PL 0.7874x10x10 SS400
5/16 5/16 20 MM THK; PLATE

7.7"
5/16 5/16 GMS PL 0.7874x10x10
1.5" 3/16 10"
3/16
3.85"
2"

2.57"
2"

1.5"
2x2.35 in=4.7
3"

SS400
6"

7.7"

10"

2.35 in
2.57"

6.5 MM THK; PLATE


3"

SFB1 PL 0.256x3.85x7.7 R.S.E / P.E (STRUCTURE) :


2"

23"
2"

H250X125 23"
0.5"
3.85"
SFB1 0.256 in
H250X125
SS400 Hole type (beam):Standard (STD)
6.5 MM THK; PLATE Hole type (connector):Standard (STD)
PL 0.256x3.85x7.7 3Bolts:M16 G_8_8

TOP VIEW SIDE VIEW FRONT VIEW PLATE DETAIL


NOTE:
SC1 250x125x6x9 COLUMN BASE PLATE CONNECTION
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
GCB2
20"x20"

M-16

SC1 SC1

3.01"

3.83"
20" H250X125 H250X125
18"

1.18
SS 400

15.01"
M-16

3'
30MM THK; PLATE

12"
PL10x18x1.18
PROJECT :
2.5"

THREE AND HALF STOREY


10"

RESISDENCE
5"

[CORNER OF 65TH & 110A STREET]


2.5"

3"

2.5" 4x3.25"=1'-1" 2.5" BLOCK NO.


GCB2 GCB2 LOT NO.
5/16
5/16

20"x20" 20"x20"
TOWNSHIP CHAN MYA THARSI, MANDALAY

SUBJECT :
TOP VIEW FRONT VIEW SIDE VIEW ANCHOR DETAIL STEEL CONNECTION DETAILS - 2
(BASE PLATE CONNECTION)

3
SCALE : 4 "=1' SHEET NO :
DATE : JUNE/2022 S-SCD.02

REVISION NO ( - ) DATE ( - )
REVISION NO ( - ) DATE ( - )

OWNER :

DAW JIT TOO MAR ZAW

L.C :

R.S.E / P.E (CONSTRUCTION) :

R.S.E / P.E (STRUCTURE) :


NOTE:
REINFORCEMENT SCHEDULE FOR FLOOR BEAM
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
SIZE TOP REINFORCEMENT BAR BOTTOM REINFORCEMENT BAR f'c = 3000psi(G20.69) FOR BEAM & SLAB
MARK SIDE BAR(g) LINKS 1 LINKS 2 LINKS 3 TYPE
(BxD) LEFT(a) MID(b) RIGHT(c) LEFT(a) MID(b) RIGHT(c) f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
GMB1,FMB6 12x18 5T18 4T18 5T18 4T18 5T18 4T18 - T10-3IN D.S T10-6IN D.S T10-3IN D.S SMRF AND ALL CAST-IN REBAR
RMB5 2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
GMB2 12x18 4T18 2T18 4T18 3T18 3T18 3T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S SMRF
GMB3,FMB3 12x18 7T18 4T18 7T18 4T18 5T18 4T18 - T10-3IN D.S T10-6IN D.S T10-3IN D.S SMRF
SMB3,TMB1
GMB4,FMB7 12x14 3T18 2T18 3T18 2T18 3T18 2T18 - T10-3IN S.S T10-5IN S.S T10-3IN S.S SMRF
TMB5,RMB3
GMB5,SMB6 12x14 4T18 2T18 4T18 3T18 3T18 3T18 - T10-3IN S.S T10-5IN S.S T10-3IN S.S SMRF
GCB1 12x18 5T18 5T18 5T18 4T18 4T18 4T18 - T10-3IN D.S T10-3IN D.S T10-3IN D.S CANTILEVER
PROJECT :
GB1,SB4,RB3 10x12 3T18 2T18 3T18 2T18 3T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S THREE AND HALF STOREY
TB3,RMB4,RTB2 RESISDENCE
[CORNER OF 65TH & 110A STREET]

FMB1 12x18 9T18 4T18 9T18 4T18 5T18 4T18 - T10-3IN D.S T10-6IN D.S T10-3IN D.S SMRF
BLOCK NO.
FMB2 12x18 5T18 3T18 5T18 3T18 5T18 3T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S SMRF
LOT NO.
FMB4 12x16 5T18 4T18 5T18 4T18 4T18 4T18 - T10-3IN D.S T10-6IN D.S T10-3IN D.S SMRF
TOWNSHIP CHAN MYA THARSI, MANDALAY
FMB5 12x16 4T18 2T18 4T18 2T18 3T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S SMRF
SUBJECT :
FCB1,TCB2 12x18 5T18 5T18 5T18 4T18 4T18 4T18 - T10-3IN D.S T10-3IN D.S T10-3IN D.S CANTILEVER
RCB1 R.C DETAIL FOR BEAM - 1

FCB2 12x16 5T18 5T18 5T18 4T18 4T18 4T18 - T10-3IN D.S T10-3IN D.S T10-3IN D.S CANTILEVER
FCB3,SCB3 12x16 4T18 4T18 4T18 3T18 3T18 3T18 - T10-3IN S.S T10-3IN S.S T10-3IN S.S CANTILEVER SCALE : SHEET NO :
TCB3 JUNE/2022 S-RBD.01
DATE :
FB1 10x16 2T18 2T18 2T18 2T18 3T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S
REVISION NO ( - ) DATE ( - )
FB2 10x12 2T18 2T18 2T18 2T18 2T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S
REVISION NO ( - ) DATE ( - )
SMB1 12x24 8T18 4T18 8T18 4T18 5T18 4T18 2T12 E.F T10-4IN D.S T10-6IN D.S T10-4IN D.S SMRF
OWNER :
SMB2 12x18 4T18 2T18 4T18 3T18 5T18 3T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S SMRF
SMB4,TMB3 12x16 4T18 2T18 4T18 3T18 3T18 3T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S SMRF
SMB5 12x16 3T18 2T18 3T18 2T18 3T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S SMRF DAW JIT TOO MAR ZAW

SCB1 12x24 7T18 7T18 7T18 4T18 4T18 4T18 2T12 E.F T10-4IN D.S T10-4IN D.S T10-4IN D.S CANTILEVER
SCB2 12x18 7T18 7T18 7T18 4T18 4T18 4T18 - T10-3IN D.S T10-3IN D.S T10-3IN D.S CANTILEVER
SCB4 12x16 3T18 3T18 3T18 3T18 3T18 3T18 - T10-3IN S.S T10-3IN S.S T10-3IN S.S CANTILEVER L.C :
SB1 12x16 4T18 2T18 4T18 3T18 3T18 3T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S
SB2,TB2 12x16 3T18 2T18 3T18 2T18 3T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S
SB3,RTB1 10x16 3T18 2T18 3T18 2T18 3T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S
SCB5 10x16 3T18 3T18 3T18 3T18 3T18 3T18 - T10-3IN S.S T10-3IN S.S T10-3IN S.S CANTILEVER
TMB2 12x18 4T18 2T18 4T18 2T18 3T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S SMRF R.S.E / P.E (CONSTRUCTION) :
TCB1 12x22 7T18 7T18 7T18 5T18 5T18 5T18 - T10-4IN D.S T10-4IN D.S T10-4IN D.S CANTILEVER
TCB4 12x18 4T18 4T18 4T18 3T18 3T18 3T18 - T10-3IN S.S T10-3IN S.S T10-3IN S.S CANTILEVER
TB1 10x18 3T18 2T18 3T18 2T18 3T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S
TCB5,RCB4 10x12 3T18 3T18 3T18 2T18 2T18 2T18 - T10-3IN S.S T10-3IN S.S T10-3IN S.S CANTILEVER
RMB1 12x16 5T18 4T18 5T18 4T18 5T18 4T18 - T10-3IN D.S T10-6IN D.S T10-3IN D.S SMRF
R.S.E / P.E (STRUCTURE) :
RMB2 10x16 4T18 2T18 4T18 2T18 3T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S SMRF
RMB6 10x18 4T18 2T18 4T18 2T18 3T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S SMRF
RCB2 12x14 4T18 4T18 4T18 3T18 3T18 3T18 - T10-3IN S.S T10-3IN S.S T10-3IN S.S CANTILEVER
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


SIZE TOP REINFORCEMENT BAR BOTTOM REINFORCEMENT BAR f'c = 3000psi(G20.69) FOR BEAM & SLAB
MARK SIDE BAR(g) LINKS 1 LINKS 2 LINKS 3 TYPE
(BxD) LEFT(a) MID(b) RIGHT(c) LEFT(a) MID(b) RIGHT(c) f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
RCB3 10x18 4T18 4T18 4T18 3T18 3T18 3T18 - T10-3IN S.S T10-3IN S.S T10-3IN S.S CANTILEVER AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
RB1 9x18 3T18 2T18 3T18 2T18 3T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
RB2 9x12 3T18 2T18 3T18 2T18 3T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S
RCB5 9x12 3T18 3T18 3T18 2T18 2T18 2T18 - T10-3IN S.S T10-3IN S.S T10-3IN S.S CANTILEVER
RSB1 9x12 2T18 2T18 2T18 2T18 3T18 2T18 - T10-3IN S.S T10-6IN S.S T10-3IN S.S
GCB2 20x20 6T18 6T18 6T18 4T18 4T18 4T18 2T12 E.F T10-4IN D.S T10-4IN D.S T10-4IN D.S CANTILEVER

PROJECT :
REINFORCEMENT SCHEDULE FOR LANDING BEAM THREE AND HALF STOREY
RESISDENCE
SIZE TOP REINFORCEMENT BAR BOTTOM REINFORCEMENT BAR [CORNER OF 65TH & 110A STREET]
MARK SIDE BAR(g) LINKS 1 LINKS 2 LINKS 3 TYPE
(BxD) LEFT(a) MID(b) RIGHT(c) LEFT(a) MID(b) RIGHT(c)
LB1 12x14 4T18 2T18 4T18 3T18 3T18 3T18 - T10-4IN S.S T10-6IN S.S T10-4IN S.S LANDING BLOCK NO.
LB2 12x14 3T18 2T18 3T18 2T18 3T18 2T18 - T10-4IN S.S T10-6IN S.S T10-4IN S.S LANDING LOT NO.
TOWNSHIP CHAN MYA THARSI, MANDALAY

SUBJECT :
R.C DETAIL FOR BEAM - 2

TOP REINFORCEMENT

SCALE : SHEET NO :
DATE : JUNE/2022 S-RBD.02
REVISION NO ( - ) DATE ( - )
REVISION NO ( - ) DATE ( - )

TOP REINFORCEMENT < 5NOS TOP REINFORCEMENT > 5NOS OWNER :

TYPICAL BEAM SECTION


DAW JIT TOO MAR ZAW
1"(TYP)

L.C :

SINGLE STIRRUP (S.S) DOUBLE STIRRUP (D.S)

STIRRUP TYPES

NOTE: FOR SEISMIC RESISTING FRAME BEAMS, THE FOLLOWING ARE TO BE PROVIDED:
-ALL TRANSVERSE REINFORCEMENT IS TO BE CLOSED HOOP.
-LAP SPLICES, IF REQUIRED, ARE TO BE EQUAL TO F.T.L FOR BOTH TOP AND BOTTOM R.S.E / P.E (CONSTRUCTION) :
REINFORCEMENT.
-LAP SPLICES SHALL NOT TO BE USED:
(A) WITHIN THE JOINTS
(B) WITHIN A DISTANCE OF TWICE THE MEMBER DEOTH FROM THE FACE OF THE
JOINT.
-SPLICING OF REINFORCEMENT SHALL BE LIMITED TO 50% OF THE TOTAL AMOUNT OF
REINFORCEMENT AT THE SECTION.
-ALL BOTTOM REINFORCEMENT IS TO BE ANCHORED TO THE SUPPORT OF A LENGTH
OF F.T.A MAXIMUM.
-IF THERE ARE MORE THAN FIVE TOP REINFORCEMENT IN THE UPPER LAYER OF THE R.S.E / P.E (STRUCTURE) :
BEAM, THE REMAINING REINFORCEMENTS MUST BE ADDED TO THE SECOND LAYER.
-MINIMUM CLEAR DISTANCE BETWEEN BARS IN LAYERS IS 1 IN.
-ALL CONCRETE WORK SHALL CONFORM TO ACI 318-14 BUILDING CODE.
-F'c = 3000PSI(G20.6) @ 28 DAYS MAX AGGREGATE SIZE = 34 IN .
-REINFORCING STEEL SHELL CONFORM TO 50000PSI(HRB400).
-PLACE MAIN REINFORCING REBAR SO THAT REBAR IS 1.5 IN CLEAR IN BEAM.
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
2 3 4 5 fy = 58000psi(HRB400) For ALL REINFORCING BARS
1 2 3 4 5 6
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
5T18 3T18
5T18 5T18
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
2T18 2T18 5T18 2H 5T18
2T18
T.L +27' T.L +27'
T.L +26.67' T.L +26.67' T.L +26.67' 2xF.T.L T.L +26.5'
1.3xF.T.L 1.3xF.T.L F.T.L 1.3xF.T.L
F.T.L

F.T.L
4T18 4T18 4T18
4T18 4T18 4T18
T10-3IN D.S T10-3IN S.S T10-5IN S.S T10-3IN S.S T10-3IN D.S T10-3IN D.S T10-5IN D.S T10-3IN D.S T10-3IN D.S

SMB7 (12x16/18/16) SMB8 (12x16/18) SCB2 (12x18)


SCALE : 3/16" = 1' PROJECT :
THREE AND HALF STOREY
12" 12" 12" RESISDENCE
12" 12" 12" [CORNER OF 65TH & 110A STREET]

18"

18"

18"
BLOCK NO.
14"

14"

14"
LOT NO.

SECTION 1-1 SECTION 2-2 SECTION 3-3 SECTION 4-4 SECTION 5-5 SECTION 6-6 TOWNSHIP CHAN MYA THARSI, MANDALAY

SCALE : 21" = 1' SUBJECT :


R.C DETAIL FOR BEAM - 3
A B
8
7 9
SCALE : AS SHOWN SHEET NO :
5T18 DATE : JUNE/2022 S-RBD.03
5T18
2T18
5T18
2H REVISION NO ( - ) DATE ( - )
T.L +27'
T.L +26.67' T.L +26.67'
1.3xF.T.L
REVISION NO ( - ) DATE ( - )

OWNER :
4T18 4T18
4T18
T10-3IN D.S T10-3IN D.S T10-5IN D.S T10-3IN D.S

DAW JIT TOO MAR ZAW


SCB5 (12x16) SMB9 (12x16/18)
SCALE : 3/16" = 1'
12"
12" 12"
L.C :
18"
14"

14"

SECTION 7-7 SECTION 8-8 SECTION 9-9


1
SCALE : 2" = 1'

R.S.E / P.E (CONSTRUCTION) :

R.S.E / P.E (STRUCTURE) : S-RBD.03


NOTE:
BEAM CROSS SECTION DETAIL BEAM CROSS SECTION DETAIL
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
BEAM TYPE BEAM TYPE f'c = 3000psi(G20.69) FOR BEAM & SLAB
AT END SUPPORT AT MID SPAN AT END SUPPORT AT MID SPAN f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
12" 12" 12" 12" AND ALL CAST-IN REBAR
TOP REIN: 5T18 TOP REIN: 4T16 TOP REIN: 5T18 TOP REIN: 4T18
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

GMB1,FMB6 FMB1 ADD. TOP REIN: 4T18

18"

18"

18"

18"
RMB5 STIRRUPS: T10-3IN D.S STIRRUPS: T10-6IN D.S
STIRRUPS: T10-3IN D.S STIRRUPS: T10-6IN D.S

BOTTOM REIN: 4T18 BOTTOM REIN: 5T16 BOTTOM REIN: 4T18 BOTTOM REIN: 5T18

12" 12" 12" 12"


TOP REIN: 4T18 TOP REIN: 2T18 TOP REIN: 5T18 TOP REIN: 3T18

PROJECT :
THREE AND HALF STOREY
GMB2 FMB2
18"

18"

18"

18"
STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S RESISDENCE
STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S [CORNER OF 65TH & 110A STREET]

BOTTOM REIN: 3T18 BOTTOM REIN: 3T18 BOTTOM REIN: 3T18 BOTTOM REIN: 5T18
BLOCK NO.

12" 12"
LOT NO.
12" 12"
TOP REIN: 5T18 TOP REIN: 4T18
TOP REIN: 5T18 TOP REIN: 4T18 TOWNSHIP CHAN MYA THARSI, MANDALAY

ADD. TOP REIN: 2T18 SUBJECT :


FMB4
18"

18"

GMB3,FMB3

16"

16"
R.C DETAIL FOR BEAM - 4
SMB3,TMB1 STIRRUPS: T10-3IN D.S STIRRUPS: T10-6IN D.S STIRRUPS: T10-3IN D.S STIRRUPS: T10-6IN D.S

BOTTOM REIN: 4T18 BOTTOM REIN: 5T18 BOTTOM REIN: 4T18 BOTTOM REIN: 4T18 1
SCALE : 2 "=1' SHEET NO :
DATE : JUNE/2022 S-RBD.04
12" 12"
12" 12" REVISION NO ( - ) DATE ( - )
TOP REIN: 4T18 TOP REIN: 2T18
TOP REIN: 3T18 TOP REIN: 2T18
GMB4, FMB7, REVISION NO ( - ) DATE ( - )
TMB5, RMB3 FMB5

16"

16"
14"

14"

STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S OWNER :

BOTTOM REIN: 2T18 BOTTOM REIN: 3T18 BOTTOM REIN: 2T18 BOTTOM REIN: 3T18

DAW JIT TOO MAR ZAW


12" 12"

12" 12" TOP REIN: 5T18 TOP REIN: 5T18

TOP REIN: 4T18 TOP REIN: 2T18

FCB1,TCB2 L.C :

18"

18"
GMB5, SMB6
14"

14"

STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S STIRRUPS: T10-3IN D.S STIRRUPS: T10-3IN D.S
RCB1
BOTTOM REIN: 3T18 BOTTOM REIN: 3T18 BOTTOM REIN: 4T18 BOTTOM REIN: 4T18

12" 12"
12" 12"
TOP REIN: 5T18 TOP REIN: 5T18
TOP REIN: 5T18 TOP REIN: 5T18

R.S.E / P.E (CONSTRUCTION) :


GCB1 FCB2
18"

18"

16"

16"
STIRRUPS: T10-3IN D.S STIRRUPS: T10-3IN D.S STIRRUPS: T10-3IN D.S STIRRUPS: T10-3IN D.S

BOTTOM REIN: 4T18 BOTTOM REIN: 4T18 BOTTOM REIN: 4T18 BOTTOM REIN: 4T18

12" 12"
10" 10"
TOP REIN: 4T18 TOP REIN: 4T18
TOP REIN: 3T18 TOP REIN: 2T18
GB1,SB4,RB3 R.S.E / P.E (STRUCTURE) :
FCB3,SCB3
TB3,RMB4,
16"

16"
12"

12"

STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S


RTB2 TCB3 STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S

BOTTOM REIN: 2T18 BOTTOM REIN: 3T18


BOTTOM REIN: 3T18 BOTTOM REIN: 3T18
NOTE:
BEAM CROSS SECTION DETAIL BEAM CROSS SECTION DETAIL
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
BEAM TYPE BEAM TYPE f'c = 3000psi(G20.69) FOR BEAM & SLAB
AT END SUPPORT AT MID SPAN AT END SUPPORT AT MID SPAN f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
12" 12"
AND ALL CAST-IN REBAR
TOP REIN: 5T18 TOP REIN: 5T18
10" 10" 2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
TOP REIN: 2T18 TOP REIN: 2T18 CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
ADD. TOP REIN: 2T18 ADD. TOP REIN: 2T18
FB1 SCB1

24"

24"
16"

16"
SIDE BARS : 2T12 (E.F) SIDE BARS : 2T12 (E.F)
STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S
STIRRUPS: T10-4IN D.S STIRRUPS: T10-4IN D.S

BOTTOM REIN: 2T18 BOTTOM REIN: 3T18


BOTTOM REIN: 4T18 BOTTOM REIN: 4T18

12" 12"
TOP REIN: 5T18 TOP REIN: 5T18
10" 10"
TOP REIN: 2T18 TOP REIN: 2T18 PROJECT :
ADD. TOP REIN: 2T18 ADD. TOP REIN: 2T18 THREE AND HALF STOREY
FB2 SCB2

18"

18"
RESISDENCE
12"

12"
STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S STIRRUPS: T10-3IN D.S STIRRUPS: T10-3IN D.S [CORNER OF 65TH & 110A STREET]

BOTTOM REIN: 2T18 BOTTOM REIN: 2T18 BOTTOM REIN: 4T18 BOTTOM REIN: 4T18
BLOCK NO.

12" 12" LOT NO.


TOP REIN: 5T18 TOP REIN: 4T18 12" 12"
TOP REIN: 3T18 TOP REIN: 3T18 TOWNSHIP CHAN MYA THARSI, MANDALAY

ADD. TOP REIN: 3T18 SUBJECT :


SMB1 SCB4

16"

16"
R.C DETAIL FOR BEAM - 5
24"

24"

SIDE BARS : 2T12 (E.F) SIDE BARS : 2T12 (E.F) STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S

STIRRUPS: T10-4IN D.S STIRRUPS: T10-6IN D.S


BOTTOM REIN: 3T18 BOTTOM REIN: 3T18 1
SCALE : 2 "=1' SHEET NO :
BOTTOM REIN: 4T18 BOTTOM REIN: 4T18
DATE : JUNE/2022 S-RBD.05
12" 12"
12" 12"
TOP REIN: 4T18 TOP REIN: 2T18 REVISION NO ( - ) DATE ( - )
TOP REIN: 4T18 TOP REIN: 2T18

REVISION NO ( - ) DATE ( - )
SMB2 SB1
18"

18"

STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S

16"

16"
STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S OWNER :

BOTTOM REIN: 3T18 BOTTOM REIN: 5T18 BOTTOM REIN: 3T18 BOTTOM REIN: 3T18

DAW JIT TOO MAR ZAW

12" 12" 10" 10"


TOP REIN: 4T18 TOP REIN: 2T18 TOP REIN: 3T18 TOP REIN: 2T18

SMB4,TMB3 SB3 L.C :


16"

16"

16"

16"
STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S

BOTTOM REIN: 3T18 BOTTOM REIN: 3T18 BOTTOM REIN: 2T18 BOTTOM REIN: 3T18

12" 12" 10" 10"


TOP REIN: 3T18 TOP REIN: 2T18 TOP REIN: 3T18 TOP REIN: 3T18

R.S.E / P.E (CONSTRUCTION) :


SMB5 SCB5
16"

16"

16"

16"
STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S

BOTTOM REIN: 2T18 BOTTOM REIN: 3T18 BOTTOM REIN: 3T18 BOTTOM REIN: 3T18

12" 12" 12" 12"


TOP REIN: 3T18 TOP REIN: 2T18 TOP REIN: 4T18 TOP REIN: 2T18

SB2,TB2 R.S.E / P.E (STRUCTURE) :


16"

16"

TMB2
18"

18"
STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S

BOTTOM REIN: 2T18 BOTTOM REIN: 3T18


BOTTOM REIN: 2T18 BOTTOM REIN: 3T18
NOTE:
BEAM CROSS SECTION DETAIL BEAM CROSS SECTION DETAIL
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
BEAM TYPE BEAM TYPE f'c = 3000psi(G20.69) FOR BEAM & SLAB
AT END SUPPORT AT MID SPAN AT END SUPPORT AT MID SPAN f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
12" 12" AND ALL CAST-IN REBAR
TOP REIN: 5T18 TOP REIN: 5T18 2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
12" 12"
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
TOP REIN: 4T18 TOP REIN: 4T18
ADD. TOP REIN: 2T18 ADD. TOP REIN: 2T18
TCB1 RCB2
22"

22"
SIDE BARS : 2T12 (E.F) SIDE BARS : 2T12 (E.F)

14"

14"
STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S
STIRRUPS: T10-4IN D.S STIRRUPS: T10-4IN D.S

BOTTOM REIN: 3T18 BOTTOM REIN: 3T18


BOTTOM REIN: 5T18 BOTTOM REIN: 5T18

12" 12" 10" 10"


TOP REIN: 4T18 TOP REIN: 4T18 TOP REIN: 4T18 TOP REIN: 4T18
PROJECT :
THREE AND HALF STOREY
TCB4 RCB3 RESISDENCE
18"

18"

18"

18"
STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S
[CORNER OF 65TH & 110A STREET]

BOTTOM REIN: 3T18 BOTTOM REIN: 3T18 BOTTOM REIN: 3T18 BOTTOM REIN: 3T18 BLOCK NO.
LOT NO.
10" 10" 9" 9"
TOP REIN: 3T18 TOP REIN: 2T18 TOP REIN: 3T18 TOP REIN: 2T18 TOWNSHIP CHAN MYA THARSI, MANDALAY

SUBJECT :
TB1 RB1 R.C DETAIL FOR BEAM - 6
18"

18"

18"

18"
STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S

1
BOTTOM REIN: 2T18 BOTTOM REIN: 2T18 BOTTOM REIN: 2T18 BOTTOM REIN: 3T18 SCALE : 2 "=1' SHEET NO :
DATE : JUNE/2022 S-RBD.06
REVISION NO ( - ) DATE ( - )
10" 10" 9" 9"
TOP REIN: 3T18 TOP REIN: 3T18 TOP REIN: 3T18 TOP REIN: 2T18
REVISION NO ( - ) DATE ( - )
TCB5,RCB4 RB2
OWNER :
12"

12"

12"

12"
STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S

BOTTOM REIN: 2T18 BOTTOM REIN: 2T18 BOTTOM REIN: 2T18 BOTTOM REIN: 3T18
DAW JIT TOO MAR ZAW

12" 12"
TOP REIN: 5T18 TOP REIN: 4T18 9" 9"
TOP REIN: 3T18 TOP REIN: 3T18
RMB1 RCB5 L.C :
16"

16"

12"

12"
STIRRUPS: T10-3IN D.S STIRRUPS: T10-6IN D.S STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S

BOTTOM REIN: 4T18 BOTTOM REIN: 5T18 BOTTOM REIN: 2T18 BOTTOM REIN: 2T18

10" 10"
TOP REIN: 4T18 TOP REIN: 2T18 9" 9"
TOP REIN: 2T18 TOP REIN: 2T18 R.S.E / P.E (CONSTRUCTION) :
RMB2 RSB1
16"

16"

12"

12"
STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S

BOTTOM REIN: 2T18 BOTTOM REIN: 3T18 BOTTOM REIN: 2T18 BOTTOM REIN: 3T18

20" 20"
10" 10"
TOP REIN: 6T18 TOP REIN: 6T18
TOP REIN: 4T18 TOP REIN: 2T18
RMB6 R.S.E / P.E (STRUCTURE) :
GCB2
20"

20"
SIDE BARS : 2T12 (E.F) SIDE BARS : 2T12 (E.F)
18"

18"

STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S

STIRRUPS: T10-4IN D.S STIRRUPS: T10-4IN D.S

BOTTOM REIN: 2T18 BOTTOM REIN: 3T18 BOTTOM REIN: 4T18 BOTTOM REIN: 4T18
NOTE:
LANDING BEAM CROSS SECTION DETAIL
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
BEAM TYPE f'c = 3000psi(G20.69) FOR BEAM & SLAB
AT END SUPPORT AT MID SPAN f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
fy = 58000psi(HRB400) For ALL REINFORCING BARS
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
12" 12"
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
TOP REIN: 4T18 TOP REIN: 2T18

LB1
14"

14"
STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S

BOTTOM REIN: 3T18 BOTTOM REIN: 3T18

12" 12"
TOP REIN: 3T18 TOP REIN: 2T18 PROJECT :
THREE AND HALF STOREY
LB2 RESISDENCE
[CORNER OF 65TH & 110A STREET]
14"

14"
STIRRUPS: T10-3IN S.S STIRRUPS: T10-6IN S.S

BOTTOM REIN: 2T18 BOTTOM REIN: 3T18 BLOCK NO.


LOT NO.
TOWNSHIP CHAN MYA THARSI, MANDALAY

SUBJECT :
R.C DETAIL FOR BEAM - 7

1
SCALE : 2 "=1' SHEET NO :
DATE : JUNE/2022 S-RBD.07
REVISION NO ( - ) DATE ( - )
REVISION NO ( - ) DATE ( - )

OWNER :

DAW JIT TOO MAR ZAW

L.C :

R.S.E / P.E (CONSTRUCTION) :

R.S.E / P.E (STRUCTURE) :


NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
COLUMN STRIP MIDDLE STRIP COLUMN STRIP COLUMN STRIP MIDDLE STRIP COLUMN STRIP fy = 58000psi(HRB400) For ALL REINFORCING BARS
0.25L 0.25L 0.25L 0.25L AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
COLUMN STRIP

COLUMN STRIP
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

T10-6IN

T10-6IN
0.25L

0.25L
T16-8IN(B) Additional
MIDDLE STRIP

MIDDLE STRIP
PARTITION WALL

t+8"
T10-6IN

T10-6IN

t
T & B REINFORCEMENT
SCHEDULE
COLUMN STRIP

COLUMN STRIP
T10-6IN

T10-6IN
0.25L

0.25L
PROJECT :
THREE AND HALF STOREY
SHORT SPAN (L) RESISDENCE
TO BE ONE SIZE BIGGER [CORNER OF 65TH & 110A STREET]
THAN AS SHOWN IN SLAB
T10-6IN T10-3IN T10-6IN T10-6IN T10-6IN T10-6IN

TYPICAL TOP REINFORCEMENT PLAN TYPICAL BOTTOM REINFORCEMENT PLAN BLOCK NO.
ADDITIONAL SLAB REINFORCEMENT UNDER PARTITION WALL
LOT NO.
TOWNSHIP CHAN MYA THARSI, MANDALAY

SUBJECT :
R.C DETAIL FOR SLAB & STAIR - 1
0.3 GRATER "L"
0.3(L1) 1
F.T.A SCALE : 2 "=1' SHEET NO :
. A

DATE : JUNE/2022 S-RSD.01


T
F .

2" CLR
REVISION NO ( - ) DATE ( - )
4"
3

0.125 0.125 0.125


(L1) (L1) (L2) LANDING SLAB REVISION NO ( - ) DATE ( - )
6" TYP L1 L2 LANDING BEAM
OWNER :

TYPICAL SLAB SECTION


T10-8IN DAW JIT TOO MAR ZAW
STEP REINFORCEMENT
3T10
REINFORCEMENT SCHEDULE FOR FLOOR SLAB STEP REINFORCEMENT

THICK REINFORCEMENT

T
MARK NESS LAYER SHORTER DIRECTION LONGER DIRECTION REMARK L.C :
(IN) COLUMN STRIP MIDDLE STRIP COLUMN STRIP MIDDLE STRIP
TOP T10-6IN T10-6IN T10-6IN T10-6IN
S1 5 TWO WAY
BOTTOM T10-6IN T10-6IN T10-6IN T10-6IN
TOP T10-6IN T10-3IN T10-6IN T10-3IN MAIN REINFORCEMENT
S2 5 TWO WAY
BOTTOM T10-6IN T10-6IN T10-6IN T10-6IN DISTRIBUTED REINFORCEMENT
TOP T10-3IN T10-3IN T10-3IN T10-3IN
CS1 5 CANTILEVER
BOTTOM T10-6IN T10-6IN T10-6IN T10-6IN
TYPICAL STAIR SECTION R.S.E / P.E (CONSTRUCTION) :
REINFORCEMENT SCHEDULE FOR LANDING SLAB
THICK REINFORCEMENT
MARK NESS MAIN REINFORCEMENT DISTRIBUTION REINFORCEMENT REMARK
(IN) (EACH FACE) (EACH FACE)
LS1 6 T12-6IN T12-6IN -

REINFORCEMENT SCHEDULE FOR STAIR


R.S.E / P.E (STRUCTURE) :
THICK REINFORCEMENT
MARK NESS MAIN REINFORCEMENT DISTRIBUTION REINFORCEMENT REMARK
(IN) (EACH FACE) (EACH FACE)
SS1 6 T12-6IN T12-6IN -
MAIN REINFORCEMENT
T12-6IN NOTE:
DISTRIBUTION REINFORCEMENT
C B T12-6IN
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
STEP REINFORCEMENT
3T10
FMB6 f'c = 3000psi(G20.69) FOR BEAM & SLAB
LVL. (+50'-00") STEP REINFORCEMENT f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
T10-8IN
RMB4 RMB3 BEAM REINFORCEMENT fy = 58000psi(HRB400) For ALL REINFORCING BARS
NOT SHOWN FOR CLARITY AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
5'-9"

FLIGHT-2 FLIGHT-2

LB2 LVL. (+44'-03")


STAIR-4
LB1
5'-9"

FLIGHT-1 BEAM REINFORCEMENT


NOT SHOWN FOR CLARITY

LVL. (+38'-06") LB1 PROJECT :


THREE AND HALF STOREY
TMB5 TMB5 MAIN REINFORCEMENT
RESISDENCE
T12-6IN [CORNER OF 65TH & 110A STREET]
DISTRIBUTION REINFORCEMENT
BEAM REINFORCEMENT NOT SHOWN T12-6IN
5'-9"

FOR CLARITY
FLIGHT-2 BLOCK NO.
STEP REINFORCEMENT
3T10
FLIGHT-1 STEP REINFORCEMENT
LOT NO.
LB2 LVL. (+32'-09")
T10-8IN
STAIR-3 TOWNSHIP CHAN MYA THARSI, MANDALAY

SUBJECT :
5'-9"

R.C DETAIL FOR SLAB & STAIR - 2


FLIGHT-1
GMB5
LVL. (+27'-00") SCALE : AS SHOWN SHEET NO :
BEAM REINFORCEMENT
SMB6 SMB6 NOT SHOWN STAIR-1 DETAILS DATE : JUNE/2022
FOR CLARITY S-RSD.02
SCALE : 14 "=1'
REVISION NO ( - ) DATE ( - )
50'

MAIN REINFORCEMENT
T12-6IN
6'

FLIGHT-2 DISTRIBUTION REINFORCEMENT


T12-6IN
REVISION NO ( - ) DATE ( - )
STEP REINFORCEMENT SMB6
LB1 LVL. (+21'-00")
3T10 OWNER :
STEP REINFORCEMENT
T10-8IN
STAIR-2 BEAM REINFORCEMENT
NOT SHOWN FOR CLARITY

FLIGHT-2 DAW JIT TOO MAR ZAW


6'

FLIGHT-1

LB1
LVL. (+15'-00")
L.C :
FMB7 FMB6

BEAM REINFORCEMENT
NOT SHOWN FOR CLARITY
6'-9"

FLIGHT-2
MAIN REINFORCEMENT
T12-6IN
LVL. (+8'-03")
LB1 DISTRIBUTION REINFORCEMENT
LB1 T12-6IN
STAIR-1
STEP REINFORCEMENT
R.S.E / P.E (CONSTRUCTION) :
3T10
BEAM REINFORCEMENT STEP REINFORCEMENT
NOT SHOWN FOR CLARITY T10-8IN
6'-9"

FLIGHT-1
FLIGHT-1

LVL. (+01'-06")

GMB4 S-RBD.03
1'-6"

GMB5 LVL. (+00'-00") R.S.E / P.E (STRUCTURE) :


6'
FMB6

BEAM REINFORCEMENT
STAIR SECTION NOT SHOWN
1 Scale: 3/16 " = 1'-0"
FOR CLARITY

STAIR-2 DETAILS
SCALE : 14 "=1'
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


MAIN REINFORCEMENT
f'c = 3000psi(G20.69) FOR BEAM & SLAB
T12-6IN f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
DISTRIBUTION REINFORCEMENT fy = 58000psi(HRB400) For ALL REINFORCING BARS
T12-6IN
AND ALL CAST-IN REBAR
STEP REINFORCEMENT TMB5 2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
3T10
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
STEP REINFORCEMENT
T10-8IN
BEAM REINFORCEMENT
NOT SHOWN FOR CLARITY

FLIGHT-2

LB2

PROJECT :
BEAM REINFORCEMENT
NOT SHOWN FOR CLARITY
THREE AND HALF STOREY
RESISDENCE
[CORNER OF 65TH & 110A STREET]

MAIN REINFORCEMENT
LB2 T12-6IN
DISTRIBUTION REINFORCEMENT BLOCK NO.
T12-6IN

LOT NO.
STEP REINFORCEMENT
3T10
BEAM REINFORCEMENT TOWNSHIP CHAN MYA THARSI, MANDALAY
NOT SHOWN FOR CLARITY STEP REINFORCEMENT
T10-8IN
SUBJECT :
FLIGHT-1 R.C DETAIL FOR SLAB & STAIR - 3

1
SCALE : 4" = 1' SHEET NO :
SMB6 DATE : JUNE/2022 S-RSD.03
BEAM REINFORCEMENT REVISION NO ( - ) DATE ( - )
NOT SHOWN
FOR CLARITY
REVISION NO ( - ) DATE ( - )

OWNER :
STAIR 3 & 4 DETAILS

DAW JIT TOO MAR ZAW

L.C :

R.S.E / P.E (CONSTRUCTION) :

R.S.E / P.E (STRUCTURE) :


NOTE:
REINFORCEMENT SCHEDULE FOR COLUMN
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
ROOF TOP LEVEL f'c = 3000psi(G20.69) FOR BEAM & SLAB
1 2 2 2 f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
LVL. +61'-06" 1
fy = 58000psi(HRB400) For ALL REINFORCING BARS
10" 6" 10" 6"
6" 8" 6" 8" 10" 6" AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN

6"
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

12"
C

6"

10"
8"
C

10"
A A B

8"

6"

6"

6"
COLUMN SIZE 14"x14" COLUMN SIZE 14"x14" COLUMN SIZE 16"x16" COLUMN SIZE 16"x16" COLUMN SIZE 16"x18"
SECOND FLOOR LEVEL MAIN BAR 8-T18 MAIN BAR 8-T18 MAIN BAR 8-T18 MAIN BAR 8-T18 MAIN BAR 10-T18
TIE BAR, So T10@4IN TIE BAR, So T10@4IN TIE BAR, So T10@4IN TIE BAR, So T10@4IN TIE BAR, So T10@4IN
LVL. +27'-00"
TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN
PROJECT :
SECOND FLOOR LEVEL THREE AND HALF STOREY
1 2 2 2 RESISDENCE
LVL. +27'-00" 1
[CORNER OF 65TH & 110A STREET]
6" 10" 10" 6" 10" 6" 12" 6"
6" 10"

6"
BLOCK NO.

12"

12"
C

10"
6"

C LOT NO.

1'
A A B
10"

6"

6"

6"
TOWNSHIP CHAN MYA THARSI, MANDALAY

SUBJECT :
COLUMN SIZE 16"x16" COLUMN SIZE 16"x16" COLUMN SIZE 16"x18" COLUMN SIZE 16"x18" COLUMN SIZE 18"x18" R.C DETAIL FOR COLUMN - 1
PILE CAP TOP LEVEL MAIN BAR 10-T18 MAIN BAR 10-T18 MAIN BAR 10-T18 MAIN BAR 10-T18 MAIN BAR 16-T18
TIE BAR, So T10@4IN TIE BAR, So T10@4IN TIE BAR, So T10@4IN TIE BAR, So T10@4IN TIE BAR, So T10@4IN
LVL. 00'-00" 1
TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN SCALE : 2 "=1' SHEET NO :
LEVEL/FLOOR DATE : JUNE/2022 S-RCD.01
C1 A1 C2 A2 B2
COLUMN NO. REVISION NO ( - ) DATE ( - )
REVISION NO ( - ) DATE ( - )
ROOF TOP LEVEL
3 OWNER :
LVL. +61'-06"
8" 8"

DAW JIT TOO MAR ZAW


10"

B
6"

L.C :
COLUMN SIZE 16"x16"
THIRD FLOOR LEVEL MAIN BAR 12-T18
TIE BAR, So T10@4IN
LVL. +38'-06"
TIE BAR, Se T10@6IN
THIRD FLOOR LEVEL THIRD FLOOR LEVEL 5
3 5
LVL. +38'-06" LVL. +38'-06"
B 10" 6"
3'-9"

8" 8" 10" 6"


R.S.E / P.E (CONSTRUCTION) :
6"
12"

C
10"

2'

B
6"

COLUMN SIZE 16"x18" COLUMN SIZE 16"x16" COLUMN SIZE 16"x24"


PILE CAP TOP LEVEL MAIN BAR 16-T18 PILE CAP TOP LEVEL MAIN BAR 12-T18 MAIN BAR 14-T18 R.S.E / P.E (STRUCTURE) :
TIE BAR, So T10@4IN TIE BAR, So T10@4IN TIE BAR, So T10@4IN
LVL. 00'-00" LVL. 00'-00"
TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN
LEVEL/FLOOR LEVEL/FLOOR
B3 C5 B5
COLUMN NO. COLUMN NO.
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


ROOF TOP LEVEL f'c = 3000psi(G20.69) FOR BEAM & SLAB
1 3 3 f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
LVL. +61'-06"
fy = 58000psi(HRB400) For ALL REINFORCING BARS
6" 10" 8" 8" 8" 8" AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS

6"
10"

10"
C
B A

10"
6"

6"
COLUMN SIZE 16"x16" COLUMN SIZE 16"x16" COLUMN SIZE 16"x16"
PILE CAP TOP LEVEL MAIN BAR 12-T18 MAIN BAR 10-T18 MAIN BAR 10-T18
TIE BAR, So T10@4IN TIE BAR, So T10@4IN TIE BAR, So T10@4IN
LVL. 00'-00"
TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN
PROJECT :
LEVEL/FLOOR THREE AND HALF STOREY
B1 C3 A3 RESISDENCE
COLUMN NO. [CORNER OF 65TH & 110A STREET]

ROOF FLOOR LEVEL BLOCK NO.


4 4 4
LVL. +50'-00"
10" 6" 14" 6" 10" 6" LOT NO.
TOWNSHIP CHAN MYA THARSI, MANDALAY
6"

12"
C 10" SUBJECT :
10"

A B R.C DETAIL FOR COLUMN - 2


6"

6"
1
SCALE : 2 "=1' SHEET NO :
COLUMN SIZE 16"x16" COLUMN SIZE 16"x20" COLUMN SIZE 16"x18"
PILE CAP TOP LEVEL MAIN BAR 12-T18 MAIN BAR 14-T18 MAIN BAR 14-T18 DATE : JUNE/2022 S-RCD.02
TIE BAR, So T10@4IN TIE BAR, So T10@4IN TIE BAR, So T10@4IN
LVL. 00'-00" REVISION NO ( - ) DATE ( - )
TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN TIE BAR, Se T10@6IN
LEVEL/FLOOR REVISION NO ( - ) DATE ( - )
C4 A4 B4
COLUMN NO. OWNER :

DAW JIT TOO MAR ZAW

L.C :

R.S.E / P.E (CONSTRUCTION) :

R.S.E / P.E (STRUCTURE) :


NOTE:
REINFORCEMENT SCHEDULE FOR PILE CAP
1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:
f'c = 3000psi(G20.69) FOR BEAM & SLAB
BOTTOM REINFORCEMENT TOP REINFORCEMENT f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
TYPE SIZE THICKNESS REMARK
LONGER DIRECTION LONGER DIRECTION fy = 58000psi(HRB400) For ALL REINFORCING BARS
(FTxFT) (IN) SHORTER DIRECTION SHORTER DIRECTION
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
1PC1 3.5x3.5 48 T22-5IN T22-5IN T22-5IN T22-5IN - CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
2PC1 3.5x9.5 48 T22-5IN T22-5IN T22-6IN T22-6IN -
2PC1A 3.5x9.5 48 T22-5IN T22-5IN T20-5IN T20-5IN -
4PC1 9.5x9.5 48 T22-5IN T22-5IN T20-6IN T20-6IN -

1 2
PROJECT :
3'-6" THREE AND HALF STOREY
9'-6"
RESISDENCE
1'-9" 1'-9" 1'-9" 6' 1'-9" [CORNER OF 65TH & 110A STREET]
1'-9"

1'-9"
BLOCK NO.
3'-6"

3'-6"
A A
1'-9"

1'-9"
LOT NO.
TOWNSHIP CHAN MYA THARSI, MANDALAY

1PC1 (PILE PLAN) 2PC1 (PILE PLAN) SUBJECT :


R.C DETAIL FOR PILE CAP - 1

1 2
3
SCALE : 16"=1" SHEET NO :
DATE : JUNE/2022 S-PC.01
T22-5IN

T22-6IN
A A
REVISION NO ( - ) DATE ( - )
T22-5IN T22-6IN
REVISION NO ( - ) DATE ( - )

OWNER :
1PC1 (TOP REINFORCEMENT PLAN) 2PC1 (TOP REINFORCEMENT PLAN)

DAW JIT TOO MAR ZAW


1 2

T22-5IN
L.C :
T22-5IN

A A
T22-5IN T22-5IN

1PC1 (BOTTOM REINFORCEMENT PLAN) 2PC1 (BOTTOM REINFORCEMENT PLAN)

R.S.E / P.E (CONSTRUCTION) :


RC COLUMN RC COLUMN
COLUMN TIE (MIN4IN) COLUMN TIE (MIN4IN)
T22-5IN T22-6IN
TIE BAR T12-5IN TIE BAR T12-5IN

STREET LEVEL (00'-00") STREET LEVEL (00'-00")


F.T.L

F.T.L
40D

40D
F.T.L

F.T.L

F.T.L
4'

4'

R.S.E / P.E (STRUCTURE) :


3"

3"
4"

4"

T22-5IN T22-5IN
3IN THK; LEAN CONCRETE 3IN THK; LEAN CONCRETE
6IN THK; HARD CORE 6IN THK; HARD CORE
Ø24IN MINI-BORED PILE Ø24IN MINI-BORED PILE
1PC1 (SECTION) 2PC1 (SECTION)
NOTE:

1.MATERIAL STRENGTH FOR STRUCTURAL MEMBERS:


f'c = 3000psi(G20.69) FOR BEAM & SLAB
3
f'c = 3000psi(G20.69) FOR COLUMN, WALL & PILECAP
3 fy = 58000psi(HRB400) For ALL REINFORCING BARS
9'-6"
AND ALL CAST-IN REBAR
2.ALL STRUCTURAL DRAWINGS SHALL BE READ IN
1'-9" 6' 1'-9"
CONJUCTION WITH THE ARCHITECTURAL DRAWINGS
1'-9" 6' 1'-9"

1'-9"
1'-9"
C

3'-6"

1'-9"

9'-6"
6'
B

2PC1A (PILE PLAN)


PROJECT :
THREE AND HALF STOREY

1'-9"
RESISDENCE
[CORNER OF 65TH & 110A STREET]

2 4PC1 (PILE PLAN)


BLOCK NO.
LOT NO.
T22-5IN
3 TOWNSHIP CHAN MYA THARSI, MANDALAY

A
T22-5IN SUBJECT :
R.C DETAIL FOR PILE CAP - 2

2PC1A (TOP REINFORCEMENT PLAN) 3


SCALE : 16"=1" SHEET NO :
DATE : JUNE/2022 S-PC.02
B REVISION NO ( - ) DATE ( - )

T22-6IN
REVISION NO ( - ) DATE ( - )
2
OWNER :
T22-6IN
T22-5IN

4PC1 (TOP REINFORCEMENT PLAN) DAW JIT TOO MAR ZAW


A
T22-5IN

2PC1A (BOTTOM REINFORCEMENT PLAN) L.C :

RC COLUMN
COLUMN TIE (MIN4IN)
RC COLUMN T22-6IN
COLUMN TIE (MIN4IN) TIE BAR T12-5IN
T22-5IN
R.S.E / P.E (CONSTRUCTION) :
TIE BAR T12-5IN STREET LEVEL (00'-00")
STREET LEVEL (00'-00")

F.T.L
B
T22-5IN

40D
F.T.L

F.T.L
4'
F.T.L

40D
F.T.L

F.T.L
4'

3"

4"
3"

4"

T22-5IN T22-5IN
3IN THK; LEAN CONCRETE
6IN THK; HARD CORE
T22-5IN
3IN THK; LEAN CONCRETE Ø24IN MINI-BORED PILE
R.S.E / P.E (STRUCTURE) :
6IN THK; HARD CORE
Ø24IN MINI-BORED PILE
4PC1 (BOTTOM REINFORCEMENT PLAN) 4PC1 (SECTION)
2PC1A (SECTION)