Professional Documents
Culture Documents
BS 6759-Part 1 Safety Valves
BS 6759-Part 1 Safety Valves
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
Safety valves
Part i.Specification for safety valves
for steam and hot water
Soupapes de sûreté
Partie 1. Soupapes de sûreté pour vapeur et eau chaude. Specification
Sicherheitsventile
Teil 1. Dampf- und Warmwassersicherheitsventile
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
BS6759 : Part 1 : 1984
Foreword
The preparation of this British Standard has been times the design pressure of the valve as specified to the
undertaken under the direction of the Pressure Vessel valve supplier by the purchaser. For this purpose a safety
Standards Committee to incorporate such requirements as valve is gagged or the seat blanked off as appropriate during
are necessitated by technical developments and to comply t h e test.
with the requirements of I S 0 4126 ‘Safety valves, general Appendix A gives the derivation of the superheat correction
requirements’, published by the International Organization factors listed in table 5 and which are used to calculate the
for Standardization. certified discharge capacity of a safety valve discharging
The opportunity has been taken to bring together in one superheated steam.
standard the requirements for safety valves. The standard Appendix B provides guidance on the mounting of safety
will be published in three Parts as follows: valves and includes recommendations for discharge piping
Part 1. Specificationfor safety valves for steam and and drainage. The advice given in this appendix i s intended
hot water to eliminate the detrimental effects on the performance of
Part 2. Specification for safety vaives for compressed safety valves which may arise from influences associated
air and inert gases (in course of preparation) with incorrect mounting.
Part 3. Specification for safety valves for process fluids It is recognized that clauses (reproduced in appendix C)
(in course of preparation) regarding inspection facilities and testing facilities which
have traditionally been incorporated into safety valve
Part 1 requires that safety valve designs shall be type tested standards are a contractual matter. Nevertheless their
for their operational and flow characteristics to the importance is such that the purchaser in agreeing a
satisfaction of an independent authority. In order to give contract should not overlook them.
manufacturers a period of grace in which to align their
This Part of this standard deals with the materials,
products with this standard, BS 759 : Part 2 has been
construction, and testing of safety valves and associated
created by amendments to the 1975 edition of BS 759
capacity calculations, but i s not intended to cover a l l
which will be retained as an obsolescent standard until
details of their installation, for which additional reference
it i s withdrawn in December 1987.
should be made to the appropriate British Standard.
To assist manufacturers and inspecting authorities, a l i s t of
N O T E 1. In order to ensure the correct functioning of boiler safety
testing establishments, together with details of facilities valves, i t IS essential that suitable equipment be provided to enable
available. has been compiled and i s available on request the proper condition of the feedwater to the boiler and the water in
from the Enquiry Section (London), British Standards the boiler to be maintained.
Institution, N O T E 2. Attention is directed to the recommendations contained
in ‘Guidance Note PM5’ entitled ‘Autornaticallv controlled steam
The hydraulic pressure testing requirements for components
and hot water boilers‘ issued by the Health and Safety Executive.
to this standard are in many cases equal to or greater than
those for the boiler to which they may be fitted, but in any
Compliance with a British Standard does not of itself
case it can be taken that any safety valve body will be
confer immunity from legal obligations.
capable of sustaining a hydraulic test pressure equal to 1.5
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document
1
Policy Group at 303-397-2295.
BS 6759 : Part 1 : 1984
British Standard
Safety valves
Part 1. Specification for safety valves for steam and hot water
Section one. General 2.1.3 supplementary loaded safety valve. A safety valve
which
1. Scope (a) has, until the pressure at the inlet o f the safety valve
This Part o f this British Standard specifies requ'rements for reaches set pressure, an additional force (supplementary
safety valves f o r steam and hot water where the set pressure load) to increase the sealing force, which may be
is greater than 1 bar gauge. provided by means of an extraneous power source which
It includes requirements for safety valves for boilers is reliably released when the pressure at the inlet of the
boiler installations and associated pipework systems where safety valve reaches the set pressure, and
the steam pressure exceeds 1 bar gauge or, in the case o f (b) attains its certified discharge capacity in the event o f
hot water boilers, where the rating i s 44 k W and above, the supplementary loading not being released at an ower-
as well as for boilers pressurized by steam for use in hot pressure not exceeding 115 X o f the set pressure.
water systems which are classified as steam boilers.
Requirements for testing safety valves f o r determination 2.1.4 pilot operated safety valve (indirect loaded safety
o f their operating and flow characteristics are given. valve). A safety valve, the operatton of which is initiated
and controlled by the fluid discharged from a pilot valve
Recommendations on safety valve mounting, discharge
wh'ch i s itself a direct loaded safety valve.
piping and drainage are given in appendix B.
2.2 blowdown of a safety valvet. The difference between
This standard does not cover safety valves for boilers used
the set pressure and the reseating pressure, normally stated
in open vented hot water systems working a t temperatures
as a percentage of set pressure, except for very low set
not exceeding 100 "C.nor safety valves for storage water
pressure when the Mowdown is.then expressed in bar.
heaters o f the unvented t y p e which normally operate a t
temperatures not exceeding 82 "C and a t pressures not 2.3 boiler operating pressure. In the case of fully-flooded
exceeding 10 bar*. F o r such boilers within the scope of h o t water boilers, not externally pressurized, t h e maximum
BS 779 and BS 855 the requirements are incorporated in operating pressure in the hot water system, including any
those standards. static head.
NOTE. The titles of the publications referred to in this standard In t h e case of externally pressurized fully-flooded h o t
are listed on the inside back cover. water boilers, the pressure a t which the boiler operates.
2. Definitions
For the purposes o f this Part of BC 6759 the following
2.4 built-up back pressure. The pressure existing at the
outlet of the safety valve caused b y flow through the valve
and the dischage vstem.
A
definitions apply. 2.5 certified discharge capacity. That portion of the
2.1 safety valve. A valve which automatically, without the measured capacity permitted t o be used as a basis for the
assistance of any energy other than t h a t o f the fluid application of a safety valve.
concerned, discharges a certified quantity of the fluid so as NOTE. The certified discharge capac'ty is derived from either
t o prevent a predetermined safe pressure being exceeded, measured flow rate x derating factor or theoretical flow rate x
and which is designed t o re-close and prevent the further coefficient of discharge x derating factor.
f l o w o f fluid after normal pressure conditions of service 2 6 cold differential test pressure. The inlet static pressure
have been restored. at which a safety valve is set to commence to lift on the test
2.1.1 direct loaded safety valve. A safety valve in which stand. This test pressure includes corrections for service
the loading due t o the fluid pressure underneath the valve conditions of back pressure and/or temperature.
disk is opposed only by direct mechanical loading such as 2.7 commencement of l i f t Initial lift such as would cause
a weight, a lever and weight, or a spring. the first indication of movement o n a linear transducer or
2.1.2 assisted safety valve. A direct loaded safety valve equivalent.
which, b y means of a powered assistance mechanism, is NOTE. Provision of such instrument facility only applies to valves
lifted a t a pressure below the unassisted set pressure and under operating characteristics tests.
will, even in the event of failure of the assistance mechanism, 2.8 design pressure. The pressure used in calculating the
comply with all the relevant requirements for safety valves thickness of a vessel or pipe system.
given in this standard. 2.9 discharge area of a safety valve. The minimum cross-
sectional area between inlet and seat, including the curtain
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 2 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
~~ ~
'F c
BSI BS*b759: PART*L O2 Lb2Llbb9 0 4 5 3 5 9 7 T50 M
area, which controls the flow of fluid through the safety 2.19 rdieving pressure (flow rating pressure). Set pressure
valve when it i s discharging i t s rated discharge capacity. plus overpressure.
NOTE. See figure 1.
2.20 reseating pressure o f a safety valve. The value of inlet
2 1 0 double safety valve. A safety valve with two body static pressure a t which the disk re-establishes contact w i t h
seats i n one body. the seat or a t which l i f t becomes zero.
2.11 equivalent calculated capacity. The calculated 2.21 set pressure. The predetermined pressure a t which a
capacity of the safety valve for conditions of pressure, safety valve under operating conditions should commence
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
temperature or nature of the fluid which differ from those t o lift. It i s the gauge pressure measured a t the valve inlet
for which certified capacities are available. a t which the pressure forces tending t o open the valve for
2.12 f l o w area. The minimum cross-sectional f l o w area the specified service conditions are i n equilibrium w i t h the
( b u t not t h e curtain area) between inlet and seat which i s forces retaining the valve disk o n its seat.
used t o calculate the theoretical flow rate, w i t h no 2.22 single safety valve. A safety valve w i t h one body
deduction f o r any obstruction. seat only.
NOTE. See figure 1. 2.23 theoretical flowing (discharge) capacity. The calcul-
2.13 f l o w diameter. The diameter corresponding t o the ated capacity expressed i n gravimetric or volumetric units
f l o w area. of a theoretically perfect nozzle having a cross-sectional
flow area equal t o the f l o w area of a safety valve.
2.14 independent authority. The competent independent
authority which bears responsibility for all aspects of
surveillance of tests, checking of calculations and certific-
ation of safety valve discharge capacities. Section twg. Material requirements and limitations
2.15 inspecting authority. The competent independent
authority or association which verifies compliance w i t h 3. Pressure containing components
this standard. 3.1 Material specification. The materials used i n the
2.16 lift. The travel of the disk away from t h e closed manufacture of bodies and bonnets o f safety valves shall
position. comply with whichever of the following is appropriate
2.17 nominal size (DN). A numerical designation o f size bearing in mind that fittings of the less ductile materiais
which is common t o all components i n a piping system are more likely t o fail under shock conditions.
other than components designated by outside diameter or (a) Cast carbon steel t o BS 1504-161, grade 480.
by thread size. I t i s a convenient round number for NOTE. This material has a maximum carbon content of 0.30 %.
reference purposes and i s only loosely related t o For valves with butt welded ends less than 3 5 mm thick and
manufacturing dimensions. intended for welding into pipelines subject to the requirements
of BS 2633, the carbon content should be 0.25 % maximum.
2.18 overpressure of the safety valve. A pressure increase Alternatively, the material may be specified as BS 1504-161,
over the set pressure of a safety valve, usually expressed as grade 430.
a percentage of set pressure. (b) Cast carbon % % molybdenum steel t o BS 1504-245.
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document
3
Policy Group at 303-397-2295.
~ ~ ~
~
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
i BS6759 : Part 1': 1984
( c ) Cast 1 % %chromium H % molybdenum steel to forged austenitic chromium nickel steel and forged austen-
BS 1504-621. itic chromium nickel molybdenum steel (m) shall not be
(dJCast 2% %chromium 1 % molybdenum steel to used a t temperatures above 700 "C.
BS 1504-622. NOTE. At temperatures above 680 " C i t IS generally accepted that
the rate of oxidation or chemical attack begins to be important.
( e ) Cast austenitic chromium nickel steel to BS 1504-
347017, or cast austenitic chromium nickel molybdenum
steel to BS 1504-316C16. 4. Body seat faces and valve disk faces
( f ) Forged carbon steel to BS 970 : Part 1,070M20. Body seat faces and valve disk faces shall be made from
(9) Forged carbon steel to BS 1503 221-430. corrosion and erosion resistant material.
(h 1 Forged carbon h ' % molybdenum steel to BS 1503
245-420. 5. Safety valve springs
(i) Forged 1 % chromium % % molybdenum steel to 5.1 Helical coil
BS 1503 620-440. 5.1.1 Material. Helical coil springs shall be made from
( i ) Forged 1% % chromium X %molybdenum steel to circular section material complying with the requirements
BS 1503 621-460. of one of the British Standards given in table 1. Table 1
(k) Forged 2% %chromium 1 %molybdenum steel to also gives the temperature limits between which springs of
BS 1503 622-560. the various materials shall be used.
NOTE. Recommended limiting sections for materials are also
(IJ Forged chromium molybdenum vanadium steel to given in table 1.
BS 1503 660-460.
5.1.2 Condition of material. Bars or wires used i n the
(m) Forged austenitic chromium nickel steel to
unmachined condition shall be in accordance with the i
BS 1503 321851-490 or BS 1503 34Ts51 or, forged
relevant British Standard. Where the relevant standard
austenitic chromium nickel molybdenum steel to
does not specify the maximum depth of surface defects
BS 1503 316851.
and decarburization, the surface defects shall be limited to
(n) Cast iron with minimum mechanical properties equal 1 % o f bar diameter or 0.25 mm whichever i s the greater,
to those specified in BS 1452 grade 220. and decarburization shall be limited t o 2 % of bar diameter
(o) Cast copper alloy with minimum mechanical or 0.30 mm whichever is the greater. No more than one-
properties equal to those specified in BS 1400 for LG 2. third of the total affected depth shall be complete
(p) Other material having properties at least equal to decarburization.
those of the material to which i t i s an intended When bars are machined, prior to hot or cold coiling into
alternative, subject to the limitations given in 3.2 and to helical springs, they shall be free from all surface defects,
agreement between the manufacturer and the purchaser, there shall be no complete decarburization and partial
W
W
such agreement being approved by the inspecting decarburization shall not exceed 0.13 mm in depth.
authority.
5.2 Torsion bar. Torsion bar springs shall be made from
3.2 Pressure and/or temperature limitations steel which has a tensile yield stress not less than
3.2.1 Cast iron. Cast iron shall not be used for the 1350 N/mm2.
f o1lowing: When selecting the material from which the spring i s
l a ) temperatures above 220 OC; manufactured, due account shall be taken of the additional
(b) pressures exceeding 13 bar gauge; deflection and hence increased stresses which apply when
(c) valves exceeding 200 mm nominal bore which are the valve is fully lifted.
connected directly to the boiler.
6. Bolting for pressure containing joints
3.2.2 Cast copper alloy. Cast copper alloy shall not be
used for temperatures above 260 O C . The dimensions and finish of bolting shall comply with the
following British Standards as appropriate.
3.2.3 Steel
Metric Inch
3.2.3.1 There are no pressure limitations on steel.
Temperature limitations are given in 3.2.3.2 to 3.2.3.7 BS 3692 BS 1768 (below 'A in)
where the letters in parentheses refer to items listed in 3.1. BS 4190 BS 1769
3.2.3.2 Cast carbon steel (a) and forged carbon steel ( f ) BS 4439 BS 2693 : Part 1
and (9) shall not be used a t temperatures above 480 O C . BS 4882 BS 2708
BS 4882
3.2.3.3 Cast carbon molybdenum steel (b) and forged
carbon molybdenum steel (h) shall not be used a t
temperatures above 540 O C .
Section three. Design and construction
3.2.3.4 Cast chromium molybdenum steel (c) and forged
chromium molybdenum steel (i)shall not be used a t 7. General
temperatures above 565 'C.
7.1 Design lift. For safety valves that have a discharge area
3.2.3.5 Cast chromium molybdenum steel (d) and forged which is less than 80 % of the flow area, the overpressure a t
chromium molybdenum steel (j) and (k) shall not be used which the design l i f t i s attained shall not exceed 1 O % of the
a t temperatures above 580 OC. set pressure.
3.2.3.6 Forged chromium molybdenum vanadium steel (I 1 For safety valves that have a discharge area which i s 80 %
shall not be used a t temperatures above 580 "C. or more of the flow area, t h e overpressurea t which the
3.23.7 Cast austenitic chromium nickel steel and cast design l i f t is attained shall not exceed 5 % of the set
austenitic chromium nickel molybdenum steel (e) and pressure.
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 4 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
BSI BSub759: P A R T u 1 O2 W 1624669 0 4 5 3 5 9 9 823
7.2 Bore. The bore of the body seat of each safety valve Calculations of scantlings shall be based on the design
connected directly to a boiler shall be not less than 20 mm. pressure as defined in BS 806 and BS 2790 or, the
The minimum area of t h e inlet connection of the safety calculation pressure as defined in BS 1113, as appropriate.
valve shall be not less than the minimum area of the body End connections shall comply with one of the following
seat or, in the case of double safety valves, it shall be not standards:
less than the sum of the minimum areas of the body seats. ( a ) flanges with BS 1560 : Part 2 or BS 4504;
7.3 Discharge. Safety valves shall be so constructed t h a t (b) screwed connections with BS 21 ;
breakage of any part or failure of any device will not (c) weld preparation with an appropriate standard
obstruct free and full discharge through the safety valves. which has t h e approval of the inspecting authority
In the particular case of pilot operated safety valves,
a t least two independent pilot device systems shall be 9. Castings
provided for each main safety valve. The two systems shall All castings shall be smooth, sound, and free from cracks,
be connected individually and arranged such that failure of significant flaws or other injurious defect. Variations in
any one pilot device system shall not prejudice the correct thickness shall be gradual, and substantial fillets shall be
functioning of t h e other system in controlling the main provided.
safety valve.
The welding of cast steel pressure containing components
7.4 Moving parts. The valve disks and spindles: shall be in accordance with the procedures laid down in
( a ) shall be guided efficiently, and BS 4570 : Part 1, cognizance being taken of the require-
(b) shall h a v e sufficient clearance to ensure freedom of ments of clauses 18 and 19 of BS 1504 : 1976 dealing with
movement under all conditions of service, and rectification of castings and freedom from defects,
(c) shall be prevented from lifting out of their seats. respectively.
Spindles shall not b e fitted with stuffing boxes. The welding of cast iron or copper alloy pressure
containing components i s prohibited.
7.5 Body seats. Body seat faces shall be either:
( a ) flat and a t right angles to the axis of the body seat; or 10. Forgings
(b) tapered, provided the included angle of the taper i s All forgings shall comply with BS 1503.
not less than 90".
Seats, other than those of integral design, shall be secured
11. Springs
effectively.
11.1 Helical coil
7.6 Prevention of alteration t o the set pressure. All safety
valves shall be sealed by the manufacturer, his representative 11.1.1 General. The spring manufacturer shall be in a
or a responsible authority. Unauthorized interference with position, if so requested, to supply a certificate stating
the load on the spring, after the safety valve has been that the spring or springs have been made from the
adjusted, shall be prevented by: prescribed material, and have been tested in accordance
with the requirements of this British Standard.
( a ) the fitting of a ferrule under the adjusting screw
collar, or 11.1.2 Dimensions. The proportion of unloaded length to
(b) the fitting of a compression ring under the adjusting external diameter of the spring shall not exceed 4 to 1.
screw collar, or 11.1.3 Srress. The shear stress, q, shall not exceed the value
( c ) the locking of the adjusting screw. for that particular material given in column 4 of table 1,
NOTE. Alternations should only be made w i t h the authority of the
subject to the maximum shear stress when the spring i s
manufacturer and/or the inspecting authority. compressed coil to coil not exceeding the value given in
column 5 of that table for the same material.
7.7 Easing gear. Safety valves shall be so arranged that,
when they are under normal working pressure, the q shall be determined from the following equation.
mechanical load on the valve head can be eased by means 8 WDKA
of suitable gear. g= ___
II d3
7.8 Gagging device. When a gagging device is provided, where
due account shall be taken of the suitability of the valve
q is the shear stress (in N/mm2);
spindle to accept additional compressive loading arising
from i t s use. W is the force a t set pressure (in N);
D is the mean diameter of the coil (in mm);
8. Scantlings d i s the diameter of the section (in mm);
The design of a safety valve body shall be such that the K is the safety valve spring correction factor (see
safety valve body i s sufficiently robust to withstand figure 2)
reaction loads which will be imposed in service. D/d + 0.2
-
Steel valves manufactured in accordance with this Part of D/d- 1 '
BS 6759 shall only be deemed t o comply with this Part of
BS 6759 if the design strength value does not exceed that
given in table 2.3 of BS 5500 : 1982. Valves shall be (2)
designed for a life of 150 O00 h except when contractual where
requirements, approved by the inspecting authority, specify
6, is the axial deflection due to force W (in mm);
a different design life.
ô2 is the l i f t (in mm) of the valve a t certified discharge
capacity.
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 5
01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
BSI BSUb759: PART*L O2 = Lb24bbï 0453b00 375
* For springs made from wire o f up to and including 5 mrn diameter, where satisfactory operation and repeatabiiitv of set pressure can be
confirmed during safety valve operational characteristics tests using steam, it i s permissible t o design the spring so that the shear stress q,
calculated from equation (11 does not exceed 38 % o f the minimum ultimate tensile strength, and the maximum shear stress, spring coil t o
coil, does not exceed 60 % o f the minimum ultimate tensile strength.
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 6 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
i
BS 6759 : Part 1 : 1984
11
I .
D/d + 0.2
Constant K =
D/d- 1
10
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
11 1.2 1.3 1-5 1.5 1.6 1.7
Constant K
Figure 2. Graph for value of constant K, the safety valve spring correction factor
(see 11.1.3)
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
BSI BS*b759: P A R T * 1 O2 1624669 OY53602 1118
BS6759 : Part 1 : 1984
NOTE. Attention ¡<drawn to the need to control the chloride specified in 15.1 and the discharae size. I
min min
Up t o and including 50 2 3
over 50 up to and including 65 2 2 4
over 65 up to and including 80 2 3 4
over 80 up to and including 100 2 4 5
over 100 up to and including 125 2 4 6
over 125 up to and including 150 2 5 7
over 150 up to and including 200 3 5 9
over 200 up to and including 250 3 6 11
over 250 up to and including 300 4 7 13
over 300 up to and including 350 4 8 15
over 350 up to and including 400 4 9 17
over 400 up to and including 450 4 9 19
over 450 up to and including 500 5 10 22
over 500 up to and including 600 5 12 24
Nominal valve sizes larger than DN 600 shall have testing times pro rata.
t Marking ES 6759 : Part 1 : 1984 on or in relation to a product is a claim by the manufacturer that the product has been manufactured
to the requirements of the standard. The accuracy of such a claim IS therefore solely the manufacturer's responsibility. Enquiries as to the
availability of third party certification to support such claims should te addressed to the Director, Quality Assurance Division, BSI,
Maylands Avenue. Hemel Hempstead, Herts HP2 4SQ for certification marks administered by ES1 or to the appropriate authority for
other certification marks.
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 8 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
B S I BSUb759: PARTUL O2 Lb24669 0453603 084
BS 6759 : Part 1 : 1984
To this end the following information shall be Supplied to
the independent authority, and shall be approved before
testing is undertaken:
(d) the manufacturer's type reference. ( a ) full particulars of the valves to be tested and the
(e) the derated coefficient of discharge or certified -range of valves and springs which they represent;
discharge capacity (stating units) indicating the reference (b) details of the t e s t rig(s) including proposed
fluid: G for gas, S for steam and L for liquid instrumentation test and calibration procedure;
NOTE. The designation letter may be placed either before or ( c ) the proposed source, capacity, pressure, temperature
after the derated coefficient of discharge or certif ed discharge
capacity, e.g. G4.815 or G-100 O00 k g h . and properties of the t e s t fluid(s).
( f ) the flow area in square millimetres; 18.5 Results calculated from t e s t The theoretical flowing
(g) the minimum lift, in millimetres, and corresponding
capacity shall be calculated (see 21.2,21.3 or 21.4) and,
overpressure expressed as a percentage of set pressure; using this value together with the actual flowing capacity a t
relieving pressure, the coefficient of discharge of the safety
(h) the design life, if other than 150 O00 h.
valve shall be calculated (see 21.1).
NOTE. A manufacturer, having complied with the requirements of
clauses 16 and 17, is not precluded from marking any item
additionally in a place other than that specified, e.g. if a marking is
required to appear on the body it may also be repeated on an
identification plate.
Additional markings may be used at the option of the manufacturer,
19. Tests to determine operating characteristics 2
19.1 Carrying out the tests. The set pressure at
which the opening characteristics are determined
A
e.g. a serial number or catalogue number, providing they do not shall be the minimum set pressure for which the
conflict with any of the specified markings. spring is used. Valves designed to discharge steam
or hot water a t or above 100 "C shall be tested on
Section six. Performance testing dry saturated steam. Valves designed to discharge
water a t below 100 'C shall be tested on water.
18. Type testing of safety valves for operating and The allowable tolerances or limits as applicable, on
these characteristics are as follows:
flow characteristics using water, steam, air or other
(a) Set pressure (applicable to steam and water valves) :
gas below 5bar f 0.14 bar
18.1 General 5 bar up to 20 bar 3% *
18.1.1 Application. This clause applies to the types of 20 bar up to 100 bar t2%
safety valves defined i n 2.1. 100 bar and above Il%%
18.1.2 Carrying out of tem. The tests to determine the (b) Lift (applicable to steam and water valves);
f 5 % of the average for a given size of valve.
operating characteristics shall be in accordance with
clause 19 and the tests to determine the flow characteristics
shall be in accordance with clause 20.
c) Adjustable blowdown (valves for steam and
water a t or above 100 "C):
2.5 % of set pressure, minimum; 5 % of set pressure,
i-
When these tests are carried out separately, the parts of the
maximum, except for valves:
valve which influence fluid flow shall be complete and
installed in the valve. (1) of the high discharge capacity type designed
specifically for blowdown of up to 10 % o f set
All testing shall be witnessed by a representative(s)of t h e
pressure;
independent authority or authorities.
(2) having values of set pressure less than 3.0 bar
18.2 Testing facilities. Type testing in accordance with the when t h e blowdown shall be a maximum of 0.3 bar
requirements of this clause shall only be carried out a t
d) Non-adjustable blowdown (valves for steam ,'.
establishments approved by the independent authority or
and water a t or above 100 T):maximum 15 7d-
authorities'.
of set pressure.
18.3 Object of tests. The object of the tests is to
e) Non-adjustable blowdown (water valves
.
determine, under specific operating conditions, particular
Characteristics of the valves before opening, while below 100 "C):
minimum 2.5 %of set pressure: maximum 20 % of set
1-
I
-
,
!
BS 6759 : Part 1 : 1984
When the rangeis e x t m d e d SO that the PreviouSlY tested In those cases where the size o f the valve is greater than can
safety valves are no longer representative of t h e range, be tested at the test facility, the independent agthority shall, d ~'
further tests shall be carried out. at i t s discretion, subject to feasibility and opportunity,
19.4 Test procedure. The tests shall be carried O u t using require one confirmatory flow test at the location of the
three significantly different springs for each size of valve. installation and require the proper function o f a t least one
Where three test pressures are required from one valve size, valve of the design to be demonstrated by test.
it is permissible to test either one valve with three NOTE. Three geometrically similar models of different sizes may be
significantly different springs or three valves of t h e same used to detemine the coefficient of discharge.
size a t three significantly different settings in order to 203.2 Test techniques. The test techniques adopted shall
comply with the requirements. Each test shall be carried be either of the following.
out a minimum of three times in order to establish and (a) The valve configuration shall be the same as that
confirm acceptable reproducibility of performance. used during the tests for operational characteristics;
For the case of valves of either novel or special design, ¡.e. the lift and, if a blowdown ring(s) is fitted, i t s
of w h i c h one size only a t one pressure rating is being posityonshall be the one(s) established for the
manufacnired, tests a t t h a t set pressure shall be carried out. particular size and overpressure during operational
F o r t h e case of valves of which one size only a t various testing.
pressure ratings is being manufactured, tests shall be carried Average values of lift shall be used h e n the tolerances
out using four different Springs which shall cover the range of 19.1 have been met. Attention is also drawn to the
of pressure for which t h e valve shall be used. requirements of 20.4.
or
(b) Thei.alve configuration shall be varied in respect of
20. Tests to detemine flow characteristics lift and/or the position of blowdown ring(s) where such
20.1 Carrying out of t e s e is fitted.
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
20.1-1safety valves for steam or water at or aboue NOTE. Technique (a) i s used where it is desired t o &rive from thi.
100 "c.After operational Characteristics have been test results the coefficient of discharge of a given configuration of
established satisfactorily using steam as the test safety value at a given overpressure.
fluid, it is acceptable to use steam, air or another Technique (b) i s used where i t i s desired to derive from test results,
usually plotted as a series of curves, the appropriate coefficient of
gas of known charack.istics as the fluid for flow discharge of a safety valve for various combinations of overpressure,
characteristics tests. When discharged quantities lift and the position of blowdown ring(s).
are being assessed using fluids other than steam,
20.3.3 T e a on valves of novel or spacial design. In the
the be at the
of valves of either novel or specid designof hi&, one
same li' as that Obtained with at the size only for various pressures i s being manufactured, tests
m
' g overpressure. shall be carried o u t at four different set pressures which
20.1.2 Safety ualues for water below 100 "C.After
operational ha\le been satisfactorily shall cover the range of pressure for which the valve will be
used or as determined by the limits of the test facility.
established using water as the test fluid it is The discharge capacities as determined by these four tests
acceptable to use water or other liquid of shall be plotted against the absolute inlet pressure, and a
viscosity for flow characteristics tests. f ' * straight line drawn through these four points and zero-zero.
20.1.3 General. It iS NÖT-permissible to use t!-L?> For liquids, the capacities as determined h e four tests
. ' steam, air Or other gas for the flow characteristics shall be plotted on log-log paper against the differential
'
testing of a water Safety valve b l o w loo "c,nor (inlet pressure minus back pressure) test pressure, and a 1
water or any other liquid for the flow straight line drawn through these four points. If all point%
characteristics testing Of a Safety valve for steam do not lie within +- 5 % of t h i s line, additional testing shall
or water at or above 100 "C. be carried out until the line is established without
20.2 Valves used in t h e test programme ambiguity.
20.2.1 Representative valves. The safety valves tested shall 20-3.4 Test In all methods described for flow
be representative of the design, pressure and size range of characteristics testing, all final results shall be within f 5 %
valves for which flow characteristics are required. of the average, or additional testing shall be carried out
until this criterion i s met.
20.2.2 Size range and number of valves to be tested. Tests
shall be carried out on three sizes unless the size range Where test technique (b) of 20.3.2 has been adopted,
contains not m o r e t h a n six sizes, when . t i s pemissible to the results obtained shall be plotted as curves to obtain the
reduce the number tested to two. When the range is unique value of discharge capacity of a valve a t a given
extended f r o m a number less than seven to a number equal overpressure and which has the b b v d o w n ring(s) a t a
to or in excess of seven, then tests on three sizes of valves given setting-
shall be carried out. 20.4 Adjustments during t e s t No adjustment to the valve
When the range is extended o that the previously tested shall be made during the test. Following any change o r
safety valves are no longer representative o f the range, deviation of the test conditions, a sufficient period of time
further tests shall be carried out. shall be allowed to permit the rate of flow, temperature
N O T E . If the size range comprises one only, see 2Q3.3. and pressure to reach stable conditions before readings
are taken.
20.3 Test procedure
20.3.1 Tests on each valve. On each of the valves to be 20.5 Recotds of tests. The test records shall include all
tested, as required by 20.2.2, flow characteristics tests for observations, measurements, instrument readings and
the determination of the coefficient of discharge shall be
.carried out at three different pressures.
In a l l cases t h e size a n d pressure range shall be represent-
ative of the design range within t h e limits of the testing
f acil ity .
Copyright British Standards Institution 10 Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
,.
BS 6759 : Part 1 : 1984
instrument calibration records for the objective(s) of the p is the actual flowing (inlet) pressure, {(set pressure x
test. Original t e s t records shall remain in the custody of ~~ 1.1) + 1 } (in bar absolute).
the test establishment which conducted the test. Copies of NOTE. It has been appreciated for many years that there is a
all test records shall be furnished to each of the parties significant divergence between the maximum isentropic steam flow
concerned with the test. Corrections and corrected values and Napier flow at pressures above 110 bar such that at 221 bar
the divergenceapproaches 18 %. To rectify this significant
shall be entered separately in the test record. undentatement of capacity with increasing pressure, a correction
20.6 Flow test equipment. The test equipment shall be factor is included in equation ( 8 ) .
designed and operated in such a way that the actual test 21.3 Theoretical flowing (discharge)capacity using air or
flowing capacity measurement shall be accurate to within any gas as the test medium
f 2 %.
21.3.1 Critical and subcritical flow
20.7 Coefficient of discharge. The coefficient of discharge
NOTE. The flow of gas or vapour through an orifice increases as the
shall be determined as specified in clause 21. downstream pressure is decreased until critical flow is achieved.
20.8 Certification of valves. The certified discharge Further decrease of the downstream pressure does not result in any
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
capacity of the valve shall be 0.9 of the capacity determined further increase of flow.
by test. For valves using the coefficient of discharge Critical flow occurs when:
method, the certified discharge capacity shall be 0.9 of
the theoretical capacity times the coefficient of discharge
(¡.e. the derated coefficient of discharge).
The coefficient of discharge shall not be used to calculate
the capacity a t a lower overpressure than that a t which tne Sub-critical flow occurs when:
test was carried out (see 20.3) although it can be used to
calculate the capacity a t a higher overpressure.
The actual capacity for a back pressure above the test back 2 is greater than
pressure condition and/or for subcritical flow shall only be P
established by test. where the validity of Rankine’s law is assumed and
NOTE. Valves having a certified coefficient of discharge established where
on critical flow a t the test back pressure may not have the same
coefficient of discharge at a higher back pressure. Calculations for
p is the actual relieving pressure { (set pressure x 1.1 )
equivalent capacities for subcritical flow will result in a theoretical
+ 1 ](in bar absolute);
capacity equivalence only. p b is the back pressure (in bar absolute);
k is the isentropic coefficient a t the relieving inlet
21. Determination of coefficient of discharge and conditions (for a perfect gas k is taken as the ratio
certified discharge capacity of specific heats).
21.1 Coefficient of discharge. The coefficient of discharge, 21.3.2 Theoretical flowing (discharge) capacity at critical
K d , shall be calculated from the following equation: fiow. Where the validity of Rankine’s law i s assumed, the
actual flowing capacity theoretical flowing (discharge)capacity, q m ,a t critical flow
(from test) shall be calculated from the following equation.
Kd = (5)
theoretical flowing capacity
(from calculation)
The derated coefficient of discharge, Kd,, shall be
calculated from t h e following equation: = 0.2883 C@ V
Kd, = Kd X 0.9 (6)
where
21.2 Theoretical flowing (discharge)capacity using dry
saturated steam as t h e test medium. Dry saturated steam qm i s the theoretical flowing capacity (in kg/h per mm2
in this context means steam with a minimum dryness of flow area);
fraction of 0.98 or a maximum degree of superheat of 10 “C. C is a function of the isentropic coefficient k
For applicationswhere the value o f p is up to and including (for rounded figures see table 3 )
110 bar: (k + l ) / ( k - 1 )
= 3 . 9 4 8 4 (k+)
qm =0.525p (7)
For applicationswhere the value of p is over 110 bar and
p i s the actual relieving pressure (in bar absolute);
up to 220 bar:
v i s the specific volume a t the actual relieving pressure
2.7644~- 1000 and relieving temperature (in m’/kg);
qm = 0.525~
3 . 3 2 4 2 ~- 1061 M is themolecular mass of the gas (in kg/kmol);
where T i s theabsolute temperature a t the inlet (in K);
q m is the theoretical flowing capacity of dry saturated Z is thecompressibility factor. In many cases it i s
steam (in kg/h per mm’ of flow area); unity and may be neglected. (See figure 3.)
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document
11
Policy Group at 303-397-2295.
fi
BS 6759 : Part 1 : 1984
k C k C k C k C 4. C k C
-
0.40 1.65 0.84 2.24 1.02 2.41 1.22 2.58 1.42 2.72 1.62 2.m
0.45 1.73 0.86 2.26 1.04 2.43 1.24 2.59 1.44 2.73 1.64 2.85
0.50 1.81 0.88 2.28 1.06 2.45 1.26 2.61 1.46 2.74 1.66 2.86
0.55 1.89 0.90 2.30 1.08 2.46 1.28 2.62 1.48 2.76 1.68 2.87
O 60 1.96 0.92 2.32 1.10 2.48 1.30 2.63 1.50 2.77 1.70 2.89
0.65 2 .o2 0.94 2.34 1.12 2.50 1.32 2.65 1.52 2.78 1.80 2.94
O 70 2 .O8 0.96 2.36 1.14 2.51 1.34 2.66 1.54 2.79 1.90 2.99
o 75 2.14 0.98 2.38 116 2.53 1.36 2.68 1.56 2 80 2.o0 3.04
O 80 2.20 0.99 2.39 1.18 2.55 1.38 2.69 1.58 2.82 2.10 3.09
0.82 2.22 1.o01 2.40 1.20 2.56 1.40 2.70 1.60 2.83 2.20 3.13
-
1.5
1.4
1 3
1.2
11
1.c
O.9
O.8
0 7
06
O. 5
O. 4
0 3
02
o 1
O
o. 1 O2 0.3 0.4 0.5 1 2 3 4 5 10 20 30
Reduced pressure Pr = PIP,
pr = PIP, where
Tr = TITc p i s the actual relieving pressure (in bar, absolute);
T is the relieving temperature (in K);
pc is the critical pressure of the pure gas {in bar absolute);
T, i s the critical temperature of the puregas (in KI.
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 12 01:53:16 MST Questions or comments about this message: please call the Document
i Policy Group at 303-397-2295.
BSI BS*b759: PART*<L O2 L b 2 4 b b ï 0453607 72T
21.3.3 Theoretical flowing (discharge)capacity at For applications where the value of p is over 110 bar and
sub-critical flow. The theoretical flowing (discharge) up to 220 bar:
capacity, q m ,a t sub-critical flow shall be calculated
from the following equation.
-
E = 0.525 p
2.7644 p
3.3242 p - 1061
- 1 O00
) AKdr (1 5)
q m =pCKb\ zr
IV
(11) where
E is the certified discharge capacity of dry saturated
steam (in kg/h);
p is the actual relieving pressure {(set pressure x 1 . l ) + 1 i
(in bar, absolute);
A i s the flow area (in mm2);
Kdr is the derated coefficient of discharge (see equation
";i
(6)).
> I i
00000000000000
m m m o m m o m m o m a l r - o
z i I
m w m o b m o m o u a w o o
m m m m w m w b r - c D m u o o
00000000000000
C
O l
4
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
p:
O
* /I
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
!I
8
I
il
c
m
a
O
ln
m n
o
n
O
o
O
CI
c
O
L
O.
21
d
O
'"
O
'0
O
c
L
L
E
O
r'
?!
O
o
8
O
<D
n
m
O
0
5
z
rn
O
c
m
O
I
8
a
O
,Ii!:
I C
I C
I
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
1
I
'E
-
I < .
i:
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
BS 6759 : Part 1 : 1984
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
22. Boilers and superheaters 23. Reheaters and superheaters separated from
In n o case shall a steam boiler with an evaporation rate of the boiler
more than 3700 kg/h or a hot water boiler with a rating of Reheaters, and superheaters separated f r o m t h e boiler by
more than 2350 k W be fitted with less than two single an intervening stop valve, shall be f i t t e d with appropriate
safety valves or one double safety valve. A t least one safety safety valves. These safety valves shall n o t be considered
valve shall be fitted on the outlet side of the superheater, as p a r t of the safety valve complement of the boiler.
where fitted, and can be considered a part of the safety
valve complement of the boiler provided t h a t there is n o 24. Safety valves for economizers
intervening stop valve between the boiler and the Economizers, except those directly connected to the boiler
superheater. without an intervening stop valve, shall be f i t t e d with a t
The discharge capacity,p, o f any safety valve on the least one safety valve. Whenever practicable, only safety
superheater o r boiler shall be calculated in accordance valves o f inlet size DN 50 shall be used. The set pressure
with 21 3 . 2 and 21.5.4 f r o m the equation: shall not exceed the maximum permissible working pressure
p=l.lp’+l o f the economizer.
wherep‘ is the highest s e t pressure (in bar gauge) of the
boiler safety valves. 25. Operational margins
NOTE. p’ should not exceed the boiler design pressure. To prevent the unnecessary lifting o f the safety valves there
The total capacity of the superheater vaive(s) so calculated shall be an adequate margin between the actual pressure at
shall be not less than 20 % of the evaporative capacity of which the boiler generates and delivers steam and the
the boiler. lowest pressure a t which any of the safety valves are set
to lift.
Previous page
Copyright British Standards Institution
Reproduced by IHS under license with BSI - Uncontrolled Copy
17
Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
01:53:16 MST Questions or comments about this message: please call the Documentis blank
Policy Group at 303-397-2295.
BS 6759 : Part 1 : 1984
Publications referred to
BS 21 Pipe threads for t u b e s and fittings where pressure-tight joints are made on the threads
BS 759' Valves, gauges and other safety fittings for application to boilers a n d t o piping installations for and in connection with boilers
Part 1 Specification for valves, mountings and fittings
Part 2 Specification f o r safety valves (obsolescent)
BS 779 Cast iron boilers for central heating and indirect hot water supply (44 kW rating and above)
BS 806 Ferrous piping systems for and in connection with land boilers
BS 855 Specification f o r welded steel boilers f o r central heating and indirect h o t water supply (rated o u t w t 44 kW to 3 MW)
BS 970 Wrough steels in the f o r m of blooms, billets, bars and forgings
Part 1 Carbon and carbon manganese steels including free cutting steels
Part 5 Carbon and alloy spring steels f o r the manufacture o f hot-fonned springs
BS 11 13 Water-tube steam generating plant (including super-heaters, reheaters and steel tube economizers)
BS 1400 Copper alloy ingots and copper alloy castings
BS 1452 Specification for grey i r o n castings
BS 1503 Specification for steel forgings (including semi-finished forged products) for pressure purposes
BS 1504 Specification for steel castings for pressure purposes
BS 1560 Steel pipe flanges and flanged fittings (nominal sizes % in to 24 in) for the petroleum industry
Part 2 Metric dimensions
BS 1726 Guide to the design a n d specification of coil springs
Part 1 Helical compression springs
BS 1768 Unified precision hexagon bolts, screws and nuts (UNC and UNF threads). Normal series
BS 1769 Unified black hexagon b o l t s , screws and nuts (UNC and UNF thread). Heavy series
BS 2056 Rust, acid and heat resisting steel wire for springs
BS 2633 Class 1 arc welding of ferritic steel pipework f o r carrying fluids
BS 2693 Screwed studs
Part 1 General purpose studs
BS 2708 Unified black square and hexagon bolts, screws and nuts (UNC and UNF threads). Normal series
BS 2790 Specification f o r shell boilers o f welded construction
BS 2803 Prehardened and tempered carbon a n d l o w alloy round steel wire for springs for general engineering purposes
BS 3692 I S 0 metric precision hexagon bolts, screws and nuts
BS 4 0 8 0 Methods f o r non-destructive testing of steel castings
BS 4190 I S 0 metric black hexagon bolts, screws and nuts
BS 4439 Screwed studs for general purposes
BS 4504 Flanges and bolting for pipes,valves a n d fittings. Metric series
BS 4570 Fusion welding of steel castings
Part 1 Production, rectification and repair
BS 4882 Bolting f o r flanges and pressure containing purposes
BS 5216 Patented c o l d drawn carbon steel wire for mechanical springs
BS 5500 Unfired fusion welded pressure vessels
I S 0 4126' Safety valves, general requirements
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
For information about BSI services relating to third party certification to suitable British Standard product specifications, schemes
for the registration of firms of assessed capability, testing and inspectionfacilities, please contact the Director, Quality Assurance
Division, BSI, Maylands Avenue, HemelHempstead, H e m HP2 4SQ Tel. Hemel Hempstead31 11.
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
B S I BS*6759: PART*L O2 1624667 0 4 5 3 6 3 3 T23 W
Ix)
Amendments issued since Dubtication v)
I I
British Standards Institution . 2 Park Street London W1A 2BS . Telephone 01-629 9000 - Telex 266933 1
8509-7 -0.5k-B
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
~ ~~ ~~~
AMD 5493
Amendment No. 1
published and effective from 3 1 March 1987
to BS 6759 : Part 1 : 1984
Safety valves
Part 1. Specification for safety valves
for steam and hot water
Revised text
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
8703-O-1.5k-6
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document PYE112
Policy Group at 303-397-2295.
AMD 8272
Amendment No. 2
published and effective from 15 February 1995
to BS 6759 :Part 1 : 1984
Safety valves
Part 1. Specification for safety valves for steam and hot water
Revised text
In item (c) in the list, delete the first line and substitute the following.
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
‘cl Adjustable blowdown (valves for steam and
water a t or above 100 ’(2):’
Delete item (d) in the list entirely and substitute
the following:
‘d) Non-adjustable blowdown (valves for steam
and water a t or above 100 ‘(2): maximum 15 92
of set pressure.’
In item (e) in the list, delete the first line and substitute the following:
‘e) Non-adjustable blowdown (water valves
below 100 T I : ’
9502-2-0.6k-- DP PVEI12
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
Clause 20.1 Carrying out of tests
Delete the existing text entirely and substitute the following.
where
R is the rating of a safety valve (in kW)*;
P is the actual relieving pressure (in bar
absolute);
A is the flow area (mm2);
Kdr is the derated coefficient of discharge
determined in accordance with 21.1
(see equation 6).
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.
= 1ib24bb9 0453592 479
where
Q,, is the certified discharge capacity of water
below 100 "C (in kg/h);
A is the flow area (in mm2);
11 is the volumetric mass (in kg/m3);
AI' is the pressure drop (in bar), i.e. P - P,;
P is the actual flowing (inlet) pressure
((set pressure x 1.1)+ 1)(in bar absolute);
Pl, is the back pressure (in bar absolute);
Kdr is the derated coefficient of discharge
determined in accordance with 21.1
(see equation 6).
--`,,,,,`````,,``,``,,`,,,`,``,-`-`,,`,,`,`,,`---
3
Copyright British Standards Institution Document provided by IHS Licensee=Bureau Veritas/5959906001, 11/24/2004
Reproduced by IHS under license with BSI - Uncontrolled Copy 01:53:16 MST Questions or comments about this message: please call the Document
Policy Group at 303-397-2295.