Download as pdf or txt
Download as pdf or txt
You are on page 1of 79

 

NTPC LTD. 
 
TALCHER SUPER THERMAL POWER STATION 
 
Operation Documentation System 
DOC NO : TS ‐ II /OPN/OI/Gen/01 
 

Operating Instructions For  
Unit Absolute Cold  Start‐up. 
 

 
TSTPP , STAGE – II UNITS (4X500 MW) 
 
Compiled By Operation Support Group  
 
 
 
Rev 2.00                                                           Date : 1‐10‐2013 
 
 
 
 
 
 
Document Approval Sheet  
 
DOC NO : TS ‐ II /OPN/OI/Gen/002 
 
4X500 MW UNITS , Stage‐ II 
 
Date : 01‐10‐2013 
 
 
 

Prepared By  Sh R.N.Das, AGM(O)   

Reviewed By   Susanta Ghosh, AGM(O) I/C   

Approved By  Sh C .Chakraborty ,GM(O)   

 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

 
A.  PURPOSE:‐ 
This  document  is  prepared  to  guide  the  operating  personnel  while  carrying  out  the 
 
operations during absolute cold start up  of the unit. 
B  SCOPE:‐ 
  This shall be applicable to all  the 4 units  of Stage – II  (4X 500 MW units ) , TSTPS, NTPC Ltd. 
C.  Responsibility : ‐ 
Shift charge Engineer/Unit Controller/ Boiler Desk Engineer/ TG Desk Engineer.
 
Operation  Support  Group  
D.  Introduction :‐ 
Generally    the    start‐up    of  a  unit  is  classified    in  to  different  categories    based    on    unit 
conditions  i.e  the  condition of  boiler & turbine  parameters . 
Based on Turbine standards  

  Normally this type of start‐up is experienced after  prolonged outage of a unit or  after annual 
overhauling  where  the turbine components are at atmospheric temperatures . This  type of 
start‐ups are  very critical  as they are  subjected  to continuous heating  once the steam is 
admitted . Hence  due  care  is to  e taken at every step  while bringing back  the  unit  into 
Bar  .  This    instruction    will    guide    the    operating    personnel    in  through  checking    the  
auxiliaries / systems before they are  put into service  & subsequent  startup activities after 
BLU (Boiler Light Up) , TG set rolling  & synchronisation , Unit load raising & achieving  the  
full load  operation . 
Here  the  MS  &  HRH    supply  steam  temp    should  be  raised  gradually    &  turbine  adequate 
soaking at  360 RPM & 3000 RPM to be ensured  before  loading  the  unit . The rate of  rise of 
MS/HRH temp   depends  on  the  quantum  of  firing  & HP bypass flow . The rate of steam 
temp rise can be 2 0 C /Min  as suggested  by BHEL start‐up curves .  
As  per  the  combined  start‐up curves given by  BHEL , the  start‐up times   for  various start‐
up  are  as follow . 

Prepared By  Reviewed By Approved  By   Sheet 1 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

DETAILS OF UNIT STARTUP PARAMETERS. 
Stage ‐ I  & Stage ‐ II  Units  
Sl  Stage ‐ I  Units  Stage‐ II Units 
Parameters  
No  Cold Warm Hot  Cold  Warm Hot 
Startup Criteria  
AA  < 160  0C  >240 < 430 0C  > 430 0C  > 48 Hrs  0‐48 hrs  < 8 Hrs 
(Mean Rotor Temp ) 
BLU  to HP/LP bypass 
1.   10 min  10 min  10 min  50 min  20min  5min 
charging  
1:20Hrs 1:15Hrs 2:05Hrs  1:25 Hrs
2.   BLU  to  Rolling Parameters   35 min  35 min 
80 min  75  min  125 min  85 min 
TG set  Rolling  Time i.e  up 
3.   50 min  17 min  07 min  45 min  6‐7  min  6‐7  min 
to 3000 RPM 
2:15 hrs 1:40 min 2:50 Hrs  1:35 Hrs
4.   BLU  to synchronization   36 min  50 min  
135 min  100 min  170 min  95  min 
Synchronization to Full Load   2:05 Hrs 1:20 Hrs 3:50 Hrs  3:20 Hrs
5.   30 Min  30  min 
Operation   125 min  80 Min  230 Min  200 Min 
6:40 Hrs  5:00 Hrs 1:20 Hrs
6.   BLU  to Full Load   4:20 hrs  3:00 Hrs  1:10 Hrs 
400 Min  300 Min  80 Min  
Starting  of Rolling To Full 
7.   189 min  110 min  12 min       
Load  (As per Turbine ) 
BB  At  the  time  of Charging HP/LP  Bypass
8.   Boiler  Pressure  0.0 ksc 0.0ksc 75.0ksc 8‐10 ksc  8‐10 ksc 75.0 ksc
CC  At  the  time  of Rolling  
9.   Total Firing   18 % 20 % 40 % 30 %  35 % 40 %
10.   Steam Flow   17% 20% 38 % 400 t/hr  500 t/hr 600 t/hr
11.   MS Pressure in ksc   85 85 100 65  80  100
12.   HRH pressure in ksc  12 12 22 12  12  22
0
13.   MS temp in   C  400 460 510 350  400  500
14.   HRH temp  0C  420 460 510 320  370  480
DD  Max Ramping  Rate     
Raise  in saturation temp  
15.   110  110  110  110  110  110 
(Max)  0C / Hr  
2.0 / 
16.   Boiler  Pressure  in Ksc /Min   1.0  1.13  4.5  2.0  3.0 
0.6 aft 65 
0
17.   MS  temp in  C/Min  5.0 5.0 5.0 3.0  2.5  2‐3
18.   HRH Temp  0C/Min  7.0 7.0 7.0 3.0  2.5  2‐3
19.   Turbine Metal  Temp   2.0 2.0 2.0 2.0  2.0  2.0
20 upto200
20.   Unit  Load  MW/Min  3.7  5.55  150  2.0  2.5 
12 above200 
0  0
EE  Max Cooling rate  Boiler   83  C / Hr  in sat  temp  83   C / Hr in sat  temp
FF  Max Cooling Turbine    5  0 C / Hr  in Turbine Temp  5  0 C / Hr in Turbine   temp
GG  Turbine  Metal Temp at  Full Load  
21.   HP  Rotor/Shaft  temp   498 0C 514 0C/5110C
22.   IP Rotor / Shaft  temp  478 0C 448 0C /4110C
HH  Total  Oil  Consumption   Targets  (  BLU  To Full Load )    
23.   Target    80 60 40 80  60 40

Prepared By  Reviewed By Approved  By   Sheet 2 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

 
 
 
  INDEX
 
Sl No  DESCRIPTION  Page No 
AA  Brief  Check list  for  various areas /systems    
1.0  OFF SITE AREAS :‐  5 
1.1.   CW  SYSTEM    5 
1.2.   CT  SYSTEM    5 
1.3.   Compressed air SYSTEM  ( SA/IA)  5 
1.4.   LDO/HFO  system    5 
1.5.   AC & VENTILATION SYSTEM    5 
2.0  BOILER SIDE CHECKS  6‐8 
2.1.   GENERAL checks   6 
2.2.   Boiler  DRAINS/VENTS  6 
2.3.   WATER AND STEAM CKT  6 
2.4.   BCW PUMPS  & AUXILIARIES   6 
2.5.   ECONOMISER  6 
2.6.   SH / RH SPRAY SYSTEM  6 
2.7.   ID FANS A/B .  7 
2.8.   FD /PA Fans .  7 
2.9.   All 4  APH  ( Secondary & Primary )  7 
2.10.   HFO/LDO  & atomising  SYSTEM   7 
2.11.   BURNER SYSTEM  7 
MILLING SYSTEM   8 
) Coal Feeding  to Bunkers   8 
2.12.  
) MILLS / Reject  Handling System   8 
) FEEDERS  .  8 
2.13.   ESP Pass A/B/C/D   8 
2.14.   BA HOPPER  / Settling Bin / Eco & Eco  Bypass Hopper Eva system   8 
2.15.   FA SYSTEM .  8 
3.0  TURBINE SIDE CHECKS.  9‐12 
3.1.   CW  SYSTEM / OLTC    9 
3.2.   ACW SYSTEM  WITH  SELF CLEANING STRAINER   9 
3.3.   DM makeup SYSTEM. (DM‐1)  9 
3.4.   Emergency Make Up  SYSTEM. ( DM ‐ 2 )  9 
3.5.   TG ECW SYSTEM  WITH PHE  9 
3.6.   SG ECW SYSTEM .WITH PHE   9 
3.7.   CONDENSATE SYSTEM.( CEP / Hotwell / Condensate )   10 

Prepared By  Reviewed By Approved  By   Sheet 3 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Sl No  DESCRIPTION  Page No 


3.8.   COND . EVACUATION  SYSTEM.  10 
3.9.   CPU  10 
3.10.   CHEMICAL DOSING SYSTEM.  11 
3.11.   DEARATOR.  10 
3.12.   MDBFP   11 
3.13.   TDBFP A/B  11 
3.14.   FEEW WATER HEATERS    LPH/ HPH’S  11 
3.15.   FW SYSTEM /FEED REGULATING STATION  ( FRS )  11 
3.16.   TG LUB OIL SYSTEM /JACKING OIL SYSTEM /BARRING GEAR   11 
3.17.   HYDRAULIC OIL SYSTEM ( Control Fluid System  )  12 
3.18.   GOVERNING SYSTEM .  12 
3.19.   HPBP SYSTEM   12 
3.20.   LP BP SYSTEM   12 
3.21.   SEAL OIL SYSTEM  12 
3.22.   H2/CO2 GAS  SYSTEM  13 
3.23.   STATOR WATER SYSTEM  13 
3.24.   MAIN  TURBINE  12 
3.25.   Turbine  DRAIN SYSTEM  to  UFT / SDFT / Flash box / ( LPFT/HPFT )   9 
3.26.   AUX. PRDS SYSTEM  LT / HT  ( From OWN system)  13 
3.27.   CONDENSER PIT DEWATERING  Pumps   13 
4.0  GENERATOR AND ELECTRICAL SYSTEMS  14 
4.1.   MAIN  GENERATOR  14 
4.2.   GCB  14 
4.3.   BUS DUCT PRESSURISATION SYSTEM  14 
4.4.   GT R/Y/B   14 
4.5.   UT A/B  14 
4.6.   400 kv system / EARTH  SWITCH / ISOLATOR  14 
4.7.   STATUS  OF MCC /SWGRS   14 
4.8.   DG SET  SYSTEM   MAIN  & STAND BY   14 
4.9.   BATTERY   CHARGERS   ( 220V DC / 24 V DC  system)  ,   14 
4.10.   UPS  14 
4.11.   CABLE GALLERIERS   14 
5.0  RECOMMISSIONING FINAL CHECKS & CLEARANCES   15‐18 
  Standard Unit Recommisioning heck list   15‐16 
  Cold start up check list   Before Light up  17‐18 
6.00  BOILER  LIGHT UP CLEARANCES  BY DEPARTMENTS .  19‐20 
7.00  Gist of  Recommissioning activities  BLU  to Synch   21 
BB  Check list cum procedure  for  Boiler Lightup (BLU) , TG set  Rolling , Synchronisation   

Prepared By  Reviewed By Approved  By   Sheet 4 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Sl No  DESCRIPTION  Page No 


, Full Load  Operation  . 
  AA  AVTIVITIES  IN BOILER SIDE  BEFORE  BLU     
  BB  ACTIVITIES  IN TG SIDE  BEFORE  BLU  .   
  CC  BOILER LIGHT UP  ACTIVITIES  ( B L U )   
  DD  ACTIVITIES  AFTER  BOILER LIGHT UP .   
  EE  CHECKS BEFORE TG SET  ROLLING TO 360  RPM   
  FF  RAISING THE  SPEED  TO  360 RPM (SOAKING SPEED  )IN NORMAL MODE   
ACTIVITIES BEFORE RAISING THE   SPEED  TO  3000 RPM  
  GG   
IN NORMAL MODE .  ( APPROX 4 ‐ 5  HRS) 
  HH  TG SET  ROLLING TO 3000  RPM ( RATED SPEED)   
  JJ  SYNCHRONISATION  OF THE  UNIT  ( AUTOMATIC ) /LOADING OF  THE UNIT .   
  KK  ACTIVITIES  AFTER  SYNCHRONISATION .     
CC   ANNEXURES :‐   
  ANNEXURE‐ 1 ( Gist  of Unit  Start‐up Activities )   
  ANNEXURE‐ 2 ( Oil gun  cut in –cut out monitoring format  )   
  ANNEXURE‐ 3 ( MCC/SWGR  supply checking status )   
  ANNEXURE‐ 4 ( Battery Chargers  checking status )   
  ANNEXURE‐ 5 ( Details  of Mulsifiers  system status )   
  ANNEXURE‐ 6 ( Turbovisory Parameters Monitoring Sheet)   
  ANNEXURE‐ 7 ( Boiler Important   Parameters Monitoring Sheet )   
  ANNEXURE‐ 8 ( Metal  Temp Parameters Monitoring Sheet)   
  ANNEXURE‐ 9 ( TG Auxiliary  Parameters Monitoring Sheet)   
  ANNEXURE‐10( Cooling Water system Parameters Monitoring Sheet)   
  ANNEXURE‐ 11( TG  drain  valves  status  & temp  Monitoring Sheet)   
ANNEXURE‐ 12 (Boiler Expansion Monitoring  Sheet   with design  
   
                            expansion  diagram ) 
ANNEXURE‐ 13( Saturation Temp at  various pressure &  
   
                            Different   Curves used  in TG  set  rolling ) 
  ANNEXURE‐ 14 ( Unit  Start up Curves  Cold/Warm/Hot )   
  ANNEXURE‐ 15 (Temp Margin Limit  &  Criteria Curves )      

Prepared By  Reviewed By Approved  By   Sheet 5 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

 
 
 

BLU , TG set  Rolling , 
Synchronisation , Full 
Load  Operation 

Prepared By  Reviewed By Approved  By   Sheet 6 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

AVTIVITIES  IN BOILER SIDE  BEFORE  BLU   
 
Checked 
ITEM  DESCRIPTION 
Status 
Boiler is filled up to normal level  with chemicals ,  all three CC Pumps   in service . BCW  Booster Pump  in 
1.    
service , Standby BP lined  up  . OH tank normal . master drain closed  
2.   Boiler water sample tested  by Chemist group & clearance  given .   

3.   All protections normalised  which were bypassed  during recommissioning .   
All Vents in drum ( 4  nos )  , SH, RH  are  open  . SH drains are  Open  with  final Manual Valve to IBD tank   in 
4.    
open position .  
Eco  recirculation  Valve    is  open  with  manual  valve    till  continuous  FW  flow    is  established    through  the  
5.    
Economiser  to Boiler  Drum . 
6.   CBD /EBD system   lined  up with  manual valves  open .   
Boiler stop valves are in closed condition & before stop valve drains ( MS 401/402) are open with  manual 
7.    
valves . Power supply Normalised  for all valves . 
8.   All ID/FD/PA  fans are  lined  up .   
All  4 APH ‘s are  in service .  Air  Motor  Available . Air pressure > 5.5 Ksc . Check  All damper  status .Ensure 
9.    
FG  Inlet  damper  power supply is isolated with damper   in  Open position . 
10.   Check all 4 passes of  ESP  are  lined  up  with their auxiliaries in service .   
Check BA /FA system are ready , BA Hopper/seal trough filled  with water . Refractory  Cooling charged . CG  
11.    
Power Supply  available . 
12.   Start one scanner fan. check  availability of DC Fan. Note down Pressure .   

13.   Start one pair of ID/FD Fans and ensure that other fans are not rotating in reverse,   

14.   Maintain air flow > 30% ( 720  T/hour),     
0
Keep both Sec. SCAPH in service, SCAPH Outlet temp may go up to 80 C . SCAPH drain  properly lined  up  to 
15.    
IBD tank  
16.   Put SADC  control in manual  to maintain a fixed furnace to wind box D P = 40 MMWC    
Charge fuel oil station & put the HFO system in long recirculation. Atomising steam lined  up  .Atmospheric 
17.    
drains are open in all 4 corners  of AB  elevation . Atomising air pr > 5.5 ksc  / steam pressure > 6.0 ksc  . 
18.   Ensure burner tilt is in horizontal position .   

19.   Ensure  Both TDBFP  or MDBFP  is  in service   ( Both   TDBFP  Rolled   >  1000 RPM )   

20.   Ensure all MFT  Conditions are  Reset  in MFT page ( all  3 channels )    

21.   Ensure all purge conditions are  satisfied.   

22.   Check Boiler is  ready for purge   has come  , Then Purge  the  Boiler for 5 minutes.   
Put  Oil guns on scavenging mode ,  check  for any steam leakage near  the  gun connection .  Ensure BMD 
23.    
person’s  availability . 
24.   Check HT PRDS  charged  , APH soot‐blowing steam charged .     

25.   SH /RH spray station also lined  up .   
 
 

Prepared By  Reviewed By Approved  By   Sheet 7 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

ACTIVITIES  IN TG SIDE  BEFORE  BLU  . 
 
Checked 
ITEM  DESCRIPTION 
Status 
1.   APRDS   HT /LT hdr  is charged  from   External source . Own source  is lined up    

2.   Check  CW  Pumps  in service & line  up  to CT  is  normal . 5+5  CT  Fans  in service .   

Check  2 ACW pumps are in service  3rd pump  available  as stand  by on Auto
3.   2 TG ECW  PHE  & one SG ECW PHE are   in service . One set ACW self cleaning strainer  in sevice.   
Other set stand  by  . 
Check 2 TG ECW pumps are  in‐service  &  DP control on auto . 3rd  Pump is  available  as stand  by 
4.    
on Auto . 

5.   1 SG ECW pump in service  &  DP control on auto . 3rd  Pump is  available  as stand  by on Auto   

Check MOT level  , Lub oil  system  , Jacking  oil  system  , TCV  , etc  . All  SLC  are  ON   , SGC oil  
6.    
system ON . No fault  in any drive /system . 
ASSOP  ,  H2S  SOP  are    in  service  &  Seal  oil  DP  Air  to  H2 side  both  T  E  &    EE  is  1.7  Ksc.  With  H2 
7.    
pressure  >3.3 ksc . 
Check TG  is  on  barring  ( one AOP,One JOP, one  VEF  are  in service ) Check Lub  oil temp. control 
8.    
valve in auto &  temp is maintained  at 45 0C . Check Lub oil /JO filters are  clean .  
Check CF pump in service  & Check  the  changeover  , TCV on auto ,  tank temp. is maintained  at 
9.   55 0C  . All  Valve  rack filters are  clean  & Rotate self cleaning  Gov Rack filters .  EHC  is  lined  up (   
Both isolating  valves are  open  . Check the Marking on valves ) 
Hotwell Makeup , Valve gland  seal Hdr , CEP  Gland  seal all are  lined  up & charged  condition .  
10.    
DM makeup pumps in service .  V/V gland  seal Hdr Pr = 
One  CEP  is    in  service    on  recirculation  after  filling  the  line  up  to  Deaerator.  If    D/A  level    is 
11.   increasing in spite of LCV being   fully close ,  then  close  the  isolating valves required to  maintain   
level  . 
Condenser  vacuum is pulled as per  standard  vacuum pulling  procedure . Ensure  the  vacuum 
12.   developed  is > 0.85 ksc  . ( If CRH/HRH atmospheric drains are kept open then  vac will  improved   
after  closing them) 
MD  BFP  is  in  service    on  recirculation  after  filling  the  line  up  to  Feed  regn.  Station,  Up  to 
13.    
Economiser  is filled & Vented .  Eco inlet  Valve  Open , select  the valve  in  maint  mode  

14.   Charge Deaerator through aux. steam. (Heating  steam)   

15.   Both TD BFP’s are on turning gear after charging feed water side ( 450 RPM)   

16.   Roll Both  TDBFP  from  Aux steam ( HT PRDS  300 0 C ) after  vacuum pulling  .   

Prepared By  Reviewed By Approved  By   Sheet 8 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
17.   Keep SH/RH  attemperation block valves closed & lined  up from all 3 BFP 's   

Turbine  side all  drains manual  valves are  open , All  UFT  drains are  open  initially  to flush the  
18.    
lines outside  & then  take them  in to  Condenser . 
Ensure  All  atmospheric  drains  connected  to  vacuum  system  are  closed.  Lines    to  condenser    are 
19.    
lined  up . 

20.   Check all coolers in TG side are  charged   from TG  ECW  side.   

• CEP  
• TG Lub oil ,  
• CF  Cooler ,  
  • TDBFP A/B Cooler  ,    
• H2 coolers ,Exciter coolers ; 
• Seal oil coolers ,  
• PW coolers . 
HP BP  OSU  are  healthy  . Warm up line valves   are  open (BP‐3 / BP‐4) . Spray kept isolated  from  
21.    
BFP  Discharge Hdr . to be  charged  afterwards  

22.   LP BP  warm up valves  are  open  , Spray  lined  up . Take 2nd CEP  into service & 3rd select on auto .   

23.   Check bearing chamber exhaust  fan is in service.   

24.   Check H2 pressure > 3.3 Ksc.  & H2 purity   > 98%.   

25.   Check  no of  tested  H2 / CO2  cylinder  available     

26.   Check  chemical dosing system  available ( Hydrazine , Ammonia , PO4)   

27.   Check SW system parameters , Alkalyser Unit  in service . All parameters .   

28.   GENERATOR is ready & Excitation system ready  , All GRP relays reset .   

29.   Inter Trip of the  Unit  Checked as per protocol format  .    

 
 
 
 
 
 
 

Prepared By  Reviewed By Approved  By   Sheet 9 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

BOILER LIGHT UP  ACTIVITIES  ( B L U ) 
 
Checked 
ITEM  DESCRIPTION 
Status 
1.   Inform  Fire  Station regarding BLU  .   
2.   Keep economizer‐recirculation valve open till there is no feed  flow through economizer.    
3.   Light  up  the boiler with  AB  elevation  4 guns   . Preferably LDO .   
Immediately start  SAPH Both Soot Blowing . Note down the  Steam Pressure . It should  be  8‐10 
4.    
ksc . Observe   the blower is rotating  . 
5.   After  30  Min  Cut in HFO guns at   CD  elevation   (  2  Guns)    
6.   After  45 min of BLU ,  Cut  in 2 more guns at CD elevation ( HFO) .     
7.   Cut out AB elevation  LDO  &  Take HFO in  AB elevation . ( 2 elevation HFO)    
8.   Start PAPH  Soot Blowing  . Put  soot blowers on continuous basis  with  the  help  of  Maint  persons .   
Check    through  Oil    Carry  Over  Probe  &  View    glasses  the      Condition  of  FG    &    The    APH  status  
9.    
respectively . 
10.   Maintain oil pressure  8 – 10 kg/cm2, atomising steam pressure 6 .5 kg/cm2.    
11.   Monitor  rate  of  BCW  suction manifold  temp Rise   , it should  not  exceed  100‐110 0/Hr   
12.   Keep one stream CBD lined up to maintain  the chemical parameters .    
13.   Keep EBD also lined  up . The valve  should operate on interlock  .   
Keep LP dozing system in service. HP dosing  system will  be  taken in to service  after  attaining  40 
14.    
ksc drum pressure . Sampling  will start at  40 KSC . 

  NOTE :        Rate of rise of drum metal temp.  1100c /Hr.    

15.   Take  additional guns after 30 minutes.  ( 2  guns  in EF  Elevation)   
0
16.   Monitor  the Boiler Drum Top /Bottom DT  . It  should  not  be > 50   C . ( Left / Middle/Right)   
17.   Check  CC  pump  cavity  temp as  boiler temp. rises .   
0
18.   Monitor the  MS/CRH/HRH  temp. rise . It should  not Exceed  2 ‐3   C   
0
19.   Take Use  of Furnace Temp Probe  , it should  not  Exceed  560   C   
 
 
 
 

Prepared By  Reviewed By Approved  By   Sheet 10 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

ACTIVITIES DURING BOILER PARAMETERS RISE  
 
HEATING  Rate  
TIME IN  Rate of Pr  Rise of Sat  TIME IN  Rate of Pr  Rise of Sat 
PRESSURE   SAT TEMP  PRESSURE  SAT TEMP 
MINUTES   Rise /min  Temp /Hr  MINUTES  Rise /min  Temp /Hr 
42  1     100 143.3 120 50 1.40  263 104.0
52.5  2.5  0.14  126 120.0 135 75 1.67  290 100.0
60  4  0.20  143 118.7 150 110 2.33  315 124.0
75  8  0.27  171 122.7 165 160 3.33  346 76.0
90  16  0.53  203 116.0 180 200 2.67  365 121.7
105  29  0.87  232 116.0 1.11 
 
Checked 
ITEM  DESCRIPTION 
Status 
  • At  Boiler Drum Pressure  2kg/cm2   : ‐ ( Sat temp.120 0 C )   
Close    all  4  Boiler  Drum    vents    .  Check  locally  for    any  passing    &    manually    tighten  them  if  required    , 
1.    
otherwise  inform  BMD . 
  ♦ At  Boiler pressure  6 kg/cm2   : ‐ ( Sat temp.160 0 C )   
Close SH  header drains & SH Hdr Vents . Close  main  manual isolating  valve  at  common hdr to IBD tank . ( 
2.   Check locally for  any passing  &  manually  tighten them if required  , otherwise  inform  BMD .)    
Start‐up Vents  Should  Be  in Open position till HP/LP bypass  is charged . 
  • At  Boiler pressure 7‐8 kg/cm2(Corresponding sat temp =165‐1700C)   
3.   Start 3rd CC  pump if  not in service  earlier .   
4.   Check that APH soot blowing is going on. Check through  oil carry over probe & APH View glasses .   
5.   Put ESP rapping system in to service on auto mode .   
  • 2
At  Boiler pressure 7‐8 kg/cm   SLOWLY  CHARGE MS LINE    
6.   MS, HRH, CRH header turbine side atmospheric  drains are already  in open condition.   
7.   MS  to PRDS line  drain Valve  AS ‐ 46 ( D/A floor) is opened to IBD tank    
8.   HP BP line drains  are  open  ( BP 101/102 ) . Ensure  the  manual valves are  open .   
Open HP bypass warm up line valves at 8.5 mtr . (BP03/04) 
9.    
( Warming up of HPBP  system)  
All  other  drains  to  SDFT/LPFT/HPFT    are    open  with  respective    manual  isolating    valves  .  (  as  per  list 
10.    
attached )  
11.   Open Boiler stop valve bypass valve.  ( MS 3,5,4,6 )   
MS, CRH , HRH, lines get warm up , close the atmospheric  drains after sufficient warm up is experienced . 
12.    
Monitor  through temp rise . 
Once  the  Pressure  /temp  Builds up in MS  line  , Open MS stop valves (MS ‐ 1 &2 ) ,  Check MS  Pressure  
13.    
& temp . 
14.   Close  the drain before MS SV   MS 401,MS402 at  65  Mtr    
  • HP / LP  Bypass  charging : ‐   
15.   LP bypass  warm up  line drains are open.( LP624/625, HRH 109/110)   
16.   Check CRH to Deaerator steam line drains are open condition.( CRH 109 /CRH 153)   
17.   CRH to TD BFPs before iso. Valves drains are  open, (CRH 116/CRH123)   

Prepared By  Reviewed By Approved  By   Sheet 11 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
18.   Check 3rd  CEP  is on auto .   
19.   Put LP bypass interface ON & LP bypass on auto.  Check  Fixed Set point is set at  12.0 ksc    
20.   Open HP  bypass valves  by  5%.   Slowly raise  this opening as  Boiler  Firing increases .     
Once  the HP /LP  Bypass is charged  , Close  the  SH  Start up vents ( S‐ 81/ 83                  &  S‐ 82/84 ) . Close  
21.    
RH vents  once  LPBP Opening >  20 % . Ensure Vacuum has  improved . 
22.   Close  HPBP  warm up valves & drains  after HPBP main valves are  opened .   
23.   Start 2nd set of ID, FD  Fans. ( if not started earlier )   
  • At  Boiler pressure 12‐15  kg/cm     2
 
24.   Start one PA Fan. Take PSCAPH  in to service .   
25.   Keep PA   Header  pressure  control on auto .  ( set point  820 mmWC )   
Open  FG outlet   damper to 100 %  of the respective  side  PAPH  where PA fan is started  & other side  to  
26.   20 ‐30 % . Also regulate the  SAPH  FG  outlet damper  to   50 %  so that the PAPH outlet air  temp . will  rise    
fast . 
27.   Start one mill & keep it warmed up  , Also  start  2 nd  mill  &  keep it warmed up    
28.   When Hot PA  Hdr  temperature  > 150 0 C  then  1st t  Mill  can be taken into service .   
st
29.   Take  the  1   Feeder into service  . Keep minimum   coal flow  based  on Mill outlet temp .   
30.   Start 2nd  Feeder   &   Keep total coal flow  around  60‐70 tons    
31.   Take  out  2 oil  guns  from   EF  elevation  .   
0
32.   Maintain SH /RH temp   ≤ 350   C . Line  up spray & Open Bok valves    
Check all  other  mills  & feeders are  lined  up & all  necessary permissive  as per  the  interlock page  is 
33.    
available . ( Coal flow is established  in Fdr ) . Acknowledge all faults  
  • MS pressure 25 kg/cm2  ( Corresponding sat temp = 228 0C).    
34.   Take  one set Boiler  Expansion  reading  .   
  • MS pressure 60 kg/cm2  ( Corresponding sat temp = 263   C).   0
 
35.   Further pressure  rise  for safety  valve  floating  after BMD clearances   .   
 
 
DR PR IN  MS PR IN  HRH PR IN  BCW SUC  MS TEMP  MS TEMP  HRH TEMP  HRH TEMP  SH MET  RH MET  STEAM 
TIME 
KSC  KSC  KSC  TEMP  L  R  L  R  TEMP  TEMP  FLOW  
0       
10       
20       
30       
40       
50       
  60       
  80       
  100       
  150       
  180       
  200       
 

Prepared By  Reviewed By Approved  By   Sheet 12 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

EE : CHECKS BEFORE TG SET  ROLLING TO 360  RPM 
 
Checked 
ITEM  DESCRIPTION 
Status 
• MS/HRH pressure: 55 ‐60 kg/cm2( Corresponding sat temp = 269 0C)./12 ksc 
   
•  MS / HRH  Temp. 350 0 C/330 0 C 
The pressure ratio MS / CRH should not be less than   4.0   for no load &  3.0  for loaded  
1.    
condition  . 
2.   Inform all relevant persons about TG rolling  ( EMD/TMD/C&I )   
Steam Purity  Checked  By  Chemist  &  Clearance  given  by Chemist   . 
3.    
( acceptable value  < 20 ppm)  Actual Value  of  MS  Sio2 = 
4.   Turbine governing characteristics taken and cleared.   
Once again ensure  the EHC is lined  up , otherwise  the speed  will  rise hydraulically   at 
1.    
Step ‐9 . 
Ensure  the  HPT  evacuation  valve  to condenser   LBJ10AA001  is  in closed position .   
2.    
( BHEL  MMI) . 
3.   Generator Trip to turbine trip kept  bypassed  for electrical testing .   
4.   HPBP 1st opening  is kept  bypassed   for elect testing    
5.   Intertrip Checking Completed    
6.   All TSI parameters  are available & note down at barring gear  before rolling    
7.   All drains manual valves are open. Valves are open or working in auto.   
Check HP /LP  Bypass  on auto , HPBP pr set point   55 ksc , LPBP  fixed  set point  11‐
8.    
12 ksc  
9.   Temp. curves X 3 , X 4,  X 5 are  satisfied .   
10.   Check Speeder gear position at 100 %. (Hydraulic Governor )   
11.   In Turbine trip parameter page  no Trip or fault is present    
12.   Power set point > 70 MW.  CMC  pressure  set point  is  40 ksc    
13.   Condenser vacuum > 0.88 ksc .   
14.   All SLC’S are  ON  ( Drain /AOP /CF/JOP /SOS etc)   
0
15.   CF TCV on auto , temp 55  c ( Internal  Set point  550c.)   
0
16.   Lub Oil temp. control valve on auto & lub  oil temp. 45 c.  ( Internal  Set point  450c.)   
17.   Lub oil  filter  is clean & stand  by filter  is ready .   
18.   Seal oil  pumps are  in service  & seal oil  DP  OK .(1.5 ksc) oil pumps interlocks checked   
19.   Seal oil coolers are in service , vented properly .    
PW system is in service. Flow adjusted and temp. control put in auto. PW N2 capping 
20.    
pressure is normal 
0
PW  temp control  on auto.  PW  temp is  3  c +  Cold gas temp. ( Internal  Set point  
21.    
450c.) 
22.   Generator  casing  H2  filling  completed  and  pressure  is  >3.7  ksc,  H2  purity  more  than   

Prepared By  Reviewed By Approved  By   Sheet 13 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
99.0%: 
0
23.   Check H2 temp. control on auto.  All  4 coolers are  charged .( set point 45  C )   
24.   Exciter coolers charged   
25.   DG set is available and diesel tank level is normal.   
26.   Turbine parameter on TG are noted and no abnormality is observed   
27.   Check the  Following  in CRT before  ATRS  Rolling .   
) EHTC page ‐1    ) EHTC page ‐2     
• Master  Set point  not blocked     • TSC  influence ON     
• Speed controller active     • LP mode selected     
28.   • Trim device ON  ( SV  off )     • GCB open      
• Plunger coil  not off     • Load gradient  15 MW/Min     
• No TSE  fault    • PR Max  100 MW     
• No speed measurement fault    • Freq influence off  ( FGMO)      
Generator trip relays are reset. Turbine  side  no trip cause persists . All protections are  
29.    
normalised . 
SLC drains  kept   “ON “ ( Check all MAL drains are  open & TEMP  in all drain line  is 
30.    
raising as per logic)  
31.   Temp  curves X1,X2, are all satisfied at  Step‐  5 . ( from standard curves ).   
32.   Both EHC isolating valves at governing rack  are  open.   
33.   Bring starting device (SD) to zero position . At  this point  Turbine  is  Reset .   
34.   Raise the  SD  up to 42% .  subject  to steam  Purity   by  Chemist  Sio2 < 20 ppb   
35.   Check that all stop valves are  opened.( Both HP/ IP )      
Check  that  HP  control  valve  body  metal  temp/  HP  Casing  temp  ,  TG  speed  are  
36.    
increasing. 
 
At the time of opening stop valve:  As per X‐1: / As per X‐2:  
 
MS Throttle pressure, ksc  HRH pressure, ksc 
MS temp. º C  HRH temp. º C 
MCV body 100/ 50% temp. ºC  IP Inner casing / IP shaft  Temp  
HP casing mid wall temp.100/50 ºC  Cond. Vacuum, ksc  
HP Shaft temp   HP control fluid temp º C 
TG Lub Oil pr in ksc  
Oil temp after cooler º C 
 
 
 
 
 

Prepared By  Reviewed By Approved  By   Sheet 14 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

 
FF :  RAISING THE  SPEED  TO  360 RPM ( SOAKING SPEED  ) IN NORMAL MODE 
 
Checked 
ITEM  DESCRIPTION 
Status 
Roll  the  Machine   through  ATRS only  by switching “ON” ( A/M) the  SGC  programme 
1.    
&  then starting the  programme by pressing the “ Start Up “ button  .  
Check at each step  all criteria’s are  satisfied & then the programme  moves  to next 
2.    
step  .  If any  fault appears  then  acknowledge  them . 
If any  criteria  is  not  satisfied record them &  then check  thoroughly . After ensuring  
3.   the reason  , then only bypass  the  step,   by pressing  the  step  bypass button once .    
( Observe that  the step does not get  bypassed  )  
Check that  the  Speed Reference Signal is raising to 360 RPM  & accordingly  the actual 
4.    
speed  of the  turbine  is raising  at  Step – 12 in ATRS programme . 
Check that TG  Barring Gear Valve closed at 240 rpm. Other wise manually close it  . ( If 
5.    
fire protection  fault  has come during the Barring gear  opening then it should  reset . ) 
Observe  the  MOT  level  rise    after  barring  gear  has  stopped  .Fire  protection    fault    is 
6.    
reset  .( Rise will be approximately 70 mm ) 
7.   Check bearing vibrations, temps. And  other  Turbovisory parameters  as per log sheet  .   
8.   Speed Reached  360 RPM   Time    
9.   Once the speed reached 360 RPM (Soaking speed ) “ switch off (A/M) “ the Programme    
10.   Check that TSE margin is >  30k.   
11.   Check drains are  operating as per  SLC logic  .   
12.   The MS/CRH/HRH line drains will remain open .   
 
 
 
GG : Activities before raising the   speed  to  3000 RPM in Normal Mode . 
         ( Approx 3 ‐ 4  Hrs FOR  satisfying  the X6 Criteria ) 
 
Checked 
ITEM  DESCRIPTION 
Status 
Check  Both  TDBFP are  rolled  from aux steam if not rolled earlier   . MDBFP  is  in 
1.    
service .  
Open SH/RH attemperation iso. Valves. &  maintain the  temp  even by giving spray . 
2.    
Operate the  Burner  Tilt  as per  requirement . 
Check all TG side  Parameters  are  normal  at 360 RPM . Take one set  of  readings at 
360  RPM  
3.    
• Turbovisory /TG Lub Oil /Control Fluid/Stator water  
• H2 Gas system/Seal Oil  system/Exciter  Air  System  
4.   The EMD  is ready  for synchronisation  .   
 

Prepared By  Reviewed By Approved  By   Sheet 15 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

HH : TG SET  ROLLING TO 3000  RPM ( Rated speed) 
 
Checked 
ITEM  DESCRIPTION 
Status 
1.   Inform MTP  to take  vibration readings at 360 RPM.   
2.   Check the  X 6 criteria is satisfied .  ( HP casing – MS Temp Bef HPBP) .   
3.   Now again switch ON  the programme .    
Now  the  speed set point will  be raised  to 3000 RPM  automatically at   step – 16   ,  
4.   accordingly  the actual speed  will  also raise  based on available  margin ( 100% margin   
= 600 RPM/ Min) 
Observe the  following  
5.   • JOP stops on auto  at 540 RPM   
• AOP stops on auto  at 2850 RPM 
Record the  Max  bearing & shaft  vibration at critical speeds . The  Critical speeds   are   
6.    
870/1075/2275/2775  RPM . 
7.   Check bearing vibrations, brng temp. other  turbovisory  parameters  as per log sheet   
8.   Check  SW parameters (Flow/temp/Pressure/Conductivity/Level etc) as per log sheet    
9.   Check  Seal Oil parameters as per log sheet    
10.   Check  H2 gas system  parameters as per log sheet .   
Check  the  TG  lub  oil  filters    status  ,  if  required    changeover    before  Synchronisation  . 
11.    
clean the  standby immediately . 
Now once  the speed reference value is reached at  3000 RPM , the programme can be 
12.    
switched off . (Actual speed  will take approximately 6 min to reach 3000 RPM) 

13.   Speed Reached  3000 RPM                                                                                                  Time    

14.   Once the speed reached  3000 RPM  MTP can be  informed to take  vibration readings .   
15.   Note & record all critical parameters  as per  formats provided .   
 
 
 
 
 
 

Prepared By  Reviewed By Approved  By   Sheet 16 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

TURBINE START UP LOG  FOR 1ST TIME ROLLING  
 
UNIT:  3/4/5/6                                            DATE: 
 
Before  
S.N.  ACTIVITY DESCRIPTION  Before 360 RPM  Before 3000 RPM 
Synchronisation 
  Date / time       
1.   Initial Unit condition:    Cold / Warm / Hot      Cold      Cold      Cold 
2.   Turbine speed on TG, rpm       
3.   Mode of Rolling (EHC,ATRS through SGC Turbine)  ATRS  ATRS  ATRS 
4.   MS  SILICA SAMPLE   PPB        
5.   Turbine reset at, (time, hrs)       
Turbine  Rolling  Mode  Selected         
6.  
Fast /Normal  / Slow  
MS Throttle pressure, ksc       
HRH pressure, ksc       
MS temp. º C       
HRH temp. º C       
HP/LP Bypass  Opening       
Steam Flow   BLI / T/hr        
MSV  body 100/50 % temp       
MCV body 100/ 50% temp. ºC       
HP casing mid wall 100/50 temp.ºC       
7.   HP shaft   100/ 50 % temp. ºC       
HP exhaust temp        
IP Inner casing / IP shaft  Temp        
 IP exhaust  temp       
LP inner casing temp        
HP/IP Turbine  DT  in º C  HP/ IP F/ IP R       
Cond. Vacuum, ksc        
HP control fluid temp º C       
TG Lub Oil pr in ksc        
Oil temp after cooler º C       
8.   Turbine rolled to 360 rpm, at   (time, hrs)       
9.   Soaking done at 360 rpm,  UP TO        
HPC Parameter   after X6  criteria satisfied         
10.  
MS TEMP  VS  HPC TEMP 
11.   Turbine rolled to 3000 rpm, at   (time, hrs)       
12.   Maximum  Shaft  Vibration Brng / Speed        
13.   Maximum  Bearing   Vibration Brng / Speed        
14.   IPS  Parameter   after X7  criteria satisfied         

Prepared By  Reviewed By Approved  By   Sheet 17 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Before  
S.N.  ACTIVITY DESCRIPTION  Before 360 RPM  Before 3000 RPM 
Synchronisation 
TSE margins:       
15.   • HPSV  / HPCV / HPC /HPS /IPS  
 
 

Prepared By  Reviewed By Approved  By   Sheet 18 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

TURBOVISORY PARAMETERS MONITORING SHEET 
BEFORE & AFTER ANNUAL OVERHAUL, AT FULL LOAD OPEARTION 
 
Sl  Before 
Description of parameters.  UNIT  Before  360  RPM  At 360  RPM  At 3000 RPM 
No  synchronisation  
Time in   
  • DIFF EXPANSION  Hrs 
     

1. HPT (F) ‐5.0 &+3.5   mm         

2. IPT (R) ‐1.0 &+8.0   mm         

3. LPT(R) ‐3.0 &+35   mm         

4. • AXIAL SHIFT           

5. Point (1) +/‐ 0.5 & +/‐ 1.0  mm         

6. Point(2)  mm         

7. Point(3)  mm         

8. • OVERALL EXPANSION            

9. HPT (F) ( 0‐30 MM)  mm         

10. IPT (R)  ) (0‐20 MM)  mm         

  • BRG. VIBRATION    >42 µ         

11. HPT (F)  1X/1Y  micron         

12. HPT (R)2X/2Y  micron         

13. IPT (R)  3X/3Y  micron         

14. LPT(R)  4X/4Y  micron         

15. GEN(F)  5X/5Y  micron         

16. GEN(R)  6X/6Y  micron         

17. EXC(R)  7X/7Y  micron         

  • SHAFT VIBRATION    >100µ         

18. HPT (F)  1X/1Y  micron         

19. HPT (R)2X/2Y  micron         

20. IPT (R)  3X/3Y  micron         

21. LPT(R)  4X/4Y  micron         

22. GEN(F)  5X/5Y  micron         

23. GEN(R)  6X/6Y  micron         

24. EXC(R)  7X/7Y  micron         

  • Turbine  Brg. Temp.    110/130         

Prepared By  Reviewed By Approved  By   Sheet 19 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Sl  Before 
Description of parameters.  UNIT  Before  360  RPM  At 360  RPM  At 3000 RPM 
No  synchronisation  
Point 1,2 

 C         
HPT (F)    TL/R 
25.
                B L/R  Point 3,4  0 
 C         

Point 5,6  0 
 C         
HPT (R)    T  L/R 
26.
                 B  L/R  Point 7,8  0 
 C         

T Bearing  Point 9,10  

 C         
RL/FR 
27.  
                   Point 11,12   0 
 C       
RL/RR 
28. IPT (R)  Point 13,14  0 
 C         

29. LPT (R)  Point 15,16  0 


 C         

Point 17,18  0 
 C         
30. GEN (TE) 
Point 19,20  0 
 C         

Point 21,22  0 
 C         
31. GEN (EE) 
Point 23,24  0 
 C         

Point 25,26  0 
 C         
32. Exciter Brng. 
Point 27,28  0 
 C         

  BRNG  Drain Oil  TEMP    
       

33. Return Oil  Temp HPF   0 
 C         

34. Return Oil  Temp HPR  0 
 C         

35. Return Oil  Temp IPR   0 
 C         

36. Return Oil  Temp LPR  0 
 C         

37. Return Oil  Temp Gen F    0 
 C         

38. Return Oil  Temp Gen R    0 
 C         

39. Return Oil  Temp Exciter  0 
 C         

40. MOT  Level   MM         

41. CFT LEVEL   MM         

 
 

Prepared By  Reviewed By Approved  By   Sheet 20 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Activities after Completion  of   Electrical  Testing  By  EMD  & Clearance  Obtained . 
 
 
Checked 
ITEM  DESCRIPTION 
Status 
1.   Carry out  ATT  for  all safety  Devices  ( RTD‐1 &2 , OS Trip  / Low  vacuum )   

2.   Oil  injection Test  from Local . Note down  the  oil  pressure .   

3.   All electrical normalisation carried  out   .   

4.   PTW  on GT / UT cancelled .   

5.   UT A/B  breakers  are  racked  in  & selected  in remote  .   

6.   Ensure  GT/UT  all mulsifiers  are  in service  . Note down the sensing line pressures .   

7.   Check Both  Sources for  marshalling  Box of  GT are ON at SS SWGR end .   

8.   Carry out  GT Back charge  with  coordination  from  Switch Yard .   

9.   Changeover  the auxiliary  supply  to UT A/ B  from  station  Bus  before  synchronisation   
 
NN : Synchronisation  of the  unit  ( Automatic ) /Loading of  the Unit . 
 
Checked 
ITEM  DESCRIPTION 
Status 
Normalise all protections  bypassed  during testing  &  overhauling  period  . Cross check 
1.    
the  P&I  Bypass  register  . ( Gen Trip  to Turbine trip / HPBP 1st open )  
Check  machine  is  at  3000  RPM    with    all  parameters    normal  .  Record  one  set    of  all 
2.    
parameters  as per  log sheet  . 
3.   Check HP/LP bypass  on auto  & Fixed set point at 11‐12 ksc .   
4.   Check the  X 7 criteria   is satisfied.  ( IP shaft – HRH  temp )   
5.   Close the  field  bkr  from CRT .   
6.   Select  the Excitation  Channel  to be kept on auto ( Ch‐1 or Ch‐2 )   
7.   Switch “ON”  the Excitation system  , observe  Voltage build up  to 21 kv automatically    
8.   Now insert  the  key  for synchronisation in vertical panel . ( Key available in SCE  room)    
9.   Key position with arrow  as follows  0‐ OFF   1‐  CHECK   2‐ ATRS     

Prepared By  Reviewed By Approved  By   Sheet 21 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
10.   In check position  check the  voltages  & adjust  if required .   
11.   Now select  the key to Position – 2 ( ATRS)   
Get ready with  Speed Ref ( raise )  &  Master set point Block  ( A/M)   commands in 
12.    
CRT . 
13.   Switch “ON”   the  Auto  synchroniser  from EHTC ‐1 page in CRT .   

14.   Observe  the GCB closes automatically  &  Unit is  synchronised .   Time :    

15.   Observe  that block load picked  up  approx  50‐70 MW    
If  the load does not raise ,  then raise the  Speed Reference immediately  & increase the  
16.    
load  of the  unit  to 70‐80 MW range . 
Ensure  Load  controller    has  come  in  to  service.    (  Try  to  put  the  load  controller  in 
17.   service as soon as possible . The SC output  remains at 29 % , Never allow the LC  out    
put to come below that ) 
Adjust MVAR from Vertical panel or through the CRT page  so that it is on  lagging side 
18.    
(+ve)  from leading side (‐ ve )  
19.   Inform   all  concerned  & give message accordingly .   
20.   Check  TG SET  bearing  areas  for  any  smoke / fire  due  to  oil  spillage .   
21.   Inform MTP  to take  vibration readings .   

Prepared By  Reviewed By Approved  By   Sheet 22 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Activities  After Unit  Synchronisation . 
  
Checked 
ITEM  DESCRIPTION 
Status 
Cut in  the   3rd  mill  & take  into service.  Adjust firing such that  the pressure rises  with 
1.    
load . Maintain mill outlet temp with  minimum loading  till FG temp increases . 

Select  the Turbine  pressure  Control  to IP mode  from LP mode  to avoid  the pressure 
2.    
variation during  load  raising . 
Observe  HP bypass  closes automatically  as MS pressure drops after load pickup . Raise  
the  HPBP  pr set point gradually so that  it should  not  open . 
100 MW – 80 ksc                                      400 MW – 150 ksc  
3.    
200 MW – 100 ksc                                    500 MW – 175 ksc  
300 MW – 125 ksc  
 
 ( N:B Don’t put the HPBP pr. Set point on Auto )  ( This is defeated  now  from CRT ) 
If  HP  BP  valves  are    kept    on  manual  then    close  /open  is  to  be    done    very  slowly    , 
4.   otherwise  the  drum level will change  very  fast & may lead  to  Unit  Tripping . If kept   
open  for prolonged period  then   the HP Exhaust temp  will  rise . Keep it under watch . 

5.   Ensure HPBP warm  up  valves BP 01/02  are  closed .   

LP bypass closes on auto immediately after  synchronisation .  Check the  fixed  set point  
6.    
is at  12 ksc . 
After  125 MW  Close all drains, MS, HRH, CRH line. (  Check  the temp. of these drains  , if 
7.    
passing suspected  after  close  indication  then manually close them further ) 
  Load 120 MW, 65‐70  kg/cm2  pressure , Charge LPH ‐ 2 & 3.   
Charge  the LPH 2 & 3 , put their  drip CV  on auto . (NLCV  set point  ‐525 , ECV – 475 for 
8.    
LPH‐ 2  & NLCV  set point  ‐460 , ECV – 400 for LPH‐ 3   .) 

9.   Peg deaerator to 3.5  kg/cm2 gradually from CRH steam .    

  Load 150 MW, 85 kg / cm2 pressure , Charge HPH ‐ 5 & 6.   

Charge  HPH  5A/6A , 5B/6B  respectively  . Put the  NLCV  & ELCV  on Auto . The level set 
10.    
point  for NLCV =  ‐540 mm &  ELCV ‐475  mm 

Prepared By  Reviewed By Approved  By   Sheet 23 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
Start  2nd PA  Fan ( after 3 mill in operation)   . Balance  both  blade pitch  . Now  adjust  
11.    
the  FG  dampers  of Both  PAPH  to 100 % open .  Observe  the  APH  FG  outlet  temp  
  Load  150 MW ,  MS  Pr 100 kg/cm2  ( HPBP pr set point – 120 ksc)   
12.   Ensure  all power supply  for ATT SV  & ATT  Motors are  normalised   for  HP/IP  Turbine .   
13.   Carry out  ATT  for  Turbine valves  at 150 MW  load .    
14.   After  successful  completion  of  ATT  for Valves   , go ahead  with   load raising     
15.   Raise  the speed  set point  of  both TDBFP  to 3000‐3500 RPM .    
16.   Charge  the D/A  from Ext  steam  . Observe the  closure of  CRH  CV  & put it  on Auto  .   
  Load 180 ‐ 200 MW:   MS  Pr 100  kg/cm2( HPBP pr set point – 120 ksc)   
As Load  increases  slowly regulate the PAPH FG outlet    dampers  &  open up  the SAPH 
17.    
FG outlet dampers  to  equalise  the FG temp at APH outlet .  
18.   Depending  upon  the  temp  isolate   the SCAPH  once  ESP  inlet temp >120 0C   
19.   Cut in  the  4th  Mill in service . Take out one elevation oil support .   
Take  Feed Water High  Range  line into service . ( Check  the drum lvl should  not  change  
20.    
much)  
  Load 200 250MW : ( MS pressure ‐ 125  ksc ) ( HPBP pr set point – 150 ksc)   
21.   Cut in  the   5th  Mill into service . Take out one elevation oil support   
22.   Load the 2nd BFP  ( TDBFP A or B )   & ensure  the RCV are  open for  both BFP in service .   
23.   Put  drum level 3 element  control  in to  service & on auto mode  . Close  the LLCV  fully .   
24.   Keep only one  elevation  oil  support with  7‐7.5  ksc pressure .   
  Load 250‐320 MW  ( MS pressure ‐ 130  ksc ) ( HPBP pr set point – 170 ksc)   
25.   Charge  the  APRDS  from CRH source .   
26.   Cut in  the   6 th  Mill into service  & completely  take out oil support .   

27.   Charge ESP fields after attaining   110‐120  0 C  FG  inlet temp to ESP .   

Load    2nd  TD  BFP    .  Unload    MD  BFP    &   keep  it  on  recirculation  for  10‐15 min    .  After 
28.   TDBFP  stabilisation  Stop  MDBFP & check permissive available &   it is on  Rapid loading   
Mode . 

Prepared By  Reviewed By Approved  By   Sheet 24 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
  Load 400 MW  ( MS pressure ‐ 150  ksc ) ( HPBP pr set point – 175 ksc)   
Cut in  the  7th Mill in to service.  ( If coal quality  is bad ) ( For <  340 Tons  firing for Full 
29.    
load  only 6  mills required ) 
  Load 500 MW  ( MS pressure ‐ 169  ksc ) ( HPBP pr set point – 175 ksc)   
Slowly Increase parameters to full load parameters  i.e. load 500MW. MS pressure  169  
30.    
ksc , MS /HRH temp  537 / 5370C 

Prepared By  Reviewed By Approved  By   Sheet 25 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

DETAIL  CHECKS  AFTER 
UNIT  SYNCHRONISATION  &  FULL LOAD  OPEARTION 
 
Unit  3/4/5/6                     Date  :‐ 
 
Checked 
ITEM  DESCRIPTION 
Status 
  Area  : SG & Auxiliaries    
1.   Oil Carry over probe  removed  , point blanked  , water  isolated    
2.   SCAPH isolated     
3.   APH Light switched  off   , APH SB operation    Normalised     
4.   WB Pressure setting  & availability  of WB  ( 88 )   
5.   LRSB  Pressure setting  & availability  of  LRSB  ( 34 )   
1.   All  boiler side valves  for  any  leakage  , passing , sound  etc  AS PER  CHECK LIST     
Check all  boiler  parameters  at full load .  Take local round to  monitor any abnormal sound , 
6.    
water/steam oil  , air  , FG  leakage  etc . 
2.   Check APH GB  area  for  any  leakage  .   
3.   Check all Expansion Joints  FOR  ANY  LEAKAGE     
4.   Check  Wind  Box area  for  Hot air  leakages     
1.   Check  SADC / Burner Tilt   for any  possible  deviation     
5.   Mill  Fineness test results    
6.   Un‐burnt  in BA  ( < 1 % ) / FA  ( < 0.1 %)   
7.   O2  online  &  ORSAT  results     
8.   Check all chemical parameters  oil ,water ,steam    
9.   IBD Tank   Steam Exhaust     
10.   Bottom ash  evacuation  &  FA  ash  Evacuation  are  normal    
11.   ESP  fields and  auxiliaries  are  in service  , Opacity  Level   
12.   ESP Hopper  Evacuation  Status    
  Area  : TG & Auxiliaries    
Check all  turbine  parameters  at full load .  Take local round to  monitor any abnormal sound , 
13.    
water/steam leakage etc . 
14.   HPH /LPH level set points are  as per  design .    
15.   All  TG valves  for  any  leakage  , passing , sound  etc  AS PER  CHECK LIST     
16.   All  Turbovisory  parameters   are  with  in  limit  .   
17.   All critical parameters  are  with  in  limit  .   

Prepared By  Reviewed By Approved  By   Sheet 26 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
18.   All  ventilation  system / AC  system are  in service   including acoustic covers    
19.   MDBFP  Stopped  &  On  auto  & start  Permissive  available .   
20.   Check Makeup Water  %  , APRDS  charged  from CRH .   
21.   Condensate  Dissolved O2  level , check as per   check list    
22.   Condenser  VP  air  discharge , should  be    <  20 kg    
23.   Gland Steam Hdr  Pressure 250 mmwc    
24.   Valve  gland  seal  hdr   Pressure   5‐8 ksc    
25.   Efficiency related parameters     
26.   Status  of OLTC  , Should  Be  taken  in service     
27.   CEP /TDBFP RCV  passing   to  be  checked  by temp gun    
28.   CRH drain pot ls  to be kept in service , check  by isolation valve  opening    
29.   HE  Drains  Status  /temp / manual tightening    
30.   APC  status     
31.   CT  area  valve  status  , main 1600 NB/ Individual Riser     
32.   SWAS  status  .   
33.   Power supply isolation  for MS  stop valves .   
34.   Selection  of  other  valves  in maintenance Mode .   
35.   H2 Purity  , Dew point , drier changeover    
36.   ACW  self cleaning Strainer one set should  be in service    
  Area  : Electrical System     
37.   All SWGR  independently charged     
38.   All Battery  charger   charged     
39.   Lighting system normalised  .   
40.   All Breaker  Dc  Both sources  are  in  service  .   
 
 

Prepared By  Reviewed By Approved  By   Sheet 27 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

ANNEXURES

Prepared By  Reviewed By Approved  By   Sheet 28 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Brief Check List  for Various 
Systems  

Prepared By  Reviewed By Approved  By   Sheet 29 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

1.0 OFF SITE AREAS  
 
Checked 
DESCRIPTION 
Status 
♦ CW  SYSTEM  :‐    

♦ Check  CW  pumps are in service  for the unit and the position of the Inter Connection valve. 
♦ CW Pump   A / B  , Discharge pressure  should  be  1.4 ksc  ( ACW suction pressure 1.7 ksc for 
Unit 3&4 , 1.0 ksc for Unit 5&6 ) 
♦ Status of stand by CW  pump ‐ C 
♦ Status of Interconnection Valve – 1 
♦ Status of Interconnection Valve – 2   
♦ Channel  level  for 3&4 > 89.2 Mtr & for 5&6  > 82.4 
♦ Makeup  water  to channel from Channel makeup pump (unit‐ 5&6) 
♦ Status of  SW  tank makeup  from this unit CW  pump  discharge . CW BD  
♦ Status of chlorination Pump house Supply water  ( 3,4,5,6 ) 
♦ CW SWGR  both section independently charged . 
♦ CT  SYSTEM  :‐    
♦ CT  ‐  A  is charged /  no of  raiser valves opened  
♦ CT  ‐  B is charged /  no of  raiser valves opened  
♦ CT Cold Basin  trash gates are  open  
♦ CT  transformer  charging status    A/B/C   
♦ CT – Both  boards are  independently  charged  
♦ CT  fans oil level  adequate  
♦ No  of CT fans  started  from PLC     CT  ‐ A    / CT – B 

♦ Compressed air SYSTEM  :‐    

♦ Instrument air to  TG side  charged &  Pressure = 
♦ Instrument air  to Boiler side charged  & pressure= 
 
♦ Plant air to Blr  side is charged  ( isolation valve at 8.5 Mtr near “C” Row)= 
♦ Inst air & service air pressure  in CCR  ( record  values )= 

♦ LDO/HFO  system   :‐    

♦ One  LDO  pressurising  pump  for  the  respective  unit  is  in  service  or  the  interconnection    at 
discharge hdr is open .  
♦ Isolation valve  at pipe  trestle  is open  
♦ Status of iso valves at firing floor /Corner  isolation valves    
♦ Status  of  HFO  pressurising  pump  in  service  or  the  interconnection    at  discharge  hdr  is  open  . 
Short recirculation , Long recirculation  
♦ Status of HFO heaters ,  Temp set point – 100 0 C  . 

♦ AC & VENTILATION SYSTEM   :‐    

• AC System  for  CCR /CER    

Prepared By  Reviewed By Approved  By   Sheet 30 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
DESCRIPTION 
Status 
• AC system for  VFD /ESP  control room    

• AC system for  VFD  AC  computer room    

Prepared By  Reviewed By Approved  By   Sheet 31 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

2.0 BOILER SIDE CHECKS 
 
Checked 
ITEM  DESCRIPTION 
Status 
2.1  • GENERAL   
  No PTW is pending on Boiler Pressure parts/Draught system /ESP /AH system etc.   
  All manhole doors of boiler/FG duct/APH/ESP/Air ducts etc. are  closed    
  All materials are removed such as scaffoldings/sky climber etc.   
Written clearance given by BMD Pr Parts / RM  group /Mill Group /ESP & Ash Handling Group  for start up of 
    
boiler. 
2.2    • BOILER  DRAINS & VENTS   
  Boiler  drum vents are  open ( B76/B77(L)  / B 78/79 (R)   
  N2 capping  vents are  closed ( B72/B73(L)  / B 74/75 (R)   
  RH vents are open From UCB ( during vacuum pulling  close  them ) R76/77,     
  RH Drain at  firing floor is  open . R‐10  With  manual  valve.   
  MS SV before drains are open from UCB LHS/RHS  MS  401 (L) / MS 402 (R )   
SH  drain hdr  all  valves are open  along  with  their  manual valves  . Common  main  manual  valve  to IBD is 
   
open . S74, S23/25 , S21/22 , S19, S24/26 
  SH  vents   S11/12 (L) , S13/14 (R ) along  with  the  start‐up vents  S81/83 (L) / S82/84 (R)  are  open .   
  EBD tanks are  lined  up  with  spray ( from SW  LINE  TO APH )    B85/B87    
CBD tank  is lined  up to  D/A  or IBD  Tank  , Manual valves are  opened  accordingly  at firing floor  . 
   
. B81 /68/83  , B 84/69/82 
  CBD  manual valve  below drum floor  is in open condition .   
  CBD sample line  root valve  is open .   
Boiler drains are  closed   at  “0” Mtr  drain station along  with  their respective  manual isolation  valves  . 
   
Main  drain  valve   to  the  IBD  tank  is also  closed  .                                                           E ‐18 ,19 , B‐92, B88/86  
2.3  • BOILER  WATER AND STEAM CKT   
Boiler is filled with water up to normal drum level ( +/‐ 50 mm ) with  chemicals  
  If filling is to be done then follow the standard filling procedure to bring up to the normal lvl. ( add chemical   
dosing during  boiler  filling ). Inform shift chemist   for  boiler  filling . 
  All  Spring loaded safety  V/Vs  are  available     
  If any  safety valve  not available   record it  with reason .   
All ERV’s  isolation   V/Vs are  open and power supply (220 V DC) made ON .  
   
SH S85/86/87/88/89   , RH ‐  R 72/73/74/75 . 
  All  expansion indicators  are available  &  the  format for expansion measurement available    
All  sample  coolers are  charged  from  water  side . All root  valves  are  open  at  different  elevations  .  After  
   
light up ensure   samples are  coming  . 
2.4  • BCW PUMPS  & AUXILIARIES    
  Check BCW  pump breakers  are  racked in after  boiler filling .   
  Check One SG ECW pump is in service .   
  Check BCW booster  pump power supply is available &  both pumps are  lined up . Keep One pump in service    
  Line  up of LP/HP purge system is  checked . It should be  in isolated condition   
Emergency make up   valve CW 525  , drain valves SD 62 ,  supply valves SD61 are closed . Over head tank is  
   
filled & HI level  alarm persists . Other wise  fill  the O/H tank . 

Prepared By  Reviewed By Approved  By   Sheet 32 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
  Check in MMI all  alarms /indications    
  Check all three  CC pump  discharge valves  are  open  , warm up system is  lined  up .   
2.5  • ECONOMISER   
  Eco. SV is open. & selected  in maint  mode     
  Eco. Drain is closed   
  Eco  recirculation line  to Bottom Ring header is open , manual  valve  open     
2.6  • SH / RH SPRAY SYSTEM   
  SH /RH spray is lined  up  from respective  BFP 's    
  All  manual spray iso valves are open at  firing floor .   
  All drains /Vents at the station are closed.   
  Air supply to the Block valve and control valves are open.   
2.7  • ID FANS A & B    
  VFD AC system is in service ./ VFD room is clean .   
  Rectifier  room is clean  & AWU  for  rectifier  room  is in service .   
  VFD  source  breaker is racked in  &  alarm at VFD room is  reset .   
  VFD  breaker ( Load breaker)  racked  in .   
  Lub  Oil systems are in service ( LOP auto change over is checked )    
  Cooling water  system charged for Lub oil coolers  & Motor cooler (ID fan)    
  All damper  operation checked .   
  All  seal air blower & valves operation checked   
  Check the MMI  for all permissive  are  available    
2.8   • FD  / PA Fans  A& B    
  All Fan Breakers are racked in .   
  Lub oil  pump  change over  checked , one pump in service  .   
  SCAPH`s are lined up for all   FD/PA  fans. Return lines are lined up to IBD  tank .   
  SCAPH is  through & bypass  dampers are  closed .   
  Fan  discharge  duct. Drain  is  closed , if  it  was   opened.    
  Discharge  damper  operation is checked  & OK    
  Blade pitch operation checked & are  in remote  . Check links are  properly locked    
  Fans are lined up to take start.   
2.9  • ALL 4  NOS  APH   ( PRIMARY & SECONDARY)   
  All motor power supplies are available.   
  Air receivers are  charged. ( 4 nos)    
  Air motor lined up and all filters are having oil.   
  Soot blowers are available . Dry  Operation of SB  checked    
  Flue gas out let dampers  for both SAPH are open AND closed for Both PAPH`s.   
  All air side  dampers are  open BOTH inlet & outlet .   
  Thermocouples for hotspot detection  are OK  ( PAPH ‐  6 , SAPH ‐9 )   

Prepared By  Reviewed By Approved  By   Sheet 33 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
  Lub oil system in service  for GB/SB  , oil  level OK    
  Oil  carry over probe   is ready , cooling water  charged  , no leakage .   
  Cooling water  system charged  for oil carry over probe / Lub oil system   
  Fire Fighting system / APH water washing  system are properly isolated .   
  Fire fighting main root valve  at Zero Mtr  is  Open .   
  APRDS  HT hdr  charged & Aux steam to APH soot  blowing  is charged .   
2.10  • HFO/LDO  &  Atomising  air  & steam SYSTEM    
  Check all iso valves in oil system are open. ( in pipe trestle )   
  Check LDO is charged or while charging check for leakage.   
  FO is charged or while charging check for leakage. After  charging  monitor  recovery  oil  tank  level.    
  Short recirculation is open. Atomising air/steam are charged    
  Check Drain oil tank level .& available  of  oil pump.    
  Check the PCV are lined up.   
  Check all drains are closed.   
  Check all return line valves are open.    
  Check tracing steam is charged   
2.11  • BURNER SYSTEM   
  Scanner cooling air fan is in service .Note down pr. Check all  hoses are connected.   
  Check availability of DC  scanner air fan    
  All level iso. Valves for guns are open. &  guns  are  clamped in position.    
All  level  Burner  tilt is  horizontal  .   
 
  All igniters are in position and fixed to guide pipe.   
  Fire  hydrant  sprinkler  system is charged &  deluge  V/V  is kept on  auto .    
2.12  • MILLING SYSTEM :   
  • Coal  Bunkers    
  Ensure  CHP  is informed  about  coal bunkering . RHS  mills are  fed  first  then  the LHS  mills   
  All  Bunker  level indications are  correctly  indicating .   
  Status of Bunker outlet gates  & their power supply .   
  If feeders  PTW are  cancelled  then all the  bunker  oultlet gates  can  be  kept  opened .   
  • MILLS   
  Check  no of mills available for operation. Respective  HT BKRS are racked in. (3.3KV)   
  Lub Oil  system is in service . Oil level & pressure  adequate .  Changeover  of Oil  pumps are  checked    
  Cooling water  system for gear  box cooler   is lined up .   
Both Seal air fans   are available & Power supply normalised.  One  Seal air  fan  EPB is  kept pressed  to avoid 
   
auto start on PA fan starting . 
  Check MDV( locked ) , Burner isolation valves are open  for  the  available  mills    
  CAG/CAD, HAG/HAD are  lined  up . All Mech  locks are  removed .   
  Check in  the  Pulveriser interlock page the  criteria are  satisfied    

Prepared By  Reviewed By Approved  By   Sheet 34 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
  • FEEDERS  .   
  Check bunker outlet gates are open . Feeder  inlet  manual gates are  open  for available feeders .   
  Seal air  valves are ready .   
  Feeder  outlet gate  air  supply charged .   
  Bunkers are filled with coal (Confirm from CHP)   
  Coal flow established  in feeders .   
  • MILL REJECT HANDLING SYSTEM    
  Check  the  service air  charged  to  both  the  air receivers  at  boiler  “ 0 ”  mtr .   
  Check all  the  gates are  lined  up  properly .   
  Check  the  PLC system  is  in service    
  The  system is  selected   in  auto  mode    
2.13  • ESP PASSES  A/B/C/D   
  All 4 passes are charged from FG side. If  any  pass is  isolated record it .   
  All 4  ESP  transformers & ESP boards are independently charged .   
All auxiliaries are in service and all field power supplies are normalised and EC panel isolators are ON. 
   
• Hopper Heaters are  ON /Shaft & Support insulator heater are ON /Purge air  blower  IN SERVICE  . 
  Status of VFD /ESP AC plant . ESP  control room  is clean .   
  ESP Fields  not available record with  reason .   
Hopper level probe power supply extended and no HI or Above LO  level alarm is persisting in  ASPH Control 
   
Room. If any thing  is persisting  inform EMD accordingly . 
2.14  • BA HOPPER   
  All Man hole doors are closed for both hopper and CG.   
  BALP pumps are in  service for refractory cooling and seal trough make up.   
BA Hopper and seal troughs are filled and seal trough is overflowing. No ash settlement is there in seal trough. 
   
( Adjust pressure  to 1.2 Ksc ) 
  BAMCC  Both sections are  charged .All CG power supply is normalised .    
  BA LCP  is charged & OK  .    
  BAHP common valve is open position    
  Eco &  Eco Bypass  system  are  lined  up .   
  Settling bin  is  filled  & Sludge pump  is in service .   
2.15  • FA SYSTEM .   
  Check Instrument air is charged  from main  plant  Or  its  compressors  are  in  service .   
  Check AE SWGR  is charged independently .   
  Check settling  Bin  is  filled  &  ready  .   
  Check all auxiliaries are available and power supplies are normalised.   
  Keep the system lined up to take start before Boiler Light up . Started  at  Date / time    
  Run the  system  , Clear all hopper  mouth  & note down hopper empty  vacuum .   
  Ensure ESP fluidising  blower readiness  with  its  heater  . Keep  them  in service     

Prepared By  Reviewed By Approved  By   Sheet 35 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

3.0 TURBINE SIDE CHECKS. 
 
Checked 
ITEM  DESCRIPTION 
Status 
3.1  • CW SYSTEM / OLTC    
Check  Both  water  boxes are charged  & valves  open indication available  in MMI  , Selected in maintenance 
   
mode  . 
  Check  CW  Inlet  outlet  temp , DP , Flow etc    
  Power supply for OLTC  system is  ON and  system is lined  .   
  OLTC  screens are  in back wash position  .  To be taken in service position  before  ball charging     
3.2  • ACW SYSTEM    
  Check  2 ACW pumps are in service and 3rd pump is available on auto.   
  Note down the PHE  for TG  & SG ECW system  in service .                                        PHE    A/B/C   , A/B    
  Check that   both the Self  cleaning systems are  in service .   
  Ensure Standby  PHE  are  in  charged condition .   
  Check the  Short recirculation  valve  status , it  should  be closed .   
3.3  • DM makeup SYSTEM. (DM‐1)   
  Check adequate  no of DM makeup pump is running in DM plant .  Pressure =    
  Hotwell level is normal  + 450 mm  , normal makeup valve is lined upon & on auto.   
  Bypass  MOV  power  supply  Extended  , it  is operating  from  remote  .   
3.4  • Emergency Make Up  SYSTEM. ( DM ‐ 2 )   
  Check CST level is adequate .  >  6.0 mtr   
Emergency make up is lined up  & make up valve is on auto.  
   
Check the availability of CT pump. 
  Bypass  MOV  power  supply  Extended  , it  is operating  from  remote  .   
3.5  • TG ECW SYSTEM    
  Stand Pipes are  charged  after   flushing  .   
ECW Over head tank lvl is  normal  > 50 % . Both  makeup sources are  lined  up . CEP  line  valve  is throttle  to  
   
avoid  pressure  drop . 
  Check 2 TG ECW  pumps are in service and 3rd pump is available on auto.   
  Turbine side all  coolers are charged  & vented  properly .   
  Check the status of ECW supply & return line to Comp. House is  charged  from  which unit , & Record it    
  Check standby PHE  is in charged condition .   
  Check the  Chemical dosing of NAOH  system is ready  & solution is  available .   
  Inform Chemistry group to  check the  ECW  sample .   
  Put  the RCV  on auto .  Check all pressure  parameters .   
3.6  • SG ECW SYSTEM  .   
  Check  one  SG ECW pump is  in service and 2rd pump is available on auto.   
  Boiler side all  coolers  are charged  , vented  properly  .   
  Put  the RCV  on auto . DP  value  ,                                Suc / Disch  pr     
3.7  • CONDENSATE SYSTEM.   
  Hot well stand  pipes are  charged  after  flushing . ( Both side  stand  pipe )   
  Hot well lvl is normal  ( + 450 mm)  And normal makeup valve (DM‐1) is on auto.   
  Emergency make up is lined up  & make up valve (DM‐2) is on auto.   
  All LP heaters are  Lined up.   
Both D/A level control valves are available and bypass valve  supply  is healthy        ( Both  Manual valves in D/A 
   
level  CV  line are  open ) 
  Cond spill is lined up at  "0"  mt as well as near CST. ( Manual valve  near  CST  is open ) (Bypass valve  is closed )   

Prepared By  Reviewed By Approved  By   Sheet 36 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
  GSC  min RCV is lined up.( Bypass valve  is closed )   
  Following iso. Valves status  from  condensate  system to be  checked    
• LPBP spray  open  ( main isolation & individual valves). 
• APRDS spray open .  
• Boiler fill valve Closed. 
• LPT Exhaust hood spray is open . 
• TFT spray is open. 
• Valve gland sealing line charged ( PCV  maintains pressure at 8.0 ksc)  
  Check all available CEP  bkr racked in & RCV manual valves are open   
  Check CEP lined up mechanically & all 3 CEP start permissive are  available  .   
Start CEP after through check up By keeping the DV power supply off. Then after charging condensate system  
   
through from IBV , main valve is to be  opened . 
3.8  • VACUUM SYSTEM.   
  GSC lined  up  , Drain  to LPDFT lined  up .   
  GSEB  is  power supply ON , VP , VP CWP  Power supply ON  . VP suction manual valves  open ( 04  nos)   
  GS  steam Hdr Warm up drain valve open. MAW 10AA010 ( No man isolating Valve)   
  Seal steam system properly lined  up from HT PRDS / LTPRDS   ( temp > 265 0 C )   
  Separators are filled with water from  valve  gland sealing  hdr   , coolers are charged  from TG ECW  side .   
  Oil supply unit pumps for supply /leak‐off valves are  running . DP  < 5 ksc    
  Condensate  valve gland sealing system is charged  from CEP , PCV on auto  mode . Pressure  > 6‐8 ksc    
  SLC   vacuum  system is  ON.    
  Exhaust hood spray  is lined  up  , valve  operation  checked  .   
3.9  • CPU   
  Bypass valve is full open.   
  All vessels are  available ,take feedback from Chemist.   
  Inform Chemist to take CPU into service  after  steam dumping    
3.10  • CHEMICAL DOSING.   
  LP dosing pumps  availability ( both NH3 pumps  )   
  HP dosing pumps availability ( both pumps )   
  Solution level  in Tanks , Chemicals in metering tank .   
  Inform chemist to take hydrazine /NH3 pump after  light up .   
PO4  pump is to be started  after  attaining   boiler  pressure  > 30 ksc  based  on chemist   instructions . PO4 
   
valve  is opened  at  Drum level  
  All MOV to BFP suction are  open .   
3.11  • DEARATOR.   
  It is filed up to normal lvl. + 500 MM   
  Stand pipes are  charged ( 2 nos)   after  proper  flushing  . All  instruments are charged   from the Stand pipes     
  Check the three Level Transmitter  output  , not  much variation is there .   
  Make up line isolation valve  from boiler  fill line is closed .   
  All MOV to D/A power supply  healthy & selected  in Remote . All PCV `s are lined up.   
  Aux steam to FST /Deaerator  is charged from  LT  APRDS , FW storage tank heating started /to be started   
  The  temp. should  not be allowed  to go up when BFP is running on recirculation  more tan 95  deg cen .   
  Over flow line is lined up to LPDFT  . manual valve  open     
3.12  • MDBFP‐ C    
  FW side charged  for   BFP .   
  Oil system is  normal ,  AOP  available .    
  RCV available  . P&I check Completed  . RCV  air  supply  normalised  .   
  All  Temp elements are  available    

Prepared By  Reviewed By Approved  By   Sheet 37 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
  Cooling water  system  normalised    
  Motor CW  system OK   , Spray system  normalised .   
  DP Gauges  & other  Local gauges  OK  , Oil  sample  result  OK    
3.13  • TDBFP A/B  • A • B   
  FW side charged  for  both  BFP .       
  Oil system is  normal ,  DC EOP available . JOP  Running . DCEOP pressure  =       
  Governing system charged . EHC  Characteristics  checked  .       
  All turbovisory parameters  are available .       
  Turbine  with  pump engaged & on barring. ( 450 RPM)  / To be put on barring        
  Aux steam from HT hdr  is charged .       
  Gland steam charged and exhaust valve is open ( After  main  Turbine  Vacuum Pulling)        
  All manual & Motorised drain valves are open       
  Extraction manual block valve is open       
  Steam side both vent valves are open        
  Exhaust hood spray lined  up  , bypass  closed         
3.14  • FEEW WATER HEATERS    LPH/ HPH’S   
During  gravity  filling/initial  charging  it  self  charge  the  feed  water/  condensate  side  of  all  heaters  and  close 
   
respective bypass valves. 
  Ensure all iso. Valves of normal and emergency drip LVL CV are open   
  Check  power supply for all Block Valves and drain valves , FCNRV are ON   
  Manual drains are closed. Stand pipes are charged   
3.15  • FW SYSTEM  /FEED REGULATING STATION   
  Low Load CV bypass valve  FD ‐ 16 is closed . Power supply normalised & selected   in remote .   
  LLCV iso. Valves are open ( manual valve at outlet  of LLCV  is open )   
  Drains before and aft. CV are closed at 8.5 MTR   
Feed water is vented up to economiser area  through gravity filling by opening MDBFP discharge IBV.  All  line  
   
Vent &  Drains  closed . 
  All the FW heaters are in service from FW side. 100 % & 50 % Bypass valves are closed.   
  All HPH Stand Pipes  are  charged  after flushing     
  BFP‐C is in lined  up  condition  / started  on recirculation    
3.16  • TG LUB OIL SYSTEM   
  Check SLC  lub oil system is ON. Selected AOP /VEF  are in service.   
  MOT level is  normal  950 MM  from  top  of  tank .  ( With  barring gear  this  will  be  increased   by 75‐ 80  MM    
  Check Availability of DCEOP. Note  down local pressure .   
Cooler is charged from water side. TCV  is on auto . other  Cooler  is  filled  from  both oil & water  side  . Cooler  
   
Changeover  Carried  out   
Status of Lub filter to Bearings  in service and stand by filter, if choking tendency is there then changes over and 
   
clean it and make available before turbine Rolling.  
  Check Return oil flow in all the bearings.   
  Jacking oil system is in service , filter clean , pressure > 165 KSC  . SLC On .   
  Centrifuge is  available  &  in service .   
  Mot sprinkler  system is  charged  &  deluge  V/V is  on manual     
  Check  The  Leakage Oil Pump is  available & Dirty Oil  tank  emptied    
  Monitor the waste oil  tank level otherwise  drain  it  to empty oil drum outside the CFT  room    
  Oil canal sprinkler system is  charged & on auto .   
3.17  • CONTROL FLUID  SYSTEM    
  CFT level is  normal  700 MM  from tank  top .  (  Total range  is  1600 mm)   
  Selected CFP  /VEF  are in service. Regeneration pump in service.   

Prepared By  Reviewed By Approved  By   Sheet 38 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
  Check SLC  CF  system is ON.   
Coolers are  charged from water side and note down the FRF  temp after cooler. TCV  is on auto . ( auto set point  
   
is 55 0 C ) . Cooler  changeover  carried  out  . 
  LPBP  & Governing racks are  charged . EHC  isolating  valves are  open .   
  All self cleaning strainers are cleaned  by rotation & they are  free  to rotate .   
3.18  • GOVERNING SYSTEM    
  Check power supply normalised  for   SD/SG /OS trip Test Device , Trim SV , Other Extraction SV  ,  etc .     
  EHC oil line  valves  are  open . ( Before  Rolling Ensure This)   
  Stop valve Test  Valves  are  Open . (Normally kept closed  during the EHC characteristic checking )    
  Plunger  Coil power supply  made ON by C&I   
  No TSC  fault  in console .   
  All temp. parameters are available  in BHEL MMI .   
3.19  • HPBP SYSTEM    
  OSU`s  are in service. ( 2 nos )  , oil level adequate . No fault in CRT .   
  Manual spray iso valve is to be  opened after  charging  , observe  temp drop after  charging .    
  Manual drains are closed.   
  Warm up line  drains  are open. ( BP 101/102 ) to  AFT near  AFT  .   
Warm up lines  are  open  with  their  respective  manual  valves  in  8.5  mtr  level . 
   
BP 03/04  ( LBF 12AA201/ LBF 22AA201 ) 
  Check the Temp & Pressure Set points  for  HPBP system  ( 2800C / 60 ‐ 65 Ksc )   
3.20  • LP BP SYSTEM    
  LPBP system governing rack  is  charged  & all isolating   valves  in  impulse  lines  also  open  .   
  LPBP Drain pot drains are  Open HRH 109/HRH 110   
  LPBP warm up valves are open . LP 625/LP 624   
  Drains at 17 mtr  (near  Gov rack Opposite ) is closed   
LPBP spray line  main isolation valve  from  condensate  system is open at 8.5 mtr , Bypass manual valves are 
   
closed . 
3.21  • SEAL OIL SYSTEM   
SOT / SOST levels  are adequate.  ( SOT – level  should be >/ 250 mm) . Purge Selection  is deselected after H2 
   
pressurisation . 
  Any  one  AC SOP is  in service and SLC  is ON   
  H2 side sea oil pump is  in service  & SLC  ON    
  Any one  BCEB is in service.   
  AS/H2 side Coolers are charged. Check the oil  Filters are clean  .   
  Check  the  DPR  line  up  is  OK  , Check the SO pressure & DP  ( 1.7 ksc)   
  SOS  Sprinkler system deluge V/V is on auto.  ( Isolation  Valve  GT  side )   
3.22  • GAS  SYSTEM   
  All  4 H2 coolers  are charged  & vented properly .   
  H2 pressure is > 3.3 kg/cm2. (  For  Better  DP control , after  synchronisation pressure  should  be made  3.5 ksc)   
  No of H 2 / CO 2 Cylinder connected to rack                           Cylinder  locking provision in place    
  No H 2 /CO2 stock.  etc.     
  Emergency CO2 cylinders available.  (  At least  50  cylinders )    
  H2 purity.> 98%  matching  with  ORSAT  reading  by chemistry .   
  Check all LLD’s are OK before TG  set rolling .   
  Check the H2   TCV  is on auto &  Operating .   
  Check the  H2  drier all auxiliaries power supply  normalised    

Prepared By  Reviewed By Approved  By   Sheet 39 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
  Check  CO2 flash evaporator Power supply made OFF .    
3.23  • STATOR WATER SYSTEM.   
  OH tank level is adequate  > 200 MM  to 250 MM    
  One pump is in service & stand by available. Check  the  availability .   
  Flow through winding  > 60  M3/hr.  ADJUSTED  , BYPASS  VALVE  FULLY CLOSED  & LOCKED (TIED )   
  Flow through bushing >1.89  m3 /hr   
  Conductivity  in main ckt   =  2.0   , Regen  Ckt  <  1.2  ms/cm  start > 2.5   stop    
  N2 capping pressure  =  0.2 ksc , N2 cylinder  connected  , N2 cylinder  available ‐    
Alkaliser  Unit  Power supply is ON  &  System is in service . NAOH tank   level is adequate . Pump is operating  on 
   
auto mode  ( 2.5.0 ms/cm  OFF /1.2 ms/cm ON )  
3.24  • Main  TURBINE   
  Check  TG is on barring gear and SLC  is on. ( speed 70/100 RPM)   
  Turbine is  reset. ( Starting Device  is 0 % , speeder gear  100 % )   
  All temps. /turbo supervisory parameters are ok    
  All fixed point  / local expansion readings are  taken .   
  Hand barring gear lever is available.   
  CRH NRV  , FC  NRV  SV   power supply  is through  , Feed back is  coming  in CRT .   
Fixing  of acoustic  Cover   , inside  area  cleaning  , approach  to  8.5 mtr  from  17 Mtr  , etc  Power supply & 
   
lights  inside . 
• Turbine    DRAIN  SYSTEM    to    UFT  /  SDFT  /  Flash  box  /LPDFT/HPDFT  (  Annexure    is 
3.25   
attached )  
  UFT  vent  to D/A  Floor  U loop drain  is open  near  the column ( in front  of  TDBFP‐ A )   
  Check all the  Drain MOV  manual valves  are  open as  per check ,list  .   
  Atmospheric drains are  open    
  UFT  drains are  lined  up     
st
1   all drains  to  be  lined  up  to  UFT  , after  sufficient dumping  , they are  to  be  taken  to  system  to reduce   
   
Silica / Iron  Parameters  in condensate  system . 
  Check the  spray system  is lined up the  respective  flash tank/box .   
  Check all other  lines leading to flash tank manual valves are  open ( Drain line  & drip lines )   
  ♦ ATMOSPHERIC DRAINS  TG “0” Mtr   
  MS  LINE   /HRH LINE /CRH LINE /LPBP LINE  DRAIN    
  ♦ UNIT FLASH TANK   
  BP 101 /BP 102/MS 419/MS 101/MS 102/HRH 101/HRH 102/HRH 604   
  ♦ STARTUP DRAIN FLASH TANK   
MS 105/MS 106/MS 417/CRH 101/CRH 501/HRH 105/HRH 106 
   
HRH 606/LP 625/LP 624/HRH 109/HRH 110 
  ♦ TURBINE DRAIN ( FLASH BOX – 1 Towards SWYD )   
  MAL 11/MAL 26/MAL 65/MAL 31/MAL 32/MAL 22   
  ♦ TURBINE DRAIN ( FLASH BOX – 2 Towards Boiler )   
  MAL 12/MAL 27/MAL 47/MAL 51/MAL 52/MAL 54/MAL 81/MAL 55   
  ♦ HP DRAIN FLASH TANK   
  EX 105/AS 122/AS 104/AS 109/CRH 129/CRH 141/CRH 135/CRH 147/CRH 109/CRH 116/CRH 123/EX 101/EX 102   
  ♦ LP DRAIN FLASH TANK   
  CRH 153/EX 109/EX 115/EX 110/EX 112/AS 113/AS 114   
3.26  • AUX. PRDS SYSTEM ( From OWN system)   
  Check both LT/HT  hdr is charged / to be charged from common hdr.   
  Check line up from  MS line.   
  Check line up from  CRH line .   

Prepared By  Reviewed By Approved  By   Sheet 40 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Checked 
ITEM  DESCRIPTION 
Status 
  Check the isolation of  spray water  from  the   Condensate & Feed water  system .   
  Keep all drains open while charging.   
  Check AS‐46 Commissioned    
  MS to PRDS manual valve in closed  position .    
  All steam traps are lined  up , Bypass  is  closed  .   
3.27  • DEWATERING system    
Check both the  de watering pumps are available. Power supply is on  & selected on auto . (  Both diverted to C 
   
row drain ) 
  Level  Switch is functioning  , tripping on Auto interlock .   
  Cond. Pit level normal.   

Prepared By  Reviewed By Approved  By   Sheet 41 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

4.0 GENERATOR AND ELECTRICAL SYSTEMS 
 
Checked 
ITEM  DESCRIPTION 
Status 
4.1  • Main  GENERATOR   
  All GRP  relays are  reset . ( 186 A1/286A1/186A2/286A2/186B/286B/186C/286C)   
  ALL 4  H 2  Coolers are charged . (4 nos)    
  Exciter coolers are charged  02  nos    
  Gen casing  is under pressurised condition  with H 2  pressure  >  3.3 ksc.  ,H 2 purify  ok.  >  98 %   
  Exciter auxiliaries , stroboscope  etc are  ready .   
4.2  • GCB   
  GCB DC power supply is normalised    
  GCB earth switch is open    
4.3  • BUS DUCT PRESSURISATION SYSTEM   
  Pressurisation system is in service & flow < 45 cu mtr   
4.4  • GT R/Y/B   , UT A/B   
  GT is to be  back charged  after  Electrical testing  .    
  Status of Middle Breaker   if connected  with start‐up XFMR    
  Check on manual mode all fans /oil pumps are available for GT and UT.    
  Marshalling box both feeders are charged. ( From SSSWGR – GT / SACDB – UT )    
  OLTC  is made off .    
Sprinkler  system  kept  charged & deluge V/V is  on  auto .  
   
Check the sensing line  Pressure  R/Y/B  =                 ,UT A/B  =   
  UT A/B incomer breaker  to be racked  in after  elect test  completion    
  UA /UB bus  to be  charged  from UT  before  Unit  synchronisation .   
4.5  • 400 kv system EARTH  SWITCH / ISOLATOR   
  Check earth switch is opened from switchyard Engineer   
  Isolators  for both 400kV bus are closed.   
• Status  of MCC /SWGRS as per  check list   attached . ( Annexure ‐ 3  ) 
4.6   
• All  charged  breakers  No fault  should  flicker  . 
4.7  • DG set  system   :‐    
♦ Availability of Own DG  set. 
♦ Availability  Stand  by DG  set  
   
♦ Oil level  in Main & stand  by  DG set  (> 80 % ) 
♦ DG set  breakers at  EMCC  end  are racked  in DC ON  (  both Main & stand  by ) No Fault  in  Breakers  
4,8  ♦ ELECTRICAL  CHARGERS   :‐    
  Status  of  Diff. DC  chargers  as per  check list  attached .  ( Annexure ‐ 4  )   
4.9  ♦ CABLE GALLERIERS / FIRE FIGHTING SYSTEM  :‐    
  Status of  cable  gallery  sprinkler  system.  / others as per  ( Annexure ‐ 5  )   
 
 
 

Prepared By  Reviewed By Approved  By   Sheet 42 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Prepared By  Reviewed By Approved  By   Sheet 43 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

ANNEXURE‐1 
Operation  Department. 
Gist of Unit Cold Start Up  Activities 
Unit 3/4/5/6                           Stage – II Units ( 4x500 mw)                                    Date : 
Sl.No  Activities  Time   Remarks 
1.   Clearance for Boiler light up.     
ST
1  SET     
2.   ID/FD fan starting.  ND
2  SET      
3.   MDBFP Running.     
4.   Drum Level Normal      
5.   CC pump  in service      
6.   Boiler purge complete.     
7.   Vac. Pulling  (Start /Complete )     
8.   BLU (Boiler Light‐up).     
9.   Drum vent closing.( > 2.0 Ksc)     
10.   SH  drains  closing  ( > 6.0 ksc)     
11.   MS SV open ( MS  line  Charging).> 7.0ksc      
12.   HP/LP by pass charging. ).>/10.0ksc     
0
13.   Parameter reached for TG  set  Rolling . (65 ksc  / 350   C )     
14.   Chemical Parameters  OK      
15.   Roll to 360 rpm.     
16.   TDBFP A Rolling to 1000 RPM .     
17.   TDBFP B Rolling to 1000 RPM .     
nd
18.   2  set of ID/FD fan taken in service     
19.   1st PA fan starting .     
20.   Cutting in  of  1st  Mill . ( Mill ‐ B)     
21.   Roll to 3000 rpm     
22.   Unit Synchronization     
nd
23.   Cutting in  of  2    Mill . ( Mill –C )     
24.   LPH 2&3 /HPH5&6 /Ext ‐ 4 to D/A charging     
rd
25.   3  mill + 3  elevation  oil      
26.   FW Hi Range valve opening ( FD‐16)     
27.   2nd PA fan starting  ( After 3 Mills PA  flow)      
28.   One TDBFP  loading ( 200 MW)     
th
29.   4  mill + 2 elevation oil     
th
30.   5  mill + 1 elevation oil     
nd
31.   2  TDBFP  loading   ( 350 MW)      
0
32.   ESP  fields  charged  ( ESP inlet temp 120 C)     

Prepared By  Reviewed By Approved  By   Sheet 44 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

33.   MDBFP Unload / stop      
th
34.   6  mill + oil with drawl      
35.   Full load achieved      
 
( Signature  Of  Unit  Control  Engr )    

Prepared By  Reviewed By Approved  By   Sheet 45 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

ANNEXURE‐2 
OPERATION  DEPARTMENT  
Oil Gun  Cutting In /Out Monitoring Sheet 
 
Unit    3/4/5/6                    Date : 
 
Total Guns  + Mills  
Remarks 
Sl  Guns Cut  In service 
Time   Elevation  Guns Cut Out  Mills Cut In 
no   IN 
Gun  Mill   

 
1.              
 
2.              
 
3.              
 
4.              
 
5.              
 
6.              
 
7.              
 
8.              
 
9.              
 
10.              
 
11.              
 
12.              
 
13.              
 
14.              
 
15.              
 
16.              

 
 
 

Prepared By  Reviewed By Approved  By   Sheet 46 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

 
 
(Signature  Of  Boiler Desk Engr)    

Prepared By  Reviewed By Approved  By   Sheet 47 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

 
ANNEXURE ‐ 3 
OPERATION  DEPARTMENT 
 
MCC/SWGR  NORMALISATION STTAUS  MONITORING SHEET 
 
Unit‐ 3/4/5/6                      Date  
STATUS  Provision  STATUS 
Sl.  Description Of  Sec ‐ A 
Location  OF  of bus  Sec‐ B Incomer From  OF 
No.  MCC/SWGR  Incomer From 
INCOMER  coupler  INCOMER 

1.   UA  3.5 mtr  UT ‐A    NO  TIE BKR FROM  SD   

2.   UB  3.5 mtr  UT ‐B    NO  TIE BKR FROM  SD   

3.   UAA/ UAB  3.5 mtr  UAT‐A    YES  UAT‐B   

DG – 4/5/78 
4.   UES  12.5 Mtr.  USS – A    NA   
DG ‐ 6/9 

5.   USS  12.5 Mtr.  UST ‐ A    YES  UST ‐ B   

SST – B 
6.   SSS  12.5 Mtr.  SST ‐ A    YES   
(FROM #6) 

7.   TMCC  12.5 Mtr.  USS – A    YES  USS‐B   

8.   TACDB  12.5 Mtr.  USS – A    YES  USS ‐ B   

Auto Stand 
9.   TVDC  12.5 Mtr.  USS ‐ A    UES   
by 

10.   SACDB  12.5 Mtr.  SSS ‐ A    YES  SSS ‐ B   

11.   220 V DCDB  12.5 Mtr.  Bat Ch‐ 1    YES  Bat Ch‐ 2   

12.   220 V DC SVDB  12.5 Mtr.  DCDB    NO     

13.   AWMCC  12.5 Mtr.  USS ‐ A    YES  USS ‐ B   

14.   AC MLDB  12.5 Mtr.  USS ‐ A    YES  USS ‐ B   

Prepared By  Reviewed By Approved  By   Sheet 48 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

STATUS  Provision  STATUS 


Sl.  Description Of  Sec ‐ A 
Location  OF  of bus  Sec‐ B Incomer From  OF 
No.  MCC/SWGR  Incomer From 
INCOMER  coupler  INCOMER 

15.   AC LIGHTING  12.5 Mtr.  USS ‐ A    YES  USS ‐ B   

16.   Vent /AHU  12.5 Mtr.  USS ‐ A    YES  USS ‐ B   

17.   BLR MCC  26.5 Mtr.  USS ‐ A    YES  USS‐B   

COAL MILL 
18.   26.5 Mtr.  SSS ‐ A    YES  SSS ‐ B   
MCC 
Auto Stand 
19.   BVDC  26.5 Mtr.  USS – A    UES   
by 
Auto Stand 
20.   BDDC  26.5 Mtr.  USS ‐ B    UES   
by 

21.   BACDB  26.5 Mtr.  USS‐A    YES  USS‐B   

22.   SBMCC  26.5 Mtr.  BACDB ‐ A    YES  BACDB ‐ B   

23.   AC SV DB  26.5 Mtr.  BACDB ‐ A    NO  BACDB ‐ B   

ESP  ESP SERVICE 
24.   ESP BOARD ‐A    YES  ESP SERVICE XFMR ‐ B   
SWGR  XFMR ‐ A 
ESP  ESP SERVICE 
25.   ESP BOARD ‐B    YES  ESP SERVICE XFMR ‐ B   
SWGR  XFMR ‐ A 
ESP  ESP SERVICE 
26.   ESP BOARD ‐C    YES  ESP SERVICE XFMR ‐ B   
SWGR  XFMR ‐ A 
ESP  ESP SERVICE 
27.   ESP BOARD ‐D    YES  ESP SERVICE XFMR ‐ B   
SWGR  XFMR ‐ A 
ESP pass‐A   ESP 
28.   ESP BOARD‐ A    YES  ESP BOARD‐ A   
ACP  SWGR 
ESP pass‐B   ESP 
29.   ESP BOARD‐ B    YES  ESP BOARD‐ B   
ACP  SWGR 
ESP pass‐C   ESP 
30.   ESP BOARD‐ C    YES  ESP BOARD‐ C   
ACP  SWGR 
ESP pass‐D   ESP 
31.   ESP BOARD‐ D    YES  ESP BOARD‐ D   
ACP  SWGR 
ESP A/C 
32.   ESP A/C MCC  ESP BOARD ‐ A    YES  ESP BOARD ‐ B   
Room 

Prepared By  Reviewed By Approved  By   Sheet 49 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

STATUS  Provision  STATUS 


Sl.  Description Of  Sec ‐ A 
Location  OF  of bus  Sec‐ B Incomer From  OF 
No.  MCC/SWGR  Incomer From 
INCOMER  coupler  INCOMER 

33.   AEMCC   VPH  AE XFMR ‐ A    YES  AE XFMR ‐ B   

34.   CW MCC ‐ 3&4  CWPH  SW MCC ‐A    YES  SWMCC‐ B   

CW MCC ‐  
35.   CWPH  SS SWGR ‐ # 6    YES  CT MCC‐ 5   
5&6 

36.   CT MCC – A  CT MCC  CT XFMR ‐ A    Standby  CT XFMR ‐C   

37.   CT MCC ‐ B  CT MCC  CT XFMR ‐ B    Standby  CT XFMR ‐C   

 
 
ANNEXURE ‐ 4 
OPERATION  DEPARTMENT 
 
UNIT‐ 3/4/5/6     Status of  Battery & Battery Chargers   DATE  :‐  
Each 
No.O Charger  Cell  Power Supply Source 
Amp 
Sl.No.  Description  f  Max     Checked status  
Hrs.  Amp 
 Cells  Current  Volta SWGR  Module 
ge  Rating 

1  220V DC‐1  990  169  400  1.4  USS  12.4F  250   

2  220V DC‐2  990  169  400  1.4  EMCC  7.4F  250   

3  UPS‐1     1.4  USS  2.4F  250   


383  294 
4  UPS‐2     1.4  EMCC  5.8F  250   

5  24V TG Charger‐1  576  1.4  USS  2.12F  160   


810  19 
6  24V TG Charger‐2  576  1.4  EMCC  5.4F  160   

7  24V TG Charger‐3  576  1.4  USS  14.8F  160   


810  19 
8  24V TG Charger‐4  576  1.4  EMCC  6.4F  160   
2R‐B 
9  24V SG Charger‐1  705  19  508  1.4  BACDB      
 1.14R 

Prepared By  Reviewed By Approved  By   Sheet 50 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

10  24V SG Charger‐2  508  1.4  EMCC  9.18F  160   


9F‐B 
11  24V SG Charger‐3  508  1.4  BACDB      
 7.3R 
705  19 
12  24V SG Charger‐4  508  1.4  EMCC  5.4R  160   

13  24V C&I Charger‐1  942  21  800  1.4  USS  3.6F  250   

14  24V C&I Charger‐2  942  21  800  1.4  EMCC  6.8F  250   

15  12V DG SET 4/7  360  2     12  EMCC         

16  12V DG SET 5/8  360  2     12  EMCC  9.11F  63   

17  12V DG SET 6/9  360  2     12  EMCC         

18  12V Disel Fire BP  75  20     1.4          

Prepared By  Reviewed By Approved  By   Sheet 51 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

ANNEXURE ‐ 5 

OPERATION  DEPARTMENT 
 
DETAILS OF MULSIFIER SYSTEM  ISOLATION VALVE STATUS  
UNIT‐ 3/4/5/6                   DATE  :‐  
 
No of 
Location of  No of  Isolatio
Sl  isolatio Present 
  the Deluge  Deluge  n valve 
no  n  Status  
valve  valves  status  
valves 
• HVW spray system 
           
• High (Medium velocity spray) 
1.   Generator transformers R/Y/B  ( 21/400 KV)  Near  GT   3  3  Open    

2.   Unit transformers ( 21/11 Kv)  Near UT   2  2  Open    

3.   Station transformers   3 / 4 ( 400 /11 Kv)  Near  ST   1  1  Open    

4.   Unit  auxiliary transformer ( 11/3.3 Kv)  Near UAT   2  2  Open    


Near  A  
5.   Main Turbine lube oil tank  (MOT)  1  1  Open    
row  
Generator seal oil unit and generator seal 
6.   Near   GT  1  1  Open    
oil pumps. 
Turbine  Driven Boiler feed pump  lube oil  Near  C 
7.   1  1  Open    
system consoles  Row  
Near   A  
8.   Oil canals   ( Below  17 Mtr )  1  1  Open    
Row  
Central oil purifier room / clean & dirty oil  Near  C  
9.   1  1  Open    
tank  (applicable to Unit ‐ 3  only )  Row  
Near  BA  
10.   Boiler burner fronts   1  1  Open    
hopper 
• MVW spray system 
           
• (Medium velocity spray) 
11.   Cable galleries   “0” Mtr  “C” Row  2  2  Open    

12.   Cable galleries   “ 5.5 ” Mtr  “C” Row  2  2  Open    

13.   Cable galleries  “ 8.5 ” Mtr  “C” Row  2  2  Open    

14.   Cable galleries  “ 13.5 ” Mtr  “C” Row  2  2  Open    

15.   Cable galleries  “  24.0 ” Mtr  “C” Row  2  2  Open    

Prepared By  Reviewed By Approved  By   Sheet 52 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Cable galleries of ESP Building cable  Near ESP 
16.   2  2  Open    
galleries  Building 

Prepared By  Reviewed By Approved  By   Sheet 53 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

ANNEXURE ‐ 6 
OPERATION  DEPARTMENT 
 
TURBOVISORY  PARAMETERS  MONITORING  LOG  SHEET 
UNIT‐ 3 /4/5/6                DATE :‐ 
Sl. BARRING  LOAD at 
Description of parameters.  UNIT  360  rpm  3000  RPM 
No  GEAR  500 Mw 
33.   TIME  Hrs   
  • DIFF EXPANSION           
34.   HPT (F) ‐5.0 &+3.5   mm  
35.   IPT (R) ‐1.0 &+5.5   mm  
36.   LPT(R) ‐3.0 &+35   mm  
37.   • AXIAL SHIFT           
38.   Point (1) +/‐ 0.5 & +/‐ 1.0  mm  
39.   Point(2)  mm  
40.   Point(3)  mm  
41.   • OVERALL EXPANSION            
42.   HPT (F) ( 0‐30 MM)  mm  
43.   IPT (R)  ) (0‐20 MM)  mm  
  • BRG. VIBRATION    >42 µ         
44.   HPT (F)  1X/1Y  micron  
45.   HPT (R)2X/2Y  micron  
46.   IPT (R)  3X/3Y  micron  
47.   LPT(R)  4X/4Y  micron  
48.   GEN(F)  5X/5Y  micron  
49.   GEN(R)  6X/6Y  micron  
50.   EXC(R)  7X/7Y  micron  
  • SHAFT VIBRATION    >100µ         
51.   HPT (F)  1X/1Y  micron  
52.   HPT (R)2X/2Y  micron  
53.   IPT (R)  3X/3Y  micron  
54.   LPT(R)  4X/4Y  micron  
55.   GEN(F)  5X/5Y  micron  
56.   GEN(R)  6X/6Y  micron  
57.   EXC(R)  7X/7Y  micron  
  • Turbine  Brg. Temp.    110/130         

HPT (F)   TL  Point 1,2  C  
58.   0 
    TR  Point 3,4  C  

HPT (R)  BL  Point 5,6  C  
59.   0 
    BR  Point 7,8  C  

T Bearing  FL/FR  Point 9,10   C  
60.   0 
                  RL/RR  Point 11,12   C  

61.   IPT (R)  Point 13,14  C  

Prepared By  Reviewed By Approved  By   Sheet 54 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 


62.   LPT (R)  Point 15,16  C  

Point 17,18  C  
63.   GEN (TE)  0 
Point 19,20  C  

Point 21,22  C  
64.   GEN (EE)  0 
Point 23,24  C  

Point 25,26  C  
65.   Exciter Brng.  0 
Point 27,28  C  
 

Prepared By  Reviewed By Approved  By   Sheet 55 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

ANNEXURE‐ 7 
Boiler  Side  Important  Parameters  
 
Sl no  Parameters/Time   Unit         

1.   Total Air flow  (t/hr)         

2.   O2 % at SRAPH‐A/B i/l  %         

3.   Boiler Drum   Pr./MS Pr.   (Ksc)         

4.   MS Temp L/R   .(0C)         

5.   HRH Pr. L/R   Ksc         

6.   HRH temp L/R.  .(0C)         

7.   FST FW temp   .(0C)         

8.   FW flow at ECO i/l    T/Hr         

9.   PRAPH‐A air i/l Temp   (0C)         

10.   PRAPH‐B air i/l temo  (0C)         

11.   SRAPH‐A air I/L Temp   (0C)         

12.   SRAPH‐B air I/L Temp   (0C)         

13.   PRAPH‐A air O/l Temp   (0C)         

14.   PRAPH‐B air O/l Temp   (0C)         

15.   SRAPH‐A air O/L Temp   (0C)         

16.   SRAPH‐B air O/L Temp   (0C)         

17.   PRAPH‐A FG I/L Temp   (0C)         

18.   PRAPH‐B FG I/L Temp   (0C)         

19.   SRAPH‐A FG I/L Temp   (0C)         

20.   SRAPH‐B FG I/L Temp   (0C)         

Prepared By  Reviewed By Approved  By   Sheet 56 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Sl no  Parameters/Time   Unit         

21.   SRAPH‐A FG O/L Temp   (0C)         

22.   SRAPH‐B FG O/L Temp   (0C)         

23.   PRAPH‐A FG O/L Temp   (0C)         

24.   PRAPH‐B FG O/L Temp   (0C)         

25.   PRAPH‐A air side DP  mmwc         

26.   PRAPH‐B air side DP  mmwc         

27.   SRAPH‐A air side DP  mmwc         

28.   SRAPH‐B air side DP  mmwc         

29.   PRAPH‐A FG side DP  mmwc         

30.   PRAPH‐B FG side DP  mmwc         

31.   SRAPH‐A FG side DP  mmwc         

32.   SRAPH‐B FG side DP  mmwc         

33.   PRAPH‐A CURRENT  Amp         

34.   PRAPH‐B CURRENT  Amp         

35.   SRAPH‐A CURRENT  Amp         

36.   SRAPH‐B CURRENT  Amp         

37.   SH metal temp. .(max)  (0C)         

38.   RH metal temp. .(max)  (0C)         

39.   Aux. Steam Pr.  Ksc         

40.   Aux. Steam temp.  (0C)         

41.   LDO pressure  ksc         

42.   HFO pressure  ksc         

Prepared By  Reviewed By Approved  By   Sheet 57 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Sl no  Parameters/Time   Unit         

43.   Atomising steam pressure   ksc         

Prepared By  Reviewed By Approved  By   Sheet 58 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

STEAM    PARAMETERS  MONITORING  LOG  SHEET 
 
Sl  Before  Before 
Description of the parameters  Unit  On Load 
no  360 rpm  3000 rpm 
  • steam parameters             
01. MS silica   PPM         
02. Main Steam Pressure Before ESV # 1  kg/cm2         
03. MS Temperature Before ESV # 1  0
C         
04. MS Temperature Before ESV # 2  0
C         
05. HP Turbine First Stage Pressure  kg/cm2         
06. HP Turbine Exhaust Pressure  kg/cm2         
07. HP Turbine Exhaust Temperature  0
C         
08. Status of HPBP (Auto/Man)           
09. HPBP opening L/R  %         
10. HPBP down stream temp L /R  0
C         
11. HRH Steam Pressure Before LPBP  kg/cm2         
12. CRH PRESSURE  kg/cm2         
13. CRH TEMP  0
C         
14. HRH Steam Pressure Before IV 1  kg/cm2         
15. HRH Steam Temperature Before LPBP  0
C         
16. HRH Steam Temperature Before IV1  0
C         
17. LPT INLET PRESSURE  kg/cm2         
18. Status of LPBP (Auto/Man)           
19. LPBP opening L/R   %         
20. LPBP down stream temp L /R  0
C         
21. LPT Exhaust  Hood temp  0
C         
22. LPT  outer casing metal temp.  0
C         
23. Condenser pressure    
       
24. Ext‐ 2 pressure   
       
25. Ext‐2 temp   
       
26. Ext‐ 3 pressure   
       
27. Ext‐3 temp   
       

Prepared By  Reviewed By Approved  By   Sheet 59 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Sl  Before  Before 


Description of the parameters  Unit  On Load 
no  360 rpm  3000 rpm 
28. Ext‐ 4.1 pressure   
       
29. Ext‐4.1  temp   
       
30. Ext‐ 5 pressure   
       
31. Ext‐5 temp   
       

Prepared By  Reviewed By Approved  By   Sheet 60 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

 
ANNEXURE‐8 
 
TURBINE METAL TEMP & DRAIN TEMP.  MONITORING LOG  
 
Sl  Barring  360 
Description of the parameters  Unit  3000 rpm  load 
no  gear  rpm 
  • Turbine Metal temp  points            
32. HPSV   TI/TM   (1)  0
C         
33. HPCV   TI/TM   (1)  0
C         
34. HP CASING  TI/TM (3)  0
C         
35. HP SHAFT   TI/TM (4)  0
C         
36. IP SHAFT   TI/TM (5)  0
C         
37. Temp  Margin Upper/Lower   0
C         
38. RPM/Min Upper/lower  RPM         
39. MW  /Min  Upper /Lower   MW         
  • Temp Margins available   
 
       
40. MSV  Upper/Lower  0
C         
41. MCV Upper/Lower  0
C         
42. HPC  Upper/Lower  0
C         
43. FPS    Upper/Lower  0
C         
44. IPS     Upper/Lower  0
C         
45. Speed   Upper/Lower  RPM         
46. Load    Upper/Lower  MW         
  • Temp DT  monitoring  points            
47. HP Casing  Top‐ Bottom  90/1000C  0
C         
48. IP Casing  Top‐ Bottom  (F) 30/450C  0
C         
49. IP Casing  Top‐ Bottom  (R) 30/450C  0
C         
50. HP casing  Top  0
C         
51. HP casing  Bottom   0
C         
52. IP casing  Top  (F)  0
C         
53. IP casing  Bottom  (F)  0
C         
54. IP casing  Top  (R)  0
C         

Prepared By  Reviewed By Approved  By   Sheet 61 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Sl  Barring  360 


Description of the parameters  Unit  3000 rpm  load 
no  gear  rpm 
55. IP casing  Bottom  (R)  0
C         
56. LP Outer Casing Rear  Metal temp  0
C         
 
0 0
57. HP exhaust  temp     485/500 C  C       

  • Drain Line temp   points            
58. Before  HPCV – 1 (MAL‐ 11)    0
C         
59. Before  IPCV – 1 (MAL‐ 26)    0
C         
60. HP Casing drain (MAL‐ 22)    0
C         
61. After  IPCV – 2 (MAL‐ 32)    0
C         
62. After IPCV  – 1 (MAL‐ 31)    0
C         
63. Before  HPCV – 2 (MAL‐ 12)    0
C         
64. Before  IPCV – 2 (MAL‐ 27)    0
C         
Warm up drain valve in seal steam supply    0  
65. C       
line  (MAW ‐ 11)  (AS 122) 
66. Ext – 5 drain  A5  (MAL‐ 47)    0
C         
67. Ext – 4.1 drain  A4.1 (MAL‐ 51)    0
C         
68. Ext – 4.2 drain  A4.2(MAL‐ 52)    0
C         
69. Ext – 3 drain  A3 (MAL‐ 54)    0
C         
70. Gland steam  Hdr  (MAL‐ 81)     
       
71. Ext – 2drain  A2(MAL‐ 55)    0
C         
72. NRV CRH  LHS  (MAL‐ 65)    0
C         

Prepared By  Reviewed By Approved  By   Sheet 62 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

 ANNEXURE‐9 
TG AUX   PARAMETERS  MONITORING  LOG  SHEET 
 
Sl 
Description of the parameters  Unit  Barring  360 rpm  3000 rpm  Load 
no 
  • Lub oil system           
01.   MOT tank level. (900/ 950/1000/1050)  Mm         

02.   Lub oil pump discharge pressure.(<4.5)  Ksc         

03.   Lub oil discharge hdr pr. after cooler.  Ksc         


0
04.   Lub oil disch. Hdr temp before cooler.  C         
0
05.   Lub oil disch. Hdr temp after cooler.  C         

06.   Lub oil TCV position.  %         

07.   JOP disch. Hdr pressure.( <145/140)  Ksc         


0
08.   Lub oil return temp brg. ‐1 (HPF)  C         
0
09.   Lub oil return temp brg.‐2 (HPR)  C         
0
10.   Lub oil return temp brg.‐3 (IPR)  C         
0
11.   Lub oil return temp brg. ‐4 (LPR)  C         
0
12.   Lub oil return temp brg.‐ 5 (GEN‐TE)  C         
0
13.   Lub oil return temp brg.‐ 6 (GEN‐EE)  C         
0
14.   Lub oil return temp brg.‐7 (Exctr)   C         

  • CF system           

15.   CF tank level. (650/700/750)  %         
0
16.   CF tank temp BEH partition.  C         

17.   HP CF pressure. (26.0ksc)  Ksc         

18.   LP CF pressure.  Ksc         

19.   HP CF temp. ( >75 0C )  0
C         

20.   HP CF temp at outlet. ( >75 0C )  0
C         

21.   Trip oil pr.   Ksc         

Prepared By  Reviewed By Approved  By   Sheet 63 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Sl 
Description of the parameters  Unit  Barring  360 rpm  3000 rpm  Load 
no 
22.   Start up oil pr.  Ksc         

23.   Sec. aux. oil pr.  Ksc         

24.   HP sec. oil pr.  Ksc         

25.   IP sec. oil pr.  Ksc         

  • SOS (Seal oil system)           

26.   Seal oil pressure AS TE  Ksc         

27.   Seal oil pressure AS EE  Ksc         

28.   Seal oil pressure H2 S TE  Ksc         

29.   Seal oil pressure H2 S TE  Ksc         

30.   H2 seal oil ∆P (TE)  Ksc         

31.   H2 seal oil ∆P (EE)  Ksc         

32.   Seal ring relief oil pr. (TE)  Ksc         

33.   Seal ring relief oil pr (EE)  Ksc         

34.   Seal oil filter ∆P AS  Ksc         

35.   Seal oil filter ∆P H2S  Ksc         

  • PW system           

36.   PW pump in service  1/ 2            

37.   PW tank level. ( > 255 & <195 )  mm         

38.   PW stator winding I/L pr.  Ksc         

39.   PW stator winding ∆P. ( > 1.5 )   Ksc         


0
40.   PW temp stator winding inlet. ( 50/55 )  C         
PW temp stator winding outlet manifold  0
41.   C         
(TE). 
0
42.   PW temp stator winding outlet.  C         
PW temp stator winding outlet flow. 3
43.   M  / hr         
( < 54 & <<48 ) 
3
44.   PW flow bushing R. ( < 1.4& <<1.33 )  M  / hr         

Prepared By  Reviewed By Approved  By   Sheet 64 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Sl 
Description of the parameters  Unit  Barring  360 rpm  3000 rpm  Load 
no 
3
45.   PW flow bushing Y. ( < 1.4& <<1.33 )  M  / hr         
3
46.   PW flow bushing B. ( < 1.4& <<1.33 )  M  / hr         
0
47.   PW temp after bushing O/L.  C         

48.   PW conductivity after ion exchanger.  µS/cm         

49.   PW conductivity after main filter.  µS/cm         

50.   PW conductivity after winding.  µS/cm         


3
51.   DP main filter ‐1  M  / hr         
3
52.   DP main filter ‐2  M  / hr         
3
53.   DP fine filter  M  / hr         

  • H2 Gas system           

54.   Gen. H2 casing pressure. ( 3.3 ksc)  Ksc         

55.   Gen. purity.  %         
Gen. cold gas temp cooler A/B (LHS)  0
56.   C         
55/600C 
Gen. cold gas temp cooler C/D (RHS)  0
57.   C         
55/600C 
Gen. Hot gas temp cooler A/B (LHS)  0
58.   C         
800C 
Gen. Hot gas temp cooler C/D (RHS)  0
59.   C         
800C 
60.   Gen. cooler TCV position.  %         
0
61.   H2 cooler ‘A’ outlet – CW temp.  C         
0
62.   H2 cooler ‘B’ outlet – CW temp.  C         
0
63.   H2 cooler ‘C’ outlet – CW temp.  C         
0
64.   H2 cooler ‘D’ outlet – CW temp.  C         
0
65.   Temp of cold air exciter (I/L)  C         

66.   Temp of hot air exciter (O/L) >75 /800C  0
C         
0
67.   Temp of hot air REC wheel  C         

  • GEN ELECT   SYSTEM   
       

Prepared By  Reviewed By Approved  By   Sheet 65 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Sl 
Description of the parameters  Unit  Barring  360 rpm  3000 rpm  Load 
no 
0
01. GT  WIND TEMP – R   C         
0
02. GT  WIND TEMP – Y  C         
0
03. GT  WIND TEMP – B   C         
0
04. UT  WIND TEMP  ‐  A  C         
0
05. UT WIND TEMP – B   C         
0
06. H2 GAS  DEW POINT   C         
0
07. H2 GAS  DEW POINT   C         
 

Prepared By  Reviewed By Approved  By   Sheet 66 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

ANNEXURE ‐ 10 
CW SYSTEM   MONITORING  LOG  SHEET 
 
Sl 
Description of the parameters  Unit         
no 
  • CW  PUMPS            
1.  Pump in service            
2.  PUMP‐ CURRENT   Amp         

3.  Max Motor Brng temp    C         

4.  Max Pump Brng temp   C         

5.  Motor Winding temp R/Y/B   C         
6.  Vibrations  X/Y axis   µ         
  • CONDENSER            

7.  CW COND  1st HALF   I/L TMP   C         

8.  CW COND  1ST HALF O/L TMP   C         

9.  CW COND 2ND HALF  I/L TMP   C         

10.  CW COND 2ND HALF  O/L TMP   C         
11.  DP ACRS COND LEFT HALF  KSC         
12.  DP ACRS COND RIGHT HALF  KSC         
  • ACW  SYSTEM            
13.  Pump I/S           
14.  Current   Amp         
15.  ACW suc  Pressure   Ksc         
16.  ACW PMP‐ DIS HDR PR  KSC         

17.  ACW TMP AT PHE I/L   C         

18.  ACW TMP AT PHE O/L   C         
  • TG ECW  SYSTEM            
19.  CLG WTR(ECW) O/H TNK LVL  %         
20.  TG ECW PUMP in service   A/B/C           
21.  TG ECW PUMP  Motor   CURRENT   AMP         
22.  TGECW  pump  suction  Pressure   Ksc         
23.  TG ECW PP DIS HDR PR  KSC         
24.  TG ECW PMP SUC & DIS DP  KSC         
25.  PHE in service  A/B/C           

26.  TG ECW  PHE I/L HDR‐TMP   C         

27.  TG ECW  PHE O/L HDR‐TMP   C         
  • SG ECW  SYSTEM            
28.  SG ECW PUMP in service             
29.  SG ECW PUMP  Motor   CURRENT   AMP         
30.  SGECW  pump  suction  Pressure   Ksc         
31.  SG ECW PMP DIS HDR PR   KSC         

Prepared By  Reviewed By Approved  By   Sheet 67 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Sl 
Description of the parameters  Unit         
no 
32.  SG ECW PMP SUC & DIS DP  KSC         
33.  PHE in service  A/B           

34.  SG ECW  PHE I/L HDR‐TMP   C         

35.  SG ECW PHE O/L HDR‐TMP   C         

Prepared By  Reviewed By Approved  By   Sheet 68 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

 
ANNEXURE ‐ 11 
DRAIN VALVES OPEARTION STATUS LOG  
 
Manual  Temp   Temp After  
Sl  MOV  Open  
Valve Tag  Description of Valve  Isolation  Before  Synchronis
No   Status  
Valve Open   Rolling   ation  
    • ATMOSPHERIC DRAINS          
01.     MS  LINE   TG “0” Mtr         
02.     HRH LINE TG “0” Mtr         
03.     CRH LINE TG “0” Mtr         
04.     LPBP line  drain TG “0” Mtr         
    • UNIT FLASH TANK         
05.   BP 101  HPBP Drain ( Left )         
06.   BP 102  HPBP Drain ( Right )         
07.   MS 419  MS Line Drain Before Strainer         
08.   MS 101  MS Strainer Drain ( Left )         
09.   MS 102  MS Strainer Drain ( Right )         
10.   HRH 101  HRH Strainer Drain ( Left )         
11.   HRH 102  HRH Strainer Drain ( Right )         
12.   HRH 604  HRH Line Drain Before Strainer         
    • STARTUP DRAIN FLASH TANK         
13.   MS 105  MS Strainer Drain ( Left )         
14.   MS 106  MS Strainer Drain ( Right )         
15.   MS 417  MS Line Drain Before Strainer         
16.   CRH 101  CRH NRV Drain         
17.   CRH 501  CRH Line Drain         
18.   HRH 105  HRH Strainer Drain ( Left )         
19.   HRH 106  HRH Strainer Drain ( Right )         
20.   HRH 606  HRH Line Drain Before Strainer         
21.   LP 625  LPBP Line Drain ( Left )         
22.   LP 624  LPBP Line Drain ( Right )         
23.   HRH 109  LPBP Warm up Line Drain ( Left )         
24.   HRH 110  LPBP Warm up Line Drain ( Right )         
    • HP DRAIN FLASH TANK         
25.   EX 105  Extraction to HPH 5 A / 5 B Line Drain         
26.   AS 122  Turbine Gland Steam Seal Drain         
27.   AS 104  Aux. Steam to BFPT – A Line Drain         
28.   AS 109  Aux. Steam to BFPT – B Line Drain         

Prepared By  Reviewed By Approved  By   Sheet 69 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Manual  Temp   Temp After  


Sl  MOV  Open  
Valve Tag  Description of Valve  Isolation  Before  Synchronis
No   Status  
Valve Open   Rolling   ation  
29.   CRH 129  CRH to BFPT – A DS Line Drain         
30.   CRH 141  CRH to BFPT – B DS Line Drain         
31.   CRH 135  Steam to BFPT – A Line Drain         
32.   CRH 147  Steam to BFPT – B Line Drain         
33.   CRH 109  CRH to DEA Pegging Line Drain         
34.   CRH 116  CRH to BFPT – A Line Drain         
35.   CRH 123  CRH to BFPT – B Line Drain         
36.   EX 101  Extraction to HPH – 6 A Line Drain         
37.   EX 102  Extraction to HPH – 6 B Line Drain         
    • LP DRAIN FLASH TANK         
38.   CRH 153  CRH to DEA Pegging DS of CV Line Drain         
39.   EX 109  Extraction to BFPT – A & B Line Drain         
40.   EX 115  Extraction to DEA Line Drain         
41.   EX 110  Extraction to LPH – 3 Line Drain         
42.   EX 112  Extraction to LPH – 2 Line Drain         
43.   AS 113  S SCAPH Line Drain         
44.   AS 114  P SCAPH Line Drain         
 
  • TURBINE DRAIN ( FLASH BOX – 1   
     
Towards SWYD ) 
45.   MAL 11  Drain Before HPCV ‐ 1         
46.   MAL 26  Drain Before IV ‐ 1         
47.   MAL 65  Drain Before CRH NRV         
48.   MAL 31  Drain After IV ‐ 1         
49.   MAL 32  Drain After IV ‐ 2         
50.   MAL 22  HP Casing Drain         
 
  • TURBINE DRAIN ( FLASH BOX – 2   
     
Towards Boiler ) 
51.   MAL 12  Drain Before HPCV ‐ 2         
52.   MAL 27  Drain Before IV ‐ 2         
53.   MAL 47  Drain of Extraction Valve  A 5         
54.   MAL 51  Drain of Extraction Valve  A 4.1         
55.   MAL 52  Drain of Extraction Valve  A 4.2         
56.   MAL 54  Drain of Extraction Valve  A 3         
57.   MAL 81  Gland Steam Header Drain         
58.   MAL 55  Drain of Extraction Valve  A 2         
 

Prepared By  Reviewed By Approved  By   Sheet 70 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Annexure‐ 12 
BOILER  EXPANSION MONITORING  SHEET  
 BOILER LIGHTUP  AFTER ANNUAL OVERHAUL  
 
AT 25 KG /100KG/ ON LOAD  
 
 
 

BOILER DRUM

73 MTR BOILER
BOTH FRONT & REAR
PASS

Prepared By  Reviewed By
Sheet 1 of
Approved  By  
3 71 Of
Sheet 70
Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

 
 
 
 
 
 
 
 
 
 
 
  45 MTR BOILER
  1 ST PASS
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
  48 MTR BOILER
 
  2 ND PASS
 
 
 
 
 
 
 
 

Prepared By  Reviewed By Approved  By   Sheet 72 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

 
 
 
 
 
 
 
Sheet 2 of 3

Prepared By  Reviewed By Approved  By   Sheet 73 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

23 MTR BOILER
1 st PASS

10.5 MTR BOILER


BOTTOM RING HDR.

Prepared By  Reviewed By Approved  By   Sheet 74 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sheet
Sh C .Chakraborty ,GM(O)  3 of 3
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

Annexure ‐ 13 
SATURATION PRESSURE/TEMP. PARAMETERS . 
Critical Pressure  Is 225 ksc/ 374 0 C 
Pressure  Temp  Temp  Pressure  Temp  Pressure  Temp 
0 Pressure ksc 0 0 0
ksc   C   C  ksc   C  ksc   C 
1.0  100  15.0  200  65.0  280  160.0  346 
2.0  120  20.0  215  70.0  285  170.0  351 
3.0  133  25.0  228  75.0  290  180.0  356 
4.0  143  30.0  233  80.0  294  190.0  360 
5.0  152  35.0  242  90.0  302  200.0  365 
6.0  160  40.0  250  100.0  310  210.0  368 
7.0  165  45.0  257  120.0  323  220.0  372 
8.0  171  50.0  263  130.0  329  225.0  374 
9.0  177  55.0  269  140.0  374     
10.0  183  60.0  275  150.0  340     
 
DIFFERENT  CURVES  USED  IN TG  SET ROLLING  
 
Curve  Used  In ATRS  
Relationship  Significance  of Use  
No  Step 

Prepared By  Reviewed By Approved  By   Sheet 75 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 
NTPC/TSTPP  OPERATION DEPARTMENT  TS‐II/OPN/OI /GEN/ /02 
AREA – Gen  Operating Instructions for Unit Hot Start Up after a  REV 3.00 
UNIT ‐  3/4/5/6  Trip out .  Date : 1‐10‐2013 

• The  ∆T  should  be > X1 
Average  Temp  Before    HPBP 
X 1  Step‐4  • Here  it    ensures    that    the    approaching    MS  
tapings1,2  &  θM HP MCV‐1  >   
temp is  > MCV  temperature . 
• The  ∆T  should  be < X2 
Minimum of  θM HP MCV‐1 &2   & 
• Here  it    ensures    that    the    approaching    MS  
X 2  Saturation  temp    Before    HPBP  Step‐4  temp  is  not  very  much    high  w.r.t  the  existing 
tapings  
MCV  temp  . 
• The  ∆T  should  be < X 3 by 15 0C . 
Temp    before    HPBP    1  &2    &  
X 3  Step‐11  • Here  it    ensures    that    the    approaching    MS  
Saturation Temp  at  that  point  
temp is  > MCV  temperature . 
Average  MS  Temp    Before    ESV  • The  ∆T  should  be >X 4 
X 4  1,2  &  θM HP  shaft   
Step‐11   

Temp  before  LPBP                      (  HRH  • The  ∆T  should  be >X 5 


X 5  temp)  & θM IP Shaft . 
Step‐11   

MS  Temp  Before  HPBP    &    50  % 


X 6  Step‐14  • Before  Rolling  to 3000 RPM  
HP casing OR HP Shaft temp . 

HRH Temp in front of IPT   & 50 %  • Before  synchronisation  &  Loading  of  the  


X 7  IP Shaft temp 
Step‐19  Machine  

Prepared By  Reviewed By Approved  By   Sheet 76 Of 70


Sri R.N.Das , AGM(O)  Susanta Ghosh, AGM(O) I/C  Sh C .Chakraborty ,GM(O) 

You might also like