Professional Documents
Culture Documents
Air Temperature Effect
Air Temperature Effect
Air Temperature Effect
a r t i c l e i n f o a b s t r a c t
Article history: The temperature of the air surrounding the windings of ventilated dry-type transformers is an important
Received 15 July 2010 factor in the cooling of the windings since they are cooled only by the air. In particular, inner windings
Received in revised form are sensitive to the air temperature in vertical cooling ducts. This study presents air temperature effect
10 November 2010
on the temperatures in foil-type inner winding for the dry-type transformers. A transformer rated at
Accepted 12 November 2010
2000 kVA was selected for the research and temperature distribution was calculated under constant and
Available online 10 December 2010
varying air temperatures inside vertical ducts at three different loads. The 2-D transient heat diffusion
equation was solved using the finite element method by coupling it with the vector potential equation
Keywords:
Air duct temperature
due to non-uniformly generated heat caused by eddy currents in the foil winding. The calculated temper-
Coupled electromagnetic-thermal model atures at constant and varying air temperatures are presented together with experimental values. The
Dry-type transformer numerical and experimental results of this study showed that the air temperature affects the accuracy
Finite element analysis of temperatures in foil-type inner winding greatly.
© 2010 Elsevier B.V. All rights reserved.
0378-7796/$ – see front matter © 2010 Elsevier B.V. All rights reserved.
doi:10.1016/j.epsr.2010.11.008
784 M. Lee et al. / Electric Power Systems Research 81 (2011) 783–789
Table 1
Measured winding surface temperatures with calculated surface temperatures at
constant and varying air temperatures in the 2nd air duct for different kVAs at 78%
of the height.
inch) air ducts were presented with respect to the average winding
temperature rises for three different coil heights, 0.32 m (12.5 inch),
0.77 m (30.5 inch) and 1.54 m (60.5 inch). Based on these temper-
ature test data, air temperature variations between the inlet and
the outlet for 0.61 m (24 inch) height coil of this study, the increase
in temperature of the air from inlet to outlet of the ducts in those
experiments was calculated to be 89.5% of average winding tem-
perature rises. For the present numerical study 90% was assumed.
This method of calculating the air temperature of the outlet is only
applicable to 12.7 mm (0.5 inch) ducts having the height between
0.32 m (12.5 inch) and 1.54 m (60.5 inch) since the air temperatures
inside the vertical ducts are highly dependent upon the height and
size of the ducts.
In this study, the finite element model was solved under two dif-
ferent air temperature assumptions in the vertical cooling ducts: (i)
constant air temperature and (ii) varying air temperature. In the for-
mer a constant air temperature inside the vertical air ducts of 25 ◦ C
was assumed. In the varying air temperature analysis the temper-
ature of the air inside the ducts was assumed 90% of the average
winding temperature rise as derived from the temperature test data
by Stewart and Whitman [8]. It was assumed to vary linearly from
the inlet to the outlet. Therefore, the coupled model was solved
for an inlet temperature of 25 ◦ C and the outlet air temperatures
were assumed to be 52.3 ◦ C for 1500 kVA, 75.5 ◦ C for 1750 kVA, and
81.5 ◦ C for 2000 kVA.
Fig. 3. Finite element domains divided into triangular elements.
air temperatures in the second air duct at 78% of the height for
the loads of 1500 kVA, 1750 kVA and 2000 kVA. The difference
between measured and calculated air temperature in the second
air duct was 0.1–4.7 ◦ C while that for constant air temperatures
was 17.7–39.1 ◦ C.
The surface temperatures calculated with varying air tem-
peratures are in good agreement with the experimental values,
particularly in the middle of the vertical length. In the case of
constant temperature, the difference between measured and cal-
culated surface temperatures is greater with increasing distance
from the bottom of the air duct and with higher load. The highest
temperature difference is about 40 ◦ C near the top of the duct for
the load of 2000 kVA.
The calculated surface temperatures for both constant and vary-
ing air temperatures in the 4th air duct for 1500 kVA, 1750 kVA and
2000 kVA loads together with the experimental values at steady
state are presented in Figs. 9–11, respectively. The measured sur-
Fig. 6. Calculated vertical surface temperatures at both constant and varying air face temperatures and calculated surface temperatures at constant
temperatures in the 2nd air duct for 1500 kVA load together with the experimental
and varying air temperatures in the fourth air duct at 78% of the
values.
height for the different loads are shown in Table 2. The largest dif-
ference between measured and calculated temperature for varying
Fig. 7. Calculated vertical surface temperatures at both constant and varying air
temperatures in the 2nd air duct for 1750 kVA load together with the experimental Fig. 8. Calculated vertical surface temperatures at both constant and varying air
values. temperatures in the 2nd air duct for 2000 kVA load together with the experimental
values.
788 M. Lee et al. / Electric Power Systems Research 81 (2011) 783–789
Table 2
Measured winding surface temperatures with calculated surface temperatures at
constant and varying air temperatures in the 4th air duct for different kVAs at 78%
of the height.
air temperatures was 10.1 ◦ C and the smallest was 1.9 ◦ C. The tem-
perature differences for constant air temperatures for the fourth air
duct were much larger. They ranged from 13.9 ◦ C to 35.4 ◦ C. The cal-
culated temperatures assuming varying air temperature in the duct
compare well with the experimental values at all loads whereas the
Fig. 9. Calculated vertical surface temperatures at both constant and varying air
calculated temperatures assuming constant air temperature differ
temperatures in the 4th air duct for 1500 kVA load together with the experimental
values.
considerably from the measured ones. These figures also show the
temperature differences are getting larger with increasing distance
from the bottom of the winding and with higher load.
As shown in Figs. 6–11, the calculated temperatures under vary-
ing air temperature conditions derived from the test data are in
good agreement with the experimental values, especially in the
middle of the vertical ducts. However, the calculated temperatures
are higher than experimental values at the top of the second vertical
ducts. The reason may be the air temperature assumption based on
the experimental data provided by Stewart and Whitman [8]. Their
data were collected with transformer coils under uniform heat gen-
eration condition. In foil-type winding, more active air movement
occurs around the top portions since more heat is generated there
by induced currents resulting in increased convective heat transfer,
and thus lowers surface temperatures. Research on the air temper-
atures inside the vertical ducts for natural convection should be
carried out intensively in order to achieve more accurate predic-
tion of surface temperatures. Air temperature changes along the
height should be measured at many locations in vertical ducts for
different size and height.
Further the difference between the calculated surface temper-
atures at constant and varying air temperatures increased with
Fig. 10. Calculated vertical surface temperatures at both constant and varying air
temperatures in the 4th air duct for 1750 kVA load together with the experimental
higher loads. Since the air temperature inside the vertical ducts is
values. higher for elevated temperature transformers. It is suggested that
air temperature changes should receive more attention when high
temperature units are considered in order to calculate tempera-
tures accurately.
The assumptions made for the air temperature in Section 3.2
may not apply to the vertical cooling ducts located in the trans-
former windows. The air flow may be quite different from the
transformer nose because of the core yokes. In addition, the core
yokes are another heat source and thus the air temperature may be
higher than that in the nose. The vertical ducts in the transformer
window should be investigated for more accurate temperature pre-
diction of all around the windings.
5. Conclusion
analysis under two different air temperature conditions inside the References
vertical cooling ducts; constant and varying air temperatures that
increased from bottom to top. The varying air temperatures were [1] F.P. Incropera, D.P. DeWitt, Fundamentals of Heat and Mass Transfer, 5th ed.,
John Wiley and Sons, Inc., New York, 2002.
determined with respect to the average winding temperature rises [2] G. Kömürgöz, Í. Özkol, Predicting hottest spot temperature in self-cooled dry-
based on the test data. The coupled model was applied to the dry- type transformer, in: International Conference on Electrical and Electronics
type transformer at three different loads, 1500 kVA, 1750 kVA and Engineering, 2003, pp. A2–06.
[3] J. Smolka, O. Bíró, A.J. Nowak, Numerical simulation and experimental valida-
2000 kVA and solved by the FEM. The calculated surface temper- tion of coupled flow, heat transfer and electromagnetic problems in electrical
atures under both air temperature assumptions were compared transformers, Arch. Comput. Methods Eng. 16 (2009) 319–355.
together with experimental values. [4] L.W. Pierce, Predicting hottest spot temperatures in ventilated dry-type trans-
former windings, IEEE Trans. Power Del. 9 (1994) 1160–1172.
The calculated temperatures at varying air temperature agreed [5] Z. Dianchun, Y. Jiaxiang, W. Zhenghua, Thermal field and hottest spot of the ven-
well with experimental values except for the very top portions tilated dry-type transformer, Proceedings of the 6th International Conference
of the foils. The difference between the calculated temperatures on Properties and Applications of Dielectric Materials, 1, 2000, pp. 141–143.
[6] E. Rahimpour, D. Azizian, Analysis of temperature distribution in cast-resin
at constant air temperatures and at varying air temperatures
dry-type transformers, Electr. Eng. 89 (2007) 301–309.
increased as the distance from the bottom of the vertical ducts [7] A. Bejan, Convection heat transfer, 3rd ed., John Wiley and Sons, Inc., New York,
and the load of the transformer are increased. The numerical 2004.
and experimental results of this study showed that air tem- [8] H.C. Stewart, L.C. Whitman, Hot-spot temperatures in dry-type transformer
windings, AIEE Trans. Part 3 63 (1944) 764–768.
perature affects the accuracy of temperatures in foil-type inner [9] D.J. Nelson, J.P. Jessee, A coupled thermal magnetic model for high frequency
winding greatly. Therefore, varying air temperature inside verti- transformers: Part I—Model formulation and material properties, IEEE Trans.
cal ducts should be applied when the temperature distribution Compon. Hybrids Manuf. Technol. 15 (1992) 730–739.
[10] J. Driesen, G. Deliége, R. Belmans, K. Hameyer, Coupled thermo-magnetic simu-
in the foil winding is calculated by the heat diffusion equation. lation of a foil-winding transformer connected to a non-linear load, IEEE Trans.
Research on the air temperatures inside the vertical ducts for Magn. 36 (2000) 1381–1385.
natural convection should be conducted for different size and [11] B.S. Ram, Loss and current distribution in foil windings of transformers, IEE
Proc. Gen. Transm. Dis. 145 (1998) 709–716.
height of the vertical ducts. The air temperature changes inside [12] B. Guru, H. Hiziroğlu, Electromagnetic Field Theory Fundamentals, 2nd ed.,
the ducts should be formulized so that they can be used to cal- Cambridge University Press, Cambridge, UK, 2004.
culate temperatures in foil-type winding for ventilated dry-type [13] IEEE C57.12.91-1995, IEEE Standard Test Code for Dry-type Distribution and
Power Transformers, 1995.
transformers.