Product Description

A7.1.3 High Voltage Fire Pump Controllers • FTA2000


2300-7200 Volt

„ Emergency Manual Run Mechanism to mechani-


cally close motor contactor contacts in an emer-
gency condition
„ Built-in Start and Stop push-buttons to bypass
automatic start circuits
„ Door mounted display/interface panel featuring
a 40 Character Vacuum Fluorescent Display,
Membrane Type User Control Push-buttons and
easy to read LED Indicators
„ Normal-Off-Test Selector Switch - Internally
mounted for functional test of control system only,
requires that isolating switch be open and a sepa-
rate 120 volt AC power source be supplied.
„ POWER ON LED
„ PUMP RUN LED
„ PHASE FAILURE LED
„ PHASE REVERSAL LED
„ LOW PRESSURE LED
„ DELUGE OPEN LED
„ INTERLOCK ON LED
„ Minimum Run Timer / Off Delay Timer
Description—Firetrol® FTA2000 combined auto- „ Daylight Savings Time Option
matic and manual class E2 high voltage controllers „ Weekly Test Timer
are intended for starting of squirrel cage motors „ Elapsed Time Meter
driving listed fire pumps. Maximum ratings are as „ Digital Pressure Display
follows: „ USB Host Controller and Port
Max. HP 3-Phase Voltage „ Solid State Pressure Transducer
1500 2200 - 2500 „ Data Log
2000 3200 - 3500 „ Event Log (3000 Events)
2500 4000 - 5000 „ True RMS Metering with simultaneous 3 phase
3500 5000 - 7200 display of amps and volts
„ Disk Error message
„ Disk Near Full message
Approvals—Firetrol fire pump controllers are listed „ Pressure Error message
by Underwriters’ Laboratories, Inc., in accordance „ Motor Over 320% message
with UL218, Standard for Fire Pump Controllers, „ Local Start message
CSA, Standard for Industrial Control Equipment, „ Remote Start message
and approved by Factory Mutual. They are built to „ Emergency Start message
meet or exceed the requirements of the approving „ Fail To Start message
authorities as well as NEMA and the latest editions „ Undervoltage message
of NFPA 20, Installation of Centrifugal Fire Pumps, „ Overvoltage message
and NFPA 70, National Electrical Code. „ High Speed Open Serial Communications Port
„ NEMA Type 2 enclosure
Standard Features—The following are included as „ Suitable for use as Service Equipment
standard with each controller:
„ Isolating Switch - NEMA Rating, 7200 Volts, 400
Amps with external operating handle with electri-
cal and mechanical interlocks to prevent opening
of the high voltage compartment door with the
isolating switch or the main contactor closed.
Interlocks prevent opening the isolating switch
with the main contactor closed.
„ Vacuum Contactor - NEMA Rating, 7200 Volts,
400 Amps
SPECIAL ENCLOSURES -JT Audible and Visible jockey pump trouble indication
-T NEMA Type 3R (IEC IP14), Painted Steel -P Built-in alarm system (Includes visible supervisory
-E NEMA Type 4 (IEC IP56), Painted Steel voltage normal indication and audible pump operat-
-F NEMA Type 4X (IEC IP56), #304 Stainless Steel, ing, phase failure and phase reversal indication)
Unfinished** -PB Built-in low system pressure visible alarm with
-FXP NEMA Type 4X (IEC IP56), #304 Stainless Steel, manual reset
Painted Finish -PE Contacts for remote indication, low system pressure
-FD NEMA Type 4X (IEC IP56), #316 Stainless Steel, -PT Built-in alarm system, 220 VAC supervisory power
Unfinished** (Includes visible supervisory voltage normal
-FDB NEMA Type 4X (IEC IP56), 12 Gauge, Seam indication and audible pump operating, phase failure
Welded, #316 Stainless Steel, Polished and and phase reversal indication)
Brushed Finish -HV Audible alarm device
-FDP NEMA Type 4X (IEC IP56), #316 Stainless Steel
Painted Finish MISCELLANEOUS
-G NEMA Type 12 (IEC IP52), Painted Steel -BAT 220-240Volt test circuit
** Unfinished (Not painted, polished or brushed). -PY Motor space heater output contacts
-S Tropicalization
ANTI-CONDENSATION SPACE HEATERS -ZPA Customized, annual service display message (when
-H 120 Volt Space Heater factory programmed or programmed by Firetrol
-J 120 Volt Space Heater With Thermostat representative during start-up)
-K 120 Volt Space Heater With Humidistat -ZPN 5150 Ethernet Connectivity Module (Allows users
-L 240 Volt Space Heater to monitor limited controller status via a single
-M 240 Volt Space Heater With Thermostat computer or over a computer network)
-N 240 Volt Space Heater With Humidistat -ZPM Serial Modbus RTU Communications Protocol
(Allows users to monitor all aspects of the controller
PRESSURE TRANSDUCERS status via a RS485 communications network
-B 0-600 psi (0-42.25 bar) Pressure Transducer for (system integration required). (Includes RS485
Fresh Water Service to twisted pair breakout module, optical isolation
-C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea module (4000 ft. range), DC power supply and
Water, Foam or Copper Corrosive Service customer connection terminal blocks).
-D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea
Water, Foam or Copper Corrosive Service Export packaging (Wooden crating to conform
to IPPC Standards)
ALARMS FTA1000 - 1900
-AC Extra contacts (normally open & normally closed) for
remote indication, pump operating *Weekly Test Timer - Standard
-AF Audible and Visible low pump room temperature alarm
-AG Built-in reservoir low alarm
-AH Audible low suction pressure alarm
-AM Contacts for remote indication, pump fail to start
-AV Contacts for remote indication, low pump room
temperature
-AW Contacts for remote indication, reservoir low
-AY Contacts for remote indication, low suction pressure
-AZ Low pump room temperature switch, mounted and
wired
-BW Extra contacts for remote indication,
phase failure/phase reversal
-BY Contacts for remote indication, pump overload
-COM Low suction pressure alarm, (Includes selectable
auto/manual reset, audible, visible and remote
alarms, initiating pressure switch not included)
-CTS Built in Low Suction Pressure Alarm Panel (Includes
selectable auto/manual reset, audible, visible and
remote alarms and mounted and wired pressure
switch)
-EG Visible Relief Valve Discharge alarm
-EH Contacts for remote indication, relief valve discharge
-EJ Built-in flow meter on alarm
-EK Contacts for remote indication, flow meter on
-KH Contacts for remote indication, common output for
any alarm
-JR Visible jockey pump running indication

(919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27518 USA