Professional Documents
Culture Documents
Experiment 4
Experiment 4
College of engineering
Mechanical department
Experiment No (4)
Investigation of the Impact of Cooling Load on
the Cooling Tower Performance
Stage: 4th
Date: 6/12/2020
Dec-2020
PURPOSE:
To investigate the effect of cooling load on the cooling tower efficiency.
APPARATUS:
The apparatus consists of the following components and instruments as explained
in the followed figure below:
1. Air distribution chamber.
2. A tank with heaters to simulate cooling loads of 0.5, 1.0, and 1.5 kW.
3. A make-up tank.
4. A centrifugal fan with intake damper.
5. Pump.
6. A water collecting basin.
7. An electrical control panel.
8. Packed column.
9. Column cap.
10. Temperature indicator.
11. Inclined tube manometer.
12. Variable area flow meter.
2
Figure 1 cooling tower apparatus
3
THEORY:-
The performance of the cooling tower depends on various parameters like cooling
Range & Approach to wet-bulb.
Approach to wet bulb: The difference between the temperature of the water
leaving the tower and the wet-bulb temperature of the air entering.
Cooling Range: The difference between the water temperature at the entry to and
exit from the tower.
𝐑𝐚𝐧𝐠𝐞
𝐄𝐟𝐟𝐢𝐜𝐢𝐞𝐧𝐜𝐲 𝐨𝐟 𝐭𝐡𝐞 𝐜𝐨𝐨𝐥𝐢𝐧𝐠 𝐭𝐨𝐰𝐞𝐫 % = ∗ 𝟏𝟎𝟎
(𝐑𝐚𝐧𝐠𝐞 + 𝐀𝐩𝐩𝐫𝐨𝐚𝐜𝐡)
Then the Cooling tower efficiency is the ratio of cooling range, to the ideal range,
i.e., the difference between cooling water inlet temperature and ambient wet-bulb
temperature.
(𝐓𝟓 − 𝐓𝟔)
𝐄𝐟𝐟𝐢𝐜𝐢𝐞𝐧𝐜𝐲 % = ∗ 𝟏𝟎𝟎
(𝐓𝟓 − 𝐓𝟐)
The cooling tower efficiency is limited by the wet-bulb temperature of air entering.
In summer the ambient air wet-bulb temperature raises when compared to winter
thus limiting the cooling tower efficiency.
4
Figure 2 shows the effect of the parameters on cooling tower efficiency
Experimental Procedure:
1- Fill water in the make-up tank, the level of the water should always be greater than
the mark of minimum level on the load tank.
2- Fill water at two positions of the wet-bulb temperature (inlet and outlet air positions).
3- Switch on the experiment.
4- Open the cover of the air intake damper to set the flow of air such that the pressure
drop through the tower is (16mm) H2O.
5- Set water flow rate at 40 g/sec.
6- Keeping water and air flows constantly during the test, the load should be increased
by 0.5 kW every test (0.5kW, 1kW, 1.5kW)
7- Record all temperature readings for each load.
5
EXPERIMENTAL PROCEDURE:
1- Fill water in the make-up tank, the level of the water should always be greater
than the mark of minimum level on the load tank.
2- Fill water at two positions of the wet-bulb temperature (inlet and outlet air
positions).
3- Switch on the experiment.
4- Open the cover of the air intake damper to set the air flow rate such that the
pressure drop through the tower is 16 mm H2O.
5- Set water flow rate at 40 g/sec.
6- Switch on the heater at 1 kW.
7- Read all temperatures each 5 min. until the system reached a steady state.
8- Fill water with the make-up tank up and measure the volume of evaporated in
10 minutes to find the rate of evaporation.
9- For the final reading plot process on the psychometric chart.
10- Calculate the mass of air flow rate 𝑚̇a, ΔḢ of system, evaporating rate, make up
the rate(𝑀̇ 𝐸 ), cooling range, approach to the wet bulb.
6
Reading:
Test No. 1 2 3
Cooling Load in kW 0.5 1 1.5
height (cm) 1.9 2.5 3.2
Water Flow Rate, g/s 40 40 40
Orifice Differential, mm H2O 16 16 16
Air Inlet Dry Bulb Temp. T1, °C 23.2 23.7 24.2
Air Inlet Wet Bulb Temp. T2, °C 17.7 17.6 18.7
Air Outlet Dry Bulb Temp. T3, °C 21.2 22.5 24.1
Air Outlet Wet Bulb Temp. T4, °C 21.3 22.5 24.6
Water Inlet Temp. T5, °C 23.4 28 32.7
Water Outlet Temp. T6, °C 20.2 20.2 23.7
Total Cooling Load, KW
Approach to wet bulb
Cooling Range
Efficiency
7
Calculation:
For reading No.1:
𝑇1 = 23.2℃ 𝑇2 = 17.7 ℃ 𝑇3 = 21.2 ℃ 𝑇4 = 21.3℃ 𝑇5 = 23.4 ℃ 𝑇6 = 20.2 ℃
𝑃𝑢𝑚𝑝 𝑖𝑛𝑝𝑢𝑡 𝑙𝑜𝑎𝑑 = 0.1𝑘𝑊 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝑙𝑜𝑎𝑑 (ℎ𝑒𝑎𝑡𝑒𝑟) = 0.5𝑘𝑊
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 % = 56.14%
8
Results:
Test No. 1 2 3
Cooling Load (kW) 0.5 1 1.5
Total Cooling Load (kW) 0.6 1.1 1.6
Approach to wet bulb (℃) 2.5 2.6 5
Cooling Range (℃) 3.2 7.8 9
Efficiency % 56.14 75 64.28
9
Draw efficiency of the cooling tower with a total cooling load (in chart):
1 56.14 0.5
2 75 1.1
3 64.28 1.6
80
75
70
Efficiency %
65
60
55
50
0.5 0.75 1 1.25 1.5 1.75
Total Cooling Load (kW)
Chart 1
10
Draw cooling range and approach to the wet bulb in chart:
1 3.2 2.5
2 7.8 2.6
3 9 5
9.5
8
Cooling Range (℃)
6.5
3.5
2
2 2.5 3 3.5 4 4.5 5 5.5
Approach to wet bulb (℃)
Chart 2
11
State the all temperatures that obtained from the experiment of the tower
with a total cooling load in a chart.
1.7
State 3
1.6
1.5
1.4
1.3
Total cooling load (kW)
1.2 T1
State 2
T2
1.1
T3
1 T4
T5
0.9 T6
0.8
0.7
State 1
0.6
0.5
15 17.5 20 22.5 25 27.5 30 32.5 35
Temperature (℃)
Chart 3
12
Discuss all results:
13
Discuss the effect of decreasing the relative humidity of the atmosphere
air on the performance of the cooling tower?
The performances of the cooling tower depend on various parameter Approach to
wet-bulb.
So, when decreasing the relative humidity it means the wet bulb temperature is
low. When the relative humidity is low much evaporation will take place, and
Approach of weld bulb will increase and it will decrease the efficiency of the
cooling tower.
That means the cooling tower isn't transferring much heat (energy) to the
environment.
The web bulb temperature is nothing but relative humidity. Wet bulb temperature
essentially measures how much water vapor the atmosphere can hold at current
weather conditions.
Effect:
When decrease the relativity humidity, wet bulb
temperature also will decrease, Approach of wet
bulb will increase, Efficiency of cooling tower
decrease.
14