Ijrvocas.v2i3.141 Fixed
Ijrvocas.v2i3.141 Fixed
Email address:
her65yan@gmail.com
*
Corresponding author
Received: November 29, 2022; Accepted: December 12, 2022; Published: December 27, 2022
Abstract: The electric panel has a function as a distribution device and as protection for electricity from the PLN. A panel
must at least have protective equipment that functions so that if a fault occurs in electrical equipment, the fault can be corrected
and does not interfere with the performance of the panel. In order for the protection equipment to work properly, accuracy is
required in selecting the current rating and breaking capacity value of the protection components used. The purpose of this
research is to analyze the breaking capacity value, nominal load current value, and short circuit current for each electrical
protection component in the busbar room panel at PT Trias Indra Saputra. The analysis was carried out by comparing the results
of manual calculations with calculations using the XL3-Pro calcul software, as well as the installed protection components. After
calculating and comparing the results, the electrical protection components are still suitable for use as protection in the event of
a fault, both short circuit fault and overcurrent on the electrical equipment in the busbar room panel at PT Trias Indra Saputra.
In the outgoing protection Q0 is a protection component that connects the power source from the LVMDP panel to the busbar
room panel at PT Trias Indra Saputra. Different results were obtained from the three comparisons. By using the MCCB current
rating of 100A, it has been able to secure the circuit from short circuit faults and overload.
Keywords: Electrical panels, electrical protection, breaking capacity, current carrying capacity, MCB, MCCB
1. Introduction
One of the technical factors that need to be considered in circuit current fault. In the distribution of electric power, a
the supply and distribution of electric power is power quality. panel must have protection equipment, which is divided into
These factors include voltage stability, service continuity, incoming and outgoing (Firmansyah et al, 2022)
protection reliability, and power capacity as needed. In the busbar space panels at PT Trias Indra Saputra there
Protection is an electrical equipment used to protect electrical are various electrical loads. In order to maintain reliability, it
components from damage caused by faults such as overload must pay attention to the electrical protection components. In
currents or short circuit currents. Good protection is protection the process of operation, unexpected faults may occur such as
that immediately responds or trips when a fault occurs. The short circuit faults or sudden overloads which may damage
type of fault that most often occurs when the system is running equipment. Therefore, we need components that can protect or
normally is an overcurrent fault or commonly called an secure these equipment so as to minimize faults that occur. The
overload. Another type of fault that often occurs is a short electrical protection components used in this panel are
44
DOI: https://doi.org/10.53893/ijrvocas.v2i3.141 45
Miniature Circuit Breakers (MCB) and Molded Case Circuit short circuit current at the start of the circuit; V = Voltage on
Breakers (MCCB) (Revi et al, 2022). MCB is a protection the circuit
circuit equipped with a thermic component (bimetal) for Compute “M” (multiplier)
overload protection and also equipped with an electromagnetic 1
𝑀 = 1+𝑓 (10)
relay for short circuit protection. While the MCCB is a
protective device which in the process of operation has two Calculates the short-circuit symmetric RMS current
functions, namely as a protection and as a connecting device available at the fault point. Add motor contribution, if
(Pratama et al, 2022). The purpose of this research is to applicable,
analyze the breaking capacity value, nominal load current 𝐼𝑠𝑐.𝑠𝑦𝑚.𝑅𝑀𝑆 = 𝐼𝑠𝑐 𝑥 𝑀 (11)
value, and short circuit current for each electrical protection Abdullah Assegaf (2019) in research about “Koordinasi
component in the busbar room panel at PT Trias Indra Saputra. Selektif MCB Metoda Waktu–Arus dengan Simulasi ETAP
Calculation analysis to determine the capacity of the MCB Selective Coordination of TimeCurrent Methods with
disconnection capability of the protection components used ETAP Simulation”. This study discusses the use of
for 'incoming' and 'outgoing' in the busbar room panel, and ETAP12.6 software to simulate electrical installation networks
adjusting the calculations using the XL3-Pro Calcul software, equipped with protection equipment, protection system
the use of protective equipment components that have been coordination, and MCB selectivity from disturbances. Starting
used, and by using the calculation formula that has been set. from protecting on the panel side of the main source of power
In = P / ( 3 x V x cos θ) (1) supply to the load side that can be coordinated precisely and
IK = In x 1,25 (2) reliably in handling a disturbance on the load side. The results
Note: In = Nominal Current (A); IK = current carrying show that from the analysis and simulation, namely by
capacity (A); P = Load Power (W); V = Voltage (V); Cos θ = selecting the right class of protection rating, the principle of
power factor of system (Astanto, et al. 2022 and Efriyanti et coordination and selectivity of protection for power outages
al, 2022). that are released due to disturbances can work properly and
Determine the full load current in the transformer (FLA) reliably ( Tanjung et al, 2018).
𝑘𝑉𝐴 𝑥 1000 Agusthinus S. Sampeallo (2022) about “Analisis
Transformator 3 phasa, 𝐼𝐹𝐿𝐴 = (3)
𝑉𝑙−𝑙 𝑥 √3
Gangguan Hubung Singkat Pada Panel Utama Tegangan
𝑘𝑉𝐴 𝑥 1000 Rendah Gardu C Bandara El Tari Kupang Untuk Menentukan
Transformator 1 phasa, 𝐼𝐹𝐿𝐴 = (4)
𝑉𝑙−𝑙
Kapasitas Pemutusan Pemutus Tenaga Menggunakan Etap
100 12.6”. This study aims to determine the magnitude of the short
𝑀𝑢𝑙𝑡𝑖𝑝𝑙𝑖𝑒𝑟 = %𝑍 𝑇𝑟𝑎𝑛𝑠𝑓𝑜𝑟𝑚𝑎𝑡𝑜𝑟 (5)
circuit value and determine the breaking capacity of a power
Determine the short circuit current breaker in the form of a Circuit Breaker (CB). In the
The short circuit current on the motor contribution and the simulation section, it is carried out using ETAP, then it is
total short circuit current. validated with the equations of the existing theory which is
Isc = Transformator F.L.A x Multiplier (6) based on the impedance value of each sequence on the
Calculating the "f" factor simulated fault. The values or numbers from the research show
√3 𝑥 𝐿 𝑥 𝐼 that a single-phase short circuit to ground is a fault with a
Fault of 3 phase, 𝑓 = 𝐶 𝑥 𝑛 𝑥 𝑉 3𝜃 (7)
𝑙−𝑙 minimum value of 4.82 KA on Switchgear 2 buses. A 3-phase
2𝑥𝐿𝑥𝐼 short circuit is a fault with a maximum value of 9.45 KA on
fault of 1 phase, line to line, 𝑓 = 𝐶 𝑥 𝑛 𝑥 𝑉𝑙−𝑙 (8)
𝑙−𝑙 Switchgear 1 and 2 buses. Breaker capacity Low voltage panel
2𝑥𝐿𝑥𝐼 power results show that the Circuit Breaker (CB) breaking
fault of 1 phase, line to netral, 𝑓 = 𝐶 𝑥 𝑛 𝑥 𝑉𝑙−𝑛 (9)
𝑙−𝑛 capacity on Bus Switchgear 1 has a breaking capacity of
Note: L = Length of conductor (conducting cable) to the 10,875 KA, on Bus Switchgear 2 the breaking capacity is 8.67
fault; C = constant value “C” for conductors and for busways; KA and on Bus Switchgear 1 and 2 the breaking capacity is
n = number of conductors per phase; I = Value of available 14,175 KA. (Agusthinus et al, 2022)
46 Herman Yani et al.: Analysis of Breaking Capacity Calculation on Busbar Room Panel at PT Trias Indra Saputra
Load Name
Numbers
Power
Current
Voltage Length
Type results from the XL3-Pro calcul software; (e) Analyzing data
(unit)
(Watt)
(A)
(Volt) (metre)
Cable from the results of comparisons between manual calculations,
calculations using the XL3-Pro calcul software, and with the
Mesin YSD 1 10.500 22,65 380 20 NYYHY
selection of electrical protection components that have been
35Y-20, 3~, 50 Hz 5x2,5mm
installed.
Mesin Milling 1 4.000 7,22 380 10 NYM
Table 2. Specifications of electrical protection components on busbar room
EX RRC, 50 Hz 3x2,5mm
panels
Mesin 1 62 0,33 220 5 NYM
Rating Rating Breaking
Gerinda Bench 4x1,5mm Name of Number of
Current, Voltage capacity IP
Mesin Adtech 1 25.500 46.2 380 20 NYYHY protection/product Pole/curva
In (A) (KV) (KA)
Q5Y-16, 3~, 50 Hz 5x2,5mm
MCCB pada Q0 3P 160 8 25 40
Mesin Punch Alfra 1 600 3,2 220 15 NYM
EasyPact CVS 160B
3x2,5mm
Schneider
DOI: https://doi.org/10.53893/ijrvocas.v2i3.141 47
MCB pada Q1 3P / C 20 6 10 20 current at the PLN source is 27.5 KA. The value of the short
Acti 9 IC60N Schneider circuit current based on the calculation on the incoming panel
MCB pada Q2 3P / C 6 10 20 20 side of the busbar room at PT Trias Indra Saputra is 17.88 KA
IC60H merk Schneider (MCCB Q0). The smallest short circuit current on the MCB
MCB pada Q3 dan Q8 3P / C 2 6 6 20 Q11 is 2.5kA. The biggest short circuit current on MCB Q6 is
Acti 9 IC60N Schneider 6.32kA.
MCB pada Q4, 3P / C 3 4 6 20 The results of manual breaking capacity calculations for
Q7, Q13, dan Q14 electrical protection are compared with the selection of
Acti 9 IK60N Schneider components from the calculation results of XL3-Pro calcul and
MCB pada Q5 dan Q6 3P / C 10 6 10 20 installed protection components, using an average breaking
Acti 9 IC60N Schneider capacity value of 6 KA and 10 KA. For example, in MCB Q1,
MCB pada Q9 1P / C 10 6 10 20
a short circuit current value of 5.19 KA is obtained, and a
Acti 9 IC60N Schneider
breaking capacity of 10 KA is used, which means that the
Mesin Euromac Table 4. Manual calculations and using XL3-Pro Calcul software
The main steps using the XL3-Pro calcul software are: a) 10. MCB Q10 ke 450 450 3 2,3
Make the system as a whole using an existing single line Kipas Angin
diagram as a reference without entering circuit specifications, 11. MCB Q11 ke 1.071 1.071 7,15 5,5
grounding system, and factor power; b) Enter the power Lamp + Lampu KO
specification for the load and/or the current rating on the 12. MCB Q12 (Spare)
circuit line and the cable length used. In this step, XL3-Pro 13. MCB Q13 ke Stop 900 900 1,1
calcul will automatically calculate the electric power used, the Kontak 3P Area QC
current in the circuit, the short circuit calculation, the value of 14. MCB Q14 ke Stop 900 900 1,1
the voltage drop, and so on. c) Select the type of protective Kontak 3P Area QC
equipment components from each circuit. XL3-Pro calcul will 15. MCCB Q0 55.431 53.600 116,564 92,2
Table 5. Comparison of Electrical Protection Components in Busbar Room 13. MCB Q13 ke Stop MCB MCB
Panels at PT Trias Indra Saputra Kontak 3P Area QC 3P/C 3P/C
Type of Protection 16 A + 16 A
Connection from Components Used ELCB
Protection XL3- 30mA
No.
to Loads Manual Pro Actual 14. MCB Q14 ke Stop MCB MCB
Calcul Kontak 3P Area QC 3P/C 3P/C
20 A 20 A 30mA
2. MCB Q2 ke Mesin MCB 10 MCB MCB 15. MCCB Q0 MCCB RCBO MCCB
Mesin Euromac A 3P/D 3P/C Data between the results of manual calculations and using
20 A 10 A the XL3-Pro calcul software, compared with the electrical
7. MCB Q7 (Spare) MCB protection components that have been installed, obtained
3P/C different values specifically for some protection components.
16 A This can be caused by the level of accuracy of an equipment
8. MCB Q8 (Spare) MCB when the actual measurement is different which affects the
3P/C results of manual calculations and calculations using the XL3-
2A Pro calcul in determining the current rating of the electrical
9. MCB Q9 ke MCB MCB MCB
protection components. Overall, the electrical protection
Lighting Led 6A 1P/C 1P/C
components in PT Trias Indra Saputra's busbar space panels
10 A 10 A
are still suitable for operation as a protection component from
2. The selection of the current rating for the protection waveletbased line protection system for multiterminal direct
components based on the results of manual calculations has a current grids, with practical IEC-61869-compliant
greater value, compared to the results of calculations using the measurements. IET Journals ISSN 1751-8687
XL3-Pro calculus, while for the electrical protection
[9] Efriyanti, R. ., Taqwa, A. . ., & Arifin, F. . . (2022).
components that are actually installed there are several
Temperature Decreasing Circulation of Solar Panels Using
components whose current ratings are smaller, and some are
Water Flow. International Journal of Research in Vocational
larger.
Studies (IJRVOCAS), 2(2), 48–52.
https://doi.org/10.53893/ijrvocas.v2i2.106
References
[10] Nurhabibah Naibaholo, Mohammad Yoverly, (2022). Analisis
[1] Abdullah Assegaf, Sunarto, Toto Tohir, (2019). Koordinasi
Perhitungan Kebutuhan Genset Stamford 670 KVA Pada
Selektif MCB Metoda Waktu -Arus dengan Simulasi ETAP
Apartemen Mustika Golf Residence Cikarang Jawa Barat,
MCB Selective Coordination of Time Current Methods with
Jurnal Elektro Vol 10 No 1 Januari 2022, ISSN : 2302-4712
ETAP Simulation. SENTER 2019, 23 - 24 November 2019, pp.
462-466 ISBN: 978-602-60581-1-9 [11] Pratama, D. A. ., Anisah, M., & Setiyadi, K. A. . (2022). The
Three Phase Induction Motor Test Using MATLAB
[2] Abrar Tanjung, Zulfahri, Hamzah, David Setiawan. (2018)
2021b/SIMULINK at Bukit Energi Servis Terpadu, Ltd.
Penerapan Sistem Proteksi Instalasi Listrik di Kecamatan
International Journal of Research in Vocational Studies
Rumbai Pesisir, Fleksibel Jurnal
(IJRVOCAS), 1(4), 60–65.