Professional Documents
Culture Documents
Mardhiah Hayati BT Abd Hamid at Sidek - Submission For Viva - Final
Mardhiah Hayati BT Abd Hamid at Sidek - Submission For Viva - Final
DOCTOR OF PHILOSOPHY
2020
ELECTRICAL PERFORMANCE OF PALM OIL AND RICE BRAN OIL
UNDER ALTERNATING CURRENT AND IMPULSE STRESSES FOR
TRANSFORMER APPLICATION
SEPTEMBER 2020
This thesis is dedicated to my families and my friends
Transformer oil does not only serve as an insulating liquid but also in
removing heat from the windings and cores. Mineral oil (MO) has been widely used
in transformers for more than 150 years. Recently, researchers have attempted to
search for alternative insulating oils due to the possibility that MO will run out in
future and the concern on fire safety and environmental pollution. Among the
potential oils are palm oil (PO) and rice bran oil (RBO). These oils offer attractive
characteristics such as non-toxic, highly biodegrade, and higher flash and fire points
than mineral oil. To use these oils in transformers, the oil physicochemical properties
and dielectric properties must be thoroughly investigated. This work presents the
studies of the physicochemical properties such as the viscosity, flash point, pour point
and moisture content of these vegetable oils. Besides that, this research also
investigates the dielectric properties of the oils (permittivity, resistivity, tan delta, AC
breakdown voltage and lightning impulse behaviour) under various electric fields and
gap distances. The results revealed that the viscosity, flash and fire points of PO and
RBO fulfilled the minimum requirement of the IEC standards. In terms of dielectric
properties such as the resistivity of the oil samples, RBO has the highest resistivity
with 6.372 TΩcm followed by PO with 5.341 TΩcm and MO with 3.042 TΩcm.
Based on this resistivity study, RBO and PO have fulfilled one of the important
criteria to be transformer insulation oil. However, the dielectric dissipation factor and
relative permittivity of RBO and PO were 93% higher than MO. Further assessment
was carried out on the 50% AC breakdown voltage which shows that RBO has the
highest breakdown voltage for all gap distances. This is followed by PO and MO. The
electrical performances of lightning impulse tests show that RBO and PO have lower
LI breakdown voltage than MO under both uniform and non-uniform electric fields.
However, the difference in LI breakdown voltages between RBO, PO and MO is
slightly small which is less than 20%. In addition, there is no significant effect in the
various testing methods under both uniform field and non-uniform field where the
percentages of difference are less than 12% and 8% respectively. The data of AC and
lightning impulse breakdown voltage were statistically analysed using Weibull
distribution to predict the withstand voltage (1%) of the oil samples. From the results,
the Weibull distributions of MO, PO and RBO have fitted well with the experiment
data at higher probability. The withstand voltages of the oil samples obtained in this
study were higher than the Weidmann curve (normally used in the transformer
industry for transformer insulation design). Finally, the relationship between
lightning impulse voltages under a non-uniform field with various parameters of PO
and RBO was obtained and proposed. From this work, it can be concluded that PO
and RBO show promising results to be considered as an alternative to MO in
transformer applications.
ii
ABSTRAK
Minyak pengubah tidak hanya berfungsi sebagai cecair penebat, tetapi juga
untuk menghilangkan panas dari belitan dan teras. Minyak mineral (MO) telah
digunakan secara meluas dalam pengubah selama lebih dari 150 tahun. Kebelakangan
ini, terdapat penyelidik yang telah berusaha mencari alternatif minyak penebat kerana
MO akan kehabisan sumber pada masa akan datang dan terdapat kebimbangan
terhadap keselamatan kebakaran dan pencemaran alam sekitar. Antara minyak yang
berpotensi adalah minyak sawit (PO) dan minyak dedak padi (RBO). Minyak-minyak
ini mempunyai ciri-ciri yang baik seperti tidak toksik, mesra alam, dan mempunyai
takat kilat dan kebakaran yang lebih tinggi daripada MO. Sebagai minyak pengganti
dalam pengubah, sifat fisiokimia dan sifat dielektrik minyak mesti dikaji dengan teliti.
Kajian ini mengkaji sifat fizikokimia seperti kelikatan, takat kilat, titik tuang dan
kandungan kelembapan minyak sayuran ini. Selain itu, kajian ini juga menyelidik
sifat dielektrik minyak (kebolehtelapan, kerintangan, faktor pelesapan, voltan
kegagalan AC dan voltan kegagalan kilat) dalam pelbagai medan elektrik dan
perbezaan jarak antara elektrod. Hasil kajian mendapati bahawa kelikatan PO dan
RBO jauh lebih tinggi daripada MO.. Kelikatan RBO dan PO yang lebih tinggi
daripada MO dapat membantu untuk perolakan haba dalam minyak. Pengukuran titik
kilat bagi PO dan RBO adalah lebih tinggi daripada MO dan memenuhi had minimum
yang ditetapkan oleh standard IEC untuk cecair penebat iaitu 135 °C. Selanjutnya,
kerintangan sampel minyak mendapati bahawa RBO mempunyai kerintangan
tertinggi dengan 6.372 TΩcm diikuti oleh PO dengan 5.341 TΩcm dan MO dengan
3.042 TΩcm. Berdasarkan kajian kerintangan ini, RBO dan PO telah memenuhi salah
satu kriteria penting untuk menjadi minyak penebat dalam pengubah. Walau
bagaimanapun, faktor pelesapan dielektrik dan kebolehtelapan relatif menunjukkan
RBO dan PO adalah 93% lebih tinggi daripada MO. Pengujian seterusnya dilakukan
pada 50% voltan kegagalan AC yang menunjukkan bahawa RBO mempunyai voltan
kegagalan lebih tinggi dalam semua situasi. Ia diikuti oleh PO dan MO. Kekuatan
elektrik pengujian voltan kegagalan kilat menunjukkan bahawa MO mempunyai
kegagalan voltan yang paling tinggi, diikuti oleh RBO dan PO. Di samping itu, tiada
signifikan dalam pengujian voltan kegagalan kilat dalam kaedah yang berbeza di
mana peratusan perbezaan ujian pada medan seragam dan medan tidak seragam
adalah kurang daripada 12% dan 8%. Data kegagalan voltan AC dan voltan kegagalan
kilat dianalisis secara statistik menggunakan taburan Weibull untuk meramalkan
ketahanan voltan pada 1% bagi sampel minyak. Dapatan menunjukkan taburan
Weibull bagi MO, PO dan RBO sesuai dengan data eksperimen yang diperolehi.
Ketahanan voltan pada 1% bagi sampel minyak yang diperoleh dalam kajian ini lebih
tinggi daripada lekuk Weidmann (biasanya digunakan dalam industri untuk reka
bentuk penebat pengubah). Akhirnya, hubungan antara voltan kegagalan kilat pada
medan tidak seragam dengan pelbagai parameter PO dan RBO diperoleh dan
dicadangkan. Kesimpulannya, kajian ini menunjukkan PO dan RBO boleh
dipertimbangkan sebagai alternatif kepada MO dalam aplikasi pengubah.
iii
ACKNOWLEDGEMENTS
First and foremost, I thank Allah SWT, who created everything and gave
me the ability to begin and complete this thesis. I would like to thank my
supervisor, Associate Professor Dr. Mohd Taufiq bin Ishak, for his guidance,
beneficial advice, helpful discussion and hard work to ensure that this project has
I would also like to thank all the sponsors for their sponsorship and
technical support. Thank you to colleagues from Sultan Abdul Samad Vocational
College especially from the Electrical Technology Program who gave me the
mother, arwah Aishah binti Musa for giving your shoulder and ears and for
holding my hand. You listened to all my expressions. You gave moral and spiritual
encouragement and understanding even if for only half of my PhD journey. Not
forgetting to my father, Abd Hamid @ Sidek bin Abidin who always remind me
to not fall down and keep encouraging me to finish what I started. Then, last but
precious princess Nur Inas Sofea and Nur Iman Safya and my adorable hero
Mohammad Iyaz Syauqi, thank you for all your supports and love.
iv
APPROVAL
I certify that the Examination Committee has met on the date of viva voce to
conduct the final examination of MARDHIAH HAYATI BT ABD HAMID @
SIDEK on her degree thesis entitled ‘Electrical Performance of Palm Oil and
Rice Bran Oil under Alternating Current and Impulse stresses for
Transformer Application. The committee recommends that the student be
awarded the Doctor of Philosophy Engineering.
Signature
Name of Chairperson, PhD
Title
Name of Faculty
National Defence University of
Malaysia
(Chairman)
(Internal Examiner)
(External Examiner)
v
APPROVAL
Malaysia and has been accepted as fulfilment of the requirement for the Doctor
Signature
Name of Chairperson, PhD
Title
Name of Faculty
National Defence University of
Malaysia
(Chairman)
(Member)
(Member)
vi
UNIVERSITI PERTAHANAN NASIONAL MALAYSIA
DECLARATION OF THESIS
_______________________ ________________________
Signature Signature of Main Supervisor
________________________
IC/ Passport No. Name of Main Supervisor
Date: Date:
Note: * If the thesis is CONFIDENTIAL OR RESTRICTED, please attach the letter
from the organisation starting the period and reasons for confidentiality and
restriction.
vii
TABLE OF CONTENTS
Page
ABSTRACT ii
ABSTRAK iii
ACKNOWLEDGEMENTS iv
APPROVAL v
DECLARATION vii
TABLE OF CONTENTS viii
LIST OF TABLES xi
LIST OF FIGURES xiv
LIST OF ABBREVIATIONS xviii
CHAPTER
1 INTRODUCTION 1
1.1 Background 1
1.2 Problem Statement 5
1.3 Research Objectives and Scope 8
1.4 Major Contribution 10
1.5 Thesis Summary 11
2 LITERATURE REVIEW 14
2.1 Introduction 14
2.2 Use and Application of Transformer 15
2.3 Insulation oil used in transformer 16
2.3.1 Mineral Oil 17
2.3.2 Vegetable Oils 20
2.3.1 Palm Oil 22
2.3.2 Rice Bran Oil 23
2.4 Dielectric and Physicochemical Properties of Vegetable 26
oil
2.4.1 Viscosity 26
2.4.2 Flash Point 27
2.4.3 Pour Point 28
2.4.4 Dielectric Dissipation Factor (Tan δ) 29
2.4.5 Relative Permittivity 30
2.4.6 Resistivity 31
2.4.7 AC Breakdown voltage 31
2.5 Lightning Impulse Breakdown Voltage 38
2.5.1 Lightning impulse breakdown voltage under 41
uniform field
2.5.2 Lightning impulse breakdown voltage under non- 44
uniform field
2.5.3. Effect of different Testing method 46
2.6 Effect of Various Gap Distances 49
viii
2.7 Statistical analysis 58
2.7.1 Weibull Distribution 58
3 METHODOLOGY 61
3.1 Introduction 61
3.2 Sample Preparation 65
3.3 Physicochemical Properties of samples 67
3.3.1 Viscosity 68
3.3.2 Flash and Pour Point 69
3.4 Pre-processing of Oil Samples 69
3.5 Dielectric Properties Test of Samples 71
3.6 AC Breakdown Voltage 72
3.6.1 AC Breakdown Voltage under BAUR Trainer 73
3.6.2 AC Breakdown Voltage under HV Laboratory 74
3.7 Lightning Impulse Test 76
3.7.1 Testing Methods of Lightning Impulse Test 78
3.7.1.1 Rising voltage 78
3.7.1.2 Up and down voltage 79
3.7.1.3 Multi-level voltage 81
3.7.2 Electrode Configuration of Uniform Field 81
3.7.3 Electrode Configuration of Non-Uniform Field 82
3.8 Statistical Analysis 84
3.9 Summary 85
ix
5.2 Effect of Lightning Impulse Breakdown Voltage of 121
Sphere to Sphere Configuration under Smaller Gap
Distances
5.3 Effect of Various Testing Method under Sphere to Sphere 124
Configuration
5.4 Comparison Lightning Impulse Breakdown Voltage with 128
Previous Study
5.5 Weibull Probability Plots for MO, PO and RBO under 129
Sphere to Sphere Configuration
5.6 Summary 131
REFERENCES 158
APPENDICES 181
CURRICULUM VITAE 203
LIST OF PUBLICATIONS 204
x
LIST OF TABLES
xi
2.17 Lightning breakdown strength of natural ester and 44
mineral oil using type 1 and type 2 electrodes at
various gap distances from 12 mm to 50 mm
4.2 The flash point and pour point of MO, PO and RBO 90
according to ASTM D92.
xii
5.2 50% breakdown voltages using sphere to sphere 127
configuration under various testing methods at 2.0
mm, 3.8 mm and 6.0 mm gap distances.
xiii
LIST OF FIGURES
xiv
2.17 Influence of voltage polarities on the 50% break- down 49
voltages of all samples at gap distances of (a) 2.0 mm, (b)
3.8 mm and (c) 6.0 mm [38].
xv
3.10 The AC breakdown voltage test setup under HV 75
Laboratory.
4.8 The electric field strength of oil samples under various 109
gap distances.
xvi
4.10 1% probability breakdown field in comparison with 117
Weidmann curve for inception field at various gap
distances
xvii
LIST OF ABBREVIATIONS
MO - Mineral oil
PO - Palm oil
RBO - Rice bran oil
HV - High voltage
VDE - Verband Deutscher Electrotechniker
α - Shape parameter
β - Scale parameter
σ - Standard Deviation
µ - Mean value
µs - Micro Second
ø - Diameter
°C - Celsius
∆U - Step Voltage Increment
∆V - Different Voltage
∆T - Time Interval
AC - Alternating Current
ASTM - American Society for Testing and Materials
cSt - CentiStokes
d - Gap Distance
E - Electric Field
FR3 - Fire Resistant Natural Ester
g/ml - Gram per Millilitre
IEC - International Electrotechnical Commission
f(x) - Probability density function of breakdown voltage
k - Number of Breakdown
kV - Kilo Voltage
kΩ - Kilo Ohm
mm - Milimetre
N - Total Sample Size
V - Voltage
xviii
CHAPTER 1
INTRODUCTION
1.1 Background
The transformer is one of the most expensive and critical components in electrical
catastrophic event which may cause server disruption and complete blackout of the
system [1]–[4]. Based on the literature [2], [5]–[7], the post-failure analyses of
Oil and paper have been used as insulation materials for power transformers over the
past century [4]. Transformer oil is used to fill the void in the paper insulation and
also fill the gaps between components in the transformer tank which increases the
dielectric strength of the insulation system. The oil not only serves as an insulating
liquid but also as a heat remover from the windings and cores [8]. The heat is a result
of the losses from the transformer windings and cores. The oil is also used as an
1
Mineral oil (MO) has been widely used in power transformers for more than
150 years. MO originated from petroleum and has a number of attractive electrical
and thermal properties for transformer application. Among the advantages of using
MO are low cost, widely available and low viscosity. It is used in oil-filled
MO also has some undesirable properties which affect oil performance. Somehow,
MO is poorly biodegradable and can cause serious environment pollution to the soil
and waterways if serious spills occur during incidents such as transformer explosion
[7] - [9]. Also, MO is a combustible liquid with a flash and fire point of 170 °C and
transformer fires do sometimes unavoidably occur. Hence, the concern of fire safety
and the inability to comply with environmental laws have encouraged the search for
alternative dielectric fluids in power transformers. In recent years, vegetable oils were
introduced as an alternative to the MO. Vegetable oils have a higher flash and fire
point than MO and are biodegradable which reduced environmental impact and are
non-toxic to organisms and humans [9]–[13]. Besides that, their superior thermo-
physical and enhanced dielectric properties help to speed up the preference in using
alternative to MO, they must be safe, economical and offer a high standard of
electrical properties over the transformer lifespan. Recently, extensive works were
carried out to investigate the suitability of vegetable oils as the alternative to MO [3],
[9] - [59]. The studies evaluated dielectric properties, physical and chemical
Vegetable oil is derived from natural sources plants and seeds. The most
attractive features of vegetable oil are its high biodegradability and non-toxic
2
property, hence posing no risk to the environment in case of spillages. Vegetable
oils also have higher fire safety and high moisture absorption ability [17] - [18].
Indeed, vegetable oils have the highest fire point in the dielectric fluid category.
According to IEC 61100, they have a fire point of 360 °C [19], ensuring more
operation safety for in-service transformers compared to MO. The high moisture
saturation levels of vegetable oils result in the absorption of water from the cellulose
materials, thus protecting the insulation paper from ageing and deteriorating.
Natural ester oil consists of total fat classified as saturated fatty acids,
Although some poor features of esters limit their usage, e.g. low oxidation
stability for vegetable oils, they have been used worldwide for many years in either
challenges faced in recent years include extending the use of vegetable oils from
industries have already tried to apply vegetable oils in large power transformers, e.g.
a 132 kV/90 MVA transformer filled with FR3 manufactured by ALSTOM Grid
(previously AREVA T&D) and put into service by UK Power Networks (previously
EDF Energy) in 2009 [63] and a 238 kV/135 MVA transformer filled with Midel
7131 being operated in Sweden [64]. In the USA, some transformers up to 230 kV
and 200 MVA have been retro-filled with esters to extend their working lives [65].
Since the physical and chemical properties of vegetable oils are different from those
of mineral oil, both the design and manufacturing process of power transformers
3
might be affected. Thus, a complete understanding of the dielectric properties of
vegetable oils and their impact on transformer design and operation is required.
transformers is palm oil (PO). To date, a lot of experiments have been carried out
covering different basic electrical, physical and chemical aspects [18], [20], [22] -
[27], [33] - [34], [38] - [39], [45] - [49], [53], [56], [66] – [72]. The results showed
that PO has a good potential as an alternative insulating fluid since the AC and
lightning breakdown strength of PO were comparable to mineral oil [10], [12], [22],
[27] - [28], [42], [47], [49], [53], [56], [66]. Another type of vegetable oil that
showed good performance is rice bran oil (RBO). Only limited numbers of studies
were done on RBO especially on the physical, chemical, and electrical properties.
In 2016, S. Senthil Kumar investigated rice bran oil (RBO) for the ability to be used
as alternative transformer oil. The initial study showed that the AC breakdown
voltage of RBO has comparable performance to other natural esters [5], [19], [22],
[39], [84]. The finding observed that RBO has better properties among other
vegetable oils.
normally carried out to test its breakdown and withstand ability since in-service
failures could be costly to the utility’s providers. Lightning studies can be carried
out under a uniform field or a quasi-uniform field and a non-uniform field. However,
current PO studies are only limited to smaller gap distances under both electric fields
4
[38], [45] and no studies reported on RBO under lighting impulse. When the
transformers.
permittivity, resistivity and tan delta is carried out to know the capability of PO and
RBO to meet the industrial standard. Besides that, an AC breakdown and impulse
the limitation specified for MO is relevant to PO and RBO before these vegetable
Among the vegetable oils that are attractive and could be proposed are palm oil (PO)
and rice bran oil (RBO). Malaysia is one of the largest palm oil producers in the world.
Palm oil is extracted from the palm nut. There are different types of palm oil produced
including Crude Palm Oil (CPO), Refined Bleached and Deodorized Palm Oil (RBDPO),
Red Palm Oil, Oleic Acid, and Palm Fatty Acid. Palm oil is one of the few vegetable oils
relatively high in saturated fatty acid and thus it is in the semi-solid form at room
temperature [28]. Rice oil, also called rice bran oil, is extensively used in Asian
5
countries [85] - [91]. Rice bran oil is produced from the rice bran and germ of Oryza
sativa seeds [92]. Due to an economic and efficient method for recovering the oil,
RBO should be acquired to avoid the wastage of rice mills. Rice bran oil is widely
used for various purposes such as cooking, fuel, biodiesel, lighting and power
Although PO and RBO are quite attractive for transformer application due to
their environmental-friendly feature, there are, however, several aspects that need be
addressed before these new vegetable oils can be applied into service. To become
acceptable as alternatives to mineral oil, both PO and RBO must be safe, economical,
and offer a high standard of electrical performance standard over a long working
lifetime and an extensive period. Therefore, for any new dielectric fluids to be used
in transformers, the viscosity, pour point, flash point, AC and lightning characteristics
of these oils need to be thoroughly investigated. Only limited numbers of studies have
been done on RBO and PO, especially on their viscosity, flash point and pour point
properties.
Blume reported that the dielectric strength of mineral oil (in kV/mm)
decreases as the distance between the electrodes increases [95]. The previous studies
for PO and RBO have only considered the AC dielectric strength of oils using small
windings can be made in the structures of disk or layer, of which each consists of
many papers wrapped turn conductors. The turn to turn insulation is made by multiple
layer oil-impregnated papers with a thickness of ~1-2 mm. Washers are used to
6
separate the disk conductors and thus oil ducts are formed between the disks with a
thickness of ~3-10 mm. The distance between windings is relatively large, which
vegetable oil subjected to lightning voltage becomes more important for insulation
design. Theoretically, lightning may strike directly to earth near overhead lines
connected to the transformer which in turn could cause overvoltage. Until now, no
one has reported any study on lightning impulse performance of RBO. For PO, most
of the studies covered only on different testing methods and small gap distances.
insulation. Thus, it is also important to study the lighting impulse of PO and RBO
Lightning studies can be carried out under uniform, quasi-uniform, and non-
uniform electrical fields. The insulations between turns, disks and windings of the
transformer may be more challenging for insulation design. At the corner part of the
end winding insulation, although there are contoured angle rings, there are still
tangential electric fields existing on the pressboard surface, which could facilitate the
creepage discharge when it happens. Creepage discharge is one of the failure reasons
for large power transformers. In addition, the bushing lead to the grounded tank could
7
form a long-distance non-uniform field. Finally, manufacturing defects, e.g.
protrusion on the copper conductor, and contaminations resulting from long term in-
service degradation, e.g. particle and moisture in the oil, could cause local electric
field enhancement (non-uniform field) and thus might initiate a discharge. Insulations
stressed in all these non-uniform fields are the weak link of a transformer, which
requires careful attention in the processes of design and manufacture. To sum up, the
this thesis will be covered both in uniform field and in non-uniform field.
To add to the complexity, parameters such as testing method, gap distance and
volume of oil used for the experiment may influence the lightning breakdown voltage
and RBO will be investigated at various conditions and compared to the common
transformer insulation oil, MO. By the end of the research, it is expected to achieve
a) To analyse the viscosity, flash and pour point, moisture content, permittivity,
8
b) To determine the AC breakdown performance of PO and RBO under
under uniform and non-uniform fields at various gap distances with different
testing methods.
a uniform field at 1.5 mm, 2.5 mm, 3.5 mm, 5.0 mm and 10.0 mm gap
distances.
RBO under a uniform field at smaller gap distances of 2.0 mm, 3.8 mm and
6.0 mm.
RBO under a non-uniform field at gap distances of 2.0 mm, 3.8 mm, 6.0
mm, 10.0 mm, 20.0 mm, 30.0 mm, 40.0 mm and 50.0 mm.
d) Three different testing methods which are rising voltage, up and down and
multiple level methods are used on the lightning impulse breakdown voltage
of PO and RBO.
9
1.4 Major Contribution
dielectric properties of RBO are more similar to MO than PO. Besides, both
the IEC 60156 test method. Additionally, the various gap distances showed
scenarios.
(c) The lightning impulse breakdown voltage under the uniform field and non-
uniform field at various conditions can be used to test the capability of a power
transformer design and from this study, both oils are comparable to MO.
10
(e) The empirical formula to determine the breakdown strength of PO and RBO
was proposed.
This thesis consists of seven chapters, which cover the introduction, literature review,
Chapter 1 describes the general background of this research and also gives an
overview of the thesis with research objectives, scope and problem statements.
Chapter 2 provides a comprehensive review of the related studies under the following
topics: background of the transformer, the new alternative transformer liquids, brief
voltage.
Chapter 3 elaborates the oil samples to be tested and the preparation procedures for
the oil samples. The experimental setup, test cell configuration and testing methods
11
Various conditions of gap distances are investigated. The discussion section contains
dielectric performance.
RBO in a uniform field under sphere to sphere electrode configuration. The influence
of various testing methods, including the rising voltage method, up and down method
and multiple levels method, are investigated at different smaller gap distances. The
results obtained are used to determine the lightning withstand voltage with a statistical
under a non-uniform field. The configuration of needle to sphere for various testing
methods, including the rising voltage method, up and down method and multiple level
method at smaller gap distances under the lightning impulse breakdown test, were
observed. Besides that, configuration of larger gap distances using the rising voltage
method were examined. The results obtained are used to determine the lightning
withstand voltage with statistical analysis. The empirical formulas were then
determined from the relationship between the lightning breakdown voltage and gap
Chapter 7 provides the overall summaries and conclusions of this research. At the end
of this chapter, recommendations for future work on the ageing assessment of the PO
12
13
CHAPTER 2
LITERATURE REVIEW
2.1 Introduction
This chapter discusses the required oil properties for insulation and coolant in high
impulse voltage. It also summarises the most recent research findings on rice bran oil
and palm oil liquids, as well as comparisons with other mineral oils.
discovered by Michael Faraday. Generally, there are four types of transformers used
voltage level, (ii) transformer based on core material, (iii) transformer based on
is often used to protect the core windings of the transformer. It is because they are
fully submerged in the oil. Another essential property of the insulating oil is its ability
to avoid the oxidation of the insulating paper made from cellulose. The transformer
oil serves as a buffer between the cellulose and the ambient oxygen. This can prevent
any direct contact and thereby reduce oxidation. Furthermore, the numerous failures
In this case, the main challenge to the engineers is to increase the reliability
15
2.3 Insulation oil used in transformer
In general, transformer oil or insulating oil is a highly refined mineral oil that is stable
at high temperatures and has excellent electrical insulating properties. It is used in oil
serves three basic functions that are to keep the transformer functions isolated, cooled
and maintained at all times. The industry has agreed on certain standards to maintain
these functions. There are many specific requirements and limits in these standards,
Many of these properties and their drawbacks are derived from the chemistry
transformer oil brands could only satisfy the requirements, others excelled. Most
transformer oils used in Malaysia are mineral oils (uninhibited mineral oils)
containing Paraffic, Naphteric, or mixed. They are supplied by Hyrax Oil Sdn. Bhd.
The transformer oil's principal function is to insulate and cool the transformer, and
the properties of the insulation oil are based on high dielectric strength and good
dielectric properties. Plus, the physicochemical of insulation oil such as low viscosity,
high resistivity, low pour point and high flash point are considered good insulation
16
In the context of the breakdown voltage, dielectric force is one of the
insulating material is the maximum electrical field strength that it can withstand
without breaking down and without any failure to its insulating properties. The
dielectric strength also means that a certain dielectric configuration and electrode
material causes minimal damage to the electrical field. The breakdown intensity in
the liquid is caused by different factors in the experiment: electrode material and
molecule structure, temperature and strain [105]. Besides, there are several
Mineral oils have been used as insulating and cooling material for almost over
a century in transformers due to their thermal and insulating features. Transformer oil
conventionally used mineral oil that has been formulated for better engineering and
power transformers to insulate, stop arcing and corona discharge, and to dissipate the
in producing gasoline and other crude oil-based petroleum products. In this sense,
17
approximately 0.8 g/cm3. Mineral oil is a relatively low value substance, and it is
produced in very large quantities. Mineral oil in light and heavy grades are available
and are often found in drug stores [109]. There are three basic classes of mineral
purposes.
hydrocarbons that have at least one carbon atoms ring. A common example
18
Table 2.3 Hydrocarbon Structure of Naphtenic oil [112].
Cyclohexane Methylcyclopentane
1,2-dimethlycyclopentane
iii. Aromatic oils, based on aromatic hydrocarbons
paraffinic oil gaining traction because it is virtually sulphur-free. Paraffinic oil has a
high viscosity index that is good for engine oil but bad for transformers. The
naphthenic oil should achieve a lower viscosity which means more transformer oil on
transformer oil is a premium uninhibited mineral insulating oil made from highly
19
hydro-treated, wax-free naphthenic oil that is excellent as a dielectric and coolant. It
has very strong fluidity at low temperatures, a high flash point and stability to the
material. Table 2.5 described the properties of uninhibited mineral oil. The properties
of mineral oils based on more previous studies are indicated in Appendix A.1. The
properties of mineral oil from [17] – [27] supported the properties gained in this
research.
Test Specification
Properties Values
Method
Min Max
Viscosity, cSt at 40 °C ISO 3104 - 12 10.4
Pour Point, °C ISO 3016 - -40 -60
Flash Point, °C ISO 2719 135 - 145
Water Content, PPM IEC 60814 - 30/40 20
Breakdown Voltage, kV IEC 60156 30/70 - 60
Density at 20 °C, g/ml ISO 12185 - 0.895 0.881
DDF at 90 °C IEC 60247 - 0.005 0.0002
Acidity, mg KOH/g IEC 6201-1 - 0.01 0.005
to overcome some of the drawbacks with mineral oils [119] - [120]. It has proven to
be a viable alternative to mineral oil used in the industry for several decades and has
several advantages over mineral oil [121]. The electric power transmission and
20
distribution industry for complicated environmental requirements seek viable
alternatives to mineral oil. Any alternative that is suitable for the environment, is
economical and has a high electrical efficiency level for an extended life needs to be
considered in current use. Recently, natural ester has been widely used in the industry.
natural ester.
For vegetable oils, a different fatty substance can esterify each position on the
glycerol molecule acid, following the patterns of plants. Triacylglycerols (TAG) are
the most common forms in which two or three types of fatty acid molecules are
All the physical and chemical properties of oils and fats are significantly
affected by the form and proportion of the fatty acids on the triacylglycerol. The
polyunsaturated fatty acid (PUFA) bonds. However, each of the vegetable oils
analysed has a specific distribution of fatty acids, depending on their plant sources
[122]. Based on previous research, the vegetable oils show that the composition of
the oils is almost similar to each other. Due to the lack of research on rice bran oil
21
dielectric properties, the properties of general vegetable oil were indicated. Therefore,
Table 2.6 presented the fatty acid composition of vegetable oils from different
Unsaturated fatty
References Vegetable acids, % Saturated fatty
oil acid, %
Mono Poly
[22], [39], [89], Rice bran
38 - 45 35 - 37 15 - 25
[123]–[126] Oil
[22], [89], [123],[125] Palm Oil 35 - 40 10 - 11 45 - 50
[22], [89], [125], Sunflower
19 - 40 37 - 69 12 - 18
[126] Oil
[89], [125], [127] Soybean Oil 22 - 24 51 - 61 14 - 15
oils are gaining worldwide attention for their use as insulating liquids in power
transformers [42], [128]. The abundance of palm oil and its derivatives encourages
studies related to the availability and affordability of such insulating liquids for
power transformers [129]. There are different types of palm oil produced including
Crude Palm Oil (CPO), Refined Bleached and Deodorized (RBD) Palm Oil, Red
suitability of the use of palm oil as an isolating liquid in the literature. A number of
studies have been conducted by comparing several existing insulating liquids [66],
22
[130]. For example, Aditama [66] has studied the comparison of temperature effects
on dielectric properties of palm oil with mineral oil of insulating liquid and silicone
oil types. The parameters measured included the decomposition, dissipation (tan μ)
and dielectric constant. Table 2.7 shows the different findings between RBD and
crude palm oil based on the ASTM standard. Appendix A.2 presented the summary
of the dielectric strength of the palm oils commonly found in previous studies.
Table 2.7 : The properties of the RBD and crude palm oils.
Palm oils
RBD Crude
Property Standard
[131], [66], [81], [11],
[81], [11] [132]
Flash point °C ASTM D92 220-330 >250
Viscosity (cSt) at 40 °C ASTM D445 37-50 42
Acidity (mgKOH/g) ASTM D974 - -
Breakdown voltage (kV) ASTM D 1816 52-86 17-23
Dissipation factor %, at 90 °C ASTM D924 0.0035-0.014 0.006
Dielectric constant, at 90 °C ASTM D924 3.5 2.1
Rice is produced in very large quantities in Southeast Asia countries [86], [87], [89]–
[92]. Rice bran oil (RBO) as a by-product of rice milling is obtained from the outer
layer of the brown rice kernel accounting for 6–8% of the paddy rice. The global
paddy rice production was 741 million tons and this huge amount of production
resulted in more than 50 million tons of rice bran in 2014 [136]. Furthermore, rice
bran is a nutrient-rich by-product mainly due to its high oil, fibre, protein, and
phytochemical contents. Although rice bran is highly nutritious, it has a very short
23
shelf-life due to lipase-induced lipid rancidity that has limited the large use of rice
bran as a food material. The oil content of rice bran varies in each variety and heavily
depends on the processes and conditions obtained during rice milling. Rice bran, as
such, has 15 to 25% of oil associated with it. Rice bran oil can be defined as a natural
oil that is produced using the rice bran inside the hull of the paddy [92]. The
Rice bran oil is the oil extracted from the rice's hard brown outer layer called
chaff (rice husk). It is known for its 232 ° C (450 ° F) high smoke point and mild
flavour, making it suitable for high-temperature cooking methods. Rice bran oil is an
edible oil that is used to make vegetable ghee. Rice bran wax, derived from RBO and
In the context of compositional analysis, Yang [137] stated that 90% of rice
bran oil’s fatty acid comprises of palmitic acids (17.0%), oleic acids (47%), and
linoleic acids (32.65%). Similar to other natural ester oil, fatty acid can be categorised
into several groups with different functions, including saturated fatty acid (SFA),
24
monounsaturated fatty acid (MUFA) and polyunsaturated fatty acid (PUFA). Rice
bran oil is similar in composition to peanut oil, with 38% monounsaturated, 37%
compared with various other vegetable oils emphasising on breakdown voltage, flash
point, fire point, viscosity, acidity, resistivity and loss factor of the natural ester.
Kumar [75] performed an analysis of vegetable liquid insulating medium for high
such as breakdown voltage, flash point, fire point and viscosity. Natural ester-based
vegetable oils have shown the ability to substitute conventional mineral oils.
Besides, Mohammed [125] have found that RBO has better properties than
other natural ester oils investigated except for viscosity. Furthermore, [75] discovered
the critical parameter of mixed insulating fluids and found that vegetable oils have
attempt to find an alternative insulating fluid with better insulating properties and
natural ester oils and mixed combinations of olive oil, rice bran oil and soya bean oil
intervals between raw rice husk and RBO due to inadequate literature on the low-
frequency response. Additionally, potential applications of raw rice husk and RBO
protection. The summarised dielectric and physicochemical properties for RBO based
25
Table 2.8 : Dielectric and physicochemical of the rice bran oil.
This section discusses the properties of commercially available esters that vary with
the product and typical representational values as the most important properties for
using vegetable oils as transformer oil. All transformer oils must withstand AC
voltage, flash impulse and flipping the impulse norms. The AC test for breakdown
voltage is the main method to assess the ability of the liquid to carry electrical stress
2.4.1 Viscosity
The viscosity of the insulating fluid affects the conductive heat transfer
capability. Viscosity is known as the measurement of resistance for oil to flow and
can be used to determine its oxidation stability. Viscosity can be measured using the
transformers is the primary heat removal method, and thus, a higher oil viscosity
26
within the transformer would be expected to result in higher hot spot temperatures.
Some tests showed that using vegetable oils in transformers leads to higher
temperatures within 1 to 3°C [142]. Besides, the viscosity of oil within the normal
efficiency. Low viscosity oil will have good natural convection and forced convection
viscosity limit (maximum) of 12 mm2/s at 40oC for mineral oil, while IEEE Standard
C.57.147 recommends 50 mm2/s at 40oC for natural ester oils [143]–[145]. Some of
the previous studies in Table 2.9 investigated the kinematic viscosity of the samples.
Table 2.9 : The kinematic viscosity of palm and rice bran oils.
Kinematic viscosity
Reference Vegetable oil
(mm2/s)
[92] Rice bran 42.87
Rice bran 40.88
[93]
Palm 43
The flash point is a primary indication for the chances of fire hazard in the
[75]. So the transformer oil should possess a very high flash point [11]. By
continuously applying flame, the minimum temperature at which oil starts to flow
under the standard test condition is said to be the fire point. The transformer oil flash
point is the minimum temperature at which the oil gives out vapour, the transformer
27
oil (mineral oil) flash point value is usually 140 °C [72]. The insulating oil is
considered good when it has a high flash point, high breakdown voltage and low
partial discharge [146]. A high flash point means that the oil will only give enough
vapours to produce a flammable mixture with air at high temperatures [29], [147].
Generally, alternative oils such as silicon oil or ester (natural ester or synthetic
ester) oils have high flash points and high relative permittivity than silicon oil [34],
[59]. Norhafiz [11] in his study found that the range of flash point for palm oil is
between 220 °C and 330 °C, slightly lower than the flash point of standard natural
ester. Appendix A.3 shows the previous study on flash point of vegetable oils.
The pour point is the temperature at which, under the prescribed conditions,
transformer oil will flow. Pour point is a useful measure of how transformer oils work
temperature conditions. Natural esters have a higher yield point than mineral oil,
usually between -15 and -25 °C, but tests showed a good cold start to -30 °C [148].
Table 2.10 : The pour point standard of mineral oil and vegetable oil.
Natural Ester
References Standard Mineral Oil
Liquid
[149], [141] ASTM D97 ≤ - 40°C ≤ - 10°C
[54] IEC 3016 ≤ - 40°C ≤ - 10°C
28
2.4.4 Dielectric Dissipation Factor (Tan δ)
The dissipation factor is known as the reciprocal ratio of the capacitive reaction
to its resistance at a given frequency between the isolating materials. It tests the
loss [141]. The dielectric dissipation factor can also be used to determine the degree
of contamination in oil [150]. Previous studies showed that there was a small effect
on the dielectric dissipation factor of vegetable oils [151]–[153]. Table 2.11 specifies
the different limits given in international standards for the dissipation factor of
mineral oil and natural ester oil. The dissipation factor is proportional to the electric
equation 2.1.
tan𝛿= 𝜎/ 𝜔𝜀 (2.1)
Where, tan δ is the electric conductivity, ω is the angular frequency, and ε is the
permittivity of oil.
29
Figure 2.3 : A cell for liquids measurement proposed by IEC 60247 [154]
[155].
% Dissipation Factor
Reference Temperature
Standard Natural ester
number (°C) Mineral oil
liquid
ASTM D924 25 0.05 ≤ 0.2
[223][226]
[227] 100 1-3 <3
[228] IEC 60247 [229] 90 ≤ 0.005 ≤ 0.05
insulating medium in creating electric fields. The dielectric constant, also called
polarised way through an electric field. Furthermore, [156] has studied the relative
permittivity of vegetable oils under ageing duration. Based on this study, there was
30
no significant change in the relative permittivity of MO. The ratio of oil-filled test
Where, εr is the dielectric constant, Cx is the capacitance of the oil filled test cell and
2.4.6 Resistivity
Resistivity refers to the resistance as electrical current flows through a conductor. The
resistivity (Ω/cm) is known as the ratio of the direct potential gradient in volts/metre
(V/m) parallel with the current flow to the current density of the samples in
amperes/square metre (A/m2) [141]. Some of the previous studies had found that
natural ester has a higher resistivity than mineral oil. The range of resistivity for
mineral oil is in between 7.6 T Ω/cm to 100 T Ω/cm and 220 T Ω/cm to 700 T Ω/cm
for natural ester and can be referred to in Table A.1 and A.2 in Appendix A.
breakdown voltage [141]. There are a number of standard test methods used where a
31
small volume of oil is exposed to a nearly homogeneous electric field and two
electrodes are submerged in the fluid until breakdown occurs as the voltage is
reported using uncoated electrodes, called bare electrodes in accordance with IEC
60156 or ASTM D1816 [157]. The bare electrode was used to demonstrate the worst-
case situation inside the transformer where there is no more insulating paper on the
conductor. The experiment is to identify the oil's tolerance tension or the lowest
breakdown voltage for the worst-case scenario. The breakdown voltage is measured
in either mushroom, sphere or plane configuration with a pair of electrodes, and has
Several tests were carried out to compare natural ester breakdown voltages
and discharge characteristics and mineral oils from different suppliers [44]. There are
many test standards for insulating liquids, but they are derivatives of three main
(mm), stir times (minutes), number of breakdowns recorded and voltage ramp rates
presented the comparison of the standard used for insulation oil breakdown test shown
in Appendix A.4.
32
impurities existing in a transformer fluid, such as the presence of excessive moisture,
voltage of an insulating fluid mostly represents the oil quality rather than oil
characteristic itself.
sparking strands between two electrodes immersed in the oil, separated by a specific
gap of 2.5 mm [20]. Table 2.13 shows the values of AC breakdown voltages of RBO
vegetable oils at various gap distances under a quasi-uniform field. The results of
palm oil are slightly lower than FR3. The measurement was done using VDE
electrode according to IEC 60156 at various gap distances from 0.5 mm to 3.5 mm.
Figure 2.4 : The variation of breakdown voltage in five types of oil [41].
oil compared to mineral oil for the oil gap of 2 mm. The experiment used Baur DTA
100 E with the gap length reduced from standardised 2.5 mm to 2 mm following IEC
60156 with minor modifications. Using a Perspex test vessel with 1.5 litres volume
of oil allowed the recognition of different electrical field stress conditions. Figure 2.5
illustrates the arrangement of electrodes under the quasi-uniform field. The result of
34
Weibull distribution shows that vegetable oil has a higher breakdown voltage than
Another study was done by R, Frotscher, Vukovic and Jovalekic [55]. Their
study investigated three types of samples which are synthetic ester (MIDEL7131),
natural ester (FR3) and mineral oil (Diala D) for the AC breakdown voltage under
various gap distances. The result of the AC breakdown voltage found that all samples
are close to each other at 2.5 and 5.0 mm gap distances. The ester oil breakdown
voltage shows an increment similar to Midel 7131. The breakdown voltage of mineral
oil is lower in small gap distances below 10.0 mm. The mean breakdown voltage for
35
Figure 2.6 : The VDE configuration with d = 2.5mm, 5mm, 10mm and 15mm
[55].
Figure 2.7 : The AC breakdown voltage of VDE configuration for various gap
distances [55].
Sanjida Islam et al. [59] had investigated alternative insulating oils with
biodegradable characteristics. The four types of natural vegetable oils used are
coconut oil, mustard oil, palm oil and soybean oil. There are other two types of
mixture oils which are coconut oil mixed with mustard oil and coconut oil mixed with
palm oil. These vegetable oils were compared with transformer oil in mushroom
36
The results obtained show that the breakdown voltage of vegetable oils are
higher than the transformer oil as shown in Figure 2.8. The mixed 50% coconut oil
with 50% palm oil breakdown voltage (58 kV) is high at the 7.5 mm gap distance.
output voltage is 60 kV. The breakdown voltages of all samples were seen close to
each other except for the mixed oils. Coconut and palm oil show higher breakdown
voltages in all gap distances than transformer oil. The authors concluded that
vegetable oil has been recognised as a good quality substitute material for transformer
oil. This was also supported with other reviews due to its high-quality
biodegradability characteristic, low pour point, high flash point and high solubility
[21]–[23], [27], [30] - [31], [43] - [44], [59], [61], [77], [169].
Figure 2.8 : The comparison of breakdown voltage for all samples across
mushroom electrodes [59].
dielectric in the transformer. The ester oils show the capability to act as mineral oil.
Their experiment used BAUR DPA75 as the oil breakdown tester attached with VDE
breakdown voltage of synthetic ester obtained was higher with 47 kV and followed
by natural ester at 41 kV and mineral oil, 39 kV. However, due to the small gap
distance, the breakdown of all samples are seen to be close to each other. Previous
studies on vegetable oils, especially with those related to this research such as palm
oil and rice bran oil, for the AC breakdown voltage were indicated in Appendix A.4.
decreases to zero [170]. The standard lightning impulse is a full lightning impulse
having a virtual front time of 1.2 μs and a virtual time to half-value of 50 μs [25].
virtual front time of 1.2 μs and a virtual time to half-value of 50 μs. Figure 2.9 depicts
38
Figure 2.9: Example of lightning impulse waveform.
The curve derived by implementing equation (2) included in [17]. (1) Time to
half the peak voltage, (2) Time to peak voltage, (3) − (4) Time above 90 % [172]
ASTM D3300 and IEC 60897 standards [173] are the commonly used
standard to conduct lightning and switching impulse breakdown voltages. The IEC
specifies a standard impulse wave with a front time of 1.2 μs ± 30 % tolerance and a
voltage of ester liquids investigated has either positive or negative polarity [2], [30],
[42], [49] - [50], [58], [175] - [182]. The ASTM D3300 has mentioned that the voltage
wave has little or no effect on the breakdown strength of a liquid. The standard
impulse test, ASTM D3300, specifies a 1.2 × 50 μs negative polarity wave. The
standard wave shape for switching surge tests on transformers is 100 μs to crest and
equal to or greater than 1000 μs to zero [145]. The comparison between the two
39
Table 2.14 : Comparison between ASTM and IEC impulse test methods [76].
occurs in the atmosphere. When there are two clouds with opposite charges, positive
and negative, are within the strike distance of each other, it will produce lightning.
Other than that, lightning also can occur when an object on earth has a connection
with the negative cloud and 95% lightning strikes in the world occurred in negative
polarity [182]. As this decreases the chance of erratic external flashover in the circuit,
fields mimic most of the electrical fields inside a transformer. Usually, the uniform
and quasi-uniform fields correspond to the configurations of the plane, chestnut and
which leads to liquid failure. The defect was caused by the configurations of the point
or point-sphere electrodes.
40
2.5.1 Lightning impulse breakdown voltage under uniform field
the studies on breakdown strength of ester liquids was done by [31]. The results
indicated that the lightning impulse breakdown strength of ester liquids is comparable
to that of mineral oils in quasi-uniform fields in clean conditions (oil samples were
Qiang [2] has conducted a lightning impulse test in negative polarity with a
waveform of 1.2/50 μs applied on a 3.8 mm sphere-sphere gap. The author used the
rising-up method with increased step by step with a step increment of 10 kV. At each
voltage level, three shots were applied and the time interval between two consecutive
shots was fixed at 60 seconds. In total, five breakdowns were made for each type of
liquid. The three types of samples used are Gemini X and Midel 7141, which are
based on the mineral oil type and FR3 which is made from natural ester oil. The result
Figure 2.10 : Comparison of lightning breakdown voltage between ester oil and
mineral oil at 3.8mm gap distances.
41
Table 2.15 : Lightning breakdown strength breakdown voltage for ester oil and
mineral oil at 3.8mm gap distance [2].
Martin [25] has also conducted the lightning impulse breakdown voltage with
a Haefely 10 stage impulse generator to provide a 1.2 μs/50 μs negative voltage wave
shape. The test cell, the gap distance of 3.8 mm and the 12.7 mm diameter spherical
Table 2.16 : Lightning breakdown voltage for ester oil and mineral oil
at 3.8mm gap distance according to ASTM D3300[25].
K. J. Rapp et al. [184] has discussed about the quasi-uniform field at gap
electrodes were used for 25 mm and 50 mm gap distance, while Type 2 electrodes
were mounted on a pressboard 3.2 mm thick and used for the 12 mm gap distance.
The oil gap test results from Type 1 and Type 2 electrodes were comparable with
industry design criteria. The Type 1 and Type 2 configurations are shown in Figure
2.11.
42
(a) (b)
Figure 2.11 : The type 1 and 2 electrode configuration under quasi uniform
field [184].
The obtained lightning breakdown voltage results are shown in Figure 2.12.
As expected, the breakdown strength of liquids generally decreases with the increase
of gap distance and volume of liquid under stress. Importantly, the breakdown
strength of natural ester is similar to that of mineral oil, both of which are higher than
the Weidmann oil design line [76]. The sample handling procedure (e.g. whether the
sample is exposed to the air environment and whether vacuum is required afterwards)
during the processing and testing was emphasised by the authors as an important
43
The authors [184] also concluded that the lightning breakdown strength of
comparable to that of mineral oil. The term comparable indicates that the lightning
breakdown strength of natural ester is approximately 10% to 15% lower than that of
mineral oil. Table 2.17 shows the lightning breakdown voltage of natural ester and
mineral oil using Type 1 and Type 2 electrodes at various gap distances from 12 mm
to 50 mm.
Table 2.17 : Lightning breakdown strength of natural ester and mineral oil
using type 1 and type 2 electrodes at various gap distances from 12 mm to 50
mm [184].
field are important as a parameter for transformer design [62]. A non-uniform field
configurations which can simulate the imperfections that could occur in transformers.
44
According to IEC 60897 [185], the determination of lightning impulse
Thien [38], [49], [180] had studied several types of vegetable oils (three types
of palm oil and coconut oil). The vegetable oils were compared to Hyrax mineral oil.
The test setup of the lightning impulse test is according to IEC 60897. All tests were
carried out at 2, 3.8, 6, 10, 15- and 25-mm electrode gap distances. The finding shows
that vegetable oil breakdown voltages are slightly lower than mineral oil for small
gap distances (2.0 mm, 3.8 mm and 6.0 mm). The lightning breakdown voltage of the
mineral oil has increased higher than the vegetable oils as gap distances increased.
Figure 2.13 shows the breakdown voltage of various types of palm oil, coconut oil
Figure 2.13 : 50% breakdown voltages for all samples based on rising-
voltage method [180]
45
Qiang [61] in his research on Ester Insulating Liquid for Power Transformer
has investigated the electrical performance of ester oils under the lightning impulse
50 mm. The voltage level was increased step by step using the rising voltage method
changing both the electrode and liquid sample. The lightning breakdown voltages of
ester liquids are lower than that of mineral oil for all gaps observed, and the
differences become bigger whenever gap distances increased as shown in Figure 2.14.
The various testing methods in Z. D. Wang et al. [40], [61] were compared to the
breakdown voltage of ester liquids and mineral oil in a 3.8 mm sphere-sphere gap
46
using negative 1.2/50 μs lightning impulses. Gemini X mineral oil shows better
lightning impulse withstanding ability than ester-based oils no matter which methods
were used. Figure 2.15 shows the results which indicated that the testing methods
have notable influences on the absolute breakdown voltages, but does not affect the
relative ranking of the liquids between ester liquids and mineral oil. The multiple-
level method gave a higher breakdown voltage than the other two methods.
The finding of the testing method effect on the breakdown voltage has been
discussed in the research by Katim N.I.A [34]. Her research was carried out for the
breakdown voltage under a uniform field at 2.0 mm and 3.8 mm gap distances as
shown in Figure 2.16. The multi-level method had the highest percentage of
differences among the methods with the biggest differences. From this study, it is
found that testing methods have a notable influence on the measured breakdown
voltage for various gap distances. The percentage of difference is less than 10%, in
47
(a) (b)
Thien [38] researched the lightning impulse breakdown voltage under a non-
uniform field. Her study was carried out to test the influences of testing methods
under negative and positive polarities at various gap distances. Overall, Thien’s
research found that all breakdown voltages of samples showed a small effect under
different testing methods. The influence of testing methods can be observed in Figure
2.17. The multiple-level method has the highest 50% breakdown voltages as agreed
by Z. D. Wang [40].
(a) (b)
48
(c)
Figure 2.17 : Influence of voltage polarities on the 50% break- down voltages
of all samples at gap distances of (a) 2.0 mm, (b) 3.8 mm and (c) 6.0 mm [38].
related to the dielectric performance of ester fluids under very large oil gaps [25],
[74], [193] - [194]. As many research was devoted to the good potential of esters to
replace the MO in distribution transformer, the behaviour of these oils for different
gap spacing is important [192] - [193]. The transformer’s windings can be made in
the structures of disk or layer, each of which consists of many papers wrapped around
turn conductors. The distance between windings is relatively large, which could be
tens of mm. A bigger transformer has larger gap distances between the disk windings.
One of the influences of the breakdown in insulating oils is by the various testing
condition gaps [178], [197] - [200]. Breakdown measurements in insulating oils are
transformers.
49
In research by J.E. Contreras et al. [74], lightning breakdown voltages of ester
fluids could be lower than that of mineral oil at very large gaps [198]. Therefore,
fluids are used in high-voltage transformers. This is also agreed by research study
larger gap also mentioned the same agreement that mineral oil shows much better
properties at larger gap distances especially ≥10 cm [199], [197]. This situation occurs
connected to high voltage was made of either brass or steel and had a 300 µm tip
diameters. A 20-litre volume was used in a larger cell built for point-plane geometry
with various gap distances up to 35 cm. The rising voltage method was used in
ester, NE was plotted using the same configuration from a previous study under
lightning impulse by Q. Liu and Z. D. Wang [197]. The result of this study can be
50
Figure 2.18 : A point-plane geometry configurations of point (300 µm tip
radius) with a) 2 cm diameter and b) 16 cm diameter plane geometry [191].
From the result in A. Denat, J.E. Contreras et al. and Q. Liu and Z. D. Wang
[152], [154] – [155], the lightning breakdown voltage increased as gap distances
increased. The breakdown voltage of ester oils observed is much lower compared to
mineral oil. The almost similar test of lightning impulse was conducted by Q. Liu and
Z. D. Wang [197]. Lightning breakdown tests of esters and mineral oil gaps extending
51
from 15 mm to 100 mm were carried out using the same procedure. The breakdown
voltages of esters are lower than that of Gemini X for all gaps observed, and the
differences become more pronounced with the gap distances increased. This
phenomenon can be seen in Figure 2.20 and exists due to the velocity of streamer fast
leading to a breakdown in ester oils with increasing gap distances. The finding also
agreed that in smaller gap distances, the breakdown voltages of all samples are almost
Figure 2.20: The 50% breakdown voltage of Gemini X, Midel 7131 and FR3
versus gap distances [197].
Thien [20] in her study of lightning impulse breakdown voltage under a non-
uniform field used the needle-plane electrode configuration. The tip radius curvature
of the needle electrode was 50±5 µm while the diameter of the plane electrode was
cell. Her tests were conducted at 25 mm and 50 mm gap distances. Mineral oil and
three types of palm oils were tested. As per results in Figure 2.21, MO showed the
highest breakdown voltage than all palm oils at the 25 mm gap distance. The
52
where MO has the highest breakdown voltage. The finding is also similar to A. Denat,
J.E. Contreras et al. and Q. Liu and Z. D. Wang [152], [154] - [155]. However,
researchers found that the breakdown voltages of all palm oils are comparable to MO
(a) (b)
Figure 2.21 : The breakdown voltage of three type of palm oils and mineral oil
at (a) 25mm and (b) 50 mm gap distances [20].
and A of palm oils (RBDPOA, RBDPOB and RBDPOC) and coconut oil (CO) as the
alternative transformer oil under the lightning impulse test. Mineral oil (MO) was
also used in her study as a benchmark. The test was carried out based on needle-
sphere electrodes where the tip radius of the copper needle electrode spherical
diameter was 200 µm and 12.7 mm respectively. The tests were carried out at 2, 3.8,
In general, the 50% breakdown voltages for all samples increased as the gap
distances increase [13], [20], [38], [41], [177], [197], [202]. The breakdown voltage
of MO was higher in all gap distances as reported in Figure 2.22. However, the
53
gap distances i.e. 2.0, 3.8 and 6 mm. The author concluded that the existing contents
saturated and unsaturated fats has no significant effect on the lightning breakdown
performances since most of the breakdown voltages of the RBDPO are quite close to
CO. The relationship between RBDPO/CO and gap distance is found to follow the
Figure 2.22 : The 50% breakdown voltages for all samples based on rising
voltage method [180].
The same pattern was observed by Katim et al. [34] even as the experiment
focused on the same type of mineral oil and vegetable as Thien [180]. The authors
carried out the test based on the sphere-sphere electrode configuration to simulate a
quasi-uniform electric field under the lightning impulse test. The tests were
performed at 2 mm and 3.8 mm gap distances under negative and positive polarities.
As expected in [20], [180], [197], for both polarities, mineral oil (MO) has the highest
54
similar where the breakdown voltage of all samples increases with increasing gap
distances. The 50% breakdown voltage of all samples can be observed in Figure 2.23.
(b) (b)
Figure 2.23 : 50% breakdown voltage of all samples at (a) 2.0mm and (b)
3.8mm gap distances [45].
uniform field. The horizontally and vertically placed coil configurations were used in
the experiment as in Figure 2.14 in Section 2.5.1. Type 1 presents the horizontal
Type 2 presents the vertical electrodes’ configuration and were tested at 12 mm gap
distance. Two types of samples were investigated in this experiment which are
mineral oil and natural ester oil. The Weidmann design line provides the minimum
impulse stress for oil samples as shown in Figure 2.24. Overall, this study indicates
that the impulse breakdown stress of natural ester fluid gaps and insulation interfaces
are similar to mineral oil. Mineral oil still leads in any situations.
55
Figure 2.24 : Impulse breakdown stress for coil electrode configurations [184].
Some of the previous studies have investigated the effect of electrode gaps
measurements. Three types of oil samples were used in his study which are mineral
oil, Midel 7131 and natural ester, FR3. The oil samples are delivered by the
of small sample sizes are shown in Figure 2.24 From the result, it is noted that at
5 mm gap distance, the mineral oil breakdown voltage is higher than ester oils. The
voltages could not be found for either mineral oil or Midel 7131 with the 10 mm gap
as both oils withstood the highest voltage that could be delivered by the test cell,
250 kV. However, the implication of this is clear that the mean breakdown voltages
[192] was carried out for samples versus gap distances under various temperatures.
56
In his study, the breakdown voltage of mineral oil had a higher value under room
temperature. Overall, the same pattern of breakdown voltage was gained in all
temperatures, although with different gap distances. The mean distribution of mineral
oil can be seen in Figure 2.25. As expected, the AC breakdown voltage of all samples
obtained increase as the gap distance is increased. Similarly, this finding is considered
Sanjida Islam et al. [59] investigated the alternative insulating oil with
biodegradable characteristics. Four types of vegetable oils used which were coconut
oil, mustard oil, palm oil and soybean oil. The other two types of samples were mixed
samples which are 50% coconut oil mixed with 50% mustard oil and 50% coconut
oil mixed with 50% palm oils. These vegetable oils were compared with the
transformer oil in four types of uniform electrodes under the AC breakdown voltage.
Four gap distances of 2.5, 5, 7.5 and 10 mm were used in each electrode configuration.
The result observed the same pattern as all reviews in this section and is supported by
previous studies. It is found that the breakdown voltage is increased as the gap
57
distances are increased for of all samples under all configurations. Overall, some
vegetable oils have high breakdown voltages and are comparable to the transformer
oil sample.
Statistical methods are commonly used to estimate the dielectric of liquid insulation
at low failure probabilities. The Weibull distributions are the methods used in the
study of the likelihood of failure voltage and play important roles in the study of
reliability. Choosing a particular distribution for each insulating oil sample is crucial
as not all data on the breakdown voltage would necessarily match and only one form
of distribution is reliable.
Statistical methods have been extensively used in dielectric failure studies. The failure
probability depends on the electrical stress applied in the liquid. Normally, the
as the one that best fit the data approximating the failure and dielectric strength [18],
[205], [206]. Many researches were carried out on Weibull distribution to predict the
withstand voltage and failure in insulation oil [20], [27], [30] - [31], [33], [40], [51],
[62], [96], [186], [211], [212]. Usually, the mean breakdown voltage (50%
breakdown voltage) and standard deviation are used to represent the breakdown
58
voltage distribution, based on the assumption that the oil breakdown voltage follows
probabilities of failure of all oil samples can be determined using statistical analysis.
can be expected from the test sample or sometimes referred to as the withstand
voltage. Meanwhile, the 50% probability is the mean breakdown voltage of the test
sample. These values are important for a transformer designer to design the
used to fit the breakdown voltages and the withstand voltage can be deduced based
on the fitted curve. Weibull statistic method is based on a stability postulate [205].
using a relatively small sample size of field or laboratory test data. Weibull
distribution is the most common distribution used for analysing breakdown voltage
distribution is obtained based on the scale and shape parameters. The cumulative
x β
F(x) = 1 − e−(α) , x ≥ 0 (2.3)
59
Where, ƒ(x) is the probability density function of breakdown voltage, x is the
breakdown voltage, α is the continuous shape parameter and β is the continuous scale
parameter.
The parameter of Weibull form, β, is also known as the Weibull slope. That
is because, in a probability plot, the value of β is equal to the line slope. Similar shape
addition, certain shape parameter values can cause the distribution equations to
diminish to those of other distributions. For example, if β = 1, the pdf of Weibull three
60
CHAPTER 3
METHODOLOGY
3.1 Introduction
This chapter specifies the methods used to carry out dielectric properties and electrical
performance strength for PO and RBO. The experimental setup and measuring
techniques of AC breakdown voltage and lightning impulse test of PO and RBO also
deal with the procedure and observation of preparation sample of insulating liquid.
The procedures start by processing oil samples, testing setup and configuring
electrical testing such as AC breakdown voltage and lightning impulse test. The
analysis technique of the experimental works in this study is explained in this chapter.
The general experiment flow used in this study is shown in Figure 3.1 while
Figure 3.2 and Figure 3.3 depict the flow of AC breakdown voltage and lightning
61
Start
Sample preparation
Dielectric tests
Physico-chemical Electrical
properties Properties
62
Start
Sample preparation
Pre-processing of samples
HV laboratory
Baur DTA 100 C Gap distance:
Unexpected
Gap distance: 1. 1.5 mm
result
1. 2.5mm 2. 2.5 mm
3. 3.5 mm
4. 5.0 mm
5. 10.0 mm
Expected
result
Statistical analysis
End
63
Start
Sample preparation
Pre-processing of samples
Test setup
Expected
result
Statistical analysis
End
64
3.2 Sample Preparation
Three samples have been selected as the case study. The samples were Mineral Oil
(MO), which is an uninhibited mineral oil conforming to BS148 and two types of
vegetable oils which were Refined Bleached and Deodorized Palm Oil (PO) and Rice
Bran Oil (RBO). Both PO and RBO products were from cooking oil directly obtained
from the manufacturer. Figure 3.4 shows the three samples used in this study.
MO PO RBO
Vegetable oils are naturally obtained from the seeds as well as the flowers.
Many industries carried out investigations for using these oils as insulating oil in
transformers and for pollution-free environments [210], [211]. Vegetable oils possess
properties like higher flash points, lower flammability and are regarded as more
environmental friendly [212], [213]. The vegetable oil has various applications in
cooking, industries, diesel fuels etc. [154], [218] - [220]. In investigating natural
ester-based vegetable oils, the breakdown voltage, flash point, fire point and viscosity
65
of oil samples are measured. These properties are considered as important in the
Mineral oil (Hyrax Hypertrans oil) is obtained from Hyrax Oil Malaysia Sdn.
Bhd., which is the most popular transformer oil distributor in Malaysia. The basic
polyaromatic as shown in Table 2.2 to 2.4 [62]. The transformer industry prefers
and is less likely to form waxes. The properties of MO insulation fluids in terms of
their physicochemical and electrical properties are indicated in Table 2.5, the
clear and bright coloured oil compared to PO and RBO which are yellow in colour.
All the samples are transparent. The properties of MO used in this study can be
Parameter Specification
Product Hyrax Hypertrans Transformer Oil
Appearance Clear & Bright
Standards Requirement IEC 60296 : 2003
Pour Point, °C -40
Flash Point, °C 135
Viscosity (cSt) 10.4
66
PO and RBO are normally characterised as saturated and unsaturated fatty
acids as shown in Table 3.2. Vitamin E, saturated and unsaturated fat for PO and RBO
are found in cooking oil. The fatty acids of PO and RBO are also in range with
previous studies.
Characteristic PO RBO
Most power transformer failures are attributed to the physicochemical reaction that
takes place in the insulation oils due to the presence of heat, moisture content,
oxidation and electrical stresses. Most transformers that are in operation nowadays
are filled with MO. MO has been successfully applied in-service owing to its excellent
nowadays, alternative fluids are currently being examined. Among the potential
substitutes for MO are vegetable oils. The physicochemical properties of different oil
samples are investigated as per specified standards and procedure as in the section of
67
experimental details. The knowledge on the physicochemical properties of PO and
RBO, especially on viscosity, can be used to determine whether the PO and RBO
should be added with an oxidation inhibitor before they can be applied as dielectric
3. 3.1 Viscosity
decreases, the viscosity in transformer oil should not change and get more viscous
along with the decrease in temperature. An oil with a low viscosity is recommended
to prevent the occurrence of flow resistance to the conventional flow of oil hence
requiring proper transformer cooling. However, very low viscosity leads to the
formation of gas bubbles [126]. In this research, to test the viscosity in oil, Brookfield
R/S Plus Rheometer in Figure 3.5 was used according to the ASTM D445-standard
test method for kinematic viscosity of transparent and opaque liquids [19], [22],
[126], [145]. All samples were tested at ambient temperature (26 °C to 27 °C).
68
3.3.2 Flash and Pour Point
Mineral oil has conventionally been widely used in transformers successfully owing
renewable and has low flash point [9], [12], [20], [72], [126], [192]. Flash point and
pour point are considered the important physical properties of the insulating fluid to
determine the thermal behaviour of oil samples. The flash point and pour point of oil
samples in this study were measured according to ASTM D92 and D97, respectively.
Before the testing procedure, the test samples were pre-processed through a filter
using the Thermo Fisher Nalgene membrane filter with a pore size of 0.2 μm. The oil
samples were then degassed and dehydrated for 48 hours in the Memmert vacuum
oven at 85 °C below 500 Pa (5 mbar). Impurities such as particles and moistures can
be reduced by filtering for three times and dehydrating the oils for two days. A further
24 hours were provided to cool the oils under vacuum to ambient temperature. The
count of particle contamination and the moisture content in each sample before and
69
Samples: three types of PO, RBO and
MO
AC Breakdown
Lightning Impulse
Voltage
Figure 3.6 : The flow of the pre-processing procedures for the test samples.
Table 3.3 : The particle contamination and moisture content in MO, PO and
RBO before and after pre-processing.
MO PO RBO
Process
Before After Before After Before After
Particle
63 32 293 181 194 84
contamination (µm)
Moisture content
32 7 799 96 689 78
(ppm)
As shown in the table, PO and RBO have higher impurities than MO before
the filtering and drying process. These impurities are due to suspended particles such
as cellulose fibres, carbon, water etc. MO has the lowest moisture content in the
100 ml sample before and after the drying process. PO and RBO have almost similar
moisture contents with 799 ppm and 689 ppm before the drying process and 96 ppm
and 78 ppm after the drying process. Moisture contents of PO and RBO are seen
70
reduced by up to 88% after the drying treatment, while MO’s was reduced by 78%.
The higher moisture content of vegetable oils than mineral oil is due to the saturated
fatty acid available in vegetable oils which cause a high potential to absorb much
more moisture compared to mineral oils [34], [42], [78]. Vegetable oils are more
hygroscopic than mineral oils, thus they can absorb more water from cellulose
insulation and thereby slow down the hydrolysis ageing process of cellulose material.
multiple functions such as the dielectric, coolant and arc quencher must be performed
by transformer oils. Standard tests or routine tests should be used for verifying the
basic characteristics of the transformer oil. The electrical properties of insulating oil
including the dielectric constant (Ɛ), dielectric loss, tan delta (dissipation factor),
resistance and resistivity of vegetable insulating oils were measured according to the
standard IEC 60247 using an automatic ADTR-2K Plus instrument. The test
equipment is shown in Figure 3.7 and the specification of oil test equipment for the
71
Figure 3.7 : ADTR-2K PLUS with Automatic oil cell heater.
The electrical breakdown performance of oil samples was investigated before being
selected in this study. The AC breakdown voltage of BAUR Oil tester DTA 100C
(BAUR Trainer) was used to compare with the AC breakdown voltage at a high
72
3.6.1 AC Breakdown Voltage under BAUR Trainer
The AC breakdown test was performed using the BAUR DTA 100C with a maximum
output voltage of 100 kV. Figure 3.8 illustrates the equipment used for the AC
breakdown test. The rate of voltage rise was set at 2 kV/s and a fixed initial standing
time of 5 minutes before voltage application. The time interval was set at 2 minutes.
A total of 50 readings on breakdowns were obtained for each sample. The tests were
breakdown tester applied AC voltage across the test cell, filled with oil samples at
50 Hz frequency.
uniform field. The AC breakdown voltage was tested under a 2.5 mm gap distance, set
up in a cubic glass with a volume of 400 ml according to the IEC 60156 standard.
73
Figure 3.9 : Mushroom to mushroom configuration for AC breakdown voltage
test using BAUR Trainer.
Prior to testing, the test cell including the walls, electrodes and other parts
were rinsed at least three times to prevent the presence of bubbles and any unwanted
particles in the container. Each oil sample was subjected to 50 measurements for the
breakdown voltage. Upon acquiring the breakdown voltage, the oil samples were
placed to rest and stirred to prevent carbon accumulation. The rest time for MO has
was set for 2 minutes while the vegetable oils were given 6 minutes.
The test setup schematic of the AC breakdown voltage is illustrated in Figure 3.10.
Two horizontal copper electrodes of uniform field were utilised. The AC breakdown
test of the samples was done using a BHT 350 kV AC generator in the HV laboratory.
Testing was conducted at a gap of 2.5 mm to compare the breakdown voltage between
74
Figure 3.10 : The AC breakdown voltage test setup using HV Laboratory.
In this study, a 2-litre sealed cylinder test cell was fabricated from transparent
as per standard to represent the uniform field and can be observed in Figure 3.11. The
breakdown voltage was investigated in five gap distances, which are 1.5 mm, 2.5 mm
(to be compared to BAUR Trainer), 3.5 mm, 5 mm and 10 mm. The tests were
AC voltage across the test cell, filled with oil samples at 50 Hz frequency with an
ascending rate of 2 kV/s. A total of 50 breakdown voltage readings were recorded for
each sample. It surpasses the amount of testing required by the IEC 60156 standard
75
Figure 3.11 : The AC breakdown voltage test of mushroom to mushroom
configuration setup under HV Laboratory.
The same process and method were used with the BAUR Trainer container,
where test cells need to be washed and dried each time the oil sample is changed. The
testing cell and electrode should be rinsed with oil samples to be tested at least three
times. However, this HV laboratory setup uses a manual process stirrer to ensure the
resulting carbon is lost. The waiting period each time after a voltage breakdown also
depends on the condition of the oil sample. Usually, the time is between 7 and 10
minutes.
impulse generator setup with 800 kV maximum voltage and 40 kJ energy to deliver
the standard lightning impulse of 1.2/50 μs can be referred to in Figure 3.13. Three
76
testing methods of rising voltage, up and down and multi-level methods have been
used to obtain the significance of different testing methods. The investigation was
done under uniform and non-uniform field electrodes in various gap arrangements
Figure 3.13: The lightning impulse test setup with maximum voltage of 800kV.
77
3.7.1 Testing Methods of Lightning Impulse Test
Various testing methods including the rising-voltage method [40], [187] up-and-
down method [187] - [188] and multiple-level method [40] have been used for oil
impulse breakdown tests in both academic and industry fields over the past decades.
Each method has its own pros and cons, and its own validity.
The method of rising voltage (1 shot/step) follows the IEC 60897 standard and can
be carried out under both AC and lightning impulse breakdown tests. Due to its easy
use, it is widely and successfully used in AC breakdown tests’ step up voltage control
operation. Both IEC 60897 and ASTM D3300 adopt the rising voltage method for the
isolating oil lightning impulse breakdown tests. Only shot by shot will increase the
voltage, or step by step. In this method, for one set of testing, the applied voltage is
increased at a specified rate (kV/s) from the specified initial voltage until a breakdown
occurs. Next, the applied voltage is reduced and the previous procedure was repeated
[2]. The time interval between two consecutive shots was fixed at 60 seconds. ∆T1 is
the time interval between two consecutive shots and ∆T2 is the time interval between
A total of 15 breakdown tests were carried out for each liquid type. Figure
3.14 shows the rising voltage method with 1 shot/step as adopted by IEC 60897. Then
78
1
v50 ∗ = ∑n1 vi (3.1)
n
Figure 3.14: Sketch procedures of the rising voltage method for 1 shot/step [92]
In this method, the initial voltage is set and increased until the first breakdown occurs
in a fixed step voltage of range ΔU. Then, by the same step of fixed amplitude, the
number of breakdowns, the steps are repeated and recorded. The average value of the
The fixed phase voltage was set to 5 kV, with an interval of 60 s between each
breakdown case. For every range of samples, a minimum of 30 shots was added. The
average value of the applied voltages is regarded as the 50% breakdown voltage with
a more detailed evaluation considering the influence of the step, ∆V and using the
79
number of breakdowns k and the number of withstands q. The 50% breakdown
A 1
v50 = V0 + ∆V (k − 2) (3.2)
Where, the sum of the two complimentary events are identical with the number of
voltage applications, n = k + q starting with the first breakdown. Next, V0 is the first
counted value. Then, i = 0, 1…. r for the subsequent higher steps. ∆V is the
differential voltage and ki is the number of breakdown events at ith step. In addition,
kB− A2
σ = 1.62 x ∆V ( + 0.029) (3.4)
k2
Where,
2k
B = ∑ri 1i i (3.5)
80
3.7.1.3 Multiple level method
A multi-level method is also known as a constant voltage method where the method
number of shots are applied, and the number of breakdowns at each voltage level is
recorded. A cumulative frequency plot is carried out from the results of the
breakdown voltage, and the breakdown voltage can be calculated [189]. 20 shots were
applied with a loading time interval of 60 s and a phase voltage of 5 kV per shot. The
initial voltage level had been set at 100 kV and 150 kV for all gap distances. The
cell made from transparent acrylic. The electrode configuration and cylindrical test
81
cell simulated are as in Figure 3.17. A pair of Ø12.7 mm geometry was tested under
uniform field configuration. The rising voltage, up and down and multiple level
for smaller gap distances (2.0 mm, 3.8 mm and 6.0 mm) [222]. The voltage
The same experiment setup with the lightning impulse test method in Section 3.7 was
used. The illustration is laid out in Figure 3.12. The difference is the electrode
configuration installed use vertically mounted needles and spheres made of copper.
82
This configuration expressed the non-uniform field. The same experiment was carried
out on the 200 µm tip radius of needle with a sphere of 12.7 mm in diameter (as per
standard) as shown in Figure 3.18. This study aims to look at the difference in voltage
breakdown under various gap distances. Testing was performed under three small
gap distances (2.0 mm, 3.8 mm and 6.0 mm) and five larger gap distances (10.0 mm,
The lightning impulse test at small gap distances (2.0 mm, 3.8 mm and 6.0 mm)
with three different non-uniform field configurations are used to observe the effect
similar to the uniform field were recorded from which 15 breakdown voltages were
rising voltage, 15 breakdown voltages were up and down and 20 breakdown voltages
were multiple level methods. As for the lightning impulse test in larger gap distances,
10 measurements were taken for each sample as agreed in IEC60897 standard with
due to the higher breakdown voltage resulting in larger gap distances and more
carbonising. This will take some time to ensure the oil is recovered from the
83
Figure 3.18 : Electrodes configuration of needle to sphere for non-
uniform field.
the withstand voltages of the three oil samples using the Weibull distribution function.
Besides, withstand voltage is vital for designing the insulation of power transformers.
The breakdown voltages were first carried out by testing the AC breakdown
voltage and lightning impulse. The data were then fitted by the cumulative probability
Weibull distribution function at 1% and 50% probabilities. The 50% probability, also
known as the nominal voltage, is the standard value used by manufacturers and
84
3.9 Summary
In this chapter, MO, PO and RBO were well prepared and pre-processed before
conducting the test setup for the AC and impulse breakdown to gain a reliable result.
To ensure the cleanliness and minimise the impurities of the test cell and particle
contaminants in oil samples that might affect the breakdown, proper filtering,
degassing and dehydrating process of the oil samples were done before the tests. The
procedures had to be carried out each time the oil samples are changed.
For an AC breakdown voltage test, mushroom brass electrodes with 1.5 and
2.5 mm gap distances as the standard gaps were used to obtain the different effects of
breakdown voltage between using a BAUR Trainer and a high voltage laboratory
setup with different volumes, configuration positions and ambience. The gap
distances were extended to 3.0 mm, 5.0 mm and 10.0 mm to predict the worst-case
For the uniform field test in lightning breakdown, a cylindrical test cell with
breakdown voltage measurements including the rising voltage, up and down and
multiple level methods usually used in lightning impulse test were used to observe
the influence towards breakdown voltage. The oil samples were required to be
The same methods used in the uniform field test are also used the in lightning
breakdown for the non-uniform field under small gap distances where the upper
85
electrode was changed to a needle. The gap distances were raised to larger gaps from
10.0 mm to 50.0 mm. A total of 10 breakdown voltage measurements using the rising
voltage method was used to replicate the method in the previous study.
general statistical tools to obtain the withstand voltage for the oil samples by fitting
the experimental data. The probability of breakdown voltage for oil samples was
86
CHAPTER 4
BREAKDOWN VOLTAGE
4.1 Introduction
breakers, and other equipment, should be tested on a regular basis to determine and
ensure the serviceability of the oil as an insulating medium. Some electrical tests are
factor, and specific resistivity of insulating oils. These tests are useful acceptance
This chapter specifies the measurement of viscosity, moisture content and flash and
pour point of PO, RBO and MO. Besides that, dielectric properties such as dissipation
factor, relative permittivity and resistivity of PO, RBO and MO are also measured in
this chapter. Lastly, the AC breakdown test for various gap distances and the
distribution and prediction of withstand voltages of three oils are also investigated.
4.2 Physicochemical Properties of samples
4.2.1 Viscosity
The PO and RBO vegetable oils’ viscosities in this study are tabulated in Table 4.1.
The viscosity of PO and RBO are significantly higher than MO. This is due to the
saturated fatty acid exhibit in the vegetable oils since they are chemically stable. The
oils with triple-unsaturated fatty acids normally exhibit lower viscosity due to their
unstable property [72]. The molecules of vegetable oils are divided into small
undergo a polymerisation process; thus strongly increasing the viscosity of oil [5].
Since the RBO and PO have higher viscosity than mineral oil, this may reduce the oil
flow, further influencing (or worsening) the cooling effect of a transformer under ON
(Oil Natural) cooling mode. Higher viscosity would be expected to result in higher
hot spot temperatures within the transformer. On the other hand, the viscosity of RBO
and PO is higher than that of mineral oils, and this could offer some compensation
for heat convection of the oil. As mentioned in chapter 2, IEEE Standard 637 and
for natural ester oils [143]–[145]. All the oil samples fulfilled the minimum
Viscosity (mm²/s) 8 45 42
88
4.2.2 Flash point and pour point
The measurement of flash point and pour point of MO, PO and RBO are tabulated in
Table 4.2. Based on flash point results, MO has a much lower flash point in
comparison with RBO and PO, which means high resistance to ignition, and
therefore, reduces the risk of fire hazard in electrical power apparatus. Comparing the
RBO and PO results in this study with the previous results (refer to Appendix A.4),
the values obtained in this study are close to previous results. The flash points for
RBO and PO in this study surpass the minimum limit sets by the IEC standard for a
However, for pour point, RBO and PO having a higher pour point than mineral
oil would affect the suitability of RBO and PO to be used in cold climate countries.
Pour point is a useful measure of how transformer oils will perform under low
temperatures, especially when it is required to cold start a transformer under very low
Maintenance of Natural Ester Fluids in Transformers [145], the pour point limit is
−10 °C for vegetable oils. Whereas, the pour point for mineral oil is −40 °C according
to the ASTM D3487 Standard Specification for Mineral Insulating Oil Used in
Electrical Apparatus [223]. Based on the results in this study, the pour point values
for RBO and PO are below the recommended value in the IEEE C57.147 standard
and hence fulfilled one of the requirements for transformer liquid insulating.
89
Table 4.2 : The flash point and pour point of MO, PO and RBO according to
ASTM D92.
angle δ is a measure of the total current flow through the oil. If the insulating oil is
free from contamination or particle, the oil and electrodes closely demonstrate the
is applied to an insulating medium, the capacitive current will lead the voltage by 90°.
increasing resistive current through the insulation (oil). The resistive current will
deviate from the ideal 90° phase shift from the applied voltage. The shift from 90° is
measured as the DDF. This phase shift or loss angle δ will indicate the level of
insulation contamination, hence the quality and reliability of the oil. The loss angle is
the angle between a purely capacitive current, Ic and the actual current that flows
through the capacitor. It is important to note that a very low loss angle (decimal values
up to 0.005) indicates excellent insulating oil. Besides, DDF is also highly dependent
upon the temperature of the insulating oil and will increase with increasing
small changes that occur in oil characteristics. For example, obtaining a high DDF
90
value at ambient temperature and an acceptable DDF value at a high temperature
temperatures. On the other hand, a high DDF value at both temperatures often
the test for DDF needs to be done at two temperatures, e.g. ambient temperature (25-
30 ºC) and 90 ºC. Due to the chemical structure of vegetable oils which are more
polarised than the traditional mineral transformer oils, there will be higher dissipation
insulator that gets polarised when an electric field is applied to it. When a dielectric
material is placed in an electric field, electrical charges never flow through the
material as compared to the way they flow in a conductor; they just slightly shift from
their mean equilibrium positions thus causing dielectric polarisation. The effect of
dielectric polarisation is that: positive charges are displaced towards the field and
negative charges shift in the opposite direction. As a result, an internal electric field
is created that reduces the overall field within the dielectric itself. Transformer oil
physical value. Relative permittivity can be defined as the ratio of the permittivity of
91
a material to the permittivity of vacuum. It can be expressed as equation 2.2 in Section
2.4.5:
that has a very high resistivity indicates a low number of free ions, ion-forming
In this thesis, the dissipation factor, dielectric constant, and resistivity were
measured using the ADTR-2K PLUS. Testing for Permittivity and Dissipation Factor
temperatures were chosen to simulate start-up (25° C), and normal operating (90° C)
conditions.
The dielectric dissipation factor, also known as tan δ, was measured when the
equipment. The DDF’s graph of MO, PO and RBO can be seen in Figure 4.1 and the
92
Figure 4.1: Comparison of dissipation factor of MO, PO and RBO under
various temperatures.
As can be seen from Figure 4.1 and Table 4.3, vegetable oils (PO and RBO)
have higher dissipation factor (tan δ) than mineral oil for all temperature ranges. This
finding agreed with the study done by M. Mehta [224]. At 90 °C, RBO has 0.02168
dissipation factor which is 7 times higher than mineral oil (0.00322). Whereas, the
PO’s dissipation factor is 12 times higher than mineral oil at 0.03846. Based on IEC
60247 in Table 2.11, all the oil samples fulfilled the requirement for transformer
liquid insulation for DDF values which is less than 0.005 for MO and less than 0.05
for vegetable oil. The higher dissipation factor value of vegetable oils is due to the
molecular structure of vegetable oils having a slightly more polar character compared
93
Based on Table 2.2 to 2.4 and Figure 2.1, mineral oil is a hydrocarbon mixture
molecular structure whereas natural ester is produced from vegetable oil. In natural
ester molecular structure, O represents oxygen bonded into the molecular structure of
an ester. This causes the molecules to be polarised and leads to an increase in its
dissipation factor. This contrasts with MO because molecules containing oxygen are
classed as the products of oxidation, which the refiner attempts to remove. Direct
comparison of the dielectric dissipation factor between oils is, therefore, not a valid
polyunsaturated. The biggest difference is in the content of C=C double bonds. The
[231]. Based on Table 3.2, RBO has 20% saturated fat, 47% monounsaturated fat and
33% polyunsaturated fat. Whereas PO has 50% saturated fat, 40% monounsaturated
fat and 10% polyunsaturated fat. This different composition might be the reason why
PO has a higher dissipation factor than RBO. The composition of fatty acids gives us
an idea about the overall physical properties of the oil, such as viscosity and oxidation
stability. The bigger the content of unsaturated fatty acids is in oil, the more liquid
the oil would be. Contrarily, the bigger the content of saturated fatty acid in oil, the
more solid it would be. This is linked with the oxidation stability of the oil—saturated
acids make oil more oxidation stable and, in that regard, unsaturated acids make it
more unstable.
94
4.3.2 Relative permittivity or dielectric constant
Figure 4.2 and Table 4.4 show the results of the permittivity of the oil samples. As
shown in the figure, the relative permittivity of oil decreases with the increase of the
temperature. This is because of the effects on dipole orientation in the oil molecule
as turning in the direction of the field. At a higher temperature, the molecule moves,
shakes, twists, and vibrates, so the polarisation is reduced. This is because the
molecules do not point in the direction of the field all the time or as much as at a
Still, the mineral oil has the lowest relative permittivity among the oil samples
followed by RBO and PO. The relative permittivity of oil samples as measured
according to IEC 60247 at 30 ºC is 1.506 for MO, 2.176 for PO and 1.901 for RBO.
The higher relative permittivity of RBO and PO than MO could be attributed to the
presence of triglycerides in the vegetable oils which have a polar nature. Normally,
vegetable oil is highly hygroscopic (absorbs more water) compared to mineral oil,
and the fact that the water molecule is polar could have a big influence on the relative
permittivity value of the vegetable oil. Comparing the permittivity of RBO and PO,
RBO has a lower relative permittivity than PO in this study, which might be due to
the different fat contents in the oils. Moreover, compared to mineral oil, the
permittivity of RBO and PO is closer to that of solid insulation (4.0) which leads to
an evener stress distribution between solid and liquid materials where the thicknesses
of the liquid gap and solid insulation are comparable. This will also reduce the local
95
Figure 4.2 : Comparison of relative permitivity of MO,PO and RBO under
various temperatures.
4.3.3 Resistivity
The values in Figure 4.3 and Table 4.5 show that the resistivity of all oil samples in
temperature increases, the atoms of the material vibrate, and this makes the valence
electrons present in the valence band to shift to the conduction band. This in turn
increases the conductivity of the material. When the conductivity of the material
increases, the resistivity decreases and the current flow increases. From Table 4.5,
RBO has the highest resistivity with 6.372 TΩcm followed by PO with 5.341 TΩcm
96
and MO with 3.042 TΩcm. IEC 60247 recommended the resistivity value of any new
oil to be higher than 1.20 TΩcm. All oil samples in this study surpass the requirement
[232] [233]. To be a good insulating material, the resistivity of the insulating oil must
resistivity study, RBO and PO have fulfilled one of the important criteria to be
97
homogenous electric field. This test is mainly used by utilities or transformer
4.4.1 Effect of AC Breakdown Voltage using BAUR DTA 100 C and High
In this study, there were two different types of equipment used to study the AC
breakdown voltage of oil samples. The first equipment was an automatic oil
breakdown tester, BAUR DTA 100C with a maximum output of 100 kV. The test
was carried out using a pair of 12.5 mm diameter brass VDE electrodes (mushroom-
shaped in accordance with 60156 standards. The voltage was applied at a rising rate
of 2 kV/s until breakdown occurs. The AC breakdown voltages were tested at 2.5 mm
gap distances using a cubic glass with a volume of 400 ml according to IEC 60156
standard. The tests were performed at room temperature (25 ºC ± 0.1 ºC). A magnetic
stirrer was used to avoid the formation of carbon during each breakdown. The rest
time between breakdowns was set 2 minutes for MO and 6 minutes for vegetable oils.
The second test equipment was a custom made 2-litre cylindrical test cell. The
test cell was fabricated from Perspex material. The VDE electrodes are 12.5 mm in
diameter and made from copper as shown in Figure 3.11. The AC voltages were
98
testing procedure as BAUR breakdown tester was applied for this study. Figure 4.4
shows the breakdown voltages of MO, PO and RBO tested using two different setups.
Figure 4.4: Comparison of MO,PO and RBO under HV laboratory and BAUR
Trainer test set up at 2.5mm.
for all oil samples. RBO has the highest breakdown voltage for both test setups with
77.21 kV for Baur oil tester and 69.17 kV for HV laboratory setup. PO is the second
best in AC breakdown voltage with 74.89 kV using Baur Trainer and 67.74 kV using
HV laboratory. MO shows the lowest breakdown voltage among oil samples with
57.96 kV for Baur oil tester and 44.55 kV for HV laboratory. These results are well
correlated with the resistivity of oil as examined in Section 4.3.3. The oils with the
highest resistivity will normally have the highest breakdown voltage. RBO
similar to the previous study [21] and much higher than the previous study done by
[96]. The breakdown voltage of MO is lower than RBO and PO, and this finding
agreed with previous findings [44], [234]. This condition could possibly be because
99
humidity of the oil which affects the breakdown voltage. The moisture can be picked
up during transfer from bottle to the test cell in which the oil sample was directly
exposed to the air. Moisture exists in the oil samples by the engrossing of moisture
reduce the breakdown voltage of MO more than in vegetable oil (FR3) as shown in
Figure 4.5. Based on the figure, the breakdown voltage of mineral oil quickly falls as
its water content increases to 50 ppm. Meanwhile, the breakdown voltage of FR3 only
begins reducing after its water content is higher than 300 ppm. This can be explained
in terms of the relative humidity of the oil. For example, at ambient temperature 30 ºC,
30 ppm of water represents almost 60% saturation in mineral oil and for a similar
expected that the effect of 30 ppm on breakdown voltage would be larger for mineral
100
Besides the water effect, the influence of particulate content in the oil is also
the reason why mineral oil has a lower breakdown voltage. According to the study by
Chanband [236], the author explained that water affects the breakdown voltages of
When the particles become more conductive, they could create larger discharges at
the electrodes, increasing the probability to initiate gas bubbles and leading to a
breakdown. A similar study is also observed by Miners [237] who reported the effect
of particles and moisture on the breakdown voltage of mineral oil using VDE
electrodes. From his study, he concluded that very low breakdown strength was
obtained when the oil experiences the combined effects of moisture and particles.
Based on CIGRE [238], a comparison between the performance of ester liquids and
mineral oil was made and the finding from the study is the breakdown voltages of
both ester liquids and mineral oil decreased with the increase in cellulose particle-
based content. However, it was found that the breakdown voltage of mineral oil is
more sensitive to particle contamination than ester liquids. This might be due to the
higher viscosity of ester which slows the motion of particles and, therefore, reduces
breakdown occurrence.
specified the breakdown voltage requirement of new insulating liquids used in power
transformers. The minimum breakdown voltage of unused mineral oil for usage in
transformers (all voltage ratings) required by IEC 60156 is 70 kV/2.5 mm [239]. The
IEEE 57.104 for use in power transformers with a nominal voltage higher than 234
kV [240]. The mean breakdown voltages of PO, RBO, and MO in this study meet the
101
specifications required by these standards. The percentage of difference of breakdown
voltage between BAUR oil tester and HV laboratory setup can be calculated using
equation 4.1, where is VBaur is breakdown voltage as the reference towards VHV for
VBAUR −VHV
PD % = ( ) × 100 (4.1)
VBAUR
samples using BAUR oil tester and HV laboratory setup has been calculated and
Table 4.6 : The percentage difference of 50% breakdown voltage (kV) and the
standard deviation (SD) of MO, PO and RBO for BAUR Trainer and HV
laboratory at 2.5 mm gap distance.
Based on Table 4.6, the percentage of the difference between using BAUR oil
tester and HV laboratory setup is between 4% and 10%. At 2.5 mm gap distance, the
breakdown voltages of MO, PO and RBO using BAUR oil tester are 77.96 kV,
89.89 kV and 93.06 kV, respectively. The HV laboratory tests showed much lower
breakdown voltage than BAUR with the difference values of 13.42 kV, 7.15 kV and
8.04 kV for MO, PO and RBO, respectively. The percentage differences of PO and
102
RBO are observed to be lower than the percentage of MO at 2.5 mm gap distance. The
standard deviation (σ) as shown in Table 4.9 shows that AC breakdown voltages of
MO, PO and RBO under BAUR oil tester show smaller standard deviation than HV
laboratory setup. However, overall standard deviations for all testing samples are less
than 9 kV which is acceptable and close to each other. MO saw the lowest standard
deviation for both tests. All breakdown voltage samples still comply with IEC 60156
standard for AC breakdown voltage test at 2.5 mm gap distance for which the
There are several factors that might influence the breakdown voltages for both
tests. One of the factors is BAUR oil tester using magnetic stirrer during the test
condition while the HV lab test did not. Based on IEC 60156 standard, the use of
stirrer is optional during the AC breakdown test. The study by M. Baur [234] who did
the study on the different position of the stirrer in the AC breakdown test for mineral
oil and natural esters found that the stirrer improves the breakdown voltage of the oil
samples. The stirring system removes decomposition products and air bubbles formed
in the insulating liquid between the electrodes during the breakdown. Besides that,
the stirring system in the test equipment helps to minimise the standard deviations of
the breakdown voltages especially when the same scatter in the results is appreciably
higher. This can be seen from the results in this study, in which the oil samples using
the stirring system will have a smaller standard deviation compared to the non-stirring
system. It can be concluded that the use of a stirring system allows a slight reduction
of the breakdown voltage scatters. This reduction is more appreciable when the
breakdown voltages are lower, maybe in consequence of the presence in the insulating
103
The other factor that influences the breakdown voltage results for this testing
setup is the electrodes’ configuration. In the BAUR oil tester, the electrodes are
are mounted in a vertical position, as shown in Figure 4.6. Based on Figure 4.6, the
horizontal electrode configuration helps to facilitate the resulting bubble not being
trapped on the top electrode configuration. With the presence of the stirring system,
the liquid flow between the electrodes is in upwards direction and this allows easier
removal of gas bubbles. On the other hand, if the electrodes are in a vertical
configuration, the gas bubbles will be trapped at the top of the electrode and this
bubble will create the weakest link in the oil and hence cause the breakdown to occur
at a lower voltage.
(a) (b)
Besides that, the volume of oil also plays an important role in the breakdown
voltage of oil. In this study, the BAUR oil tester uses 400 ml of oil whereas the HV
laboratory setup uses as much as 2000 ml of oil which is 5 times larger in terms of
104
volume than the BAUR container. The greater the oil volume, the higher the
present, the lower would be the breakdown voltage of the liquid [31], [61], [200].
This can be seen in the results obtained in this study, in which BAUR oil tester
produced a higher breakdown voltage than the HV laboratory setup due to the
difference in the volume of testing oils. The theory behind the impurities can be
explained using the suspended particles include solid particles such as cellulose
fibres, carbon, water etc. These impurities usually cause a reduction in the dielectric
strength of insulating liquids and the largest effect being that of the simultaneous
presence of moisture and fibre. The floating moist fibres tend to bridge the oil gap
The cathode and anode materials also influence the breakdown voltage. In this
study, two different electrode materials were used. The BAUR oil tester was using
brass electrodes and the HV laboratory was using copper electrodes. Basically, brass
is an alloy made of copper and zinc which has greater mechanical strength and wear
resistance than copper. The composition of brass is 62% copper and 38% zinc. Brass
with 30% zinc has only 25% electrical conductivity compared to copper [186]. Since
the conductivity of copper is higher than brass, theoretically the copper will have a
lower breakdown voltage than brass and it is proved such in this study. The HV
laboratory equipment using copper electrodes shows lower breakdown voltages for
all oil samples. The finding in this study is supported by the study on the dielectric
characteristics of liquid nitrogen [242]. It was found that the breakdown voltage of
liquid nitrogen was largely dependent on the electrode materials in which the brass
electrodes used for the AC and lightning test for liquid nitrogen having higher
105
breakdown voltages than copper electrodes. It can be concluded that the electrode
transformer oil.
gap distances.
In the power transformer, there are different oil gaps between the transformer
structures, and this will cause different electric stresses experienced by the oil.
different oil gaps beside the standard (2.5 mm). In this study, the AC breakdown
voltage test for PO, RBO and MO were conducted at 1.5 mm, 3.5 mm, 5.0 mm and
10 mm gap distances. Since the limitation of BAUR oil tester to have larger gap
distances between the electrodes, the HV laboratory with custom made test cell was
used in this study. The graph in Figure 4.7 shows the results of breakdown voltage
for all samples tested under different gaps. As per previous pattern obtained, all
sample breakdown voltages increased as the gap distance was increased [205], [243].
106
Figure 4.7 : The 50% and standard deviation of AC breakdown voltage
for oil samples under various gap distances.
behaviour of the oils with respect to gap distances, the percentage of the difference
between RBO, PO and MO were calculated by equation 4.3, where VMO is breakdown
voltage as the reference towards MO and value of VPO and VRBO is the breakdown
VMO −VPO/RBO
PD % = ( ) × 100 (4.3)
VMO
107
Table 4.7 : 50% breakdown voltage (kV) and the standard deviation (SD) of
MO, PO and RBO for various gap distances.
From Table 4.7, it is observed that the breakdown voltage increases with the
increasing gap distance between the mushroom-mushroom electrodes for all oil
samples. RBO gained the highest breakdown voltage of all AC breakdown voltage
test among other oils. Besides that, the AC breakdown of PO and RBO liquids start
out slightly higher than mineral oil but converge closely to mineral oil at 10 mm oil
gap. The trend can be seen by the percentage difference between PO with MO and
RBO with MO. As seen in the table, the percentage difference between PO with MO
and RBO and MO reduces as the gap increases. For example, the percentage
108
difference of RBO at 1.5 mm gap is 34.5% which reduces to only 6.97% at the 10 mm
gap. This is expected due to the condition of the electric field surrounding the
electrodes. It is believed that as the gap increases, the electric field becomes more
non-uniform and hence reduces the breakdown of vegetable oils. The electric field
Ubr kV
Ebr = [mm] (4.2)
g
Where Ebr is the electric field strength, Ubr is the average breakdown voltage and g
is the electrode gap (1.5, 2.5, 3.5, 5.0 and 10.0mm). As expected, the breakdown
strength of liquids generally decreases with the increase in gap distance and the
volume of the liquid under stress. Similar results were also found by Markovic [195].
More importantly, the breakdown strength of natural ester behaved like mineral oil
and both graphs are higher than the Weidmann oil design line. The Weidmann oil
curve is the curve being used by the transformer designer to design the insulation of
the transformer.
Figure 4.8 : The electric field strength of oil samples under various gap
distances.
109
4.6 Statistical Weibull Distribution under AC Breakdown Voltage
failure probability. The failure probability depends on the electrical stress applied in
the liquid. Normally, the Weibull distribution approach is generally accepted in the
field of electrical insulation as the one mathematical representation that best fit time
for data approximating the failure and dielectric strength [18], [205], [206]. The
Weibull distribution is obtained based on the scale (α) and shape parameters (β). The
the AC breakdown voltages in this study uses the Weibull distribution. The
breakdown voltages data were used to fit the Weibull distribution curve. From this
curve, the withstand voltage can be determined. Similar approaches have been used
in previous studies [2], [62], [222], [244]. To make sure the data from different test
methods are reliable, some steps and precautions need to be followed such as (i) the
liquid was filtered, dehydrated and degassed before the tests; (ii) a 60-second time
interval, according to IEC and ASTM standards [28], [196], was used between two
consecutive shots; and (iii) after breakdown occurred, there was at least 5 minutes of time
interval till next shot and the liquid sample was regularly changed after about 10
breakdowns on average. A distribution is considered a good fit if the data points follow
a straight line.
withstand voltage of the oil. Meanwhile, the 50% probability of failure is a standard
110
failure rate used by industry and utilities. Figures 4.9 shows the Weibull probability
As seen in the figures, the Weibull distribution for MO, PO and RBO show
deviations at the tails (<5% probabilities), demonstrating that the Weibull distribution
may be inaccurate at low probabilities except for the 1.5 mm gap distance. The
Weibull distributions tend to give lower prediction values than the measured
breakdown voltages. For higher probabilities, the Weibull distributions for all
samples fit well to the experiment results. The data deviates from the distribution by
5% to 10% depending on the oil. It is a concern that the lowest breakdown voltages
deviate below the trend-line because this indicates that the probability of the oils
failing at these voltages is lower than estimated using the Weibull distribution.
(a)
111
(b)
(c)
112
(d)
(e)
Figure 4.9 : Weibull probability plot for the AC breakdown voltage at (a) 1.5
mm, (b) 2.5 mm, (c) 3.5 mm, (d) 5.0 mm and (e) 10.0mm gap distances.
The PO and RBO performed similarly and are comparable to MO. The RBO
has the highest values of breakdown voltages for 1% and 50% failure probabilities
followed by PO. At 50% failure probability, it was observed at 1.5 mm gap distance,
113
the breakdown voltage of PO is lower than RBO but higher than MO with the
percentage difference of 53%. The breakdown voltage of all oil samples at 1% and
50% probability of failures are shown in Figure 4.9 (a) to (e), and the estimated values
Table 4.8 : 50% of Breakdown voltage of MO, PO and RBO at 1%, 50%
probabilities of failure by Weibull distribution for various gap distances test.
114
Table 4.8 shows the breakdown voltages estimation using Weibull distribution
at 1% and 50% probabilities at all gaps. At a gap of 1.5 mm, for 1% probability of
breakdown voltage, PO has a higher breakdown voltage than MO and RBO. At this
and MO with 37.58 kV. It is observed that the percentage of difference between RBO
and PO is around 32% at this probability. However, for the 50% probability, RBO
has the highest breakdown voltage followed by PO and MO. Similar results were also
always used to fulfil the safety requirements of the insulation systems. Despite using
a withstand value where the transformer liquids will not fail as a dielectric, the
withstand voltage could be considered as a level where the risk of failure is acceptably
low [44], [193]. Usually, a failure rate of 1% is regarded as the acceptable level [44],
withstand voltage of transformer liquids. This value also determines the amount of
insulation material used in the transformer, thus determining the size of the
transformer [193]. For example, if the withstand voltage of an insulating liquid is big,
smaller bulk oil gaps and creepage distances should be given to fulfil the safety
requirements of a transformer. This will reduce both the size and the overall cost of
the transformer. For transformers in-service, the withstand voltages of the transformer
liquids might be gradually decreased during the ageing and deterioration process.
115
Therefore, transformer liquids with high withstand voltages will ensure the safe
tabulated in Table 4.9 while the 1% breakdown stress is in Table 4.10. The 1%
breakdown voltage U1% from Table 4.9 is used to calculate electric field strength
according to equation 4.2 previously. This value is compared to the Weidmann curves
used in the transformer industry and insulation design [245] as shown in Figure 4.10.
Table 4.9 shows the withstand voltage prediction using the Weibull
distribution for all oil samples. As seen in the table, vegetable oils have higher
withstand voltages than MO for all gaps. At the lower gap of 1.5 mm, PO has the
highest withstand voltage while RBO has the highest withstand voltage from 2.5 mm
to 10.0 mm gap distances. MO has the lowest among all samples. As expected, the
breakdown strength of liquids generally decreases with the increase in gap distance
116
Table 4.10: The 1% of electric field strength of MO, PO and RBO.
As can be seen from Figure 4.10, PO and MO show higher electric field
strength than MO and more importantly are higher than the Weidmann curve [162],
[166], [167]. This result proves that PO and RBO are passed the minimum
transformers.
117
4.8 Summary
oils. RBO has a balanced configuration in unsaturated and saturated fatty acids
between vegetable oils. RBO possesses superior dielectric constant and experiences
the lowest electric field stress. Overall result for physicochemical properties revealed
that the viscosity, moisture content, flash and pour point of PO and RBO are
comparable to MO. It also proved that PO and RBO fulfilled the standards. The
dielectric dissipation factor, relative permittivity and resistivity of PO and RBO are
The means of the AC breakdown voltages for vegetable oils and mineral oil
by using the BAUR Trainer are higher compared to the high voltage (HV) laboratory
setup. This is due to the presence of a carbonised stirrer which helps to eliminate the
resulting breakdown voltage and the test setup of different electrode configuration
positions. However, the increments of all samples show a similar trend for both
equipment setups. Due to the gap distance limitation in using BAUR Trainer, the
various gap distances of 1.5, 2.5, 3.5, 5.0 and 10.0 mm were conducted by using HV
laboratory. The AC breakdown voltages in all conditions indicate that the RBO has
the highest breakdown voltage followed by PO and MO. In quasi-uniform fields, the
breakdown event is mainly controlled by the streamer initiation, of which the results
indicate the similarities between ester liquids and mineral oil. More importantly, the
breakdown strengths of PO and RBO are similar to MO and all samples have higher
118
CHAPTER 5
5.1 Introduction
Transformer oils should withstand not only power frequency AC voltage but also
mentioned in Chapter 4, the AC breakdown test is normally used for oil quality check
and control due to its sensitivity to contaminations. Whereas, the lightning impulse
test is used as a criterion (Basic Insulation Level) for large power transformer
insulation design. The lightning impulse test is commonly required in factory routine
predominated by the oil intrinsic properties. In simple words, it can be used to detect
so complex. There are large numbers of structures with different potentials existing
these stresses. Most electric fields in a transformer e.g. between disk and disk and
119
turn and turn, are made up of uniform or quasi-uniform field. Since the physical and
chemical properties of rice bran oil (RBO) and palm oil (PO) are different from
mineral oil, it is expected that there will be some differences between their lightning
alternative for MO, the tests in this chapter attempted to understand and identify the
lightning impulse breakdown strength of these oils in a uniform field. This chapter
will discuss the lightning impulse breakdown strength of RBO and PO for various
provide a standard lightning impulse 1.2 (±30%)/50 (±20%) µs. The lightning
breakdown voltage was measured as per the standard IEC 60897 and only negative
polarity lightning impulse was used in this study. To create a uniform electric field,
sphere-sphere copper electrodes were used and the gaps between electrodes were set
to 2.0 mm, 3.8 mm and 6.0 mm. 12.7 mm in diameter of spherical copper electrodes
were used in this study. These electrode configuration were vertically immersed in a
cylindrical test cell made from transparent acrylic with a volume of 2 litres as
various oils, all attributions should be controlled to the same level. Otherwise, the
number of weak links for various oils will be different, and thus it will be difficult to
compare. To control the quality of the results, the oil samples were processed
carefully as explained in Section 3.2. All the experiments were conducted at room
temperature (29 ºC± 0.1 ºC) with 50-70% humidity. A total of 50 measurements in
breakdown voltage were recorded for each sample which comprised of 15 breakdown
120
voltages of rising voltage method, 15 breakdowns voltage for up and down method
The lightning impulse breakdown voltage test of all oil samples including PO, RBO
and MO as a benchmark was done for small various gap distances (2.0 mm, 3.8 mm
and 6.0 mm) and had been summarised in Figure 5.1 (a) and (b). As shown in the
figures, the breakdown voltage increases linearly as the electrode gap increases. This
is in good agreement with the previous works [247]. For all gap distances, the mean
break breakdown voltage of MO is the highest with 130.76 kV, 224.03 kV and
291.28 kV for 2 mm, 3.8 mm and 6.0 mm gaps, respectively. RBO has the second
highest breakdown voltage at 122.03 kV, 200.23 kV and 256.08 kV for 2.0 mm,
3.8 mm and 6.0 mm gaps, respectively. Lastly, PO has the lowest breakdown voltage
with 121.03 kV at 2.0 mm, 196.14 kV at 3.8 mm and 252.54 kV at 6.0 mm. Similar
results were also obtained in [45] at 2.0 mm and 3.8 mm gap distances using a similar
size of spherical electrodes for MO and PO. The details of the breakdown voltages
121
Figure 5.1 : 50% breakdown voltages and standard deviation of sphere to
sphere configurations for various gap distances.
between vegetable oils (RBO and PO) and MO can be calculated based on equation
5.1. VMO are 50% breakdown voltages of MO and the value of VVo is interchangeable
among RBO and PO. The PD% calculated are tabulated in Table 5.1.
𝑉𝑀𝑂 −𝑉𝑉𝑂
(𝑃𝐷 𝑂𝑖𝑙 %) = ( ) × 100 (5.1)
𝑉𝑀𝑂
122
Table 5.1 : The 50% breakdown voltages and standard deviation (SD) of
sphere to sphere configuration at 2.0 mm, 3.8 mm and 6.0 mm gap distance.
and RBO with MO appears to be increasing with the increased gap distance. At
2.0 mm gap distance, the difference of PO is 7.44% while RBO is 6.68% lower than
MO. For the 3.8 mm gap, the percentage difference between PO and MO is 12.45%
while RBO and MO is 10.62%. For the 6.0 mm gap, the highest percentage difference
for the vegetable oils are 13.30% and 12.08% for PO and RBO, respectively. From
this study, it was shown that the percentage difference for vegetable oils is lower by
13.5% when compared to MO for all conditions. The results show that the RBO and
test. Furthermore, the performance of RBO and PO is almost similar to each other.
From the results, MO is seen to have a higher breakdown voltage than PO and RBO
in all situations. This might be due to streamer propagation in vegetable oils being
123
different than in mineral oil. The previous studies in a divergent field and
uniform/quasi-uniform field showed that the ester liquids have lower impulse
breakdown voltages, especially at larger gaps, than mineral oil. This is because
streamers in the vegetable oils propagate faster and further than in the mineral oil at
the same voltage level. Liu [203], [244] mentioned that the average time to
breakdown for ester oils is approximated 3.8 μs compared to 5.7 μs in mineral oil. He
also mentioned that the streamer velocity in vegetable oil is around 10 km/s at 50 mm
oil gap and reaches 30 km/s at 100 mm. The streamer velocity in mineral oil remains
at a constant speed of 1–2 km/s. Moreover, some studies suggested that these
phenomena are related to the differences in the fluids’ chemical compositions [241],
[249], [250]. From this study, the breakdown voltage differences between these two
Configuration
Lightning impulse testing methods, including the rising voltage method, up and down
method and multiple level method, are usually used for impulse breakdown tests.
Each method has its own advantages and disadvantages. When comparing the
lightning impulse breakdown strength of oils, the results on different methods are
likely to be different. Therefore, the influence of the testing method on the lightning
breakdown voltage of PO, RBO and MO was examined in this section using the
124
The cross comparison of impulse breakdown voltages between PO, RBO and
MO are plotted in Figure 5.2. The 50% lightning impulse breakdown voltages of PO,
RBO and MO using various testing methods are summarised in Table 5.2.
(a)
(b)
125
(c)
Figure 5.2 : Comparison of 50% breakdown voltage of all samples using sphere
to sphere configuration for various testing methods at (a) 2.0 mm, (b) 3.8 mm
and (c) 6.0 mm gap distances.
previous studies [182], [222] and as the commonly used test method in the industry,
the percentage of difference, PD% for the 50% breakdown voltages of oil samples
between various testing methods can be calculated using equation 5.2 [182]. The
difference in percentage (PD%) of oil samples using the various testing methods are
126
Table 5.2 : 50% breakdown voltages using sphere to sphere configuration for
various testing methods at 2.0 mm, 3.8 mm and 6.0 mm gap distances.
It can be seen in Table 5.2 that the multiple level method has the highest
breakdown voltage among all methods for all gap distances. At 2.0 mm gap, the
highest percentage difference for the multiple level method can be seen in MO with
9.48% followed by RBO with 5.14% and lastly PO with 5.10%. For the up and down
method, the highest percentage difference can be seen for MO with 4.42% while RBO
has the lowest percentage difference. As the gap increases to 3.8 mm, the percentage
difference for the multiple level method has increased for all samples with MO having
the highest difference with 11.62% followed by PO (10.19%) and RBO (8.93%). For
the up and down method, the percentage difference is maintained around 2% for all
oil samples. As the gap is increased to 6.0 mm, the percentage difference for the multi-
127
level is reduced to less than 4% with the RBO having the biggest difference with
3.73%. For the up and down method, the percentage difference is maintained low.
Overall, the percentage of difference for the multiple level method for all oil samples
and all gaps are less than 12%. For the up and down method, all the percentage
differences are less than 5% with MO having the highest difference with 4.42%.
Comparing the oil samples, the various testing methods do not affect the ranking of
oil samples in which vegetable oils are always showing lower LI breakdown voltage
than MO [182]. It can be seen from Figure 5.3 that RBO has comparable 50%
breakdown voltages with PO at various gap distances and testing methods where the
highest percentage of difference is less than 11.0%. On the other hand, PO and RBO
difference being less than 10.19% for all methods and gap distances, which agreed
Study
The lightning impulse test in this study used sphere electrodes 12.7 mm in
conducted the lightning impulse breakdown voltage test for 2.0 mm and 3.8 mm gap
distances [34] with an oil volume of 300 ml. In this study, the volume of the oil is
larger than [34] at 2000 ml. Hence, a comparison between the previous work and this
work is made in this section. The 50% lightning breakdown voltage from [45] and
this work can be obtained in Table 5.3. The percentage of difference (PD%) of oil
128
samples from a previous and in this study findings had been calculated by equation
5.4.
The 50% lightning breakdown voltage difference between this study and the
previous study by Katim N.I.A [34] shows that both breakdown voltages are
comparable to each other. The percentage of differences observed are less than 7%
for mineral oil and less than 7.5 % for PO. The different oil volumes in both
experiments did not affect the breakdown voltage of oil samples. This is due to
smaller gap distances which give very minimal effect for the breakdown voltage of
the oils [31], [44]. Overall, the 50% lightning breakdown voltages from this study are
129
5.5 Weibull Probability Plots for MO, PO and RBO under Sphere to
Sphere Configuration
The Weibull distributions for each oil sample were plotted based on the data obtained
in this study and can be referred to in Appendix B. The summary of the distribution
failure for Weibull distribution at 2.0 mm, 3.8 mm and 6.0 mm gap distances. At 1%
probability for the withstand voltage of 2.0 mm gap distance as shown in Figure 5.6
130
(a), RBO has a higher withstand voltage (with 108.13 kV) than PO (100.19 kV) and
and MO is 7.9% and for RBO and PO, it is 0.11%. However, for probabilities of
failure at 10% and above, MO has the highest withstand voltage compared to PO and
3.8 mm and 6.0 mm gap distances with 177.81 kV and 260.99 kV respectively
compared to all oil samples. PO is the second best after MO for both gaps with
202.54 kV and 258 kV respectively followed by RBO with 198.22 kV (3.8 mm) and
254.1 kV (6.0 mm). The percentage of difference for PO and RBO with MO at 1%
and 50% are in a range between 10.64% and 22.08%. As indicated in Table 5.4, the
50% breakdown voltages of PO and RBO are lower than MO, which is consistent
with the previously drawn conclusion using various testing methods. Moving down
becomes smaller.
5.6 Summary
The electrical strengths of vegetable oils in a uniform field for various gap distances
were studied in this chapter. Detailed investigation and analysis had been done with
various testing methods including the rising voltage method, up and down method
131
According to the findings, the lightning impulse performance under a uniform
field for PO and RBO is comparable to that of MO for all cases. This is due to the
difference of 50% breakdown voltage of PO and RBO with MO is less than 20% for
all situations. Nevertheless, among the vegetable oils, RBO shows a higher 50%
breakdown voltage compared to PO. The patterns of MO, PO and RBO are almost
the same for the relationship between breakdown voltage and gap distance. Overall,
the finding in this chapter is RBO and PO are comparable to each other for all gap
Furthermore, it was found that the testing methods have a notable influence
on the measured breakdown voltage for all testing methods for all gap distances. The
percentage of difference is less than 16% and agreed with the previous studies done
by [45]. The multi-level method has the highest percentage of difference for all cases.
Besides that, the multi-level method and rising up method provide the closest results
to each other, which are generally higher than those obtained using the up and down
method. However, no matter whichever testing methods were used, PO and RBO
always showed lower breakdown voltages than MO. All the testing methods are
suitable to be used in the lightning impulse breakdown study since only a small
difference in terms of breakdown voltage was found in this study. Lastly, the
withstand voltages for PO and RBO were compared using Weibull distribution at 1%
probability. The withstand voltages of RBO and PO show lower values than MO for
132
CHAPTER 6
FIELD
6.1 Introduction
moisture), contaminations in the oil will possibly cause strong non-uniform fields to
exist in transformers. These strong non-uniform fields could lead to the enhancement
of local electric fields and initiate a discharge in transformer oils. In addition, streamer
field, i.e. point-sphere electrodes, are proved to be closely associated with liquid
Negative polarity and a point-sphere electrode gap are considered in the study.
This chapter focuses on the breakdown strength of both RBO and PO under
analysed for various gap distances up to 50 mm and using similar methods as the
previous chapter. The 50% breakdown voltages at various gap distances are compared
between RBO, PO and MO. A relationship between the results under the lightning
impulse and previously published results is built up and empirical formulas are
obtained to predict the lightning breakdown voltages of PO and RBO at very large
gaps.
The test set-up for the lightning impulse breakdown tests is shown in Figure
3.13. For this non-uniform field, the lightning impulse dielectric strengths of the oils
were carried out using standard IEC 60897 with the point (needle) and spherical
electrode configuration. Tungsten needle was equipped as the point electrode, whose
microscope. The needle was regularly changed after each set of tests, i.e. per liquid
type per gap distance. A spherical electrode of 12.7 mm in diameter was used as the
ground electrode. An 8–stage CDYL impulse generator (as shown in Figure 3.13)
with a maximum voltage of 800 kV and energy of 40 kJ was used to provide the
The lightning breakdown voltages of the dielectric insulation oil under a non-uniform
field were found to be dependent upon the composition of oil samples and
configuration of electrodes [46], [203]. The 50% breakdown voltages of PO, RBO
and MO under the non-uniform field at 2.0 mm, 3.8 mm and 6.0 mm gaps can be
134
referred to in Figure 6.1. A total of 50 breakdown voltage measurements were made
breakdown voltages from the up and down method and 20 breakdown voltages from
According to Figure 6.1, generally, the 50% breakdown voltage for all
samples increases as the gap distance increases. The results show that there is a
significant effect of breakdown voltage with various gap distances which agreed with
the previous finding [38], [187], [204]. MO has the highest 50% breakdown voltage
at all gap distances. The highest percentage difference of 50% breakdown voltage
MO and vegetable oils (RBO and PO) is less than 16% for all conditions as shown in
Table 6.1.
135
Table 6.1 : 50% breakdown voltages and standard deviation (SD) of needle to
sphere configuration at 2.0mm, 3.8mm and 6.0mm.
MO PO RBO
PD Oil PD Oil
Mean SD Mean SD % Mean SD %
From the Table 6.1, at gap distance of 2.0 mm, the 50% breakdown voltages
of MO and PO are 83.31 kV and 73.02 kV respectively. They are higher from the
MO at 2.0 mm, 3.8 mm and 6.0 mm gap distances are 7.22%, 11.08% and 12.92%
respectively. Meanwhile, the difference between RBO and MO are 5.73%, 12.29%
and 11.18% for 2.0 mm, 3.8 mm and 6.0 mm, respectively. PO has the highest 50%
around 5 kV to 14 kV. Even though RBO almost has a larger breakdown voltage than
PO, the 50% breakdown voltage of RBO is quite close with PO at all gap distances.
This might be due to the physical and chemical properties of the RBO and PO are
136
6.3 Effect of Various Testing Methods under Needle to Sphere
Configuration
In this part, a similar study was carried out on the various testing methods for a non-
uniform field lightning impulse test. The influence of testing method on the lightning
breakdown voltage of MO, PO and RBO was examined using the standard negative
PO and MO are plotted in Figure 6.2. Meanwhile, the percentage difference of the
50% breakdown voltage under various testing methods is summarised in Table 6.2.
(a)
137
(b)
(c)
Figure 6.2 : Comparison of 50% breakdown voltage of all samples using needle
to sphere configuration for various testing methods at (a) 2.0 mm, (b) 3.8 mm
and (c) 6.0 mm gap distances.
138
Table 6.2 : 50% breakdown voltages of needle to sphere configuration for
various testing methods at various small gap distances.
From Table 6.2, there is only a small effect of testing methods that can be seen
on the breakdown voltages of all samples at all gap distances. The highest percentage
difference is less than 7.50%. This finding is close to the previous work by Yvone
[38] which is 13.8%. Similar to the lightning breakdown voltage under a uniform
field, the multi-level method has the highest 50% breakdown voltages compared with
other methods. For all testing methods, MO has the highest 50% breakdown voltages
breakdown voltage for PO and RBO are comparable with MO. The lowest percentage
139
of difference for all samples is just 0.54% and the highest percentage of difference is
7.5%, corresponding to only 1 kV and 3 kV. Among all different testing methods, the
multiple level method always has the highest 50% breakdown voltage for all samples
at various gap distances, followed by the rising voltage method and the up and down
method. Therefore, breakdown voltages do not affect the ranking of liquids for the
aim of comparison purposes even when using different testing methods [182], [253].
Configuration
The dielectric failure of oil is initiated by some weak links. As the volume of
electrically stressed oil increases, the probability that weakness is present in the oil
volume also rises. Therefore, for a large oil gap, it is necessary to investigate whether
that of mineral oil or not. The large gap represents the situation between the lead of
the winding and the wall of the transformer tank, which is earthed [25].
In this section, the study is carried out to investigate the influence of gap
distances on the lighting breakdown voltage under a non-uniform field. The lightning
impulse breakdown voltage test was performed using the rising-up method. This
study uses a needle to sphere electrode following the IEC Standard 60897 [30], [38],
[40]. All tests were carried out at 2.0 mm, 3.8 mm, 6.0 mm, 10.0 mm, 20.0 mm, 30.0
mm, 40.0 mm and 50.0 mm gap distances. The 50% breakdown voltage with different
gap distances is plotted in Figure 6.3. The comparison of 50% impulse breakdown
140
voltages of all samples is shown in Table 6.3. From the graph, the 50% breakdown
voltages for all samples increase as the gap distances increase. A similar pattern was
also found by [200], [201], [243], [254]. The 50% breakdown voltages of the PO and
RBO are much lower than the MO at all gap distances under a non-uniform field. The
difference in the 50% breakdown voltages became larger as the gap distance increases
25.0 mm, the percentage of differences for the 50% breakdown voltages between MO
and PO is in the range of 17.1% and 20.3% while for RBO, it is between 15.4% and
20.3%.
Figure 6.3 : 50% breakdown and the standard deviation of needle to sphere
configuration for various gap distances.
141
Table 6.3 : 50% breakdown voltages of needle to sphere under various larger
gap distances.
Based on Figure 6.3 and Table 6.3, the 50% breakdown voltages of vegetable
oils (PO and RBO) are lower than the MO for all gaps observed, and the differences
become larger as the gap distances increased. The breakdown voltages of PO and
RBO are almost identical for all gaps. The lowest percentage difference of RBO and
PO towards MO are 14.9% and 15.82% where the value is almost 23 kV and 24 kV
each. This pattern is also in line with previous researches where the MO interface
becomes higher than vegetable oils’ interface. The percentage of difference between
35.11%. The difference was more pronounced at larger gap distances [13], [252],
[255].
This finding agreed with the studies by [2], [10], [31]. The reason why this
142
process of breakdown. According to [31], small gaps’ breakdown is caused by slow
streamers of which the average propagation velocity is low. With increasing gap
distances, the fast streamer appears at the breakdown voltage level and starts to take
over the control of breakdown. There is a range of transition gap distance where slow
and fast streamer-induced breakdowns can occur. Once this transition occurs at
certain gaps, the fast streamers will purely control the breakdown of the oil. In the
case of natural esters, the appearance of this transition gap distance happens earlier
than MO, which causes lower breakdown voltages at very large gaps. Besides that,
according to [37], [256], [257], the chemical compositions and electron affinity of
backbone that consists of three fatty acids groups. This group consists of saturated
and unsaturated fatty acids. PO contains approximately 50% saturated fatty acids,
with 44% palmitic acid (C16:0), 5% stearic acid (C18:0), and trace amounts of
myristic acid (C14:0). The unsaturated fatty acids are approximately 40% oleic acid
(C18:1) and 10% polyunsaturated linoleic acid (C18:2) and linolenic acid (C18:3).
Meanwhile, RBO contains palmitic acid (22.7%) as the major saturated fatty acid. It
is high in oleic acid (43.9%). Linoleic acid in the largest component (29.6%) of
polyunsaturated fatty acids, followed by low level (1.25%) linolenic acid. PO and
RBO have some percentage of C=C double bonds in the oleic and linoleic acid side
chains. The presence of these bonds can cause a low ionisation potential which leads
to higher streamer propagation speeds and hence lowers the lightning impulse
breakdown voltages of RBO and PO compared to MO. Besides that, there is a high
143
lightning impulse breakdown in RBO and PO. At the same voltage, the streamer in
vegetable oils propagates further with higher velocity and more branches than MO.
According to a study done by [10], the streamer velocity for PO is around 3.5 km/s
whereas for MO it is only 2.0 km/s which can be a reason for vegetable oils having
Gap Distances
stress applied in the liquid. Weibull distribution approach is generally accepted in the
field of electrical insulation as the one that best fit time for data approximating the
failure and dielectric strength [18], [205], [206]. The Weibull distribution is obtained
based on the scale and shape parameters. The cumulative functions of Weibull
measurement in this chapter were used to plot the Weibull distribution to predict the
accumulative of 15, 15 and 20 breakdown voltages from rising voltage, up and down
and multiple level methods, respectively. The breakdown voltage distribution and the
probability plots can be referred to in Appendix C.2. The Weibull probability plots
144
voltage for MO, PO and RBO. For all gap distances, the breakdown voltages for all
probability and are close to each other. The 1% and 50% probability of breakdown
Table 6.4 : The 1% and 50% probabilities of MO, PO and RBO at 2.0 mm, 3.8
mm and 6.0 mm gap distances under needle to sphere configuration.
between MO and vegetable oils is very low at smaller gap distances. At 2.0 mm gap
distance, the difference between MO and vegetable oils ranges from 4.4 kV to 5.8 kV
(5.73% to 7.2%). However, the voltage breakdown probability differed for MO and
However, the distribution of vegetable oils is well fitted with the reference line at all
145
gap distances. At 6.0 mm gap distance, the distributions of all samples were well
plotted at the probability line. The 1% and 50% probability were predicted lower but
almost close to the probability line. The difference of percentage at 50% probability
of MO, PO and RBO between the breakdown voltage distributions and the probability
line are calculated to be in the range of 1.4%, 1.6% and 1.1% respectively.
Gap Distances
The breakdown voltages of MO, PO and RBO for larger gap distances were collected
from the experimental data in Section 6.4.10 for distances between 10.0 mm and
50.0 mm gap distances. The Weibull probability plots can be referred to in Appendix
C.3.
The distribution breakdown voltages in Appendix C.3 indicate that almost all
samples were well matched to the probability line. MO shows a higher probability at
all various gap distances and is followed by RBO and PO. PO and RBO have a slight
difference between each other, especially at 50% probability. The 1% and 50%
146
Table 6.5 : 1% and 50% probabilities of MO, PO and RBO at larger gap
distances under needle to sphere configuration.
The result in Table 6.5 indicates that the differences in the breakdown voltages
at 50% and 1% probabilities between MO and PO/RBO are significantly higher at all
various gap distances. The probabilities of breakdown voltages between PO/RBO and
MO increase as the gap distance increases where the highest percentage of difference
probability is in the range from 11% to 32%, while for PO is in the range of 14% to
33%. The 50% probable breakdown voltages also show the average increasing
147
percentage difference between MO and PO/RBO when the gap distance increases.
RBO is in the range of 14% to 33%. On the other hand, the highest percentage
difference between PO and RBO at 1% and 50% probabilities are comparable with a
The breakdown voltage test is one of the most important transformer oil diagnostic tests
performed to know how much electrical stress it can withstand. The withstand voltage
of the oils is one of the imperative parameters for insulation design of transformers
and is defined as the voltage where the risk of failure is acceptably low [7]. The
subsections above does not point out the number of withstands at the mean voltage of
The breakdown voltage of vegetable oils at very large gaps is important for their
application in large power transformers. In this part, the relationship between the
results under the lightning impulse and the previously published data under step
148
voltage will be built up so that the breakdown voltages of vegetable oils at very large
gaps are extrapolated. Based on the previous studies by [45], [180], [182], [197],
[258], [259], a power law model was found to be suitable to represent the relationship
lightning impulse [45], [180], [182], [197]. The relationship between the lightning
breakdown voltage and the gap distance using the power law model is based on
equation 6.1 where V is the lightning breakdown voltage, d is the gap distance while
V = α × dβ (6.1)
formulas for the relationship between breakdown voltage (kV) and gap distance, d
probability for all samples. The 1% withstanding voltage and 50% breakdown voltage
fittings of these equations can be obtained in Figure 6.4 (a) and (b). Most of these
data fit well toward the power law equation, where the r2 values are from 0.83 to 0.97.
From the equations, it is observed that the constant values of α and β for both
of the equation matches the data quite well as shown in Figure 6.5 (a) and (b). The
1% withstanding voltage and 50% breakdown voltage matches the line based on
equations 6.2 to 6.7. It is found that the 50% breakdown voltage in this study show a
higher breakdown than previous studies but become closer to each other as the gap
distance increases. Overall, the equation for the non-uniform field in this study can
(a)
(b)
Figure 6.4 : Lightning impulse breakdown voltage fitting at empirical equation
at (a) 1% withstand voltage and (b) 50% breakdown voltage under a non-
uniform field.
150
6.8 Summary
In this chapter, a detailed investigation and analysis had been done with various
smaller and larger gap distances and various testing methods including the rising
voltage method, up and down method and multiple level method to determine the
The 50% lightning impulse performances of all samples are slightly different
at small gap distances in which the breakdown voltage difference is less than 5.8%.
The breakdown voltage increased as the gap increased. The percentage of the
difference between MO and both vegetable oils increase with increased gap distances
which ranged from 14.9% to 35%. The 50% breakdown voltages of RBO were higher
compared to PO and closer to MO. This might be due to the fast streamer appearing
at the breakdown voltage level and starts to take over the control of breakdown when
Furthermore, the 50% failure prediction using Weibull distribution for a non-
uniform field under lightning impulse test showed that almost all samples match the
probability line. The withstand voltage (1%) showed fewer matches, especially at
2.0 mm gap distance. Both vegetable oils, PO/RBO showed a nearly equal probability
of breakdown voltage and approached each other in all cases. MO almost showed the
highest prediction of 50% probability. It is followed by RBO and PO. The Weibull
distribution at larger gap distances also found the same finding as the small gap
distance where MO became the leading breakdown voltage. RBO was well fitted
compared to PO and gained a breakdown voltage lower than the probability line in
151
all cases. RBO breakdown data fitted better with Weibull distributions than MO. The
empirical formula for predicting the lightning impulse under a non-uniform electric
152
CHAPTER 7
7.1 Conclusions
liquids under AC voltage and lightning impulse test including various transformer
liquids and various field configurations. The measurement and diagnosis methods for
dielectric performance were also discussed and improved for the application of
researches, the objectives of this thesis were achieved, and useful findings were
successfully accomplished.
oil.
153
IV. Application of a lightning impulse of non-uniform field configuration
electrode according to standard IEC 60897 for various small and larger gap
distances.
liquids. To replace the existing transformer insulation oil with vegetable oils, it is
important to know the dielectric performance of vegetable oils. To reduce the size of
liquids with improved dielectric properties, due to the resultant higher levels of
electrical stress.
considering the effect of various electric fields, methods and gap distances. The
designer should consider the withstand capability of a transformer and ensure these
The main findings were reviewed on the basic properties of liquids samples, the
154
In AC breakdown tests, it was relatively notable the influence of different test
setups between using the BAUR oil tester (DTA 100C) and the high voltage setup in
a laboratory for insulation oils at 2.5 mm gap distance. The result of using BAUR oil
tester observed that MO gained the breakdown voltage within the range as
and MO. The vertical and horizontal electrode configuration and volume of oil
influences the breakdown strength. Nevertheless, PO and RBO performed better than
MO in five gap distances. The percentage difference between both vegetable oils saw
Hence, from the AC breakdown study, RBO has better dielectric properties and AC
breakdown voltage.
For the lightning impulse breakdown voltage under a uniform electric field,
RBO and PO have comparable performances to MO, which is promising results for
liquid insulation. In addition, there are notable effects of testing methods on the
and down method and multiple level method. The lightning impulse breakdown
voltage of PO is almost similar to RBO at various gap distances and testing methods.
The values of MO in all testing methods are higher than PO and RBO at all gap
distances.
field, results show that lightning impulse of PO and RBO are slightly lower than MO
for all conditions. However, the difference is so small and comparable to each other.
The testing methods include the rising-up voltage, up and down and multiple level
155
methods. For all of these, no significant effect on the lightning breakdown voltage
was observed. The multiple level method has slightly higher than rising voltage and
extended at larger gap distances. Due to the small effect on the lightning breakdown
voltage of the testing method at small gap distances, the rising voltage method is
recommended. The common testing method used is standard IEC 60897 and ASTM
3300. The study found the effects on lightning breakdown voltage increased as gap
distances increased. Overall, the findings are reliable and consistent with the previous
research on larger gap distances under a non-uniform field. Based on the testing data
under a non-uniform lightning impulse, an empirical formula had been proposed. The
proposed equation fits well with the data from the literature.
7.2 Recommendations
156
For the AC breakdown study:
and RBO. The geometries of the conductors inside a transformer are actually
more complex than this and may be included for the next research. As notified,
all the conductors within each winding in a power transformer are covered by
insulation and pressboard particles can be carried out to look at the consequence
of the contaminants with different concentrations in the insulating oil and fully
II. To monitor the condition of PO and RBO, the Dissolved Gas Analysis (DGA)
compounds generated from these oils can be investigated. The study could
uniform field tend to differentiate the oils. These configurations also represent
change the result. It is worth studying the streamer characteristic for breakdown
streamers in PO and RBO under impulse voltage by considering the previous test
of a uniform field.
157
II. Other interesting studies that can be carried out is to determine the ageing
158
REFERENCE
[2] Q. Liu, “Electrical Performance of Ester Liquids under Impulse Voltage for
Application in Power Transformers,” Word J. Int. Linguist. Assoc., p. 293,
2011.
[7] S. Farokhi, “Mechanisms of arc propagation over an ice surface ,” Mech. arc
Propag. over an ice Surf. , September, 2010.
159
[12] S. S. Sinan, S. N. Shawaludin, J. Jasni, N. Azis, M. Z. A. A. Kadir, and M. N.
Mohtar, “Investigation on The AC Breakdown Voltage of RBDPO Olein,” in
2014 IEEE Innovative Smart Grid Technologies - Asia, ISGT ASIA 2014, pp.
760–763, 2014.
[16] Y. Jing et al., “Dielectric Properties of Natural Ester, Synthetic Ester Midel
7131 and Mineral Oil Diala D,” IEEE Trans. Dielectr. Electr. Insul., vol. 21,
no. 2, pp. 644–652, 2014.
160
[23] S. S. Kumar, “Analysis of Vegetable Liquid Insulating Medium for
Applications in High Voltage Transformers,” International Conference on
Science, Engineering and Management Research (ICSEMR 2014), 2014.
[27] A.A.H. Zaidi, N. Hussin,and Dina Maizana, “Palm Oil as The Cooling Liquid
in Single Phase Transformer for Better Efficiency,” Applied Mechanics and
Materials, vol. 793, pp. 192–196, 2015.
[29] D. Martin, “Evaluation of the Dielectric Capability of Ester Based Oils for
Power Transformers,” PhD thesis , University of Manchester, 2007.
161
[35] W.U.Lu, “Pre-Breakdown and Breakdown Phenomena of Alternative
Transformer Liquids Under Lightning Impulse Voltages,” PhD thesis,
University of Manchester, 2015.
162
[47] M. M. Yaacob and M. A. Alsaedi, “Use Palm Oil as Alternative with
Insulation Oil in High Voltage Equipment,” Physical and Science
International Journal, vol. 5, no. 3, pp. 172–178, 2015.
163
[58] V. H. Dang, A. Beroual, and C. Perrier, “Investigations on Streamers
Phenomena in Mineral, Synthetic and Natural Ester Oils under Lightning
Impulse Voltage,” IEEE Trans. Dielectr. Electr. Insul., vol. 19, no. 5, pp.
1521–1527, 2012.
[59] R. Frotscher et al., “Behaviour of Ester Liquids under Dielectric and Thermal
Stress – From Laboratory Testing to Practical Use." CIGRE Paris Conf. Pap.
D1_105, pp. 1–12, 2012.
[62] Q. Liu and Z. Wang, “AC and Lightning Breakdown Strength of Mineral Oil
Nytro Gemini X and 10Gbn,” Int. Electr. Insul. Conf., pp. 14–19, 2009.
164
[70] A. A. Abdelmalik, J. C. Fothergill, and S. J. Dodd, “Electrical Conduction and
Dielectric Breakdown Characteristics of Alkyl Ester Dielectric Fluids
obtained from Palm Kernel Oil,” IEEE Trans. Dielectr. Electr. Insul., vol. 19,
no. 5, pp. 1623–1632, 2012.
[76] Russell Martin et al, “Experiences in Service with New Insulating Liquids,”
Cigre A2-35, no. October, 2010.
165
[81] S. Suwarno, F. Sitinjak, I. Suhariadi, and L. Imsak, “Study on the
Characteristics of Palm Oil And it’s Derivatives as Liquid Insulating
Materials,” 7th International Conference on Properties and Applications of
Dielectric Materials, vol. 2, pp. 495–498, 2003.
[85] E. R. Cousins, S. P. Fore, H. J. Janssen, and R. O. Feuge, “Rice bran oil. VIII.
Tank Settlings from Crude Rice Bran Oil as a Source of Wax,” Journal of the
American Oil Chemists Society, vol. 30, no. 1, pp. 9–14, 1953.
[86] Tiwari, G.J., Aumeeruddy, A. and Rahman, S., “Improving the Economic
Value of Rice Bran Oil,” Malay. appl. Biol., vol. 43, pp. 1–8, 2014.
[87] Lei Lei Aung, “Preparation of Activated Kaolin for Bleaching Rice Bran Oil
and Synthetic Kaolinites to Assess Sorption Properties of These Particles in
Relation to their Morphology,” PhD thesis, King Mongkut’s University Of
Technology Thonburi, 2014.
[88] F. Zaccheria, M. Mariani, and N. Ravasio, “The Use of Rice Bran Oil within
a Biorefinery Concept,” Chem. Biol. Technol. Agric., pp. 1–8, 2015.
[89] Y. P. Pal and A. P. Pratap, “Rice Bran Oil : A Versatile Source for Edible and
Industrial Applications,” Journal of Oleo Science, vol. 556, no. 6, pp. 551–
556, 2017.
[91] Nantiyakul , Nantaprapa, " Processing Rice Bran to Yield Added-Value Oil
Based Extracts ," PhD thesis , University of Nottingham, 2012.
[92] A. Probudha, A. Wakil, and A. Kafy, “Prospect of Rice Bran for Biodiesel
Production in Bangladesh,” 10th International Conference on Mechanical
Engineering, ICME 2013, vol. 90, pp. 746–752, 2014.
166
[93] M. Rashid, “Management of Renewable Sources of Energy : A Case on Rice
Bran oil and Vegetable oils of Bangladesh Perspective,” Energy Science and
Technology, vol. 2, no. 1, pp. 62–67, 2011.
[94] Y. Ju and S. R. Vali, “Rice Bran Oil as a Potential Resource for Biodiesel : A
Review,” Journal of Scientific & Industrial Research, vol. 64, no. November,
pp. 866–882, 2005.
[105] J. Y. Sha, Zhou, Y., Nie, D., Wu, Z., & Deng, “A Study on Electric
Conduction of Transformer Oil,” IEEE Trans. Dielectr. Electr. Insul., vol. 21,
n, pp. 1061–1069, 2014.
167
[106] D. Wang, C. Mao, J. Lu, S. Fan, and F. Peng, “Theory and Application of
Distribution Electronic Power Transformer,” Electric Power System
Research., 2007.
[113] Hyrax Oil Sdn. Bhd, “Product Information – Hyrax Hypertrans Transformer
Oil (IEC 60296: 2012) –Edition 4,"
http://www.hyraxoil.com/Transformer1.htm
[116] Bertrand, Y and Hoang, LC, “Vegetable Oils as Substitute for Mineral Oils,"
7th Intemational Conference on Properties and Applications of Dielectric
Materials, Nagoya,” , vol. 2, pp. 491-494, 2003.
168
[120] M. Martins, “Vegetable Oils, an Alternative to Mineral Oil for Power
Transformers- Experimental Study of Paper Aging in Vegetable Oil Versus
Mineral Oil,” IEEE Electr. Insul. Mag., vol. 26, no. 6, pp. 7–13, 2010.
[124] Rui Carlos Zambiazi, Roman Przybylski, Moema Weber Zambiazi, Carla
Barbosa Mendonça “Fatty Acid Composition Of Vegetable Oils And Fats,”
Bol. do Cent. Pesqui. Process. Aliment., 2007.
[130] N. A. Mohamad et al., “A Study on the Dielectric Properties of Palm Oil and
Coconut Oil,” IEEE International Conference on Power and Energy, PECon
2014, 2014.
169
[131] Kiasatina, M. Kamarol, M. Zulhilmey, and Y. A. Arief, “Breakdown
Characteristics of RBDPO and Soybean Oil Mixture for Transformer
Application,” InECCE 2011 - International Conference on Electrical, Control
and Computer Engineering, 2011.
[140] M. Hikita and J. Tokiyoshi, “Partial Discharge Properties of Ester Oils having
Different Molecular Structures,” IEEE International Symposium on Electrical
Insulation, pp. 26–29, 2012.
[141] Transformers Committee IEEE, IEEE Std C57.147TM-2008, IEEE Guide for
Acceptance and Maintenance of Natural Ester Fluids in Transformers. 2008.
170
[143] Cargill Electrical apparatus R2000 – Dielectric Fluids – EnvirotempTM
FR3TM Fluid, 2013.
[144] E. Society, "IEEE Guide for Acceptance and Maintenance of Natural Ester
Insulating Liquid in Transformers," 2018.
[153] Z.D .Wang, D. Martin, I. Khan, et al, “An Overview of the Suitability of
Vegetable Oil Dielectrics for Use in Large Power Transformers,” Euro
TechCon, pp. 1–23, 2006.
171
[156] T. V. Oommen, C. C. Claiborne, and J. T. Mullen, “Biodegradable electrical
insulation fluids,” in Proceedings of the Electrical/Electronics Insulation
Conference, 1997.
[158] “ASTM D1816, Test Method for Dielectric Breakdown Voltage of Insulating
Oils of Petroleum Origin using VDE Electrodes’,” ASTM Int. USA., 2004.
[159] “ASTM D877, ‘Standard Test Method for Dielectric Breakdown Voltage of
Insulating Liquids using Disk Electrodes,’” ASTM International USA., 1995.
[162] Cargill, "Envirotemp FR3 fluid product datasheet," BEES, Version 4.0e,
Building and Fire Research Laboratory, National Institute of Standards and
Technology, 2007.
[163] M&I Materials Ltd, “Product Overview Midel 7131,” Tech. Datasheet No 2,
vol. 01, 2017.
172
[169] U. M. Rao, I. Fofana, and S. Member, “Alternative Dielectric Fluids for
Transformer Insulation System : Progress , Challenges , and Future
Prospects,” IEEE Access, vol. 7, 2019.
[173] ASTM D3300, “Standard Test Method for Dielectric Breakdown Voltage of
Insulating Oils of Petroleum Origin under Impulse Conditions,” ed. United
States, 2012.
[180] W. Sima, C. Jiang, P. Lewin, Q. Yang, and T. Yuan, “Modeling of the Partial
Discharge Process in a Liquid Dielectric: Effect of Applied Voltage, Gap
Distance, and Electrode Type,” Energies, pp. 934–952, 2013.
173
[181] K. J. Rapp, C. P. McShane, J. Vandermaar, D. Vukovic, and S. Tenbohlen,
“Long Gap Breakdown of Natural Ester Fluid,” 2010 International
Conference on High Voltage Engineering and Application, ICHVE 2010, pp.
104–107, 2010.
174
[192] V. Champa, A. N. Nagashree, B. V. Sumangala, and G. R. Nagabhushana,
“Breakdown Behaviour of New Bio-degradable Dielectric Coolants under
50Hz AC for Different Electrode Configurations,” Material Today: Proc.,
vol. 5, no. 1, pp. 3099–3108, 2018.
[195] M. Markovic and Z. Stih, “New Method for Prediction of Insulating Liquid
AC Breakdown,” IEEE Trans. Dielectr. Electr. Insul., vol. 24, no. 1, pp. 437–
454, 2017.
175
[203] Liu, R.; Törnkvist, C.; Chandramouli, V.; Girlanda, O.; Pettersson, L.
"Geometry impact on streamer propagation in transformer insulation liquids."
Proceedings of the Annual Report CEIDP, West Lafayette, IN, USA, 17–20
2010.
[205] W. Yuan et al., “Weibull Statistical Analysis of Size Effects on the Impulse
Breakdown Strength in Transformer Oil,” IEEE Int. Conf. Dielectr. Liq., no.
Icdl, pp. 29–32, 2017.
[209] N.I.A. Katim, " Electrical Breakdown Performances of Palm Oil and Coconut
Oil Under Uniform," PhD thesis , National Defence University of Malaysia,
2017.
176
[215] C. Sun, J. Li, X. Li, and S. Grzybowski, “Electric Properties of Vegetable Oil-
Based Dielectric Liquid and Lifetime Estimation of the Oil-Paper Insulation,”
in 2006 IEEE Conference on Electrical Insulation and Dielectric Phenomena,
pp. 680–683, 2006.
177
[227] “ASTM D 924 : Test Method for Dissipation Factor (or Power Factor) and
Relative Permittivity (Dielectric Constant) of Electrical Insulating Liquids,”
ASTM Int. West Conshohocken, PA, 2008.
[235] Cooper Industries, “Envirotemp FR3 Fluid testing guide,” Cooper Ind. Inc,
87. Waukesha, USA, 2004.
[238] P. Wang, Z.D.; Liu, Q.; Wang, X.; Yi, X.; Jarman, P.; Wilson, G.; Dyer, “Ester
Insulating Liquids for Power Transformers,” CIGRE Paris, France., 2012.
178
[240] IEEE std C57. 147-2008, “IEEE Guide For Acceptance And Maintenance Of
Natural Ester Fluids In Transformers.,” 2008.
[245] D. Tschudi and P. Heinzig, “State of the Art Solid Insulation after 125 years
of Transformer Practice,” Int. Colloq. Transform. Res. Asset Manag., 2009.
179
[252] Q. Liu and Z. D. Wang, “Streamer Characteristic and Breakdown in Synthetic
and Natural Ester Transformer Liquids with Pressboard Interface under
Lightning Impulse Voltage,” IEEE Trans. Dielectr. Electr. Insul., vol. 18, no.
6, pp. 1908–1917, 2011.
[254] H. Yilmaz; S. Guler, “The Effect of Electrode Shape, Gap and Moisture on
Dielectric Breakdown of Transformer Oil," 12th International Conference on
Conduction and Breakdown in Dielectric Liquids, pp. 354–357, 1996.
[258] J. Cygan, P.Laghari, “Models for Insulation Aging under Electrical And
Thermal Multistress,” IEEE Trans. Electr. Insul. 25, pp. 923–934, 1990.
180
APPENDICES
APPENDIX A
A.1 Properties of uninhibited mineral oil from previous studies
A.2 The Dielectric and physicochemical properties of the palm
oils.
A.3 The flash point of vegetable oil based on previous studies.
A.4 AC breakdown voltage of vegetable oils.
A.5 Standards for insulating oil breakdown test.
APPENDIX C
C.1 Weibull Distribution of Lightning Impulse Breakdown
Voltage under Non-Uniform Field at Small Gap
Distances
APPENDIX D
D.1 AC breakdown voltage between using HV laboratory and
BAUR Trainer equipment.
D.2 AC breakdown voltage of MO, PO and RBO under
various gap distances.
APPENDIX E
E.1 Lightning impulse breakdown voltage under uniform field.
APPENDIX F
F.1 Lightning impulse breakdown voltage under non-uniform
field at small gap distances.
181
APPENDIX A
182
Table A.2 The Dielectric and physicochemical properties of the palm oils.
Properties Bdv, kv Viscosity DDF Dielectric Resistivity, Flash Pour Water Density
@40°c constant Ω-cm point , point, content, g/ml
°C °C ppm
183
Table A.3 The flash point of vegetable oil based on previous studies.
184
Table A.5 AC breakdown voltage of vegetable oils.
185
Table A. 6 Standards for insulating oil breakdown test.
ASTM
Standards ASTM D877 IEC 60156
D1816
Origin USA USA Europe
Test Cell
Shape
Electrodes
Gap size 2mm / 1mm 2.54mm 2.5mm
Impeller Yes Optional
Oil sample
Magnetic
stirring No option Not stirred Optional
bead
Ambient – 20-30°C – 15-25°C – for referee
Laboratory Liquid
must record must record tests
test
Ambient Within 5°C of oil
temperature 20-30°C Must record
sample
Ambient –
Liquid Must record 15-25°C
Outside test must record
temperature 20-30°C – for Within 5°C of oil
Ambient Must record
referee tests sample
Rise rate 0.5kV/s 3kV/s 2kV/s
Test voltage
Frequency 45-65 Hz 45-65 Hz 45-62 Hz
Definition <100 V <100V 4mA for 5ms
Number in
5** 5* 6
sequence
Breakdowns
Time
between 1-1.5 minutes 1 minute 2 min
breakdown
Test voltage Normal
Not specified Not specified <10ms
switch off time (mineral oil)
following
Silicon oil Not specified Not specified <1ms
breakdown
Time between filling and
3-5 minutes 2-3 minutes 2 minutes
start of test
BS EN 60156
CEI EN 60156
Equivalent standards None None
UNE EN 60156
186
APPENDIX B
Figure B.1 Weibull distribution plot for MO, PO and RBO of sphere to sphere
configuration at (a) 2.0 mm, (b) 3.8 mm and (c) 6.0 mm gap distances.
(a)
(b)
187
(c)
188
APPENDIX C
Figure C.1 Weibull distribution plot for MO, PO and RBO at (a) 2.0 mm, (b) 3.8
mm and (c) 6.0 mm gap distances under non-uniform field.
(a)
(b)
189
(c)
190
Figure C.2 Weibull distribution plot for MO, PO and RBO under non-uniform
field at (a) 10.0 mm, (b) 20.0 mm, (c) 30.0 mm, (d) 40.0 mm and (e) 50.0 mm gap
distances.
(a)
(b)
191
(c)
(d)
192
(e)
193
APPENDIX D
194
64.5 77 83.5 73.5 93.5 87
66.1 85.93 83.7 73.7 93.7 85.93
67.8 72.65 90.9 80.9 90.9 82.65
64.6 89.34 90.7 80.7 90.7 89.34
63.2 78.61 82.7 82.7 92.7 88.61
65 73.67 85.5 85.5 85.5 83.67
61.6 86.02 82.1 82.1 92.1 86.02
62.3 80.64 83.7 83.7 93.7 100.64
68.6 90.67 78.6 78.6 78.6 100.67
66.8 78.78 87.7 77 87.7 88.78
67.5 82.42 88 78 88 92.42
195
Table D.2 AC breakdown voltage of MO, PO and RBO under various gap distances.
45.62 69.1 66.01 65.5 86.63 82.8 73.8 96.63 89.46 116.22 130.34 132.61 157.01 176.7 185.14
42.38 67.5 65.07 63.2 82.39 82.5 75.2 92.39 89.58 111 132.83 128.38 156.52 177.6 179.48
45.79 74.5 64.07 66.1 81.18 93.2 73.6 91.18 88.76 118.42 135.3 128.14 156.85 180.74 176.77
44.19 68.8 64.38 63.9 76.12 89.2 81.1 96.12 101.14 113.56 127.15 131.17 164.56 174.61 184.76
45.33 77.2 62.98 61.1 82.29 96.6 68.1 92.29 96.48 121.03 117.08 127.42 158.74 180.1 177.23
46.92 65.3 59.91 68.1 83.76 82.4 67.7 93.76 89.82 113.49 128.06 129.56 158.78 173.75 178.51
43.54 69.4 57.28 67.8 79.75 89.8 72.7 89.75 96.8 112.49 125.9 129.61 162.11 175.05 179.49
43.72 72.8 65.24 66.8 76.32 81.9 70.9 89.32 101.74 106.51 135.1 125.01 165.27 173.43 178.96
43.8 69.1 69.47 66.9 88.76 84.6 73.9 98.76 93.62 111.723 126.08 128.17 166.37 173.67 179.11
45.66 62.1 79.92 69.2 89.42 81.3 80.1 99.42 88.74 108.45 124.38 129.43 152.63 177.36 182.9
42.41 62.1 58.4 67.8 73.22 91 73 93.22 101.44 119.73 129.2 130 164.82 172.78 180.34
43.93 62.8 57.2 61.4 86.82 90 63.8 96.82 89.84 103.18 125.52 129.63 157.02 181.92 180.14
44.21 65.5 55.21 64.4 90.46 89.6 76.6 90.46 94.32 107.08 129.06 127.14 158.18 180.34 176.57
43.55 78.4 59.1 62.4 80.26 90.5 72.4 90.26 88.12 123.13 126.1 130.26 158.21 179.75 178.44
43.82 67.5 60.4 61.7 89.55 81.5 86.5 89.55 92.6 121.16 120.58 129.44 152.78 181.12 180.79
43.21 72.5 64.39 63.8 82.68 80.4 81.6 92.68 93.76 112.8 120.58 132.2 153.84 177 179.19
46.87 72.1 63.6 61.7 89 81 87.2 89 90.8 113.38 121.06 127.15 152.73 172.91 185.65
43.56 68.4 62.58 68 76.27 87.7 79.2 96.27 101.34 100.91 126.51 128.6 151.98 172.53 177.05
42.68 75.3 60.1 64 82.4 87.2 72.6 92.4 102.2 99.89 131.73 131.93 161.79 173.63 178.14
45.3 69.9 68.45 64.5 77.83 79.8 75.7 89.83 89.96 110.53 132.09 130.32 152.21 176.79 183.49
45.16 80.4 78.112 63.5 92.4 78.1 79.9 92.4 102.9 117.6 129.54 126.99 156.37 178.65 183.62
45.35 70.3 76.01 61.7 91.42 77.6 75.5 91.42 97.34 118.09 127.5 126.05 164.82 178.7 186.66
196
45.22 73.9 76.5 65.3 85.51 82.6 74.5 95.51 96.52 121.89 126.92 129.13 164.57 182.2 182.15
42.45 67.7 65.14 61.7 90.01 81.6 73.3 96.01 96.72 119.41 124.77 129.68 165.45 178.65 181.4
44.72 63.7 74.1 63.7 90.16 80.7 70.1 96.16 94.22 123.55 126.02 129.13 156.61 178.7 175.16
42.92 68.5 73.8 60.3 79.62 83.7 75.5 89.62 103.74 104.78 125.75 129.06 159.8 176.16 180.99
44.3 72.1 77.8 67.7 91.82 84.8 65.1 91.82 98.54 120.34 132.9 129.14 161.77 176.47 180.76
45.51 66.1 79.26 65.4 83.88 81.4 73.9 93.88 93.86 112.71 133.64 128.07 160.54 175.84 180.44
42.29 67.5 70.53 63.9 77.82 86.9 80.4 97.82 95.24 118.53 124.72 128.15 159.03 175.94 180.78
43.3 63.3 79.4 63.3 82.15 85.9 71.2 92.15 101.1 113.54 125.78 128.3 160.97 180.9 178.78
42.91 68.5 58.4 60.6 72.3 78.7 84.9 92.3 89.7 117.54 125.14 129 153.78 176.91 177.65
42.66 66.3 70.39 61.7 89.89 87.2 82.4 89.89 97.38 107.68 119.38 126.73 161.28 180.63 177.94
43.81 61.5 72.8 69.6 84.27 85.5 74 94.27 102.54 117.75 131.59 128.45 161.22 180.54 178.97
45.48 67.1 73.4 69.2 75.06 83.8 72.6 95.06 97.52 115.114 126.35 128.28 158.99 178.65 181.76
48.7 77.2 77.46 60.2 83.37 81.1 70.2 93.37 96.54 110.84 129.36 132.09 158.94 181.87 179.17
44.73 64.7 76.1 69.4 71.68 81.2 79.2 91.68 94.16 119.93 116.27 127.32 152.76 180.63 180.76
47.47 64.6 74.67 67.2 80.35 83.1 68.2 90.35 102.5 123.79 126.81 127.65 159.01 178.92 178.2
47.61 65.7 61.6 67.5 85.94 83.1 67.7 95.94 94.18 117.03 132.91 125.74 159.03 180.15 176.77
47.86 63.5 77.8 64.8 83.37 86.1 77.2 93.37 89.54 106.37 126.84 126.43 163.72 179.02 175.28
42.34 62.5 66.2 64.5 77 83.5 84.8 97 91.2 116.52 128.78 126.47 160.31 179.99 181.98
44.3 63.3 76.33 66.1 85.93 83.7 72.4 95.93 89.46 118.92 129.43 126.94 144.89 182.24 184.18
43.44 65.1 73.8 67.8 72.65 90.9 69.9 92.65 101.4 118.18 132.25 128.33 164.67 181.1 184.85
43.76 65.1 76.8 64.6 89.34 90.7 82.5 89.34 96.18 114.45 129.81 130 160.98 181.12 181.04
43.27 63.3 79.6 63.2 78.61 82.7 86 98.61 91.22 110.01 129.18 129.99 159.88 182.4 184.67
42.82 62.9 68.7 65 73.67 85.5 91 93.67 96.34 118.14 124.98 126.94 159.98 182.07 181.24
44.53 61.5 68.9 61.6 86.02 82.1 81 96.02 91.04 116.01 124.81 127.65 161.67 183.28 179.93
46.54 66.8 73.6 62.3 80.64 83.7 87.1 96.64 94.18 111.59 125.26 129.74 159.33 174.96 182.48
44.87 64.6 73.33 68.6 90.67 78.6 79.2 96.67 82.14 101.54 129.92 132.09 160.21 181.89 181
43.76 65.7 72.7 66.8 78.78 87.7 77.5 98.78 90.06 105.25 129.47 128.82 161.87 179.18 185.22
48.96 63.5 71.8 67.5 82.42 88 81.6 92.42 96 116.51 131.72 129.32 163 181.49 179.28
197
APPENDIX E
198
Gap MO PO RBO MO PO RBO MO PO RBO
distance
(mm) 2.0 3.8 6.0
199
APPENDIX F
200
Gap MO PO RBO MO PO RBO MO PO RBO
distance
(mm) 2.0 3.8 6.0
201
Table F.2 Lightning impulse breakdown voltage under uniform field at larger gap distances.
152.11 129.73 129.30 181.83 149.29 154.22 211.30 163.55 168.87 249.72 175.85 184.71 323.65 202.83 211.62
150.46 128.82 129.91 182.97 151.76 153.48 198.28 161.63 167.77 253.78 183.97 185.79 297.64 204.78 209.71
153.64 126.87 128.56 183.63 151.74 153.72 211.68 161.00 168.85 255.67 183.82 185.97 311.83 198.54 210.39
155.87 127.47 128.73 181.30 151.10 154.31 211.56 162.03 169.71 252.68 184.35 184.81 320.25 203.74 210.98
151.95 128.05 130.12 179.34 152.45 155.03 211.55 163.13 168.36 251.88 176.24 185.64 312.76 203.66 211.63
149.58 130.10 128.16 181.99 136.98 152.84 210.80 163.98 163.27 249.87 178.23 182.85 312.53 191.14 204.47
151.27 127.36 129.48 178.19 144.72 151.98 197.01 164.72 164.27 252.26 184.95 185.71 300.92 205.83 202.31
149.65 125.65 127.78 183.08 159.71 152.86 193.37 159.71 164.17 253.87 181.96 183.86 314.28 205.23 205.74
150.37 123.35 128.77 177.31 151.89 152.89 196.23 161.89 165.10 253.72 185.20 184.28 313.55 206.45 202.71
149.23 127.23 127.37 182.63 152.26 152.83 196.80 162.26 164.38 254.26 182.80 180.92 316.25 203.83 203.61
202
CURRICULUM VITAE
Seri Petaling and SMT Kuala Selangor. Later on, she studied at
Electrical Engineering. After that, she furthered her studies in 2008 at the University of
Tun Hussein Onn Malaysia (UTHM) and received her Bachelor Degree in Electrical
Engineering with Honour in 2010 and Master Degree in Technical and Vocational
Education in 2013. After finishing her study, she worked at Sepakat Setia Perunding Sdn.
Bhd. as an Electrical Engineer for almost two years. Currently, she works as a lecturer at
the Sultan Abdul Samad Vocational College. She is studying for her PhD in the
203
LIST OF PUBLICATIONS
2. Katim, N., Ishak, M., Mohamad Amin, N., Hamid, M.H.A, Amali Ahmad, K.,
& Azis, N. “Lightning Breakdown Voltage Evaluation of Palm Oil and Coconut
Oil as Transformer Oil under Quasi-Uniform Field Conditions”. Energies,
11(10), 2676. 2018.
4. Ariffin, M. M., Roslan, M. H., Ishak, M. T., Hamid, M. H. A., Katim, N. I. A.,
Hashim, F. R., & Razali, S. (2018). “Hypervelocity penetration against
mechanical properties of target material”. International Conference on
Engineering and Technology (IntCET 2017), AIP Conf. Proc. 1930, 020014-1–
020014-9; 2018
204
8. Katim, N. I. A., Ishak, M. T., Amin, N. A. M., Razali, S., Hamid, M. H. A.,
Ariffin, M. M., & Azis, N. “Investigation on AC breakdown of vegetable oils
with insulated electrodes”. 2017 International Conference on High Voltage
Engineering and Power Systems (ICHVEPS). 2017.
9. Hamid, M. H. A., Ishak, M. T., Ariffin, M. M., Katim, N. I. A., Amin, N. A. M.,
& Azis, N. “Dissolved gas analysis (DGA) of vegetable oils under electrical
stress” 2017 International Conference on High Voltage Engineering and Power
Systems (ICHVEPS). 2017.
10. Ariffin, M. M., Ishak, M. T., Hamid, M. H. A., Katim, N. I. A., Ishak, A. M., &
Azis, N. “Ageing effect of vegetable oils impregnated paper in transformer
application”. 2017 International Conference on High Voltage Engineering and
Power Systems (ICHVEPS). 2017
12. Hamid, M. H. A., Ishak, M. T., Din, M. F., Suhaimi, N. S., & Katim, N. I. A.
“Dielectric Properties of Natural Ester Oils Used for Transformer Application
Under Temperature Variation”. In 6th International Conference on Power and
Energy.2016.
13. Suhaimi, N. S., Ishak, M. T., Katim, N. I. A., & Hamid, M. H. A.. “Investigation
on Breakdown Strength of Mineral Oil Based Carbon Nanotube”. In 6th
International Conference on Power and Energy.2016.
205