8 10
10 1400 1432
DIMENSIONS:
21 33
6 1. MINIMUM CREEPAGE DISTANCE : 4495 mm
2. ARCING DISTANCE (BETWEEN EARTH) FOR CICA ASSEMBLY : 1580 > 1300 mm
4
5 177 9
200
1130
2 6 7 MECHANICAL CHARACTERISTICS:
(I). POST INSULATOR: φ133*1912 mm
1. SPECIFIED MECHANICAL LOAD (TENSILE) : 100 kN
2. SPECIFIED MECHANICAL LOAD (COMPRESSION) : 220 kN
285
4 ELECTRICAL CHARACTERISTICS:
1. NOMINAL SYSTEM VOLTAGE : 132 kV
1822 2. HIGHEST SYSTEM VOLTAGE : 145 kV
3. SYSTEM FREQUENCY : 50 Hz
1580
4. WET 1 MINUTE POWER FREQUENCY WITHSTAND VOLTAGE : 275 kV
1436
PLAN VIEW
IN-AEGCL-SMAREPC-04
11 SUSPENSION METAL STRING F.S.(CL-IV) AS PER IS: 2004 1
(Sheet 1 of 4)
ADDITIONAL MEMBER AT LG FACE HT-E350, Fe490 IN-AEGCL-SMAREPC-03
10 1
FOR LINE INSULATOR CONNECTION AS PER IS: 2062 (Sheet 6 of 7)
ADDITIONAL MEMBER AT TR FACE HT-E350, Fe490 IN-AEGCL-SMAREPC-03
9 1
FOR LINE INSULATOR CONNECTION AS PER IS: 2062 (Sheet 7 of 7)
LINE INSULATOR CONNECTION HT-E350, Fe490 IN-AEGCL-SMAREPC-03
8 1
PLATE AS PER IS: 2062 (Sheet 5 of 7)
IN-AEGCL-SMAREPC-03
7 CLEVIS EYE F.S.(CL-IV) AS PER IS: 2004 1
(Sheet 4 of 7)
IN-AEGCL-SMAREPC-03
6 ADJUSTMENT PLATE F.S.(CL-IV) AS PER IS: 2004 1
(Sheet 3 of 7)
Φ18 MM SOLID CORE IN-AEGCL-SMAREPC-03
5 LINE INSULATOR 1
(FRP) (Sheet 1 of 7)
ADDITIONAL MEMBER AT LG FACE HT-E350, Fe490 IN-AEGCL-SMAREPC-02
4 2
FOR POST INSULATOR CONNECTION AS PER IS: 2062 (Sheet 4 of 4)
POST INSULATOR FLANGE AT LOW HT-E350, FE490 AS PER IN-AEGCL-SMAREPC-02
3 1
VOLTAGE END IS: 2062 (HDG) (Sheet 2 of 4)
POST INSULATOR FLANGE AT HIGH HT-E350, FE490 AS PER IN-AEGCL-SMAREPC-02
2 1
VOLTAGE END IS: 2062 (HDG) (Sheet 2 of 4)
Φ133 MM SOLID CORE IN-AEGCL-SMAREPC-02
1 POST INSULATOR 1
(FRP) (Sheet 1 of 4)
C C
3
1
4
C-C
2
MECHANICAL CHARACTERISTICS:
1. SPECIFIED MECHANICAL LOAD(TENSILE): 100 kN
Notes
2. SPECIFIED MECHANICAL LOAD(COMPRESSION ): 220 kN 1. FOLLOWING MARKINGS BY PIN MARKING/LASER MARKING
3. CANTILEVER LOAD : 15 kN SHEMAR
MONTH & YEAR
ELECTRICAL CHARACTERISTICS: 132kV 4 POST INSULATOR FLANGE AT HT-E350, Fe490 AS PER IS: 2062 1
IN-AEGCL-SMAREPC-02
LOW VOLTAGE END (HDG) (Sheet 2 of 4)
1. NOMINAL SYSTEM VOLTAGE: 132 kV AEGCL POST INSULATOR FLANGE AT HT-E350, Fe490 AS PER IS: 2062 IN-AEGCL-SMAREPC-02
3 1
HIGH VOLTAGE END (HDG) (Sheet 2 of 4)
2. HIGHEST SYSTEM VOLTAGE: 145 kV 2. GALVANIZATION CONFORMS TO IS: 2629-1990, 2633-1992, 6745-1990
2 POST INSULATOR SHED HTV-SILICONE RUBBER - -
4. WET 1 MINUTE POWER FREQUENCY WITHSTAND VOLTAGE: 275 kV 4. PURITY OF ZINC USED SHALL BE 99.95% (FRP)
C C
C-C
C
2 CONNECTION PLATE PART-2 HT-E350, Fe490 AS PER IS: 2062 4 10MM THK PLATE (HDG)
1 CONNECTION PLATE PART-1 HT-E350, Fe490 AS PER IS: 2062 4 10MM THK PLATE (HDG)
A detail
2 STIFFENER PLATE HT-E350, Fe490 AS PER IS: 2062 1 12MM THK PLATE (HDG)
2. HIGHEST SYSTEM VOLTAGE: 145 kV 5. NUMBER OF DIPS WHICH THE END FITTINGS CAN WITHSTAND IN THE STANDARD PREECE TEST - 2Nos 2 LINE INSULATOR SHED HTV-SILICONE RUBBER 1 -
3. SYSTEM FREQUENCY: 50 Hz 6. TOLERANCE ON DIMENSIONS: 0.15 MM. 1 LINE INSULATOR CORE ROD FIBER REINFORCED POLYMER 1 -
(FRP)
4. WET 1 MINUTE POWER FREQUENCY WITHSTAND VOLTAGE: 275 kV 7. SILICON CONTENT FOR WEATHER SHEDS AND HOUSING> OR= 30% SL.NO. DESCRIPTION MATERIAL QTY. DRG. NO.
PROJECT NAME : RANGIA-SIPAJHAR 132kV SC LINE,
5. DRY LIGHTNING IMPULSE WITHSTAND VOLTAGE : 650 kVp 8. MIN. THICKNESS OF SHEATH COVERING OVER THE CORE: 5 MM ASSAM
9. ALL DIMENSIONS ARE IN MM. JIANGSU SHEMAR ELECTRIC CO.,LTD.
CLIENT : ASSAM ELECTRICITY GRID CORPORATION
APPLICABLE STANDARDS: LIMITED (AEGCL)
TITLE: LINE INSULATOR OF 132kV-COMPOSITE INSULATED CROSS-ARM (CICA)
1. INSULATOR: IEC: 61109-2008 (SUSPENSION TOWER SINGLE ACSR PANTHER CONDUCTOR - 132KV S/C TRANSMISSION LINE)
2. GALVANIZATION IS: 2633-1986 C
YUJIE
HUANGQING
-
-
YUJIE
01/11/21
01/11/21
Not to Scale IN-AEGCL-SMAREPC-03 1 of 7 INDIA-AEGCL 132kV CICA LINE INSULATOR A
1 EYE FITTING FORGED STEEL EN8D BS: 970 2 HDG
80
2
285
120
3
PROJECT NAME : RANGIA-SIPAJHAR 132kV SC LINE, SL.NO. DESCRIPTION MATERIAL QTY. DRG. NO.
ASSAM
JIANGSU SHEMAR ELECTRIC CO.,LTD.
CLIENT : ASSAM ELECTRICITY GRID CORPORATION
LIMITED (AEGCL)
TITLE: SUSPENSION METAL STRING OF 132kV-COMPOSITE INSULATED CROSS-ARM (CICA)
(SUSPENSION TOWER SINGLE ACSR PANTHER CONDUCTOR - 132KV S/C TRANSMISSION LINE)
YUJIE - 01/11/21
C YUJIE
HUANGQING - 01/11/21
Not to Scale IN-AEGCL-SMAREPC-04 1 of 4 INDIA-AEGCL 132kV CICA METAL STRING A
1 SHACKLE LINK - 70kN F.S.(CL-IV) AS PER IS: 2004 1 HDG
PROJECT NAME : RANGIA-SIPAJHAR 132kV SC LINE, SL.NO. DESCRIPTION MATERIAL QTY. REMARKS
ASSAM