DOCUMENT NO. DATE REVISION NO.

SIZE SHEET
ME4320A-2 0 A4 1 of

WORK:

AIR HANDLING UNIT DETAIL DESIGN


FOR
KM. SUNDALA
TITLE:

Cooling Load Calculation for Ships Air Handling Unit

OWNER:

PROGRAM STUDI TEKNIK PERMESINAN KAPAL


POLITEKNIK PERKAPALAN NEGERI SURABAYA

CONSULTANT:

NURMAN DWI HARMAJI


0319040042

0 2021/06/30 FOR APPROVAL NDH GEK MAM


0319040042
REV. DATE DESCRIPTION PREPARED CHECKED APPROVED
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

DOCUMENT HISTORY SHEET

Rev. Date Description

0 21/10/2022 Project Explanation


1 28/10/2022 Dimension of refrigerated hold calculation
2 04/11/2022 Selecting Type and Thickness of Material Insulation
3 11/11/2022 Cooling capacity Calculation
4 18/11/2022 Unit Selection for Refrigerated Hold
5 23/11/2022 Ducting Calculation
6 12/12/2022 Line Ducting Desain with pipe flow expert software

1
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

Daftar isi

1. INTRODUCTION ................................................................................................................... 5

2. SCOPE OF WORKS ............................................................................................................... 5

3. REFERENCES ........................................................................................................................ 5

3.1. Codes ................................................................................................................................................................ 5

3.2. Standards.......................................................................................................................................................... 5

3.3. Technical documentation of the assets.............................................................................................................. 5

3.4. Other references ............................................................................................................................................... 5

4. DESIGN BASIS ....................................................................................................................... 6

4.1. Principal Dimention ....................................................................................................................................... 66

4.2. Rencana Umum KM. SUNDALA ................................................................................................................... 6

4.3. Data Spesifikasi Ruang Akomodasi pada Main Deck .......................................................................................... 7

5. METHODOLOGY .................................................................................................................. 8

6. DETAILED CALCULATIONS AND RESULTS ................................................................ 9

6.1. Perhitungan Beban Pendinginan ....................................................................................................................... 9

6.2. Perhitungan kapasitas ruangan ....................................................................................................................... 12

6.3. Pemilihan unit refrigerasi ................................................................................................................................ 13

6.4. Pemilihan Ducting ........................................................................................................................................... 15

6.5. Perencanaan Ducting ....................................................................................................................................... 16

7. CONCLUSIONS ANDRECOMMENDATIONS ............................................................................ 16

7.1. Conclusions...................................................................................................................................................... 16

7.2. Recommendation ............................................................................................................................................ 16

2
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

LIST OF FIGURE

Gambar 4.1 Rencana Umum KM. SUNDALA ..................................................................................................... 6


Gambar 6.1 Kondukvitas thermal dari material insulasi (ASHRAE).................................................................... 9
Gambar 6.2 Pembacaan grafik untuk diameter pipa utama ........................................................................... 15

3
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

LIST OF TABLE

Table 4.1 Principal Dimention…………………………………………………………………………………………………………………………6


Table 4.2 Data spesifikasi ruang akomodasi pada main deck………………………………………………………………………….7
Table 4.3 Penentuan jumlah ABK ...................................................................................................................... 7

4
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

1. INTRODUCTION
Air Handling Unit adalah unit penanganan udara yang digunakan untuk mengatur dan
memproses udara sebelum disalurkan ke gedung atau ruangan-ruangan yang akan dikondisikan.
Dengan adanya Air Handling Unit, suhu udara di kapal dapat terkondisikan dengan baik.

KM. Sundala merupakan jenis kapal Tanker dengan jumlah ABK sebanyak 21 orang dan
dengan Panjang LPP kapal adalah 88.08 m, Tinggi kapal adalah 8 m, lebar kapal 15 m dan
tinggi sarat air adalah 7 m. Dengan menggunakan standart perhitungan yang telah ditetapkan
pada modul pendingin. Dalam laporan ini perhitungan total beban yang didapatkan dari total
beban panas transmisi, beban panas akibat panas penghuni ruangan, beban panas akibat
rambatan dari jendela, beban panas akibat penggunaan lampu penerangan,beban panas dari
peralatan yang digunakan. Setelah itu pada laporan ini juga menghitung kapasitas udara,
kebutuhan udara segar. Yang nantinya akan digunakan untuk menentukan spesifikasi
kompartmen pada AHU.

2. SCOPE OF WORKS
1. Perhitungan beban pendinginan
2. Perhitungan kpaasitas udara ruangan
3. Pemilihan unit system refrigerasi
4. Pemilihan unit refrigerant
5. Pemilihan ducting
6. Desain ducting dan penempatan AHU

3. REFERENCES
3.1. Codes
- ASHRAE
- ISO

3.2. Standards
- ASHARAE HANDBOOK 2018-Refrigeration SI
- Iso 7547-1985E

3.3. Technical documentation of the assets


- General Arrangement of KM. SUNDALA
- Material insulation of fish, meat and vegetables cool storage by 3E-Plus Software
- Compressor and Condensor Selection by Bitzer Software
- Evaporator Selection by Gunter Software

3.4. Other references


- (2018 ASHRAE HANDBOOK, n.d.)

5
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

4. DESIGN BASIS
4.1. Principal Dimention
Berikut adalah dimensi utama kapal yang digunakan untuk perhitungan beban pendingin
dan desain ruang akomodasi:

Tabel 1 Principal Dimention


Data Utama Kapal
1 Jenis Kapal = Tanker
2 Lpp = 88.08 m
3 Lwl = 91.6032 m
4 Ldisplacement = 89.8416 m
5 Lebar (B) = 15 m
6 Sarat Air (T) = 7 m
7 Tinggi Geladak (H) = 8 m
8 Kecepatan (Vs) = 11.5 knot
9 Vdisplacement = 7021.38528 mᶟ
10 Koefisien midship/Cm (β) = 0.956
11 Koefisien blok/Cb (δ) = 0.73
12 Koefisien prismatik/Cp (ϕ) = 0.745

4.2. Rencana Umum KM. SUNDALA

Gambar 4.1 Rencana Umum KM. SUNDALA

6
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

4.3. Data Spesifikasi Ruang Akomodasi pada Main Deck


Berikut adalah data dimensi setiap ruangan pada main deck . Setiap ruangan diasumsikan
memiliki 1 jendela dengan jumlah ABK 21 orang

Tabel 2 Data spesifikasi ruang akomodasi pada main deck

Parameter Design
No. Ruangan ho hi k x T1 T2 p l
t (m)
(W/m^2.K) (W/m^2.K) (W/m.K) (mm) (°C) (°C) (m) (m)
Ruang cadet 1 +
1 30 9.3 0.037 50 27 35 4.28 3.35 2.5
boys
2 Tally Office 30 9.3 0.037 50 27 35 2.90 2.35 2.5
3 Ruang fireman 30 9.3 0.037 50 27 35 4.28 3.35 2.5
Ruang oiler +
4 30 9.3 0.037 50 27 35 4.28 3.35 2.5
fireman
5 Ruang boys 30 9.3 0.037 50 27 35 4.28 3.35 2.5
6 Assistant cook 30 9.3 0.037 50 27 35 4.28 2.68 2.5
7 Ruang oiler 30 9.3 0.037 50 27 35 4.28 2.68 2.5
8 Mess room 30 9.3 0.037 50 27 35 4.28 2.68 2.5
9 Galley 9.3 9.3 0.037 50 27 35 4.28 3.00 2.5
10 Workshop 9.3 9.3 0.037 50 27 35 4.94 1.15 2.5

7
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

5. METHODOLOGY

Mulai

Studi Literatur
1. Data utama kapal KM. Jangka Bumi
2. Data jumlah ABK
3. Rute Pelayaran
Pengumpulan data 4. Data kondisi udara di dalam dan luar
ruang akomodasi kapal (ISO 7547-
1985E)

1. Beban panas transmisi


2. Beban panas penghuni
Perhitungan Beban panas 3. Beban panas jendela
ruangan 4. Beban panas lampu
5. Beban panas peralatan
6. Beban panas total

Perhitungan kapasitas udara 1. Kapasitas udara supply


ruangan 2. Kapasitas udara segar
3. Kpaasitas udara resirkulasi

Pemilihan unit refrigerasi Software


Bitzer dan
GPC

Pemilihan ducting Standard


ASHRAE

Kesimpulan

Selesai

8
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

6. DETAILED CALCULATIONS AND RESULTS


6.1. Perhitungan Beban Pendinginan
1. Ruang Cadet + Boys
A. Beban panas Transmisi (𝑄𝑇𝑟)

Gambar 6.1 Kondukvitas thermal dari material insulasi (ASHRAE)

1
𝑈 = 𝑥 1
1
+ +
ℎ𝑖 𝑘 ℎ𝑜
1
𝑈 = 50 1
1
+ +
9.3 0.037 30
𝑈 = 0.67
𝐴 = 2 𝑥 (𝑝 𝑥 𝑡 + 𝑙 𝑥 𝑡)
𝐴 = 2 𝑥 (4.28 𝑥 2.5 + 3.35 𝑥 2.5)
𝐴 = 38.2 𝑚2
∴ 𝑄𝑇𝑟 = 𝑈 𝑥 𝐴 𝑥 ∆𝑇
= 0.205 𝑘𝑊
B. Beban panas penghuni ruangan (𝑄𝑃)
Berdasarkan ASHRAE 1964 Guide and Data Book Heat Grain from People
(For Marine Air Conditioning Loads) setiap orang mengeluarkan kalor pada
berbagai kegiatan sebagai berikut:
Tabel 3 Panas dari Penghuni

9
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

Light activity (state rooms, crews, berthigs etc at 27oC .


𝑁𝑃 =2
∴ 𝑄𝑃 = 𝑁𝑝 𝑥 𝐻𝑒𝑎𝑡 𝑅𝑎𝑡𝑒/𝑝𝑒𝑟𝑠𝑜𝑛
= 2 𝑥 117
= 0.234 𝑘𝑊
C. Beban panas dari panas rambatan dari jendela (𝑄𝖶)
Berdasarkan “Draft Modul Refrigeration and HVAC” didapatkan beban panas
rambatan dari jendela yang dilengkapi dengan shading yaitu sebesar 240W/m 2 dan
diasumsikan diameter 30cm untuk keseluruhan ruangan
∴ 𝑄𝖶 = 𝐿𝑢𝑎𝑠 j𝑒𝑛𝑑𝑒𝑙𝑎 𝑥 𝑃𝑎𝑛𝑎𝑠 𝑦𝑎𝑛𝑔 𝑚𝑒𝑟𝑎𝑚𝑏𝑎𝑡
3.14
= 𝑥 0.32 𝑥 240
4

= 0.02 𝑘𝑊

D. Beban panas dari penggunaan lampu penerangan (𝑄𝐿)


Tabel 4 Panas dari Lampu

Lampu yang digunakan untuk ruang akomodasi kapal umumnya menggunakan


tipe fluorescent
𝐴 = 38.2 𝑚2
∴ 𝑄𝐿 = 𝐴 𝑥 𝐻𝑒𝑎𝑡 𝐺𝑎𝑖𝑛 𝑓𝑟𝑜𝑚 𝐺𝑒𝑛𝑒𝑟𝑎𝑙 𝐿𝑖𝑔ℎ𝑡𝑖𝑛𝑔
= 38.2 𝑥 8
= 0.305 𝑘𝑊

E. Beban panas dari peralatan yang digunakan dalam ruangan (𝑄𝑚)


Tabel 5 Beban Panas Peralatan

Beban panas dari peralatan yang digunakan dalam ruangan diambil berdasarkan pada
gambar di atas, yaitu di antara range 100-500.
∴ 𝑄𝑚 = 0.1 𝑘𝑊

10
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

F. Beban total
𝑄𝑡𝑜𝑡 = 𝑄𝑇𝑟 + 𝑄𝑃 + 𝑄𝖶 + 𝑄𝐿 + 𝑄𝑚
= 0.205 + 0.234 + 0.02 + 0.305 + 0.1
= 0.86 𝑘𝑊
Tabel 6 Beban Total Keseluruhan Ruangan

Parameter Design Beban Panas (kW)


ho hi Np HRl Beba Beban Beban Beban Total
No. Ruangan k x T1 T2 p A ΔT HRp HRj Aj HRe Beban
n
(W/m^ (W/m l (m) t (m) U (org (W/m Pengh Jendel Perala Beban
(W/m.K) (mm) (°C) (°C) (m) (m^2) (°C) (W) (W/m^2) (m^2) (W) Trans Lampu
2.K) ^2.K) ) ^2) uni a tan Panas

1 Ruang 30 9.3 0.037 50 27 35 4.28 3.35 2.5 0.6701 38.2 8 117 2 240 0.07 8 100 0.205 0.234 0.02 0.305 0.1 0.86
2 Tally Office 9.3 9.3 0.037 50 27 35 2.90 2.35 2.5 0.6384 26.3 8 117 1 240 0.07 8 100 0.134 0.117 0.02 0.210 0.1 0.58
3 Ruang 30 9.3 0.037 50 27 35 4.28 3.35 2.5 0.6701 38.2 8 117 2 240 0.07 8 100 0.205 0.234 0.02 0.305 0.1 0.86
4 Ruang oiler 30 9.3 0.037 50 27 35 4.28 3.35 2.5 0.6701 38.2 8 117 2 240 0.07 8 100 0.205 0.234 0.02 0.305 0.1 0.86
5 Ruang boys 30 9.3 0.037 50 27 35 4.28 3.35 2.5 0.6701 38.2 8 117 2 240 0.07 10 100 0.205 0.234 0.02 0.382 0.1 0.94
6 Assistant 30 9.3 0.037 50 27 35 4.28 2.68 2.5 0.6701 34.8 8 117 2 240 0.07 10 100 0.187 0.234 0.02 0.348 0.1 0.89
7 Ruang oiler 30 9.3 0.037 50 27 35 4.28 2.68 2.5 0.6701 34.8 8 117 2 240 0.07 8 100 0.187 0.234 0.02 0.278 0.1 0.82
8 Mess room 30 9.3 0.037 50 27 35 4.28 2.68 2.5 0.6701 34.8 8 117 8 240 0.07 8 250 0.187 0.936 0.02 0.278 0.3 1.67
9 Galley 30 9.3 0.037 50 27 35 4.28 3.00 2.5 0.6701 36.4 8 117 2 240 0.07 8 100 0.195 0.234 0.02 0.291 0.1 0.84
10 Workshop 30 9.3 0.037 50 27 35 4.94 1.15 2.5 0.6701 30.5 8 117 3 240 0.07 8 100 0.163 0.351 0.02 0.244 0.1 0.87
26 Jumlah 9.18

11
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

6.2. Perhitungan kapasitas ruangan


1. Ruangan Cadet + Boys
A. Kapasitas Udara Supply (𝑉𝑠) Tiap Ruangan pada Main Deck
𝑄𝑡𝑜𝑡 = 0.86 𝑘𝑊
𝑘𝐽
𝐶𝑝 = 1.025
𝑘𝑔. °𝐶
𝜌 = 1.2 𝑘𝑔/𝑚3
∆𝑇 = 8°𝐶
𝑄𝑇𝑟
∴ 𝑉𝑠 =
𝐶𝑝 𝑥 𝜌 𝑥 ∆𝑇
0.86
=
1.025 𝑥 1.2 𝑥 8
3
= 314.88 𝑚

= 87.468 𝑙/𝑠
B. Kebutuhan Udara Segar (𝑉𝑓𝑎)

Tabel 7 Kebutuhan Udara Segar pada Beberapa Negara

𝑉𝑓𝑎 = Kebutuhan Udara Segar x Jumlah orang


= 17 𝑚3/ℎ/𝑝 𝑥 21 𝑜𝑟𝑎𝑛𝑔
= 611 𝑚3/ℎ
= 169.72 𝑙/𝑠

C. Kebutuhan Udara Resirkulasi (𝑉𝑟)


𝑉𝑟 = 𝑉𝑠 − 𝑉𝑓𝑎
= 761.992628 𝑙/𝑠

12
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

6.3. Pemilihan unit refrigerasi


A. Enthalpy Udara Campuran (ℎ𝑚𝑖𝑥)
Berikut adalah data suhu dan kelembaban udara pada setiap titik dengan kondisi tekanan 1
atm
Tabel 8 Kondisi udara ruangan

T fresh air 35°C


T evaporator 11°C
T ruangan 27°C
RH fresh air 70%
RH evaporator 50%
RH ruangan 50%
Kemudian dilakukan perhitungan nilai enthalpy dan volume spesifik udara menggunakan
software EES
Tabel 9 Nilai enthalpy dan volume spesifik udara campuran

h fresh air 100,7 kJ/kg


h ruangan 55,99 kJ/kg
h evaporator 21,43 kJ/kg
v fresh air 0,9208 m^3/kg
v evaporator 0,821 m^3/kg
v ruangan 0,8772 m^3/kg
𝑉𝑓𝑎 𝑉
[( )ℎ +( 𝑟)ℎ ]
𝑣𝑓𝑎 𝑓𝑎 𝑣𝑟 𝑟
∴ ℎ𝑚𝑖𝑥 = 𝑉𝑓𝑎 𝑉𝑟
[( 𝑣 ) + ( ) ]
𝑓𝑎 𝑣𝑟
= 61.6 𝑘𝐽/𝑘𝑔
B. Beban panas akibat pernapasan manusia
(𝑁𝑃 𝑥 𝑄𝑃)
∆ℎ𝑒 =
𝑉𝑠 𝑥 𝜌
= 1,86 𝑘𝐽/𝑘𝑔
C. Perhitungan kpaasitas beban pendingin (𝑄𝐿)
𝑄𝐿 = 𝑉𝑠 𝑥 𝜌 𝑥 ∆ℎ
Dimana
𝑉𝑠 = Kapasitas udara dingin yang disupplai ke dalam ruangan (m^3/h)
𝜌 = Density udara rata-rata pada tekanan atmosfer (kg/m^3)
∆ℎ = jumlah perbedaan enthalpy antara udara yang masuk evaporator (ℎ𝑚𝑖𝑥) dan sesudah
evaporator (kJ/kg) dengan enthalpy yang harus diturunkan untuk mengimbangi penambahan
RH dalam ruangan yang disebabkan adanya uap air dari nafas penghuni (∆ℎ𝑒).
13
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

∴ 𝑄𝐿 = 47,08 𝑘𝐽/𝑠
= 47,08 kW
Berdasarkan hasil kapasitas beban pendingin yang sudah didapat, yaitu 62.741 kW, maka unit
yang dipilih yaitu sebagai berikut :
a) Kondensing Unit
Unit Type : LH135E/6HE-28Y-40P
Refrigeran : R134a
Capacity steps : 100%
Cooling capacity : 62.7 kW
Evaporator capacity : 62.7 kW
Power input : 24 kW
Current (400V) : 40.8 A
Voltage range : 380 - 420 V
Mass flow : 1860 kg/h

b) Evaporator
Unit type = GACV RX 090.1LF/1A-40.A-1876.1HBM
Cooling capacity = 62.7 kW
Refrigeran = R134a
Evaporation temp = 11°C
Superheating = 5°C
Cond. temp = 51°C
Subcooled temp = 46°C
Air Inlet = 19°C
Air Outlet = 13.7°C
Air Pressure = 1013 mbar
Air flow = 25608 m^3/hr

14
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

6.4. Pemilihan Ducting


Berikut ini adalah pemilihan ducting berdasarkan ASHRAE, dengan cara membaca diagram
untuk penentuan diameter. Untuk penentuan pipa utama dengan menggunakan kapasitas
udara total semua ruangan, sedangkan untuk penentuan pipa cabang dengan menggunakan
kapasitas udara di tiap-tiap ruangan.

Gambar 6.2 Pembacaan grafik untuk diameter pipa utama

Setelah dilakukan penentuan diameter dari pembacaan grafik, kemudian dilakukan


penentuan dimensi ducting

15
AIR HANDLING UNIT DETAIL DESIGN Prep. : NDH
Calculation Reports And Drawings
Chk. : GEK
Document No. : ME4320A-2 Revision : 0 Date : App. : MAM

Dari Pembacaan grafik dan tabel, dapat ditentukan untuk dimensi ducting yaitu sebesar 300 x
450 mm

6.5. Perencanaan Ducting

7. CONCLUSIONS ANDRECOMMENDATIONS
7.1. Conclusions
Berdasarkan perhitungan system pengkondisian udara pada KM. SUNDALA, maka dapat disimpulkan
sebagai berikut :

1. Didapatkan beban panas total sebesar


2. Kapasitas udara suplai total sebesar l/s atau setara dengan m3/hr
3. Kebutuhan udara segar yaitu sebesar
4. Kebutuhan udara resirkulasi yaitu sebesar
5. Condensing unit yang digunakan yaitu Bitzer tipe
6. Evaporator yang digunakan yaitu Guntner tipe

7.2. Recommendation
Pemilihan unit refrigerasi dapat mempertimbangkan harga setiap unit agar dapat t ercipta
system pengkondisian udara yang efisien baik dari segi kerja unit maupun segi ekonomis.