Professional Documents
Culture Documents
Brevik Documentation
Brevik Documentation
Brevik Documentation
Table of contents
1. CE documentation
2. Safety assessment
Børresen Cooltech AS
Rosenholmveien 13, Postboks 130 Holmlia N-1203 OSLO
Telefon: 2316 9400 Faks 2316 9401
Label to be found on unit
0435
Postboks 130, Holmlia
1203 Oslo Norway
Tlf.: 23 16 94 00
Faks.:23 16 94 01
Serialnumber: 100341
Production
year:
2009
Relief valve setting:
24,8 Bar
Design
pressure:
25,0 Bar
Test
pressure:
28,0 Bar
Coolant: R-407C
Compressor
oil :
32FC
Børresen Cooltech AS
Rosenholmveien 17
Postboks 130 Holmlia
Tel. +47 23 16 94 00
Fax. +47 23 16 94 01
N-1203 Oslo, Norway
Company no NO 918,890,025 MVA
Customer: _______________________________
Units address: _______________________________
Operator/Fitter: _______________________________
Date of startup: ______________
Safety mechanism:
S. mech. 1 S. mech. 2 S. mech. 3 S. mech. 4
Frost monitor
LP/HP pressostat
Flow switch
Diff. press. monitor
Other
Other
Visual check: ______
Leakage check: ______ Abnormal vibrations : __________
2. Safet assessment
Børresen Cooltech AS
Rosenholmveien 13, Postboks 130 Holmlia N-1203 OSLO
Telefon: 2316 9400 Faks 2316 9401
Safety assessment
Refrigerant: HFC
Oil: Ester
Pipe material: Cu
• Read instructions carefully. Consistent adherence to the procedures is vital for operator
safety, performance and operation.
• Avoid skin contact with the refrigerant due to extremely low boiling point (-50 - -25 °C)
which can cause frostbite.
• Always wear goggles and gloves when working with the refrigerant or performing
maintenance. Avoid contact with the refrigerant – can cause blinding or other
injuries.
• Keep well away from naked flames or hot surfaces: high temperatures break the
refrigerant down and release contaminants which are dangerous to the environment
and to personnel.
• Do not allow refrigerant to be released into the atmosphere during maintenance. This is
not only due to international environmental legislation, but also to avoid problems
identifying leaks in a heavily polluted atmosphere.
• Do not adjust settings on valves unless 100% sure of the consequences. Trapped
liquids can cause extreme pressure increase, with dangerous consequences.
• Check that characteristics of the electric current match those of the compressor.
• Before starting compressor, check suction and pressure cocks are fully open and that
connection box cover is fitted.
• Unscrew compressor and disconnect power before removing connection box cover.
• Compressor must always be correctly connected and protected with an earthed power
cable.
• Do not touch compressor until it has been out of operation for an extended period. The
operating temperature can reach 100oC, and it must be allowed to cool.
• Do not touch the pressure pipes until the compressor has been out of operation for an
extended period, as they can have a surface temperature of over 100°C
• Maintenance procedures can only be performed under the direct and continuous
supervision of the operator.
2.1 Guide to safe use of compressor units (safety
assessment)
Before reading this point, all the above points must have been read. All work,
adjustments and repairs made shall be performed by trained specialists in this type of
unit.
2.1.4 Fire
The refrigeration unit is a pressurised system, in which pressure varies significantly
with the temperature. In the event of a fire in the vicinity of the unit, it should be
stopped and allowed to cool down. If the pressure exceeds 26 bars, the safety valve
will activate releasing the refrigerant to relieve the pressure. Refrigerant coming in
contact with flames or very high temperatures can fissurise and cause highly toxic
gases. Always be aware of where the discharge from the safety valves is directed to
avoid risk of suffocation and poisoning.
2.1.5 Noise
The refrigeration unit compressors will produce a lot of noise when operating. Ear
defenders must therefore be worn when in the room or in the vicinity.
2.1.6 Vibrations
The compressors are balanced to give minimum vibration in the unit. Some vibration
can still occur. Major vibration is a sign of abnormal operation or fault in the system.
Vibrations and temperature changes can cause screws to loosen. If clamps, screws
etc loosen, they must be tightened again to avoid damage to components and danger
to personnel.
2.1.7 Operation
The unit operates at a pressure of 1.5 to 10bar. When stopped, the pressure will
stabilise in the entire unit at approx. 4 - 7 bar. Always bear this in mind whenever
operating or working on the unit. Trapped liquid (e.g. between two valves causing a
pocket) can cause the pressure to exceed the unit's safety level, and parts involved
can burst as if they explode. Do not touch any valves without being 100% sure of the
consequences. Normally operation of the unit should make the formation of pressure
pockets impossible, due to design and choice of components.
Always lift frame with forks between the feet. See figure below.
Two trolley jacks inserted in parallel are needed to move large frames.
Always keep sufficient distance from ceiling!
3. Prosedyrer og sertifikater
Børresen Cooltech AS
Rosenholmveien 13, Postboks 130 Holmlia N-1203 OSLO
Telefon: 2316 9400 Faks 2316 9401
Starting and maintenance
procedures for compressor units
Safety precautions
• Read instructions carefully. Consistent adherence to the procedures is vital for operator
safety, performance and operation.
• Avoid skin contact with the refrigerant. due to extremely low boiling point (-50 - -25 °C) which
can cause frostbite.
• Always wear goggles and gloves when working with the refrigerant or performing
maintenance. Avoid contact with the refrigerant – can cause blinding or other injuries.
• Keep well away from naked flames or hot surfaces: high temperatures break the refrigerant
down and release contaminants which are dangerous to the environment and to personnel.
• Do not allow refrigerant to be released into the atmosphere during maintenance. This is not
only due to international environmental legislation, but also to avoid problems identifying
leaks in a heavily polluted atmosphere.
• Check that characteristics of the electric current match those of the compressor.
• Before starting compressor, check suction and pressure cocks are fully open and that
connection box cover is fitted.
• Unscrew compressor and disconnect power before removing connection box cover.
• Compressor must always be correctly connected and protected with an earthed power cable.
• Do not touch compressor until it has been out of operation for an extended period. The
operating temperature can reach 100oC, and it must be allowed to cool.
1
1. Introduction to FRASCOLD semi-hermetic compressor
Børresen Cooltech supplies a range of modern products with high performance for
refrigeration and air conditioning. These include single phase semi-hermetic piston
compressors from Frascold. These are available in 70 different models in 9 ranges, which
differ in design, with cylinder displacement (at 50 Hz) from 3.95 m3/h up to 205.80 m3/h and
refrigeration capacity from 200 W to 280,000 W.
For more details, request the commercial product catalogue ”FRASCOLD semi-hermetic
compressors”.
1.1 Name plate
Every compressor has a type plate with details of the machine.
1.2 Protection
Compressors in A-, B-, D-, F-, Q-, S-, V-, Z- and W- series are fully equipped with
integrated protection in accordance with DIN44081. A PTC thermistor is located in the
electric motor stator, connected to a KRIWAN electronic control module (model INT69 for
A-, B-, D-, F-, Q- and S series, model INT69TM for V-, Z-, and W series). The INT69TM
module has period delay which only permits startup of the compressor at least 5 minutes
after stop. This prevents the period between start and stop being too short. All compressors
with single phase motors have electrothermic protection. S series compressors can be fitted
with a temperature sensor fitted direct on the cylinder head pressure side upon request. This
will be connected in series with the PTC thermistor, has automatic reset and is calibrated to
140oC. The compressor will stop when the temperature reaches a critical value.
Temperature sensors are standard on V-, Z-, and W series.
NB! The box contains a complete gasket set for pressure and suction cocks.
The terminal board for power supply is complete with jumpers and nuts.
When connecting the compressor,”2.3 Electrical connections" must be followed.
1.4 Lubrication
A-, B-, D-, F-, Q- and S series compressors are lubricated by a rotating disc which spreads
oil (splash lubrication), whilst V-, Z-, and W series are lubricated by a high pressure oil
pump. All compressors with oil pumps are complete with oil filter and connections for
measuring pump pressure. We recommend installing a differential oil monitor to protect the
compressor against damage due to poor lubrication.
2
1.5 Lubricating oil
All FRASCOLD compressors are supplied filled with lubricating oil. Oil type and viscosity
depend on refrigerant and evaporation temperatures which the compressor is expected to
work at.
The letter Y at the end of the model designation indicates that the compressor is filled with
ester oil. For example:
D 3 16 compressor is filled with mineral- or semi-synthetic oil.
D 3 16 Y compressor is filled with ester oil.
The same oil type must always be used when changing oil,
or another type approved by FRASCOLD.
Always release the pressure by opening the service cocks carefully before working on
the machine.
2. Installation
2.1 Secure unit to floor
The unit must be installed on a perfectly level surface to ensure correct lubrication of moving
parts, and will ensure that the compressor works without undue stress.
Always release the pressure by opening the service cocks carefully before working on
the machine.
When replacing parts in the refrigeration unit, braising is often required. Refrigerant
circulation will be reduced if foreign objects are left in the circuit. Atmospheric pressure and
damp entering during fitting work can be removed by vacuuming (see ”3. Vacuuming and
filling with refrigerant”). Removing impurities formed during braising on the other hand is a
more difficult and expensive operation. The size of such impurities is so small that they can
pass the filters installed in the pipe system. During connection of the refrigerant circuit and
servicing, we recommend taking every precaution to prevent impurities. In addition to
elementary precautions with regard to cutting pipes, avoid excessive use of flux, and if
possible use dry nitrogen or other inert gases in the pipes during braising. To avoid damaging
the inner parts of cocks or equipment due to overheating during braising, we recommend
removing the cock or the connection (by removing the gasket) and protecting the cock with a
wet cloth. See also the special fitting instructions for each component.
3
2.3 Electrical connections
Electrical connections must comply with the wiring diagram in the manual, and with safety
rules for the installation area. Applicable rules in the EU are EN60204 (Electrical apparatus
for industrial machinery – general requirements) and EN60355 (Safety for electrical
instruments for domestic use or the like – special requirements for compressors). For correct
connection, see wiring diagram on inside of connection box cover.
Electrical connections must be performed by a qualified operator.
a) remove connection box cover
b) slacken nuts if necessary. Replace or remove jumpers as indicated; the three jumpers
connected for direct start of compressor, as for the last factory test.
Incorrect electrical connection can cause short-circuit or anti-phase and
thereby fire in the motor.
c) insert a suitable PG nipple in the holes in the connection box to achieve the original
protection level
d) connect power source for connection box using the correct insulated cables and cable
contacts for the terminals
e) tighten screws to following torque moment
Connection box – torque moment________
screw dimensions M4 M6
Torque moment Nm 5 10
f) once the cover is removed, secure protection equipment for control system and
protection circuit according to wiring diagram.
Do not apply power direct to terminals A and B connected to PTC thermistors
g) replace cover for protection equipment and connection box.
NB. If the compressor has an oil heater, it must be connected so that it can be switched
on manually at least 2 hours before starting the compressor after a long period of
inactivity, and under normal working conditions when the compressor will not start.
NB. The compressor's nominal output is not equivalent to maximum input for its
electric motor.
4
3.1 Filling refrigerant
Refrigerant is filled as a liquid on the high pressure side using flexible hoses, which
have previously been vacuumed to avoid non-condensable gases. If the cylinder used
for filling has no hose, we strongly recommend using a suitable dry filter installed between
cylinder and connection point on the refrigerant circuit. These precautions will prevent any
impurities in the cylinder or the flexible hoses getting into the refrigerant circuit.
We recommend turning up the oil heater full before filling refrigerant to prevent condensation
in the lubricating oil.
Filling on the high pressure side prevents liquid refrigerant reaching the compressor
crankcase and diluting the lubricating oil there. Refrigerant added closes the compressor
pressure valve (acts as a non-return valve). The refrigerant expands through the thermic
valve and reaches the compressor suction cock as vapour.
Filling can be speeded up if the refrigerant is warmed up (and therefore at higher pressure)
in the cylinder, but for safety reasons, the cylinder temperature must never exceed
+40oC. To maintain a constant temperature during filling, we recommend submerging the
cylinder in warm water, or using a suitable heater tape with thermostat.
Never heat the cylinder with braiser flames or naked flames in general.
5
4.2 Measuring supply voltage
Supply voltage must be within the tolerance margin (+/- 10% of nominal voltage). This applies
not only when running, but also during startup, when power consumption is at its highest. The
voltage drop which occurs when the compressor starts (often due to too narrow power cables)
must not exceed 4% (minimum startup voltage = normal voltage - 4%).
In the event of abnormal noise and vibration during startup, stop compressor
immediately, identify and correct cause.
Measurement of operating current is performed at the same time as reading off operating
pressure. The value measured must be less or equivalent to the stated value from Frascold
(see ”1.1 Type plate”). Higher values can be due to imbalance in the voltage between
phases, insufficient refrigerant or incondensable gas in the refrigerant.
Do not pollute the environment with oil. Refer to applicable legislation and regulations
for disposal.
7
Shell and tube marine condensers M
Advanced
Heat Transfer Solutions
Advanced Heat Transfer Solutions
MATERIALI MATERIALS
La costruzione standard dei condensatori marini a fascio tubiero Standard type construction of type “M” series shell & tube con-
serie “M” prevede l’utilizzo dei seguenti materiali: densers comprise:
testate: acciaio al carbonio rivestite internamente con rivesti- headers: carbon steel with protective sea water resistant coa-
mento resistente all’acqua di mare ting
collare: SBR ring: SBR
piastre tubiere: acciaio al carbonio con rivestimento resistente tubesheets: carbon steel with protective sea water resistant
all’acqua di mare coating
mantello: acciaio al carbonio shell: carbon steel
connessioni refrigerante: acciaio al carbonio refrigerant connections: carbon steel
tubi: lega CuNi 90/10 tubes: CuNi 90/10 alloy
viti: acciaio legato screws: steel alloy
Altri materiali possono essere utilizzati su richiesta purchè compatibili Alternative materials are available within our production facilities and
con le nostre capacità produttive. can be supplied on request.
Su richiesta inoltre possono essere eseguiti condensatori di potenza Other condensers with higher capacity and different number of passes
superiore e con numero di passi diverso dallo standard. can be also manufactured.
A tal fine prego contattare L’Ufficio Commerciale Onda S.p.A. Please contact Onda S.p.A Sales Department.
LEGENDA / NOMENCLATURE
REV. 1.0
CONSIGLI PER UNA CORRETTA SELEZIONE CORRECT SELECTION PROCEDURE
Il fattore di sporcamento (f.f.) è un elemento fondamentale per il Use of the correct fouling factor (f.f.) is essential for a correct selection
dimensionamento di un condensatore, si suggerisce quindi di adottare il of water cooled condensers. Onda suggests use of the following value
seguente valore al fine di eseguire una corretta selezione: in order to obtain the right selection:
Si consiglia inoltre di mantenere la velocità dell‘acqua all’interno dei It is recommended to limit water velocity inside tubes between 1,0 and
tubi nell’intervallo compreso tra 1,0 e 2,2 m/s. 2,2 m/s.
REV. 1.0
3
Un’azienda tecnologica basata sulla qualità
S:
Piastre saldobrasate
Brazed plate heat exchanger
SCIROCCO:
Raffreddatori
Liquid coolers
Shell and tube marine condensers M
attacco di servizio
service connection
7
Shell and tube marine condensers
M
REV. 1.0
M
MODELLO / MODEL M 168 210 252 315 418 514 660 751
kW 168 210 252 315 418 514 660 751
Potenza / Capacity
Tons (RT) 47,8 59,7 71,6 89,5 118,8 146,1 187,6 213,5
Portata / Flow rate m3 / h 29,1 36,4 43,6 54,5 72,3 89,0 114,2 130,0
DP / Pressure drop kPa 20,7 21,4 22,3 24,0 22,1 20,8 22,0 23,0
Portata Max / Max Flow Rate m /h
3
35,2 44,0 52,8 66,1 88,1 108,7 139,5 158,6
Passi / Passes n 2 2 2
Peso / Weight kg 205 223 240 267 385 523 585 624
d1 ODS 54 OD 76 OD 88,9
Connessioni refrigerante
d2 ODS 42 ODS 54 OD 76
Refrigerant connections
d3 1” NPT 1” NPT 1” NPT
Connessioni acqua Per posizioni e tipologia vedere tabella a pagina 10
Water connections See table on page 10 for position and type
REV. 1.0
9
Connessioni / Connections
Diametro / Diameter
mm 220 240 320 370 460
D
Passi / Passes 4 4 2 4 2 2
Figura / Figure A A B A B B
X 35 40 53
40 40 60
Y - - -
mm
Z
40 45 60 60 75 90
K
IN (diametro / diameter) G 1 1⁄4” G 1 1⁄2” DN 80 (*) G 2 1⁄2” DN 100 (*) DN 125 (*)
OUT (diametro / diameter) G 1 1⁄4” G 1 1⁄2” DN 80 (*) G 2 1⁄2” DN 100 (*) DN 125 (*)
(*) Attacco Victaulic / Victaulic Connections
ODS ID OD
mm inch mm mm inch
14 - 14,2 17,3 3
/8”
18 - 18,2 21,3 1
/2”
22 - 22,3 26,9 3
/4”
28 - 28,3 33,7 1
35 1” 3/8 35,3 42,4 1” 1/4
42 - 42,3 48,3 1” 1/2
54 2” 1/8 54,3 60,3 2”
64 - 64,4 76,1 -
67 2” 5/8 67,5 76,1 -
70 - 70,5 76,1 (*) -
82 - 82,5 88,9 3”
89 - 89,5 101,6 3” 1/2
100 - 100,5 114,3 4”
(*) Versione standard nei modelli M 418 - 751 / Standard version for M 418 - 751 model
28 - 28,2
REV. 1.0
Ricambi / Spare parts
diametro / diameter D
modello / model passi / passes codice / code
mm
anteriore / front F8013005
4 220
posteriore / rear F8013015
anteriore / front F8013105
4 240
posteriore / rear F8013115
anteriore / front F8013205
2
posteriore / rear F8013215
320
anteriore / front F8013225
4
posteriore / rear F8013235
anteriore / front F8013305
2 370
posteriore / rear F8013315
anteriore / front F8013405
2 460
posteriore / rear F8013415
Il kit testata anteriore comprende: Chiusura + collare + viti di chiusura / Front header kit includes: Cover + ring + screws
Il kit testata posteriore comprende: Chiusura + anodi + collare + viti di chiusura / Rear header kit includes: Cover + anodes + ring+ screws
REV. 1.0
11
Accessori su richiesta
Accessories on request
KIT SPIE DI LIQUIDO / SIGHT GLASSES KIT
SG4 OD x ID = 90 x 48 F7020004
SGR 5 RTLK 1” /4 UNF
1
OD x ID = 40 x 18 F7020003
SGR 7 RTLK 1” 3/4 UN OD x ID = 55 x 28 F7020002
STAFFE / SUPPORTS
M 31 ÷ M 112 S2500205
M 150 ÷ M 670 S2500206
ID
Tipo / Type codice / code
mm
14,2 M4100011
RTLK 1’’ UNS 16,2 M4100012
18,2 M4100013
22,2 M4100021
RTLK 1” 1/4 UNF
28,2 M4100022
28,2 M4100030
RTLK 1” /4 UN
3 35,2 M4100031
42,2 M4100032
REV. 1.0
COLLETTORE USCITA REFRIGERANTE / COLLECTING PIPE FOR REFRIGERANT OUTLET
Dimensioni / Dimensions mm
Materiale / Material ODS Codice / Code
L1 L2 L3
Rame / Copper 18 800 ~50 ~15 S1240005
Rame / Copper 22 800 ~50 ~15 S1240010
Rame / Copper 35 800 ~80 ~30 S1240015
acciaio al carbonio / carbon steel OD 48,3 1900 ~75 ~60 S1240020
acciaio al carbonio / carbon steel OD 60,3 1700 ~90 ~65 S1240025
acciaio al carbonio / carbon steel OD 76,1 1700 ~110 ~75 S1240030
REV. 1.0
13
Accessori su richiesta
Accessories on request
Flangia / Flange ODS ID OD
mm mm inch mm mm inch
22 7
/8 ” 22,5 27 3
/4 ”
70 x 70 28 1” 1/8 28,9 34 1”
35 1” 3/8 35,3 42 1” 1/4
28 1” 1/8 28,9 34 1”
35 1” 3/8 35,3 42,5 1” 1/4
75 x 75
42 - 42,3 48 1” 1/2
42 1” 5/8 41,7 48 1” 1/2
28 1” 1/8 28,9 34 1”
35 1” 3/8 35,3 42,5 1” 1/4
90 x 90
42 - 42,3 48 1” 1/2
54 2” 1/8 54,5 61 2”
54 2” 1/8 54,5 61 2”
100 x 100 64 - 64,4 76 -
67 2” 5/8 67,2 76 -
54 2” 1/8 54,5 61 2”
64 - 64,4 76 -
120 x 120 67 2” 5/8 67,2 76 -
76 - 76,5 82,5 -
80 3” 1/8 80,4 90 3”
diametro mantello
shell diameter A1 Flangia / Flange ODS ID OD B1
B
mm mm mm mm mm mm mm mm mm
22 7
/8 ” 22,5 27 3
/4 ”
273 Ø 99 70 x 70 28 1 ” 1/8 28,9 34 1” 85
35 1 ” 3/8 35,3 42 1
/4 ”
28 1 ” 1/8 28,9 34 1”
35 1 ” 3/8 35,3 42,5 1” 1/4
273 / 324 Ø 106 75 x 75 85
42 - 42,3 48 1” 1/2
42 1 ” 5/8 41,7 48 1” 1/2
28 1 ” 1/8 28,9 34 1”
35 1 ” 3/8 35,3 42,5 1” 1/4
Ø 127 90 x 90 88
42 - 42,3 48 1” 1/2
54 2 ” 1/8 54,5 61 2”
54 2 ” 1/8 54,5 61 2”
Ø 141 100 x 100 64 - 64,4 76 - 87
324 / 406 67 2 ” 5/8 67,2 76 -
54 2 ” 1/8 54,5 61 2”
64 - 64,4 76 -
Ø 170 120 x 120 67 2 ” 5/8 67,2 76 - 86
76 - 76,5 82,5 -
80 3” 1/8 80,4 90 3”
Ø 170 Ø 170 - - - 114,3 4” 92
406 Ø 190 Ø 190 - - - 141,3 5” 92
REV. 1.0
GARANZIA WARRANTY
A - ONDA S.p.A. garantisce l’assenza di vizi e difetti nella lavorazione e nei A - ONDA S.p.A. warrants that the Products shall be free from defects in material
materiali dei propri Prodotti per 18 mesi dalla data della consegna. and workmanship for a period of 18 months from the date of the delivery.
Pertanto ove, durante il periodo di garanzia, gli eventuali difetti dei prodotti Therefore, should ONDA S.p.A., within the warranty period, acknowledge
risultino oggettivamente fondati e siano riconosciuti per iscritto da ONDA and recognise in writing the existence of the defects in the products and said
S.p.A., quest’ultima provvederà gratuitamente alla riparazione o, a sua defects be materially grounded, ONDA S.p.A. shall, at its discretion, repair the
discrezione, alla sostituzione dei Prodotti difettosi, con consegna effettuata defective Products at no costs for the Client or replace them by delivering the
franco fabbrica (Ex Works – Incoterms 2000). substitutive products Ex works (Incoterms 2000) at ONDA S.p.A.’s premises.
Stabilimento di ONDA in via Lord Baden Powell, 11 – 36045 Lonigo (VI). ONDA’s facilities located at via LORD Baden Powell, 11 – 36045 Lonigo (VI).
B - Pena di decadenza dalla garanzia, il Cliente dovrà comunicare per iscritto, B - Subject to loss of the warranty, notice of any defect shall be given by
a mezzo raccomandata con ricevuta di ritorno, i vizi o i difetti riscontrati entro the Client in writing with return receipt registered letter within, and not later
e non oltre 10 (dieci) giorni dal ricevimento dei Prodotti presso la sede del than, 10 (ten) days from the date of receipt of the products at the Client’s
Cliente o altro luogo da questi indicato o, trattandosi di vizi e/o difetti occulti, premises or in the different delivery place, previously indicated by the latter.
entro e non oltre 10 (dieci) giorni dalla scoperta degli stessi. In questo caso, Subject to loss of the warranty, notice of any latent defect of the Products by
l’onere della prova della data della scoperta graverà sul Cliente. the Client shall be given in writing, by return receipt registered letter, within
and not later than 10 (ten) days from the date of the relevant discovery. It is
C - ONDA S.p.A. garantisce inoltre che i Prodotti sono fabbricati in conformità hereby understood that the burden of the proof of the date of the discovery
alle leggi italiane e alle normative comunitarie vigenti alla data di conferma shall be borne by the Client.
da parte di ONDA S.p.A. del relativo ordine del Cliente.
Salvo diverso accordo scritto tra le parti, tutte le altre spese accessorie agli C - ONDA S.p.A. also warrants that the Products are manufactured in
interventi di sostituzione e/o di riparazione, saranno a carico e a rischio del compliance with the Italian and European Laws and Regulations in force on
Cliente. the date of the confirmation by ONDA S.p.A. of the relevant Client’s order.
Unless otherwise expressly agreed in writings by the parties, Client shall
D - La garanzia è esclusa qualora i vizi o difetti dei Prodotti siano stati bear any other additional expenses related to the operations of repairing or
determinati dalle seguenti cause: replacing of the defective products.
- naturale usura e deterioramento;
- riparazioni o modifiche non autorizzate; D - This warranty shall not apply should the defects of the Products be caused by:
- uso e applicazione impropri; - natural wear and tear;
- eccessiva sollecitazione termica, anche occasionale; - unauthorised repairs or modifications;
- eccessiva sollecitazione elettrica o meccanica; - unsuited use or application;
- mancato rispetto dei parametri funzionali e ambientali indicati da ONDA - thermal overexposure, also when occasional;
S.p.A. per il corretto impiego e funzionamento dei Prodotti; - electrical or mechanical over-stress;
- installazione dei Prodotti difforme da quella indicata nelle specifiche - failure of respecting the functional and environmental parameters suggested
tecniche fornite da ONDA S.p.A.; by ONDA S.p.A. for the correct use and exploitation of the products;
- qualsiasi altra causa imputabile a negligenza del Cliente. - installation of the products not in compliance with the technical
specifications provided by ONDA S.p.A.;
E - La garanzia è inoltre esclusa in caso di: - any other cause due to the Client’s negligence or to occasional faults of the
- eventuale non conformità dei Prodotti a leggi e/o normative in vigore products as consequence of mass-production procedures.
nel luogo in cui i Prodotti sono installati e/o assemblati dal Cliente e/o
nel luogo di finale utilizzazione dei Prodotti, qualora il Cliente non abbia E - This warranty shall also not apply in case of:
espressamente richiesto la conformità dei Prodotti a tali leggi e/o normative - non compliance of the Products with Laws and/or Regulations in force in
e non abbia regolarmente informato ONDA S.p.A. del loro contenuto prima the place where the Products are installed and/or assembled by the Client
della data di trasmissione della conferma d’ordine di quest’ultima. and/or in the place of their final use, should the Client not expressly require
- Resta inteso che la presente limitazione si intende efficace anche con the conformity of the Products to said Laws and Regulations and not duly
riferimento a specifiche normative vigenti in Stati dell’Unione Europea ed inform ONDA S.p.A. of their content before the date of transmission of the
applicabili in via autonoma rispetto alle normative comunitarie. latter’s order confirmation.
- This limitation of the warranty is also applicable with reference to peculiar
F - In caso di eventuale non conformità dei Prodotti a leggi e/o normative Laws and Regulations valid and binding in States of the European Union
italiane e/o estere entrate in vigore dopo la data della trasmissione della independently of the European Laws and Regulations.
conferma d’ordine di ONDA S.p.A. è esclusa la sostituzione in garanzia dei
Prodotti o il loro eventuale adeguamento in garanzia alle nuove normative. F - In the case of non compliance of the Products with Italian and/or foreign
ONDA S.p.A declina, comunque, ogni responsabilità riguardo l’utilizzo di Laws and/or Regulations entered in force after the date of transmission of
Prodotti non conformi a leggi e/o normative italiane e/o estere entrate in the order confirmation by ONDA S.p.A., the replacement or any possible
vigore dopo la data della trasmissione della relativa conferma d’ordine di adjustment under warranty conditions will not be applied.
ONDA S.p.A.. ONDA S.p.A. is, at any rate, not responsible for the use of the Products not
conform to Italian and foreign Laws and/or Regulations entered in force after
G - Il Cliente non dovrà vendere o commercializzare Prodotti non conformi the date of transmission of their order confirmation by ONDA S.p.A..
alle leggi e/o normative indicate nella precedente lettera E-F. In caso
contrario, il Cliente solleverà ONDA S.p.A. da ogni danno e/o perdita G - The Client shall not sell or market Products not in compliance with the
dalla stessa sofferto in seguito a contestazioni, sollevate in via giudiziale Laws and Regulations mentioned under letter E-F above. In the negative,
o stragiudiziale, da qualsiasi soggetto terzo o da pubblica autorità in the Client shall keep ONDA S.p.A. harmless of any damage or loss suffered
conseguenza della fabbricazione da parte di ONDA S.p.A. di prodotti non by the latter, due to any third party’s and/or authority’s claim raised as
conformi alle summenzionate leggi e/o normative. a consequence of the manufacture by ONDA S.p.A. of Products not in
compliance with the above mentioned Laws and Regulations.
H - Ferma restando l’applicazione del DPR 224/1988, in materia di
responsabilità per danno da prodotti difettosi, e la responsabilità di H - Without prejudice to the application of DPR 224/1988 on product liability
ONDA S.p.A. in caso di dolo o colpa grave, quest’ultima non sarà in alcun and liability for gross negligence or wilful misconduct, ONDA S.p.A. shall
caso responsabile per i danni diretti, indiretti o incidentali che dovessero never be liable for direct, indirect or occasional damages which in any
in qualsiasi modo derivare dalla difettosità dei Prodotti. manner derived from defective products.
REV. 1.0
15
REVISIONE 1.0 del 26/01/2005
Onda spa
via Lord Baden Powell, 11 - 36045 Lonigo (VI) Italy
Tel. +39 0444 720 720 Fax +39 0444 720 721
www.onda-it.com - e-mail: onda@onda-it.com
Shell and tube evaporators
MPE
Potenza totale = somma di tutti i circuiti / Total capacity = sum total of all circuits
PESO / WEIGHT kg 34 39 44 48 53 60 65 70
Temperatura entrata acqua / Inlet water temperature +12°C Temperatura di evaporazione / Evaporation temperature +2.5 °C
DATI NOMINALI
NOMINAL DATA R 407C Temperatura uscita acqua / Outlet water temperature +7°C Temperatura di condensazione / Condensation temperature +45 °C
MPE
MPE 180÷390
MODELLO / MODEL MPE 121 137 160 180 230 300 335 390
Potenza totale kW 121 137 160 180 280 300 335 390
Total capacity Tons (RT) 34,4 39,0 45,5 51,2 79,6 85,3 95,3 110,9
3
Portata / Flow rate m /h 20,8 23,5 27,5 30,9 39,5 51,5 57,5 67,0
Perdite di carico / Pressure drop kPa 23 25 30 20 27 42 47 49
Volume gas 13 15 17 19 22 30 34 41
L
Volume H2O 30 35 37 51 55 105 99 90
Potenza totale = somma di tutti i circuiti / Total capacity = sum total of all circuits
Temperatura entrata acqua / Inlet water temperature +12°C Temperatura di evaporazione / Evaporation temperature +2.5 °C
DATI NOMINALI
NOMINAL DATA R 407C Temperatura uscita acqua / Outlet water temperature +7°C Temperatura di condensazione / Condensation temperature +45 °C
MPE
MODELLO / MODEL MPE 460 510 570 650 750 820 880 975
Potenza totale kW 460 510 570 650 750 820 880 975
Total capacity Tons (RT) 130,8 145,0 162,1 184,8 213,2 233,2 250,2 277,2
Portata / Flow rate m3/h 79,0 87,5 97,8 111,6 128,7 140,8 151,0 167,4
Perdite di carico / Pressure drop kPa 41 46 62 52 62 43 46 91
Volume gas 45 52 61 69 80 95 102 118
L
Volume H2O 143 134 121 230 216 196 240 210
Potenza totale = somma di tutti i circuiti / Total capacity = sum total of all circuits
PESO / WEIGHT kg 340 350 360 540 553 580 610 670
Temperatura entrata acqua / Inlet water temperature +12°C Temperatura di evaporazione / Evaporation temperature +2.5 °C
DATI NOMINALI
NOMINAL DATA R 407C Temperatura uscita acqua / Outlet water temperature +7°C Temperatura di condensazione / Condensation temperature +45 °C
3
Rev.00 del 30/03/2006
Shell and tube evaporators
MPE
Potenza totale = somma di tutti i circuiti / Total capacity = sum total of all circuits
A 2900 2900
B 322 340
C 94 94
D 457 508
MPE../2
ATTACCHI /
Temperatura entrata acqua / Inlet water temperature +12°C Temperatura di evaporazione / Evaporation temperature +2.5 °C
DATI NOMINALI
NOMINAL DATA R 407C Temperatura uscita acqua / Outlet water temperature +7°C Temperatura di condensazione / Condensation temperature +45 °C
Single Compressor System It is recognised best practice to fit a solenoid valve, sight glass, and
A single compressor has the most basic oil system. The compressor shut-off valve in the oil return line. These components are not shown
discharge is piped to the inlet of an oil separator (2) and the outlet of in the diagram.
the oil separator is piped to the condenser (3). A discharge check valve
should be fitted (4). An oil return line (6) is connected from the oil Refer to equipment list for further details
separator through an oil strainer (5), oil filter (10) or oil filter-drier (11), on each component in the oil system
to the compressor crankcase.
A float valve in the oil separator opens and feeds a small amount of oil
by-passing the rest of the cooling system. The oil is returned under
discharge pressure to the crankcase. The float valve prevents hot gas
from bypassing to the crankcase by closing when the oil level falls.
It is recognised best practice to fit a solenoid valve, sight glass, and
AC&R
shut-off valve in the oil return line. These components are not shown
in the diagram.
Refer to equipment list for further details
on each component in the oil system
1. Compressor. 10. Oil Filter – The function of an Oil Filter is to remove system
2. Oil Separator – The function of an Oil Separator is to remove oil debris from the refrigerant oil. An oil filter is recommended for
from the discharge gas and return it to the compressor, either HFC/POE systems instead of individual oil strainers, where
directly or indirectly. This helps maintain the compressor crankcase filtration only is required.
oil level and raises the efficiency of the system by preventing 11. Oil Filter-Drier –The function of an Oil Filter-Drier is to remove
excessive oil circulation. Oil separators are not 100% efficient, so both system debris and moisture from the refrigerant oil. An oil
installing an oil separator should not be viewed as a replacement filter-drier is recommended for HFC/POE systems instead of
for oil traps, accumulators, or good oil return piping practices. individual oil strainers, where both filtration and moisture removal
Henry Technologies manufacture two different types of oil is required.
separator, Helical and Conventional.
12. Pressure Vent Valve – The function of a Pressure Vent Valve is
3. Condenser. to maintain a positive pressure in the Oil Reservoir above the
4. Discharge Check Valve – The function of a Check Valve is to compressor crankcase pressure. Three different pressure settings
allow fluid flow in one direction only. This prevents condensed are available; 0.35 barg, 1.4 barg and 2.4 barg. A higher pressure
liquid refrigerant returning down the discharge line into the differential will increase the oil flow rate from the oil reservoir
separator. If this check valve is not installed the separator can feed back to the compressors. The pressure setting should be selected
excessive liquid refrigerant to the compressor on start up. This can taking into account the allowable oil pressure differential of the oil
cause oil dilution, excessive foaming, erratic oil pressures and level regulator type.
possible compressor damage. The check valve must be installed 13. Oil Separator-Reservoir – The function of an Oil Separator-
after the oil separator. Reservoir is to provide a Separator and Oil Reservoir in one unit.
5. Oil Strainer – The function of an Oil Strainer is to remove system It is designed for high pressure systems and eliminates the need
PRODUCTS
debris from the refrigerant oil. Their purpose is to protect for a separate Oil Reservoir and its associated piping.
compressors and oil level regulators from damage. For 14. Optronic Oil Regulator – The function of the Optronic
recommendations on HFC/POE systems, refer to section on oil Regulator is to control the oil level in the compressor crankcase.
filters and oil filter-driers. This protects the compressors from damage. This regulator can be
6. Oil Return Line. used on high pressure systems.
9
Henry_AC&R_section_20.7.06 1/8/06 14:25 Page 11
O I L S E PA R ATO R S
H E L I C A L O I L S E PA R ATO R S
Outlet Connection
The function of a Helical Oil Separator is to efficiently remove
oil from the discharge gas and return it to the compressor,
either directly or indirectly. This helps maintain the compressor
crankcase oil level and raises the efficiency of the system by
preventing excessive oil circulation.
A higher level of efficiency is to be expected compared to a
conventional type oil separator. Inlet Connection
Helical
Flighting
Applications
Helical oil separators can be used in a wide variety of applications.
Common applications include multi-compressor racks and remote Mesh Screen
condensing units.
Helical oil separators are intended for Low Pressure Oil Management
Systems. These products are designed for use with scroll and
Second Mesh
reciprocating type compressors. They are not recommended for screw
Screen
or rotary vane compressors.
Oil Drain Baffle
The standard product range is designed for use with HCFC and HFC
refrigerants, along with their associated oils. The SN range is suitable for
use with HCFC, HFC and ammonia refrigerants. The SH high-pressure
range is intended for R410A and sub-critical CO2 applications.
Ball Float
Oil Return
Please contact Henry Technologies for new or special Connection
applications.
PRODUCTS
of the helical flighting. A float activated oil return needle valve allows the o o
Allowable operating temperature = -10 C to +110 C
separated oil to return to the compressor crankcase or oil reservoir. There
is a permanent magnet positioned at the bottom of the oil collection Materials of Construction
chamber to capture any system metal debris, which could impair the
operation of the needle valve. With proper selection, an oil separation The main components; shell, end caps and connections are made from
efficiency of up to 99% can be achieved. carbon steel. The oil float is made from stainless steel. The needle valve
seat is made from either brass or steel, dependent on model.
Main Features
• Patented Henry Technologies Design#
COMPONENTS
11
Henry_AC&R_section_20.7.06 1/8/06 14:25 Page 12
H E L I C A L O I L S E PA R ATO R S
STANDARD RANGE
Part No Conn Size Dimensions (mm) Mounting Drawing Weight (kg) Pre-charge CE Cat
(Inch) details reference qty (l)
ØA B C D E F ØG
S-5180 1/4 ODS 64 166 45 43 N/A 19.5 N/A M10 fig.1 1.2 0.1 SEP
S-5181 3/8 ODS 64 195 45 71 N/A 19.5 N/A M10 fig.1 1.4 0.1 SEP
S-5182-CE 1/2 ODS 102 333 69 64 N/A 58.5 N/A M10 fig.2 3.4 0.4 CAT I
S-5185-CE 5/8 ODS 102 384 69 66 N/A 58.5 N/A M10 fig.2 3.9 0.4 CAT I
S-5187-CE 7/8 ODS 102 434 74 76 N/A 58.5 N/A M10 fig.2 4.6 0.4 CAT I
S-5188-CE 1 1/8 ODS 102 483 75 78 N/A 58.5 N/A M10 fig.2 4.6 0.4 CAT I
S-5190-CE 1 3/8 ODS 152 384 108 91 N/A 60.5 N/A M10 fig.2 8.9 1.1 CAT I
S-5192-CE 1 5/8 ODS 152 428 108 98 N/A 60.5 N/A M10 fig.2 9.5 1.1 CAT I
S-5194-CE 2 1/8 ODS 152 436 114 105 N/A 60.5 N/A M10 fig.2 9.7 1.1 CAT I
S-5285-CE 5/8 ODS 102 513 69 66 95 N/A 120.7 2 x Ø11mm fig.3 6.3 0.7 CAT I
holes
S-5287-CE 7/8 ODS 102 563 74 76 95 N/A 120.7 2 x Ø11mm fig.3 7 0.7 CAT I
holes
S-5288-CE 1 1/8 ODS 102 614 75 78 95 N/A 120.7 2 x Ø11mm fig.3 7 0.7 CAT I
holes
SN-5290-CE 1 3/8 ODS 152 508 108 91 99 N/A 113 2 x Ø14mm fig.3 12 0.7 CAT I
slots (see note 1)
SN-5292-CE 1 5/8 ODS 152 559 108 98 99 N/A 113 2 x Ø14mm fig.3 12.5 0.7 CAT I
slots (see note 1)
SN-5294-CE 2 1/8 ODS 152 559 114 105 99 N/A 113 2 x Ø14mm fig.3 13 0.7 CAT I
slots (see note 1)
S-5411-CE 1 5/8 ODS 219 641 148 164 100 N/A 166 3 x Ø14mm fig.4 25 0.7 CAT III
slots
S-5412-CE 2 1/8 ODS 219 641 148 164 100 N/A 166 3 x Ø14mm fig.4 26 0.7 CAT III
slots
S-5413-CE 2 5/8 ODS 273 750 183 201 100 N/A 223 3 x Ø14mm fig.4 39 0.7 CAT III
slots
S-5414-CE 3 1/8 ODS 324 821 215 229 100 N/A 273 3 x Ø14mm fig.4 53 0.7 CAT IV
slots
Notes:-
1. For use with ammonia, the CE Category increases to II
Adding the suffix “M” to the part number denotes that metric
PRODUCTS
connections are preferred e.g. S-5192M-CE. The suffix “X” denotes that
a 10mm ODS oil return is preferred instead of the standard 3/8 flare e.g.
S-5185X-CE. Adding the suffix “XM” denotes the separator is to be
fitted with both variations. Please contact Henry Technologies for
availability of M, X and XM versions.
COMPONENTS
AC&R
H E L I C A L O I L S E PA R ATO R S
1 Inlet
2 Outlet
3 Oil return,
3/8 SAE Flare
Fig.1 Fig.2
PRODUCTS
COMPONENTS
13
Henry_AC&R_section_20.7.06 1/8/06 14:25 Page 14
H E L I C A L O I L S E PA R ATO R S
Helical Separator Selection The general recommendation is that the calculated maximum flow should
using the Graphs not exceed the rated capacity of the separator. Also, the minimum flow
3
To use the selection graphs, the refrigerant type, maximum refrigeration should not be below 25% of the rated capacity. Using these m /hr
capacity, minimum refrigeration capacity, evaporating temperature and figures, the recommended helical separator selection is either model S-
3
the condensing temperature is required. 5190-CE or SN-5190-CE, both with a rated capacity of 18.7 m /hr. The
final selection depends on whether or not the user requires a separator
Example model with a removable/cleanable oil float assembly.
Refrigerant R404A
COMPONENTS
3
Maximum discharge volume flow rates = (0.42 x 40) = 16.8 m /hr minimal amount and the system has unloading characteristics, select
3
Minimum discharge volume flow rates = (0.42 x 25) = 10.5 m /hr the smaller separator. It is not recommended to oversize.
3
The maximum and minimum m /hr figures should be compared with
the rated capacity of the helical separator. Refer to the Performance Data
Table for the rated capacities.
H E L I C A L O I L S E PA R ATO R S
0.55
Discharge (m3/hr)
Chart-R404A/R507
0.5
0.45
25
0.4
30
0.35 35
40
45
0.3
50
55
0.25
-40 -35 -30 -25 -20 -15 -10 -5 0 5
Evaporator Temp (0C)
0.55
Discharge (m3/hr)
Chart-R22
0.5
25
0.45
0.4
35
0.35 40
45
0.3
50
55
0.25
-40 -35 -30 -25 -20 -15 -10 -5 0 5
PRODUCTS
Evaporator Temp (0C)
0.45
Discharge (m3/hr)
Chart-R717
0.4 25
COMPONENTS
Condensing Temp (0C)
0.35 30
m3/hr/kW
35
0.3
40
0.25 45
50
AC&R
0.2 55
-40 -35 -30 -25 -20 -15 -10 -5 0 5
Evaporator Temp (0C)
15
Henry_AC&R_section_20.7.06 1/8/06 14:25 Page 16
H E L I C A L O I L S E PA R ATO R S
To use the Flow Rate Calculation method, the maximum and minimum
system mass flow rates are required along with the density of the gas at
the inlet to the separator. These mass flow rates can either be calculated
from first principles or by using refrigeration cycle analysis software. In
this way, superheating (useful and un-useful), sub-cooling, etc. can be
accounted for in the mass flow rate calculation.
Example
Refrigerant CO2 (R744)
Maximum refrigeration capacity = 62 kW
Minimum refrigeration capacity = 40 kW
o
Evaporating temperature = -35 C
o
Condensing temperature (Cascade) = 0 C
Degree of superheat, useful = 5K
Degree of superheat, un-useful = 6K
Degree of sub-cooling = 2K
From calculation:-
Maximum mass flow rate = 904 kg/hr
Minimum mass flow rate = 583 kg/hr
3
Gas density, superheated, at inlet to separator = 63.5 kg/m
o
(for a separator inlet temperature of 60 C)
583 3
Calculated minimum discharge volume flowrate = 63.5 = 9.2 m /hr
3
Using these m /hr figures,the recommended helical separator selection
is model SH-5188-CE (reference additional note 3 for guidance on
minimal under-sizing).
PRODUCTS
O I L R E S E RV O I R S
Main Features
• Three sizes available in both standard and high pressure ranges
• Robust construction
• All models supplied with Rotalock valves
• Sight glass with floating ball
• Double seal on sight glass for leak integrity: thread sealant and
O-ring
• Premium quality O-ring seals
• Standard models supplied with mounting brackets
• Mounting brackets available on request for high pressure range
Selection Guidelines
Technical Specification Both ranges of Henry Technologies reservoirs include three different oil
For standard models: holding capacities of approximately 7.5, 11.5 and 15 litres.
Allowable operating pressure = 0 to 31 barg The required holding capacity is dependent on a number of system
Allowable operating temperature = -10o C to +130o C design factors such as oil return piping practice, compressor type, number
of compressors, compressor run times, etc.
For SH models:
For single stage parallel systems, a simple selection guide can be used.
Allowable operating pressure = 0 to 40 barg
For other systems, please contact Henry Technologies. The selection guide
Allowable operating temperature = -10o C to +110o C uses total compressor theoretical displacement, V h , as an indicator of
required oil reservoir capacity.
Materials of Construction
Example:-
PRODUCTS
The shell, end caps and fitting connections are made from carbon steel.
8 compressors each with a theoretical displacement of 17 m3/hr.
Therefore V h (total) = 136 m3/hr.
The selected model is S-9109-CE, with a V h rating of up to 150 m3/hr.
Refer to selection table.
Note: It is known that some users select oil reservoir capacity using
different rules from the above or from field experience. The method
presented above is for guidance purposes only. If in doubt, select a larger
COMPONENTS
capacity reservoir.
Installation – Main issues
1. Full instructions are given in the Product Instruction Sheet, included
with each reservoir.
O I L R E S E RV O I R S
4 Sight glass
PRODUCTS
COMPONENTS
Fig.3 Fig.4
31
Henry_AC&R_section_20.7.06 1/8/06 14:29 Page 23
O I L L E V E L R E G U L ATO R S
MECHANICAL OIL
L E V E L R E G U L ATO R S
The function of a Mechanical Oil Level Regulator is to control
the oil level in the compressor crankcase. This protects the
compressor from damage.
There are two main types of Mechanical oil level regulators -
fixed level and adjustable level.
Applications
Mechanical oil level regulators are used in Low Pressure Oil Management
Systems. They are designed for use with reciprocating compressors. They
are not recommended for scroll compressors.
All regulators are suitable for HCFC and HFC refrigerants, along with
their associated oils. The unique features of the SN model allow it to be
used in ammonia, R410A and sub-critical CO2 applications.
How it works
Oil is fed to the regulator via an inlet connection. An internal needle
valve either allows or shuts off an oil supply to the regulator. An internal
ball float controls the position of the needle valve. During compressor
operation, the crankcase oil level reduces. A reduction in oil level
activates the regulator, which ensures the correct crankcase oil level is
achieved and maintained.
The adjustable regulator has an in-built mechanism that allows the ball
float to be adjusted up or down. This means that the crankcase oil level
can be adjusted, in line with the compressor manufacturer’s guidelines.
Technical Specification
The fixed level regulator does not have an adjusting feature hence the
crankcase will be maintained at a fixed oil level. For all models, excluding SN model:-
Some regulator models are fitted with an equalisation connection that Allowable operating pressure = 0 to 31 barg
enables the oil levels between several compressors to be balanced. Allowable operating temperature = 0o C to +130o C
In the majority of cases, Henry Technologies oil level regulators can For SN model:-
be fitted directly to the compressor sight glass port. Where direct
Allowable operating pressure = 0 to 40 barg
mounting is not possible, a separate adaptor can be used. Refer to
Adaptor Kit table. Allowable operating temperature = -10o C to +110o C
Refer to table for the allowable oil pressure differential for the Henry
Main Features
range of regulators.
• Proven needle valve design
• Stainless steel ball float Important information
• Special mounting flange - allows direct fitting to standard 1. As a result of a modification to the Bitzer oil ventura device in May
PRODUCTS
compressors 1997, it is no longer necessary to provide an oil guard on the oil
• Premium quality neoprene seals level regulator.
• Seal adaptor kit supplied with each model 2. Copeland confirm a 1/2 sight glass oil level is acceptable, rather
• Visual indication of oil level via large sight glass than 1/4 sight glass, for all compressors fitted with an oil
• Double O-ring stem seal design - adjustable model management system.
• Easy adjustment mechanism - adjustable model
Materials of Construction
The main components; shell, end caps and connections are made from
carbon steel. The ball float is made from stainless steel. The needle valve
COMPONENTS
23
Henry_AC&R_section_20.7.06 1/8/06 14:29 Page 24
M E C H A N I C A L O I L L E V E L R E G U L ATO R S
Fig.1 Fig.3
2 Adjustment
Fig.2
Dimensions in mm
PRODUCTS
Selection Guidelines
The correct selection depends on the refrigerant type, differential oil
pressure acting on the regulator, and the user’s preference for crankcase
oil level control. Some users prefer the simplicity of model S-9510 while
others prefer model S-9530E, owing to the larger pressure differential,
oil level adjustment and equalisation features.
Note: Differential oil pressure is the difference between the supply
pressure at inlet to the regulator and the pressure inside the compressor
crankcase. Gravity pressure head should be included also, if applicable.
COMPONENTS
4. The oil level must be set and controlled in line with the compressor
manufacturer’s guidelines.
5. Full instructions are given in the Product Instruction Sheet included
with each regulator.
M E C H A N I C A L O I L L E V E L R E G U L ATO R A D A P TO R K I T S
Compressor Model Sight Glass Configuration Adaptor Kit Part Number CE Cat
PRODUCTS
included. It is designed for the S-95 series regulators.
5. This is the standard seal kit supplied with each S-95 series regulator.
It includes all the parts in 3-033-201 along with a special sandwich
piece and O-ring for sealing a Bitzer 4 bolt sight glass.
COMPONENTS
AC&R
25
Henry_AC&R_section_20.7.06 1/8/06 14:57 Page 42
S U C T I O N L I N E A C C U M U L ATO R S
Main features
• Prevents liquid slugging
• Controlled liquid return
• Large flow capacity
PRODUCTS
Technical Specification
S-76 series:
MWP = 20.8 barg @ +100o C
S-704 series (all models), S-7061-CE to S-7065-CE (except HE
COMPONENTS
S U C T I O N L I N E A C C U M U L ATO R S
1 Inlet
2 Outlet
3 Liquid injection
connection, 1/2 FPT
S-76 SERIES
PRODUCTS
COMPONENTS
AC&R
43
Henry_AC&R_section_20.7.06 1/8/06 14:57 Page 44
S U C T I O N L I N E A C C U M U L ATO R S
S-7742-CE* - - 4 1/8 ODS 508 1130 330 N/A 457.2 4 Ø16.3mm holes N/A fig.4* 130 CAT IV
on square base
*S-7742-CE features a square mounting plate - not mounting brackets
1 Inlet 3 Relief connection, 1/4 FPT 5 Liquid level switch connection, 7 Relief connection, 1/2 FPT.
1 FPT. (Refer to note 1) (Refer to note 3)
2 Outlet 4 Heat Exchanger coil connection
(HE models only) 6 Liquid level switch connection, 8 Relief connection, 1/2 FPT.
1 FPT. (Refer to note 2) (Refer to note 4)
S U C T I O N L I N E A C C U M U L ATO R S
Refrigerant Holding
Part No Capacity (kg at -18°C) Recommended kW of refrigerant at Suction Evaporating Temp (°C)
R134a R22 R404A R134a R22 R404A / R507
5° -7° -18° -29° -40° 5° -7° -18° -29° -40° 5° -7° -18° -29° -40°
S-7615-CE 10.6 10 8.8 MAX 53 35 Horizontal accumulators 102 70 Horizontal accumulators 100 57 Horizontal accumulators not
S-7621-CE 14.4 13 11.9 MAX 101 69 not suitable for 176 106 not suitable for 173 117 suitable for applications
S-7625-CE 21.2 19 17.6 MAX 176 123 applications below -10°C 334 229 applications below -10°C 328 217 below -10°C
MAX 3.2 2.3 1.5 1 0.6 6.3 4.5 3.1 2.1 1.3 6.3 4.3 2.8 1.8 1.1
S-7043 1 1 0.7
MIN 0.7 0.6 0.5 0.4 0.3 0.9 0.8 0.7 0.6 0.7 0.9 0.7 0.6 0.5 0.4
MAX 1.6 1.2 0.8 0.5 0.6 3.2 2.3 1.6 1.0 0.7 3.1 2.2 1.5 0.9 0.6
S-7044 2 1.9 1.7
MIN 0.3 0.2 0.2 0.2 0.1 0.5 0.4 0.3 0.2 0.2 0.5 0.3 0.3 0.2 0.2
MAX 3.2 2.3 1.5 1 0.6 6.4 4.5 3.1 2.1 1.3 6.3 4.3 2.8 1.8 1.1
S-7045 2 1.9 1.7
MIN 0.7 0.6 0.5 0.4 0.3 0.9 0.8 0.7 0.6 0.4 0.9 0.7 0.6 0.5 0.4
MAX 4.5 3.1 2.1 1.4 0.8 8.8 6.2 4.2 2.8 1.8 8.7 5.9 3.8 2.5 1.5
S-7046 2 1.9 1.7
MIN 0.9 0.7 0.6 0.5 0.4 1.2 1 0.8 0.7 0.6 1.3 1 0.8 0.6 0.5
MAX 7.7 5.4 3.6 2.3 1.4 15.2 10.7 7.1 4.7 3 14.9 10.2 6.5 4.2 2.6
S-7057-CE 4.2 3.9 3.5
MIN 1.3 1.1 0.9 0.7 0.6 1.8 1.6 1.3 1.1 0.9 1.8 1.5 1.2 1 0.7
MAX 16.3 11.4 7.3 4.8 2.9 32 22.8 14.4 9.7 6.1 31.4 21.7 13.2 8.6 5.2
S-7061-CE 5.8 5.4 4.9
MIN 2.1 1.8 1.5 1.2 1 3 2.5 2.2 1.8 1.4 2.9 2.4 2 1.6 1.2
MAX 27.8 18.8 12 7.6 4.7 54.9 37.7 23.8 15.6 10 53.9 35.9 21.8 13.8 8.6
S-7063-CE 9.9 9.1 8.3
MIN 4.4 3.7 3.1 2.5 2 6.1 5.1 4.4 3.6 2.9 6 4.9 4 3.2 2.5
MAX 49.3 33.8 21.1 13.4 8.2 96.8 67.6 41.5 27.4 17.5 95 64.1 38 24.3 15
S-7065-CE 9.9 9.1 8.3
MIN 7.6 6.3 5.3 4.4 3.5 10.5 8.8 7.6 6.4 5.1 10.3 8.4 7 5.7 4.4
MAX 109 70.4 49.3 26.4 17.6 204 141 91.5 63.4 42.2 201 134 84.5 56.3 35.2
S-7721-CE 14.7 13.6 12.3
MIN 14.1 12.3 10.6 8.8 7 21.1 19.4 15.8 14.1 10.6 21.1 17.6 14.1 12.3 8.8
MAX 109 70.4 49.3 26.4 17.6 204 141 91.5 63.4 42.2 201 134 84.5 56.3 35.2
S-7722-CE 14.7 13.6 12.3
MIN 14.1 12.3 10.6 8.8 7 21.1 19.4 15.8 14.1 10.6 21.1 17.6 14.1 12.3 8.8
MAX 172 113 75.7 42.2 22.9 313 215 144 98.6 54.6 308 204 132 88 47.5
S-7725-CE 22 20 18.2
MIN 21.1 19.4 15.8 12.3 3.5 31.7 29.9 24.6 22.9 5.3 31.7 28.2 22.9 21.1 5.3
MAX 172 113 75.7 42.2 22.9 313 215 144 98.6 54.6 308 204 132 88 47.5
S-7726-CE 22 20 18.2
MIN 21.1 19.4 15.8 12.3 3.5 31.7 29.9 24.6 22.9 5.3 31.7 28.2 22.9 21.1 5.3
MAX 253 194 130 84.5 33.4 465 324 215 141 82.7 456 308 197 125 70.4
S-7731-CE 36.4 33.2 30
MIN 35.2 31.7 24.6 22.9 5.3 54.6 45.8 40.5 33.4 8.8 52.8 44 37 29.9 8.8
MAX 253 194 130 84.5 33.4 465 324 215 141 82.7 456 308 197 125 70.4
S-7732-CE 36.4 33.2 30
MIN 35.2 31.7 24.6 22.9 5.3 54.6 45.8 40.5 33.4 8.8 52.8 44 37 29.9 8.8
MAX 401 259 156 107 69.7 792 510 306 211 137 757 503 320 201 116
S-7741-CE 62 61 55
MIN 109 89.4 75.7 59.8 47.2 151 125 109 86.6 31.7 174 113 73.9 45.8 24.6
MAX 401 259 156 107 69.7 792 510 306 211 137 757 503 320 201 116
S-7742-CE 127 126 114
MIN 109 89.4 75.7 59.8 47.2 151 125 109 86.6 31.7 174 113 73.9 45.8 24.6
Selection Guidelines Heat pump systems must use the HP accumulator models. Winter
The accumulator should have adequate holding capacity. Normally, heating can cause too much liquid refrigerant to slug back to the
this should not be less than 50% of the total system charge. compressor. Heat pump accumulators incorporate a smaller orifice to
prevent excessive liquid flow.
The system designer should check that the minimum and maximum
system refrigeration capacities are within the limits of the accumulator. Two accumulators can be piped in series to increase holding capacity. Oil
will be metered from one accumulator to the next to ensure proper oil
The recommended minimum and maximum kW capacities are listed in flow to the compressors. Adding a second identical accumulator will
the table. The maximum kW capacities are based on accumulator effectively double the holding capacity of a single accumulator.
PRODUCTS
pressure loss and oil return. The pressure loss is equivalent to 1/2o C.
The minimum kW capacities are to ensure proper oil return. Piping two identical accumulators in parallel will double the kW capacity.
Two identical accumulators must be used.
Example: On low temperature systems (-18o C and below) a heater band should be
Refrigerant R404A installed to help boil off the liquid refrigerant and aid oil flow. Do not
System maximum refrigeration capacity = 170 kW add too much heat or there is a risk of overheating the compressors.
System minimum refrigeration capacity = 65 kW Horizontal accumulators should not be used when the liquid refrigerant
o temperature is less than -10o C.
Evaporating temperature = -18 C
COMPONENTS
45
Thermostatic expansion valves,
type TE 5 - TE 55
REFRIGERATION AND
AIR CONDITIONING Teknisk brochure
Technical leaflet Thermostatic expansion valves, type TE 5 - TE 55
Contents Page
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Superheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Ordering:
R22:
Thermostatic element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Orifice assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Valve body. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
R407C:
Thermostatic element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Orifice assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Valve body. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
R134a:
Thermostatic element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Orifice assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Valve body. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
R404A/R507:
Thermostatic element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Orifice assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Valve body. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Capacity:
R22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
R407C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
R134a . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
R404A/R507 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Design - Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Dimensions and weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Introduction
Thermostatic expansion valves regulate the Therefore the valves are especially suitable
injection of refrigerant liquid into evaporators. for liquid injection in ”dry“ evaporators where
Injection is controlled by the refrigerant the superheat at the evaporator outlet is
superheat. proportional to the evaporator load.
MOP-points
Range N Range NM Range NL Range B
− 40 → +10°C − 40 → − 5°C − 40 → − 15°C − 60 → − 25°C
Refrigerant
MOP-point in evaporating temperature te and evaporating pressure pe
+15°C/+60°F 0°C/+32°F − 10°C/+15°F − 20°C/− 4°F
R22 7.0 bar / 101 psig 4.0 bar / 57.5 psig 2.6 bar / 37.8 psig 1.4 bar / 20.9 psig
R134a 4.0 bar / 57.4 psig 1.9 bar / 27.8 psig 1.0 bar / 15.0 psig
R404A/R507 8.6 bar / 124 psig 5.0 bar / 72.4 psig 3.4 bar / 49.1 psig 2.0 bar / 29.0 psig
R407C 6.5 bar / 94.3 psig
MOP = Max. Operating Pressure
Superheat SS = static superheat opening begins to where the valve gives its rated
OS = opening superheat capacity Qnom.
SH = SS + OS = total superheat
Qnom = rated capacity Example
Qmax = maximum capacity Static superheat SS = 5 K
Opening superheat OS = 6 K
Static superheat SS can be adjusted with setting Total superheat SH = 5 + 6 = 11 K
spindle.
The standard superheat setting SS is 5 K for valves
without MOP and 4 K for valves with MOP.
The opening superheat OS is 6 K from when
Ordering
Thermostatic element R22
Code no.
Pressure Capillary
Valve Range N Range NM Range NL Range B
equalization tube
type –40 to +10°C –40 to –5°C –40 to –15°C –60 to –25°C
/4 in. / 6 mm
1
m Without MOP MOP+15°C MOP 0°C MOP –10°C Without MOP MOP –20°C
TEX 5 Ext. 1) 3 067B3250 067B3267 067B3249 067B3253 067B3263 067B3251
TEX 12 Ext. 2) 3 067B3210 067B3227 067B3207 067B3213 067B3211
TEX 12 Ext. 2) 5 067B3209 067B3212
TEX 20 Ext. 2) 3 067B3274 067B3286 067B3273 067B3275 067B3276
TEX 20 Ext. 2) 5 067B3290 067B3287
TEX 55 Ext. 2) 3 067G3205 067G3220 067G3206 067G3207
TEX 55 Ext. 2) 5 067G3209 067G3217
1
) Pressure equalization with solder connector can be supplied on contacting Danfoss.
2
) Available as accessory: solder adapter for TE 12, TE 20 and TE 55. Code no. 068B0170.
Orifice assembly
Rated capacity Rated capacity
Range N: Range B:
Valve type Orifice no. Code no.
–40 to 10°C –60 to –25°C
kW kW
TEX 5-3 19.7 11.9 01 067B2089
TEX 5-4.5 26.9 16.7 02 067B2090
TEX 5-7.5 38.8 24.8 03 067B2091
TEX 5-12 55.3 35.4 04 067B2092
TEX 12-4.5 26.8 17.2 01 067B2005
TEX 12-7.5 43.4 28.2 02 067B2006
TEX 12-12 64.0 41.4 03 067B2007
TEX 12-18 84.4 55.9 04 067B2008
TEX 20-30 108.0 70.0 01 067B2172
TEX 55-50 239.0 148.0 01 067G2005
TEX 55-85 356.0 228.0 02 067G2006
Valve body
Connection
Code no.
Inlet × Outlet
Type Orifice no.
Flare Solder Solder Solder
in. mm
angleway angleway straightway flanges
01 - 03 1/2 × 5/8 067B4013 067B4009 067B4007
TE 5 03 1
/2 × 7/8 067B4010 067B4008
04 5/ × 7/
8 8 067B4011
01- 03 12 × 16 067B4013 067B4004 067B4002
TE 5 03 12 × 22 067B4005 067B4003
04 16 × 22 067B4012
01 - 02 5 /8 × 7/8 067B4022 1) 067B4020 1) 067B4025 1)
TE 12 03 - 04 /8 × 1
7
067B4026 1)
03 - 04 7/ × 11/
8 8 067B4023 2) 067B4021 2)
01 - 02 16 × 22 067B4018 1) 067B4027 1)
TE 12 03 - 04 22 × 25 067B4015 1)
03 - 04 22 × 28 067B4017 2) 067B4016 2)
01 7
/8 × 11/8 067B4023 2) 067B4021 2)
TE 20
01 22 × 28 067B4017 2) 067B4016 2)
01- 02 11/8 × 13/8 067G4004 3) 067G4003 3)
TE 55
01- 02 28 × 35 067G4002 3) 067G4001 3)
1
) ODF × ODF
2
) ODF × ODM
3
) ODM × ODM
ODF = Internal diameter
ODM = External diameter
Ordering
(continued)
Thermostatic element R407C
Code no.
Pressure Capillary
Valve equalization tube Range N
type –40 to +10°C
/4 in. / 6 mm
1 m Without MOP MOP+15°C
TEZ 5 Ext. 1) 3 067B3278 067B3277
TEZ 12 Ext. 2) 3 067B3366 067B3367
TEZ 20 Ext. 2) 3 067B3371 067B3372
TEZ 55 Ext. 2) 3 067G3240 067G3241
1) Pressure equalization with solder connector can be supplied on
contacting Danfoss.
2) Available as accessory: solder adapter for TE 12, TE 20 and
Orifice assembly
Rated capacity
Range N:
Valve type Orifice no. Code no.
–40 to 10°C
kW
TEZ 5-3.2 21.3 01 067B2089
TEZ 5-5.0 29.1 02 067B2090
TEZ 5-8.0 41.9 03 067B2091
TEZ 5-13 59.7 04 067B2092
TEZ 12-5.0 28.9 01 067B2005
TEZ 12-8.0 46.9 02 067B2006
TEZ 12-13 69.1 03 067B2007
TEZ 12-19.5 91.2 04 067B2008
TEZ 20-32.5 116.0 01 067B2172
TEZ 55-54 259.0 01 067G2005
TEZ 55-92 385.0 02 067G2006
The rated capacity is based on:
Evaporating temperature te = +5°C for range N
Condensing temperature tc = +32°C
Refrigerant temperature ahead of valve tl = +28°C
Valve body
Connection
Code no.
Inlet × Outlet
Type Orifice no.
Flare Solder Solder Solder
in. mm
angleway angleway straightway flanges
01 - 03 1/2 × 5/8 067B4013 067B4009 067B4007
TE 5 03 1
/2 × 7/8 067B4010 067B4008
04 5
/8 × 7/8 067B4011
01- 03 12 × 16 067B4013 067B4004 067B4002
TE 5 03 12 × 22 067B4005 067B4003
04 16 × 22 067B4012
01 - 02 5
/8 × 7/8 067B4022 1) 067B4020 1) 067B4025 1)
TE 12 03 - 04 /8 × 1
7 067B4026 1)
03 - 04 7/ × 11/
8 8 067B4023 2) 067B4021 2)
01 - 02 16 × 22 067B4018 1) 067B4027 1)
TE 12 03 - 04 22 × 25 067B4015 1)
03 - 04 22 × 28 067B4017 2) 067B4016 2)
01 7/8 × 11/8 067B4023 2) 067B4021 2)
TE 20
01 22 × 28 067B4017 2) 067B4016 2)
01- 02 11/8 × 13/8 067G4004 3) 067G4003 3)
TE 55
01- 02 28 × 35 067G4002 3) 067G4001 3)
1
) ODF × ODF
2
) ODF × ODM
3) ODM × ODM
Ordering
(continued)
Thermostatic element R134a
Code no.
Pressure Capillary
Valve equalization tube Range N Range NM
type –40 to +10°C –40 to –5°C
1
/4 in. / 6 mm m Without MOP MOP +15°C MOP 0°C
TEN 5 Ext. 1) 3 067B3297 067B3298 067B3360
TEN 12 Ext. 2) 3 067B3232 067B3233
TEN 12 Ext. 2) 5 067B3363
TEN 20 Ext. 2) 3 067B3292 067B3293
TEN 20 Ext. 2) 5 067B3370
TEN 55 Ext. 2) 3 067G3222 067G3223
TEN 55 Ext. 2) 5 067G3230
1 ) Pressure equalization with solder connector can be supplied on contacting Danfoss.
2 ) Available as accessory: solder adapter for TE 12, TE 20 and TE 55. Code no. 068B0170.
Orifice assembly
Rated capacity
Valve type Orifice no. Code no.
kW
TEN 5-3.7 12.9 01 067B2089
TEN 5-5.4 19.1 02 067B2090
TEN 5-8.3 29.1 03 067B2091
TEN 5-11.2 39.6 04 067B2092
TEN 12-4.7 16.7 01 067B2005
TEN 12-7.7 27.2 02 067B2006
TEN 12-11.4 40.0 03 067B2007
TEN 12-15 53.0 04 067B2008
TEN 20-18 65.0 01 067B2170
TEN 55-41 145.0 01 067G2001
TEN 55-62 220.0 02 067G2002
The rated capacity is based on:
Evaporating temperature te = +5°C
Condensing temperature tc = +32°C
Refrigerant temperature ahead of valve tl = +28°C
Valve body
Connection
Code no.
Inlet × Outlet
Type Orifice no.
Flare Solder Solder Solder
in. mm
angleway angleway straightway flanges
01 - 03 1
/2 × 5/8 067B4013 067B4009 067B4007
TE 5 03 1/2 × 7/8 067B4010 067B4008
04 5/ × 7/
8 8 067B4011
01- 03 12 × 16 067B4013 067B4004 067B4002
TE 5 03 12 × 22 067B4005 067B4003
04 16 × 22 067B4012
01 - 02 5
/8 × 7/8 067B4022 1) 067B4020 1) 067B4025 1)
TE 12 03 - 04 /8 × 1
7 067B4026 1)
03 - 04 7
/8 × 11/8 067B4023 2) 067B4021 2)
01 - 02 16 × 22 067B4018 1) 067B4027 1)
TE 12 03 - 04 22 × 25 067B4015 1)
03 - 04 22 × 28 067B4017 2) 067B4016 2)
01 7
/8 × 11/8 067B4023 2) 067B4021 2)
TE 20
01 22 × 28 067B4017 2) 067B4016 2)
01- 02 11/8 × 13/8 067G4004 3) 067G4003 3)
TE 55
01- 02 28 × 35 067G4002 3) 067G4001 3)
1
) ODF × ODF
2
) ODF × ODM
3
) ODM × ODM
ODF = Internal diameter
ODM = External diameter
Ordering
(continued) Thermostatic element R404A/R507
Code no.
Pressure Capillary
Valve equalization tube Range N Range NM Range NL Range B
type –40 to +10°C –40 to –5°C –40 to –15°C –60 to –25°C
/4 in. / 6 mm
1
m Without MOP MOP +15°C MOP 0°C MOP –10°C Without MOP MOP –20°C
TES 5 Ext. 1) 3 067B3342 067B3357 067B3358 067B3344 067B3343
TES 12 Ext. 2) 3 067B3347 067B3345 067B3348 067B3349
TES 12 Ext. 2) 5 067B3346 067B3350
TES 20 Ext. 2) 3 067B3352 067B3351 067B3353 067B3354
TES 20 Ext. 2) 5 067B3356 067B3355
TES 55 Ext. 2) 3 067G3302 067G3303 067G3304 067G3305
TES 55 Ext. 2) 5 067G3301 067G3306
1
) Pressure equalization with solder connector can be supplied on contacting Danfoss.
2
) Available as accessory: solder adapter for TE 12, TE 20 and TE 55. Code no. 068B0170.
Orifice assembly
Rated capacity Rated capacity
range N: range B:
Valve type Orifice no. Code no.
–40 to 10°C –60 to –25°C
kW kW
TES 5-3.7 13.0 8.0 01 067B2089
TES 5-5.0 17.6 11.2 02 067B2090
TES 5-7.2 25.3 16.6 03 067B2091
TES 5-10.3 36.2 23.7 04 067B2092
TES12-4.2 14.8 11.6 01 067B2005
TES 12-6.8 23.9 18.9 02 067B2006
TES 12-10.0 35.2 27.7 03 067B2007
TES 12-13.4 47.1 37.5 04 067B2008
TES 20-16.5 59.0 41.0 01 067B2175
TES 55-37.0 130.0 95.0 01 067G2011
TES 55-56.0 197.0 144.0 02 067G2012
Valve body
Connection
Code no.
Inlet × Outlet
Type Orifice no.
Flare Solder Solder Solder
in. mm
angleway angleway straightway flanges
01 - 03 1
/2 × 5/8 067B4013 067B4009 067B4007
TE 5 03 1/2 × 7/8 067B4010 067B4008
04 5/ × 7/
8 8 067B4011
01- 03 12 × 16 067B4013 067B4004 067B4002
TE 5 03 12 × 22 067B4005 067B4003
04 16 × 22 067B4012
01 - 02 5
/8 × 7/8 067B4022 1) 067B4020 1) 067B4025 1)
TE 12 03 - 04 /8 × 1
7 067B4026 1)
03 - 04 7
/8 × 11/8 067B4023 2) 067B4021 2)
01 - 02 16 × 22 067B4018 1) 067B4027 1)
TE 12 03 - 04 22 × 25 067B4015 1)
03 - 04 22 × 28 067B4017 2) 067B4016 2)
01 7
/8 × 11/8 067B4023 2) 067B4021 2)
TE 20
01 22 × 28 067B4017 2) 067B4016 2)
01- 02 11/8 × 13/8 067G4004 3) 067G4003 3)
TE 55
01- 02 28 × 35 067G4002 3) 067G4001 3)
1
) ODF × ODF
2
) ODF × ODM
3
) ODM × ODM
ODF = Internal diameter
ODM = External diameter
Capacity
Capacity in KW for Range N: −40°C to +10°C R22
Orifice Pressure drop across valve ∆p bar Pressure drop across valve ∆p bar
Valve type
no. 2 4 6 8 10 12 14 16 2 4 6 8 10 12 14 16
Evaporating temperature +10°C Evaporating temperature 0°C
TEX 5-3 01 12.4 16.3 18.8 20.5 21.7 22.4 22.8 23.0 12.8 16.7 19.1 20.8 22.0 22.7 23.2 23.3
TEX 5-4.5 02 17.2 22.5 25.9 28.1 29.7 30.6 31.1 31.3 17.7 22.9 26.1 28.3 29.9 30.9 31.5 31.7
TEX 5-7.5 03 25.3 32.8 37.4 40.6 42.6 43.9 44.5 44.7 25.9 33.0 37.5 40.6 42.8 44.2 45.0 45.3
TEX 5-12 04 35.8 46.6 53.3 57.8 60.8 62.6 63.6 63.9 36.6 47.0 53.5 58.0 61.2 63.2 64.3 64.7
TEX 12-4.5 01 16.8 22.5 26.1 28.6 30.3 31.4 32.1 32.3 16.1 21.2 24.5 26.8 28.5 29.6 30.3 30.6
TEX 12-7.5 02 27.3 36.4 42.1 46.1 48.8 50.7 51.6 52.0 26.2 34.5 39.8 43.5 46.1 47.8 48.9 49.3
TEX 12-12 03 40.2 53.3 61.6 67.2 71.1 73.5 74.9 75.5 38.7 50.8 58.5 63.9 67.7 70.3 71.9 72.6
TEX 12-18 04 53.2 70.2 80.9 88.1 93.0 96.1 97.8 98.5 51.7 67.6 77.8 85.0 90.2 93.7 95.8 96.9
TEX 20-30 01 72.0 94.4 108 118 124 129 131 132 66.3 86.0 98.5 107 113 118 120 121
TEX 55-50 01 158 209 241 263 278 287 293 295 145 190 218 237 251 260 265 267
TEX 55-85 02 239 313 360 391 412 425 432 434 221 286 326 355 375 388 395 397
Evaporating temperature -10°C Evaporating temperature -20°C
TEX 5-3 01 11.1 14.3 16.3 17.7 18.8 19.5 19.9 20.1 11.5 13.0 14.1 15.0 15.6 16.0 16.2
TEX 5-4.5 02 15.4 19.7 22.4 24.3 25.7 26.7 27.3 27.6 15.9 18.1 19.6 20.8 21.6 22.1 22.4
TEX 5-7.5 03 22.7 28.7 32.7 35.6 37.8 39.4 40.4 40.9 23.2 26.3 28.7 30.6 32.0 32.9 33.5
TEX 5-12 04 32.3 41.1 46.8 51.0 54.1 56.3 57.7 58.4 33.2 37.7 41.1 43.7 45.7 47.0 47.8
TEX 12-4.5 01 18.7 21.4 23.4 24.8 25.8 26.4 26.6 15.9 18.1 19.6 20.8 21.6 22.1 22.4
TEX 12-7.5 02 30.4 34.8 37.9 40.2 41.8 42.8 43.2 25.9 29.4 32.0 33.9 35.2 36.1 36.5
TEX 12-12 03 44.5 50.9 55.6 59.0 61.4 62.9 63.7 37.7 42.9 46.7 49.6 51.7 53.1 53.9
TEX 12-18 04 59.1 67.7 74.0 78.7 82.1 84.3 85.6 49.9 57.0 62.3 66.4 69.6 71.8 73.1
TEX 20-30 01 75.4 85.9 93.6 99.2 103 106 107 63.7 72.4 78.8 83.8 87.4 90.0 91.4
TEX 55-50 01 166 189 205 217 225 229 231 140 158 171 181 187 191 193
TEX 55-85 02 251 285 309 327 339 346 349 213 240 260 275 285 291 294
Evaporating temperature -30°C Evaporating temperature -40°C
TEX 5-3 01 9.0 10.2 11.1 11.7 12.2 12.5 12.7 7.9 8.5 9.0 9.4 9.7 9.8
TEX 5-4.5 02 12.6 14.3 15.4 16.4 17.0 17.5 17.8 11.1 12.0 12.7 13.3 13.7 13.9
TEX 5-7.5 03 18.3 20.8 22.7 24.2 25.4 26.2 26.8 16.2 17.7 19.0 19.9 20.7 21.2
TEX 5-12 04 26.3 29.8 32.5 34.6 36.3 37.5 38.2 23.2 25.3 27.1 28.5 29.5 30.2
TEX 12-4.5 01 14.8 16.0 16.9 17.6 18.0 18.3 11.9 12.8 13.5 14.0 14.4 14.6
TEX 12-7.5 02 24.2 26.2 27.7 28.8 29.5 29.9 19.4 21.0 22.2 23.1 23.7 24.1
TEX 12-12 03 35.1 38.1 40.5 42.4 43.7 44.5 28.1 30.6 32.6 34.1 35.3 36.1
TEX 12-18 04 46.6 51.0 54.6 57.4 59.6 61.0 37.4 41.1 44.2 46.8 48.8 50.3
TEX 20-30 01 59.2 64.5 68.8 72.0 74.4 75.8 47.5 51.8 55.4 58.2 60.4 61.9
TEX 55-50 01 129 139 146 151 155 156 102 110 116 120 122 123
TEX 55-85 02 197 212 224 232 237 240 158 170 178 185 189 191
Capacity (continued)
Capacity in KW for Range B: −60°C to −25°C R22
Orifice Pressure drop across valve ∆p bar Pressure drop across valve ∆p bar
Valve type
no. 2 4 6 8 10 12 14 16 2 4 6 8 10 12 14 16
Evaporating temperature -25°C Evaporating temperature -30°C
TEX 5-3 01 8.1 10.2 11.6 12.5 13.3 13.8 14.2 14.4 7.2 9.0 10.2 11.1 11.7 12.2 12.5 12.7
TEX 5-4.5 02 11.3 14.2 16.1 17.4 18.5 19.2 19.7 20.0 10.1 12.6 14.3 15.4 16.4 17.0 17.5 17.8
TEX 5-7.5 03 16.4 20.7 23.5 25.6 27.3 28.6 29.5 30.0 14.6 18.3 20.8 22.7 24.2 25.4 26.2 26.8
TEX 5-12 04 23.5 29.6 33.6 36.6 39.0 40.8 42.1 42.8 20.9 26.3 29.8 32.5 34.6 36.3 37.5 38.2
TEX 12-4.5 01 11.3 14.5 16.4 17.8 18.8 19.6 20.0 20.3 10.2 13.1 14.8 16.0 16.9 17.6 18.0 18.3
TEX 12-7.5 02 18.5 23.6 26.8 29.0 30.7 31.9 32.7 33.2 16.8 21.4 24.2 26.2 27.7 28.8 29.5 29.9
TEX 12-12 03 26.8 34.2 38.9 42.3 45.0 46.9 48.3 49.1 24.3 30.9 35.1 38.1 40.5 42.4 43.7 44.5
TEX 12-18 04 35.4 45.3 51.7 56.6 60.4 63.4 65.6 67.0 32.0 40.8 46.6 51.0 54.6 57.4 59.6 61.0
TEX 20-20 01 46.0 58.0 66.0 72.0 76.0 80.0 82.0 83.0 41.0 52.0 59.0 65.0 69.0 72.0 74.0 76.0
TEX 55-35 01 100 127 143 155 163 169 173 174 91.0 115 129 139 146 151 155 156
TEX 55-60 02 154 194 218 236 249 258 264 267 140 175 197 212 224 232 237 240
Evaporating temperature -40°C Evaporating temperature -50°C
TEX 5-3 01 5.6 7.0 7.9 8.5 9.0 9.4 9.7 9.8 5.5 6.1 6.6 7.0 7.3 7.5 7.7
TEX 5-4.5 02 7.9 9.9 11.1 12.0 12.7 13.3 13.7 13.9 7.7 8.7 9.4 9.9 10.4 10.7 10.9
TEX 5-7.5 03 11.4 14.3 16.2 17.7 19.0 19.9 20.7 21.2 11.2 12.7 13.9 14.9 15.8 16.4 16.9
TEX 5-12 04 16.3 20.5 23.2 25.3 27.1 28.5 29.5 30.2 16.0 18.2 19.9 21.3 22.5 23.4 24.1
TEX 12-4.5 01 8.3 10.5 11.9 12.8 13.5 14.0 14.4 14.6 8.5 9.5 10.2 10.8 11.2 11.5 11.7
TEX 12-7.5 02 13.7 17.2 19.4 21.0 22.2 23.1 23.7 24.1 13.9 15.5 16.8 17.7 18.5 19.0 19.4
TEX 12-12 03 19.6 24.8 28.1 30.6 32.6 34.1 35.3 36.1 19.8 22.5 24.5 26.2 27.6 28.6 29.4
TEX 12-18 04 25.5 32.6 37.4 41.1 44.2 46.8 48.8 50.3 25.9 29.9 33.1 35.9 38.2 40.2 41.6
TEX 20-20 01 33.0 42.0 47.0 52.0 55.0 58.0 60.0 62.0 33.0 38.0 42.0 45.0 47.0 49.0 51.0
TEX 55-35 01 73.0 92.0 102 110 116 120 122 123 73.0 81.0 87.0 91.0 94.0 96.0 97.0
TEX 55-60 02 114 141 158 170 178 185 189 191 113 126 135 142 147 150 151
Evaporating temperature -55°C Evaporating temperature -60°C
TEX 5-3 01 4.4 4.9 5.3 5.6 5.9 6.1 6.2
TEX 5-4.5 02 6.2 7.0 7.6 8.0 8.4 8.6 8.8
TEX 5-7.5 03 9.0 10.3 11.3 12.1 12.9 13.5 13.9
TEX 5-12 04 12.9 14.7 16.1 17.3 18.3 19.2 19.8
TEX 12-4.5 01 7.6 8.5 9.2 9.7 10.1 10.4 10.5
TEX 12-7.5 02 12.5 14.0 15.1 16.0 16.7 17.2 17.5
TEX 12-12 03 17.8 20.3 22.1 23.7 25.0 26.0 26.7
TEX 12-18 04 23.3 27.0 30.0 32.6 34.8 36.7 38.2
TEX 20-20 01 30.0 34.0 37.0 40.0 43.0 45.0 46.0
TEX 55-35 01 66.0 73.0 78.0 82.0 84.0 86.0 87.0
TEX 55-60 02 102 113 121 127 131 134 135
Correction for subcooling ∆tsub The evaporator capacities used must be dividing the required evaporator capacity by the
corrected if subcooling deviates from 4 K. correction factor below. Selections can then be
The corrected capacity can be obtained by made from the tables above.
∆tsub 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.06 1.11 1.15 1.2 1.25 1.3 1.35 1.39 1.44
flash gas. factor
Capacity (continued)
Capacity in KW for Range N: −40°C to +10°C R407C
Orifice Pressure drop across valve ∆p bar Pressure drop across valve ∆p bar
Valve type
no. 2 4 6 8 10 12 14 16 2 4 6 8 10 12 14 16
Evaporating temperature +10°C Evaporating temperature 0°C
TEZ 5 - 3.2 01 12.9 16.8 19.2 20.7 21.7 22.0 22.1 22.1 13.3 17.2 19.5 21.0 22.0 22.2 22.5 22.4
TEZ 5 - 5.0 02 17.9 23.2 26.4 28.4 29.7 30.0 30.2 30.0 18.4 23.6 26.6 28.6 29.9 30.3 30.6 30.4
TEZ 5 - 8.0 03 26.3 33.8 38.1 41.0 42.6 43.0 43.2 42.9 26.9 34.0 38.3 41.0 42.8 43.3 43.7 43.5
TEZ 5 - 13 04 37.2 48.0 54.4 58.4 60.8 61.3 61.7 61.3 38.1 48.4 54.6 58.6 61.2 61.9 62.4 62.1
TEZ 12 - 5.0 01 17.5 23.2 26.6 28.9 30.3 30.8 31.1 31.0 16.7 21.8 25.0 27.1 28.5 29.0 29.4 29.4
TEZ 12 - 8.0 02 28.4 37.5 42.9 46.6 48.8 49.7 50.1 49.9 27.2 35.5 40.6 43.9 46.1 46.8 47.4 47.3
TEZ 12 - 13 03 41.8 54.9 62.8 67.9 71.0 72.0 72.7 72.5 40.2 52.3 59.7 64.5 67.7 68.9 69.7 69.7
TEZ 12 - 19.5 04 55.0 72.0 83.0 89.0 93.0 94.0 94.9 94.6 53.8 70.0 79.0 86.0 90.0 92.0 92.9 93.0
TEZ 20 - 32.5 01 75.0 97.0 110 119 124 126 127 127 69.0 89.0 100 108 113 116 116 116
TEZ 55 - 54 01 164 215 246 266 278 281 284 283 151 196 222 239 251 255 257 256
TEZ 55 - 92 02 249 322 367 395 412 417 419 417 230 295 333 359 375 380 383 381
Evaporating temperature -10°C Evaporating temperature -20°C
TEZ 5 - 3.2 01 11.5 14.6 16.5 17.7 18.8 19.1 19.3 19.1 11.7 13.1 14.1 14.9 15.1 15.4 15.2
TEZ 5 - 5.0 02 16.0 20.1 22.6 24.3 25.7 26.2 26.5 26.2 16.2 18.3 19.6 20.6 21.0 21.2 21.1
TEZ 5 - 8.0 03 23.6 29.3 33.0 35.6 37.8 38.6 39.2 38.9 23.7 26.6 28.7 30.3 31.0 31.6 31.5
TEZ 5 - 13 04 33.6 41.9 47.3 51.0 54.1 55.2 56.0 55.5 33.9 38.1 41.1 43.3 44.3 45.1 44.9
TEZ 12 - 5.0 01 19.1 21.6 23.4 24.8 25.3 25.6 25.3 16.2 18.3 19.6 20.6 21.0 21.2 21.1
TEZ 12 - 8.0 02 31.0 35.1 37.9 40.2 41.0 41.5 41.0 26.4 29.7 32.0 33.6 34.1 34.7 34.3
TEZ 12 - 13 03 45.4 51.4 55.6 59.0 60.2 61.0 60.5 38.5 43.3 46.7 49.1 50.1 51.0 50.7
TEZ 12 - 19.5 04 60.3 68.4 74.0 78.7 80.5 81.8 81.3 50.9 57.6 62.3 65.7 67.5 68.9 68.7
TEZ 20 - 32.5 01 77.0 87.0 94.0 99.0 101 103 102 65.0 73.1 78.8 83.0 84.8 86.4 85.9
TEZ 55 - 54 01 169 191 205 217 221 222 219 143 160 171 179 181 183 181
TEZ 55 - 92 02 256 288 309 327 332 336 332 217 242 260 272 276 279 276
Evaporating temperature -30°C Evaporating temperature -40°C
TEZ 5 - 3.2 01 9.2 10.3 11.0 11.5 11.7 11.9 11.8 7.9 8.3 8.6 8.9 9.0 9.0
TEZ 5 - 5.0 02 12.9 14.4 15.2 16.1 16.3 16.6 16.6 11.1 11.8 12.2 12.6 12.7 12.8
TEZ 5 - 8.0 03 18.7 21.0 22.5 23.7 24.4 24.9 24.9 16.2 17.3 18.2 18.9 19.3 19.5
TEZ 5 - 13 04 26.8 30.1 32.2 33.9 34.8 35.6 35.5 23.2 24.8 26.0 27.1 27.4 27.8
TEZ 12 - 5.0 01 14.9 15.8 16.6 16.9 17.1 17.0 11.9 12.5 13.0 13.3 13.4 13.4
TEZ 12 - 8.0 02 24.4 25.9 27.1 27.6 28.0 27.8 19.4 20.6 21.3 21.9 22.0 22.2
TEZ 12 - 13 03 35.5 37.7 39.7 40.7 41.5 41.4 28.1 30.0 31.3 32.4 32.8 33.2
TEZ 12 - 19.5 04 47.1 50.5 53.5 55.1 56.6 56.7 37.0 40.0 42.0 44.0 45.4 46.3
TEZ 20 - 32.5 01 59.8 63.9 67.4 69.1 70.7 70.5 48.0 51.0 53.0 55.0 56.2 56.9
TEZ 55 - 54 01 130 138 143 145 147 145 102 108 111 114 113 113
TEZ 55 - 92 02 199 210 220 223 225 223 158 167 171 176 176 176
Correction for subcooling ∆tsub The evaporator capacities used must be dividing the required evaporator capacity by the
corrected if subcooling deviates from 4 K. correction factor below. Selections can then be
The corrected capacity can be obtained by made from the tables above.
∆tsub 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.08 1.14 1.21 1.27 1.33 1.39 1.45 1.51 1.57
flash gas. factor
Capacity (continued)
Capacity in KW for Range N: −40°C to +10°C R134a
Orifice Pressure drop across valve ∆p bar Pressure drop across valve ∆p bar
Valve type
no. 2 4 6 8 10 2 4 6 8 10
Evaporating temperature +10°C Evaporating temperature 0°C
TEN 5 - 3.7 01 10.4 13.3 14.8 15.6 16.0 8.8 11.1 12.4 13.0 13.3
TEN 5 - 5.4 02 15.7 19.6 21.9 22.9 23.4 13.2 16.6 18.4 19.4 19.8
TEN 5 - 8.3 03 22.8 28.3 31.2 32.6 33.3 19.5 24.3 27.0 28.5 29.2
TEN 5 - 11.2 04 32.3 40.4 44.6 46.7 47.7 27.8 34.7 38.7 40.8 41.8
TEN 12 - 4.7 01 13.1 17.0 19.0 20.1 20.7 11.4 14.6 16.3 17.3 17.7
TEN 12 - 7.7 02 21.3 27.5 30.9 32.7 33.5 18.6 23.8 26.8 28.1 28.8
TEN 12 - 11.4 03 31.4 40.4 45.3 47.9 49.2 27.2 34.7 38.9 41.1 42.2
TEN 12 - 15 04 42.0 53.8 60.2 63.7 65.5 36.3 46.1 51.7 54.9 56.5
TEN 20 - 18 01 52.8 67.1 74.7 78.8 80.7 45.6 57.5 64.2 67.8 69.5
TEN 55 - 41 01 117 128 167 176 180 101 128 142 150 153
TEN 55 - 62 02 178 226 251 264 270 155 195 216 227 232
Evaporating temperature -10°C Evaporating temperature -20°C
TEN 5 - 3.7 01 7.0 8.8 9.8 10.3 10.5 5.5 6.8 7.5 7.9 8.1
TEN 5 - 5.4 02 10.6 13.2 14.7 15.5 15.8 8.3 10.2 11.4 12.0 12.3
TEN 5 - 8.3 03 15.5 19.3 21.5 22.8 23.5 12.0 14.9 16.7 17.8 18.3
TEN 5 - 11.2 04 22.2 27.6 30.8 32.7 33.6 17.2 21.3 23.9 25.4 26.2
TEN 12 - 4.7 01 9.6 12.1 13.5 14.3 14.6 7.8 9.7 10.8 11.4 11.7
TEN 12 - 7.7 02 15.7 19.8 22.0 23.3 23.8 12.8 15.9 17.7 18.7 19.1
TEN 12 - 11.4 03 22.8 28.7 32.1 34.0 34.9 18.4 23.0 25.6 27.3 28.0
TEN 12 - 15 04 30.1 38.0 42.7 45.5 46.9 24.1 30.3 34.1 36.6 37.9
TEN 20 - 18 01 38.0 47.5 53.0 56.2 57.8 30.6 38.0 42.5 45.2 46.6
TEN 55 - 41 01 84.6 106 117 123 125 68.7 84.5 93.2 97.8 99.5
TEN 55 - 62 02 130 161 179 188 192 106 130 143 151 153
Evaporating temperature -30°C Evaporating temperature -40°C
TEN 5 - 3.7 01 4.2 5.1 5.7 6.0 6.2 3.3 4.0 4.4 4.6 4.7
TEN 5 - 5.4 02 6.4 7.8 8.7 9.2 9.4 5.0 6.1 6.7 7.1 7.3
TEN 5 - 8.3 03 9.2 11.4 12.7 13.6 14.1 7.1 8.8 9.8 10.6 11.0
TEN 5 - 11.2 04 13.2 16.3 18.2 19.5 20.2 10.2 12.6 14.1 15.1 15.7
TEN 12 - 4.7 01 6.3 7.7 8.5 9.0 9.1 5.1 6.2 6.8 7.2 7.3
TEN 12 - 7.7 02 10.3 12.6 13.9 14.7 15.0 8.3 10.1 11.1 11.7 12.0
TEN 12 - 11.4 03 14.6 18.1 20.2 21.5 22.2 11.7 14.4 16.1 17.2 17.7
TEN 12 - 15 04 18.9 23.7 26.8 28.9 30.2 15.0 18.8 21.4 23.2 24.4
TEN 20 - 18 01 24.2 30.0 33.5 35.8 37.1 19.4 23.9 26.8 28.7 29.8
TEN 55 - 41 01 54.9 66.6 73.0 76.4 77.5 44.4 53.2 58.0 60.4 61.1
TEN 55 - 62 02 84.9 103 113 118 120 68.8 82.6 90.1 94.1 95.3
Correction for subcooling ∆tsub The evaporator capacities used must be dividing the required evaporator capacity by the
corrected if subcooling deviates from 4 K. correction factor below. Selections can then be
The corrected capacity can be obtained by made from the tables above.
∆tsub 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.08 1.13 1.19 1.25 1.31 1.37 1.42 1.48 1.54
flash gas. factor
Capacity (continued)
Capacity in KW for Range N: −40°C to +10°C R404A/R507
Orifice Pressure drop across valve ∆p bar Pressure drop across valve ∆p bar
Valve type
no. 2 4 6 8 10 12 14 16 2 4 6 8 10 12 14 16
Evaporating temperature +10°C Evaporating temperature 0°C
TES 5 - 3.7 01 9.9 12.8 14.3 15.1 15.5 15.7 15.8 15.8 9.4 12.1 13.7 14.5 14.9 14.9 14.9 14.9
TES 5 - 5.0 02 13.6 17.4 19.4 20.5 21.0 21.2 21.4 21.3 13.0 16.6 18.6 19.6 20.1 20.2 20.2 20.2
TES 5 - 7.2 03 19.9 25.1 27.7 29.1 29.9 30.2 30.4 30.4 19.3 24.4 27.3 28.8 29.5 29.6 29.6 29.5
TES 5 - 10.3 04 28.2 35.8 39.7 41.7 42.8 43.2 43.5 43.5 27.4 34.9 39.1 41.4 42.4 42.4 42.4 42.3
TES 12 - 4.2 01 11.8 15.5 17.5 18.7 19.4 19.6 19.8 19.8 10.3 13.5 15.3 16.31 6.7 16.8 16.9 16.8
TES 12 - 6.8 02 19.2 25.2 28.5 30.3 31.3 31.7 31.9 32.0 16.9 22.0 24.8 26.4 27.2 27.4 27.4 27.3
TES 12 - 10.0 03 28.4 37.0 41.8 44.5 46.0 46.6 47.0 47.0 24.7 32.2 36.4 38.7 39.9 40.2 40.3 40.3
TES 12 - 13.4 04 38.0 49.4 55.7 59.2 61.2 62.1 62.7 63.0 33.0 42.8 48.5 51.7 53.4 53.9 54.2 54.4
TES 20 - 16.7 01 48.0 62.0 69.0 73.0 75.0 76.0 77.0 77.0 42.0 53.0 60.0 64.0 66.0 66.0 66.0 66.0
TES 55 - 37 01 106 137 154 164 169 170 171 171 92 119 134 142 145 146 145 145
TES 55 - 56.0 02 161 208 232 245 252 254 255 255 141 181 203 214 219 219 219 218
Evaporating temperature -10°C Evaporating temperature -20°C
TES 5 - 3.7 01 7.9 10.1 11.3 12.0 12.4 12.4 12.3 12.2 7.9 8.9 9.6 9.8 9.9 9.8 9.7
TES 5 - 5.0 02 10.9 13.9 15.6 16.6 17.0 17.0 16.9 16.8 11.0 12.4 13.3 13.7 13.8 13.6 13.5
TES 5 - 7.2 03 16.0 20.4 23.0 24.5 25.1 25.2 25.2 25.2 16.1 18.3 19.8 20.5 20.7 20.6 20.6
TES 5 - 10.3 04 22.9 29.1 32.9 35.0 36.0 36.2 36.1 36.1 23.1 26.2 28.4 29.3 29.6 29.6 29.4
TES 12 - 4.2 01 9.0 11.7 13.2 14.1 14.5 14.5 14.4 14.3 6.2 10.9 11.7 12.0 12.0 11.9 11.7
TES 12 - 6.8 02 14.8 19.1 21.6 23.0 23.6 23.6 23.5 23.3 15.7 17.8 19.1 19.6 19.7 19.5 19.3
TES 12 - 10.0 03 21.6 27.8 31.5 33.6 34.7 34.8 34.7 34.6 22.8 25.9 28.0 28.8 29.2 29.1 28.9
TES 12 - 13.4 04 28.6 37.0 42.1 45.1 46.7 47.1 47.2 47.2 30.2 34.6 37.6 39.1 39.9 39.9 40.0
TES 20 - 16.7 01 36.0 46.0 52.0 56.0 57.0 58.0 58.0 57.0 38.0 43.0 47.0 48.0 49.0 49.0 48.0
TES 55 - 37.0 01 80.0 103 115 122 125 125 123 122 84.0 94.0 101 103 103 101 100
TES 55 - 56.0 02 124 157 176 186 190 190 188 186 129 145 155 158 158 156 153
Evaporating temperature -30°C Evaporating temperature -40°C
TES 5 - 3.7 01 6.9 7.3 7.6 7.6 7.5 7.5 5.1 5.5 5.7 5.7 5.6 5.5
TES 5 - 5.0 02 9.7 10.3 10.7 10.7 10.6 10.5 7.2 7.7 8.0 8.0 7.9 7.8
TES 5 - 7.2 03 14.3 15.4 16.2 16.4 16.3 16.2 10.7 11.6 12.3 12.5 12.5 12.4
TES 5 - 10.3 04 20.5 22.1 23.1 23.4 23.3 23.2 15.3 16.6 17.5 17.8 17.8 17.7
TES 12 - 4.2 01 8.7 9.3 9.6 9.6 9.5 9.3 6.7 7.2 7.4 7.4 7.3 7.2
TES 12 - 6.8 02 14.3 15.3 15.8 15.9 15.7 15.4 11.1 11.8 12.3 12.3 12.1 11.9
TES 12 - 10.0 03 20.8 22.4 23.4 23.7 23.5 23.4 16.1 17.4 18.3 18.6 18.5 18.4
TES 12 - 13.4 04 27.8 30.3 32.0 32.7 32.9 32.9 21.6 23.8 25.3 26.1 26.3 26.5
TES 20 -16.7 01 35.0 37.0 39.0 40.0 40.0 39.0 27.0 29.0 31.0 31.0 31.0 31.0
TES 55 -37.0 01 75.0 80.0 82.0 81.0 80.0 78.0 58.0 61.0 62.0 62.0 60.0 59.0
TES 55 - 56.0 02 116 123 127 126 124 121 90.0 95.0 97.0 97.0 94.0 92.0
Capacity (continued)
Capacity in KW for Range B: −60°C to −25°C R404A/R507
Orifice Pressure drop across valve ∆p bar Pressure drop across valve ∆p bar
Valve type
no. 2 4 6 8 10 12 14 16 2 4 6 8 10 12 14 16
Evaporating temperature -25°C Evaporating temperature -30°C
TES 5 - 3.7 01 8.1 8.5 8.6 9.1 9.2 9.4 9.5 9.5 7.7 8.1 8.3 8.6 8.9 9.1 9.1 9.2
TES 5 - 5.0 02 12.0 12.5 13.0 13.5 14.7 15.3 15.9 16.0 11.2 11.7 12.2 12.6 13.4 14.2 14.7 14.8
TES 5 - 7.2 03 19.8 20.5 21.3 22.3 24.4 25.1 25.8 26.2 18.0 18.2 18.8 19.6 20.8 21.8 22.9 23.4
TES 5 - 10.3 04 20.0 24.0 26.0 27.0 27.5 28.0 28.5 29.0 18.0 22.0 24.8 25.0 25.5 26.0 26.3 26.5
TES 12 - 4.2 01 9.8 12.8 13.6 14.6 15.1 15.4 15.5 15.9 9.4 11.1 12.3 13.0 13.3 13.5 13.6 14.1
TES 12 - 6.8 02 18.4 21.2 22.8 24.9 25.7 25.8 26.2 26.3 16.5 18.6 20.2 21.5 22.1 22.2 22.4 22.8
TES 12 - 10.0 03 30.5 35.3 37.4 41.7 42.4 43.0 43.2 43.6 27.7 30.7 33.8 35.8 36.5 37.1 37.4 37.9
TES 12 - 13.4 04 34.3 40.2 42.8 47.0 48.4 48.8 49.1 49.3 30.5 34.4 37.7 40.5 40.9 41.4 41.6 42.1
TES 20 - 11.7 01 34.0 41.0 46.0 50.0 51.0 52.0 53.0 53.0 30.0 37.0 40.0 43.0 45.0 45.0 46.0 47.0
TES 55 - 27.0 01 71.0 91.0 97.0 104 109 109 111 112 63.0 79.0 86.0 93.0 94.0 95.0 96.0 96.0
TES 55 - 41.0 02 111 140 147 161 170 171 174 175 99.0 124 132 143 145 146 147 149
Evaporating temperature -40°C Evaporating temperature -50°C
TES 5 - 3.7 01 6.3 6.6 6.7 7.1 7.2 7.3 7.5 4.4 4.6 4.7 4.8 4.9 4.9 5.3
TES 5 - 5.0 02 10.0 10.1 10.3 10.5 11.0 11.3 11.4 7.8 7.9 8.2 8.3 8.3 8.4 8.6
TES 5 - 7.2 03 14.2 14.4 14.6 15.3 15.8 16.1 16.4 10.3 10.5 10.6 10.7 11.0 11.1 11.3
TES 5 - 10.3 04 17.5 19.5 20.0 20.5 21.0 21.0 21.2 13.5 15.0 15.5 16.0 16.0 16.0 15.5
TES 12 - 4.2 01 9.0 9.6 10.0 10.5 10.6 10.8 10.9 7.1 7.4 7.8 7.9 8.0 8.1 8.3
TES 12 - 6.8 02 14.8 15.8 16.2 16.7 17.0 17.1 17.5 11.4 11.8 12.4 12.9 13.1 13.3 13.4
TES 12 - 10.0 03 24.7 27.0 27.0 28.2 28.5 28.8 29.1 19.5 20.5 21.0 21.7 21.9 22.1 22.7
TES 12 - 13.4 04 27.7 29.4 30.5 31.9 32.1 32.3 32.6 21.9 23.1 23.9 24.4 24.9 25.1 25.4
TES 20 - 11.7 01 31.0 33.0 34.0 34.0 35.0 35.0 35.0 26.0 26.0 27.0 27.0 27.0 28.0 28.0
TES 55 - 27.0 01 63.0 67.0 70.0 73.0 74.0 75.0 76.0 46.0 48.0 50.0 51.0 52.0 53.0 54.0
TES 55 - 41.0 02 98.0 106 108 114 115 115 116 74.0 78.0 79.0 81.0 82.0 82.0 83.0
Evaporating temperature -55°C Evaporating temperature -60°C
TES 5 - 3.7 01 3.0 3.3 3.4 3.4 3.4 3.5
TES 5 - 5.0 02 6.6 6.8 6.9 6.9 7.1 7.3
TES 5 - 7.2 03 7.8 7.9 8.0 8.1 8.2 8.2
TES 5 - 10.3 04 11.5 12.0 12.2 12.3 12.2 12.0
TES 12 - 4.2 01 6.3 6.9 7.0 7.1 7.3 7.8
TES 12 - 6.8 02 10.7 10.9 11.2 11.3 11.4 11.5
TES 12 - 10.0 03 17.9 18.5 18.9 19.2 19.5 19.7
TES 12 - 13.4 04 20.2 20.5 20.9 21.3 21.6 22.0
TES 20 -11.7 01 24.0 24.0 25.0 25.0 26.0 26.0
TES 55 - 27.0 01 39.0 39.0 41.0 41.0 42.0 42.0
TES 55 - 41.0 02 63.0 64.0 65.0 65.0 66.0 66.0
Correction for subcooling ∆tsub The evaporator capacities used must be dividing the required evaporator capacity by the
corrected if subcooling deviates from 4 K. correction factor below. Selections can then be
The corrected capacity can be obtained by made from the tables above.
∆tsub 4K 10 K 15 K 20 K 25 K 30 K 35 K 40 K 45 K 50 K
Note:
Insufficient subcooling can produce Correction
1.00 1.1 1.2 1.29 1.37 1.46 1.54 1.63 1.7 1.78
flash gas. factor
TE 5
TE 12 / TE 20
X = R22
N = R134a
S = R404A/R507
Z = R407C
TE 5 TE 5
Inlet side L1 L2 D
∅D1 mm Range N 115.5 ∅16.0
1
/2 in. / 12 mm ODF 10 Range B 111.0 ∅20.3
5/8 in. / 16 mm ODF 10
Outlet side L1
∅D2 mm
5/8 in. / 16 mm ODF 12
7
/8 in. / 22 mm ODF 17
TE 12 and TE 20 Bulb - TE 12
Inlet side L1 L2 D
∅D1 mm Range N 111.0 ∅20.3
5/8 in. / 16 mm ODF 12 Range B 148.0 ∅20.3
7/8 in. / 22 mm ODF 17
TE 55 Bulb - TE 55
Inlet side L1 L2 D
∅D1 mm Range N/B 148.0 ∅20.3
/8 in. / 22 mm ODF
7
17
11/8 in. / 28 mm ODM 25
Outlet side L1
∅D2 mm
11/8 in. / 28 mm ODF 22
13/8 in. / 35 mm ODM 27
REFRIGERATION AND
AIR CONDITIONING
Technical leaflet
Technical leaflet Coils for solenoid valves
Features Encapsulated coils with long operating life, Standard coils from 12 V to 420 V, 50, 60
even under extreme conditions or 50/60 Hz
Standard coils for a.c. or d.c. Standard coils dimensioned for max. opening
Standard coils available with 3-core cable, differential pressure (MOPD) of up to 21 bar
terminal box or DIN plugs Coils can be fitted without the use of tools
See "Opening differential pressure" under "Technical data" for the valve concerned.
When replacing a coil with terminal box, it is sufficent to change the coil unit itself. Therefore, order
coil with DIN plugs and protective cap.
Accessories
Description Code no.
DIN socket 042N0156
Terminal box with build-in light emmiting indicator diode for solenoid valves 018Z0089
Features ATEX approved for use in EX zone 2 Mounting on valve without use of tools
Embedded coils with long lifetime - even Standard coils for a.c. and d.c.
under extreme conditons Standard coils from 24 to 240 V
Available with 1 m 3-core cable or terminal Standard coils dimensioned to max. opening
Quick and safe mounting with "clip-on"coil differential pressure (MOPD) up to 21 bar
Note:
Always install a fuse ahead of the coil.
It should not exceed 2 A for coils rated less
than 50 V and it should not exceed 1 A for coils
rated 50 V or more.
25 VA
Inrush:
48 VA
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
PRODUCT BULLETIN
Series P78
Dual Pressure Controls for Refrigeration,
Air-conditioning and Heatpump Applications
Introduction
These dual pressure controls are designed for
use in a variety of applications involving
refrigeration high or low pressure. Models
supplied have a “whole range” design, enabling
them to be used with refrigerants R22, R134A,
R404A and all other non-corrosive refrigerants
which are within the operating range of the
control. They may also be used for other high or
low pressure applications such as air, water etc.
Models which can be used with ammonia as
well as controls tested, conforming to DIN
32733, and approved by TÜV are included in
the program. DIN models are also tested and
approved according to PED 97/23EC Cat. IV
Description
The P78 series pressure controls may be used
for control functions or limit functions, P78 Dual Pressure Control for
depending on model number. All models are Refrigeration
provided with alarm contacts (except P78ALA).
All standard models have phosphor bronze
bellows and brass pressure connections.
Models for use with ammonia are provided with
stainless steel bellows and connectors. Devices
conforming to DIN 32733 have a double
bellows on the high pressure versions. Their
IP54 classification means that these pressure
controls are suitable for almost all applications.
Adjustment
D
A - B closed
(fan 1 ON)
Fig.3a
Repair and replacement
Repair is not possible. In case of an improperly Line ~
A
M1 M2
Fig. 3b
Dual pressure controls for Non-corrosive refrigerants, built in accordance with DIN 32733 and
approved by TÜV Germany (Except P78PGB-*). LP Pmax.: 20 bar HP Pmax.:33 bar
Family Code Pressure Connection Left Side Right Side Contact Approved
function according
Style 5 Style 28 Range Diff. Range Diff. (Figure) to PED
(bar) (bar) (bar) (bar) 97/23EC
Ind. Code*** Bulk- Ind. Cat. IV
Pack. pack Pack.
P78LCW -9300 P78W -9320 -9800 -0.5 to 7 0.5 to 3 3 to 30 3 (fixed) 1 Yes
P78MCB -9300 P78B -9320 -9800 -0.5 to 7 0.5 to 3 3 to 30 Man. res.** 1 Yes
P78MCS -9300 P78S -9320 -9800 -0.5 to 7 0.5 to 3 3 to 30 Man. res.** 1 Yes
P78PGB -9300 P78P **** -9800 -0.5 to 7 Man. res.* 3 to 30 Man. res.** 1 Yes
P78PLM -9350 P78BS **** -9850 3 to 30 Man. res.** 3 to 30 Man. res.** 2 Yes
**** Can be set up for quantity orders
*** Wholesaler code only for individual pack
** Resetable at 3.5 bar below cut-out point
* Resetable at 0.5 bar above cut-out point
Dual pressure Fan cycling controls for Air-cooled condensers (Non-corrosive refrigerants)
HP Pmax.: 30 bar
Family Code Pressure Connection Left Side Right Side Contact Construction
Style 5 Style 30 Range Diff. Range Diff. function
(bar) (bar) (bar) (bar) (Figure)
Ind. Code*** Bulk- Ind.
Pack. pack Pack.
P78ALA -9351 P78A **** -9451 3.5 to 21 1.8 (fixed) 3.5 to 21 1.8 (fixed) 3 HP/HP
**** Can be set-up for quantity orders
*** Wholesaler code only for individual package
Note: 100 kPa = 1 bar ≈ 14.5 psi
Pressure connections
Accessories (optional)
Fig. 8
Dimensions (mm)
Fig. 12
Dimensions (mm)
53 70 9
25 48.5
13
5.5
16.5
1
8
2
25
55
80
3
10
4
10
110
61
75 23.5
122
6
53 6
21.5
26
1. 5
Fig. 13
Notes
Specifications
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond
these specifications, consult the local Johnson Controls office or representative. Johnson Controls shall not be liable for damages
resulting from misapplication or misuse of its products.
123456
12345
Ø 123456
A B
Applications Lubricant.
2. COMPOSITION/INFORMATION ON INGREDIENTS
3. HAZARDS IDENTIFICATION
General Remove victim immediately from source of exposure. General first aid, rest, warmth
and fresh air. Get medical attention if any discomfort continues.
Ingestion Rinse nose, mouth and throat with water. Do not give victim anything to drink if he is
unconscious. Do not induce vomiting. If vomiting occurs, the head should be kept low
so that stomach vomit doesn´t enter the lungs. If vomiting occurs, keep head low so
that stomach content doesn´t get into the lungs. Get medical attention.
Skin Wash skin with soap and water. Remove contaminated clothing. Get medical attention
if any discomfort continues.
Eyes Promptly wash eyes with plenty of water while lifting the eye lids. Continue to rinse for
at least 15 minutes. Get medical attention if any discomfort continues.
Special fire fighting procedures Move container from fire area if it can be done without risk. Cool containers exposed to
flames with water until well after the fire is out.
1 /5
14078 - FRASCOLD 32FC Revision date2003-01-13
Hazardous combustion products Fire or high temperatures create: Carbon monoxide (CO). Carbon dioxide (CO2).
Protective measures in fire Wear self-contained breathing apparatus (SCBA) to prevent contact with thermal
decomposition products.
Personal precaution in spill Wear appropriate personal protective equipment - see Section 8.
Spill cleanup methods Runoff or release to sewer, waterway or ground is forbidden. Clean area with an
appropriate cleanser. Do not let washing down water contaminate ponds or waterways.
Collect and reclaim or dispose in sealed containers in licensed waste. Inform
Authorities if large amounts are involved.
Usage precautions Avoid spilling, skin and eye contact. Ventilate well, avoid breathing vapours. Use
approved respirator if air contamination is above accepted level.
Storage precautions Keep in cool, dry, ventilated storage and closed containers. Suitable containers: Mild
steel.
Ingredient comments Occupational exposure standard for oil mist, mineral, is 1 mg/m3 (2001).
Protective equipment
Process conditions Use engineering controls to reduce air contamination to permissible exposure level.
The concentrations of air pollutants shall be kept as far under the given exposure
standards as possible. Unnecessary influence of pollutants shall be avoided and the
conditions shall be proper. Provide eyewash station.
Ventilation Well ventilated area.
Respirators Normally not required. CCROVDM, CCR with organic vapour cartridge and dust and
mist filter.
Protective gloves Use protective gloves made of: Nitrile. Polyvinyl chloride (PVC).
Eye protection Wear approved chemical safety goggles where eye exposure is reasonably probable.
Other Protection Wear appropriate clothing if necessary.
Hygienic work practices Wash at the end of each work shift and before eating, smoking and using the toilet.
2 /5
14078 - FRASCOLD 32FC Revision date2003-01-13
Appearance Fluid.
Colour Tan.
3 /5
14078 - FRASCOLD 32FC Revision date2003-01-13
Acute fish toxicity LC50 (rainbow trout): >1000 mg/l (96 hour).
IC50 (Ps.putida): >10 mg/l (6 hour).
Disposal methods Dispose of at an approved land disposal site in accordance with local authority
requirements.
Chemicals must be disposed of in compliance with the respective national or local
regulations to ensure proper disposal.
Waste class Not special waste.
ROAD TRANSPORT:
4 /5
4. Compressor unit, general construction
Børresen Cooltech AS
Rosenholmveien 13, Postboks 130 Holmlia N-1203 OSLO
Telefon: 2316 9400 Faks 2316 9401
C€
1 General
The unit is designed and dimensioned to fulfil the standards for Norwegian refrigeration
norms, best engineering practice and the recommendations from component manufacturers.
It is composed of equipment which has previously been CE-marked, and which have been
dimensioned and matched for optimum performance.
The product is dimension for maximum pressure of 25 bar. If this is exceeded, the pressure
relief valves will open. The pressure relief valves are mounted on the water cooled condenser
or liquid tank. Other safety equipment includes pressostats to stop the compressors if set
pressure is exceeded.
The relevant tables for suppliers of refrigerants have been used for dimensioning pipes.
No pipe conduits in the unit are larger than DN100.
1.6 Frame
The compressor unit frame is dimensioned and designed for lifting using forks and
not using lifting gear.
5. Compressor unit specific design details
Børresen Cooltech AS
Rosenholmveien 13, Postboks 130 Holmlia N-1203 OSLO
Telefon: 2316 9400 Faks 2316 9401
Techn. dpt .
List of Components
Piping dimensions
Pos.no. Dimension Description Material Pipe
Pipe/Rør 1 2 5/8” High pressure pipe Cu
Pipe/Rør 2 1 3/8” Fluid pipe Cu
Pipe/Rør 3 3 1/8” Suction gas pipe Cu
Pipe/Rør 4 2 1/8” Suction gas pipe, compressor Cu
Pipe/Rør 5 2 1/8” High pressure pipe, compressor Cu
Components
Pos no. Description Type BC Part no.
1 Compressor Z 40-126 3/690V/60HZ 3000504
2 Oil separator S-5413CE 5300024
3 Shell and tube condenser Onda CT417CE 63,4 ltr. 3500400
4 Filter, fluid pipe V8144CE 1-3/8” 5300561
5 Sight glass, fluid pipe SA-211 4060860
6 Ball valve, fluid pipe Henry 900511-CE 1-3/8”ld 5351307
7 Solenoid valve EVR32 4150624
8 Expansion valve TEZ55 R407 4120050
9 Vibration damper, pressure pipe VTG54- 2-1/8” 5500060
10 Pressure relifevalve 5244 24,8 bar-CE 1"MPT-1"FPT 5317070
11 Pressure switch LP\HP P78MCB-9300 4511710
12 Evapourator Onda MPE390/2 3500100
13 Suction line accumulators S-7791CE 9001250
14 Non return valve NRVH 35S 4151251
15 Oil reservoir S-9109 7,6L. 5300312
16 Pressure valve S-9104 0,3bar 5300315
17 Oil filter S-4005 5300301
18 Sight glass, oil return SGN 10 4150820
19 Shut off valve, oil return BML 10 4151321
20 Oil level regulator S-9510 5300200
21 Solenoid 10W 240V 50Hz 4150502
22 Shut off valve M2-264 5010370
23 Low pressure gauge 825-G-BC/447 9000265
24 High presure gauge 823-G-BC/447 9000266
25 Oil Pressure gauge Refco R3-248-10 1-10 Bar 9000230
26* Oil differential pressure switch DELTA-P 3200003
27** Crankcase oilheater 150W 230V/1ph/50-60Hz 3200816
* Supplied with compressor ** Not drawn in P&ID
Børresen Cooltech AS
Rosenholmveien 17, Postboks 130 Holmlia, N-1203
Phone: 0047 2316 9400 Fax: 0047 2316 9401 Norway >
POS N:O DESCRIPTION MADE BY TYPE NOTE NUMBER REMARK
AS 1 Enclosure Eldon Vasa MAS0608030 HxBxD 600x800x300 E2516438 Plate
AS ) 1 Flange Knock-out Eldon Vasa AFK22 E2516542
C 1-2 2 Contactor Telemecanique LC1-D80 P7 230VAC 3 Pol AC3 80A E3233094 1 NO/NC
F 1-3 3 Miniature circuit breaker Moeller PLSM-C2/2-MW 2A 10kA 2 pol E2141602 C Karakteristik
H 1-2 2 Operating time Telemecanique XBKH70000002M 230VAC 7 digits 1/100h
MS 1 1 Main switch Technoelectric VC2P 160A 3 Pol E3174044
MS ) 1 1 Handle Technoelectric ( VC1-2P/F ) Dörrförregl. E3174090
MS ) 1 1 Shaft Technoelectric ( VC1-2P/F ) 300mm. E3174094
MS ) 1 1 Screen-protect Technoelectric ( VC2P ) 6018061
PE 1 Earth bar BS-elcontrol BS250
Q 1-2 2 Motor protection Telemecanique GV3P50 37-50 A 22 kW 50kA E3116405
Q 3 1 Motor protection Telemecanique GV2-ME05 0,63-1 A 0,25 kW E3116508
Q) 1-2 2 Auxilliary motor prot. Telemecanique GV-AE11 1 NO 1 NC 2 Pol E3116636
R 1-7 7 Relay Schrack PT370T30 230VAC 10A 3 Pol E4020984 LED-ind.
R) 1-7 7 Relay socket Telemecanique RXZE2S111M 14-PIN E4027816
RC 1 1 Microchiller Carel MCH2001030 24VAC 1416258
S 1-2 2 Switch Kraus & Naimer CH10 A200E 0-1 10A 1 Pol
T 1 1 Transformer Noratel SU120C-660230 660-690/230VAC 500VA
T 2 1 Transformer Carel TRA 12 220/12V 3VA 1416093
TM 1-2 2 Termistor Kriwan INT69VS
REQ. Terminal Weidmüller
BREVIK OFFSHORE TJ
DATE ARCHIVE