Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT

HVAC GENERAL NOTES

THE FOLLOWING NOTES SHALL BE APPLICABLE FOR ALL HVAC DRAWINGS

S.NO. DESCRIPTION

01

02 ALL FRESH & EXHAUST AIR LOUVERS SHALL HAVE BRASS INSECT MESH 26g 20" MESH

03 DUCT SIZES SHOWN AS CLEAR INSIDE SIZES.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR SHIFTING OF A/C UNITS FROM GROUND FLOOR
04 TO THEIR RESPECTIVE LOCATION INCLUDING OWNER SUPPLIED EQUIPMENTS.

THE CONTRACTOR SHALL COORDINATE THE FIXING OF AIR DEVICES WITH OTHER CONTRACTORS
05 AND WOULD ADJUST THE LOCATION OF AIR DEVICES WHEREVER REQUIRED

THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONSTRUCTION OF EQUIPMENT


06 FOUNDATION WHICH WILL BE MADE IN 1:2:4 R.C.C

PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT


PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT

07 THE CONTRACTOR SHALL CHECK THE SITE AND PREPARE THE SHOP DRAWING ACCORDING
TO ACTUAL SITE CONDITIONS BEFORE COMMENCEMENT OF WORKS.

08 ALL SUPPLY AND RETURN AIR DUCTS SHALL BE INSULATED

09 INSPECTION HOLES SHALL BE PROVIDED IN AIR DUCTS.

10 THE SLAB OPENING SHALL BE 4" LARGER THAN THE DUCT SIZES MARKED ON THE DRAWING .

THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SUPPLYAND INSTALLATION OF M.C.C. AND
11 ELECTRIC WIRING BETWEENM.C.C AND EQUIPMENT. THE EMPLOYER SHALL SUPPLY THE
ELECTRIC SUPPLY POINTS AS SHOWN IN THE DRAWINGS.

12 GAS WELDING SHALL BE DONE ONLY BY QUALIFIED WELDER AS PER SPECIFICATION.

ALL PIPING SHALL BE PROPERLY SUPPORTED ON CLAMS, HANGERS, ETC. THE SUPPORTS SHALL
13 PERMIT FREE EXPANSION CONTRACTION.

14 ALL THE FLOOR SUPPORTS SHALL BE PROVIDED WITH SPRING TYPE VIBRATION ISOLATORS.

15 THE PIPING SHALL BE ASSEMBLED IN SUCH A MANNER THAT IT WILL AVOID THE UNDUE STRAIN.

THE PIPES SHALL BE PROPERLY INSTALLED TO SECURE EASY CIRCULATION AND PREVENT
16 NOISE AND WATER HAMMER.

17 ALL ELBOWS SHALL BE LONG RADIUS TYPE.

18 ALL INSULATED PIPES SHALL BE JACKETED BY 26 GAUGE G.I. SHEET.

19 ALL RAWAL BOLTS SHALL BE OF HILTI MAKE.

TENDER DRAWING
CLIENT'S NAME : DRAWING TITLE : REV REVISIONS DATE

NBS
HVAC, MECHANICAL & PLUMBING CONSULTANTS
DESIGN TEAM:
MR. RAHEEL MEGHANI
PROJECT'S NAME :
Y.H. ASSOCIATES SCALE:- N.T.S
REVISION:

0
NEW BUILD SOLUTIONS
DIAMOND SUPERMARKET ARCHITECTURE, PLANNING, INTERIOR, 308 & 309, 3rd FLOOR, ANUM ESTATE, GENERAL NOTES DATE:- 01-03-2019
DRAWING NO.

SHAHRAH-E-FAISAL, KARACHI-75350, PAKISTAN PHONE NO : +


PROJECT'S ADRESS :- PROJECT MANAGEMENT 921 - 4315071 & 2 ; DRAWN BY: U.F 19/09/119
PLOT # A-913, SECTOR 11-B, F-61, 1st FLOOR, GLASS TOWER, CLIFTON, KARACHI FAX NO : + 921 - 4382527
T: +92 331 3520462 E: abdullah@semcpak.com EMAIL: info@yhassociates.com
NORTH KARACHI. PROJECT NO: 19-09-DSM

PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT