NIMAC

VRLA BATTERY 6-GFM-150J 12V150A h

SLA BATTERY—GEL TECHNOLOGY SERIES

Specification
Nominal Voltage 12V
Number of cell 6
Nominal Capacity 150Ah@10hr-rate (15.0A to 1.80V/cell @25℃)
Weight Approx.42.0Kg
Terminal M8,Φ=16&18

Container Material ABS (UL94-HB), Flammability resistance Introduction


of UL94-V1 can be available upon request.
The NIMAC GEL-TECH batteries designed
154.2Ah 20hr-rate (7.71A to 1.80V/cell @25℃) with 15+ years service life. The SOLID-GEL
150.0Ah 10hr-rate (15.0A to 1.80V/cell @25℃) system can avoid corrosion and stratification.
Rated Capacity 125.5Ah 5hr-rate (25.10A to 1.75V/cell @25℃) The special separator can properly prevent
91.5Ah 1hr-rate (91.5A to 1.60V/cell @25℃) short-circuit. It can offer high deep discharge
Max. Discharge Current ability, super thermal stability, good recovery-
750A(5sec)
ability after deep discharging. The deep dis-
Internal Resistance Approx.3.4mΩ(Fully charged) charge cycles of GEL-TECH batteries can be
more than 30% compared with other normal
Discharge: -40 ℃~60 ℃ AGM batteries.
Operating Temp. Range Charge : -20℃~50℃
Storage : -40℃~60℃ Applications
Charging Current: ≤30.0A Auto control system &ATM machine
Cycle Use Voltage:14.2V ~14.4V Electronic apparatus and equipment
Temperature compensation:-30mV/℃ Emergency light & Emergency backup
power supply & Alarm/Security system
Charging Current:No limit
Standby Use Voltage:13.6V ~13.8V Power generation system (solar and
Temperature compensation:-20mV/℃ wind power system,etc.)
o
Communication power & DC power
Self-Discharge less than 1% at 25C Electric Power System(EPS)
Design Life 15 years (floating charge) Uninterruptable Power System (UPS)
…………

Dimensions 483
Ø16

240 5
Length 483±1mm (19.05 inches)
170

Width 170±1mm (6.69 inches) M8


Heigth 240±1mm (9.45 inches)
Total Heigth 240±1mm (9.45 inches)
Unit: mm

Constant Current Discharge Characteristics: A (25℃)


F. V/Time 5min 10min 15min 30min 1h 2h 3h 4h 5h 8h 10h 20h
1.60V/cell 496.7 355.9 259.0 162.6 91.89 52.46 36.90 30.54 25.72 18.26 15.72 8.314

1.65V/cell 483.4 338.7 253.7 159.9 91.47 52.06 36.76 30.39 25.56 18.11 15.57 8.163

1.70V/cell 455.6 326.7 249.7 158.5 90.62 51.67 36.47 30.25 25.41 17.96 15.42 8.012

1.75V/cell 409.1 301.5 237.7 154.5 89.77 51.28 36.33 29.97 25.11 17.81 15.27 7.861

1.80V/cell 369.2 274.9 219.1 147.7 87.65 50.36 35.34 29.26 24.66 17.51 15.12 7.710

1.85V/cell 321.4 245.7 196.6 138.4 83.27 48.12 33.79 27.85 23.60 16.77 14.66 7.256

Constant Power Discharge Characteristics: W (25 ℃)


F. V/Time 5min 10min 15min 30min 1h 2h 3h 4h 5h 8h 10h 20h
1.60V/cell 4731 3459 2547 1835 1051 603.5 425.8 352.9 297.7 211.8 176.8 93.38

1.65V/cell 4634 3304 2494 1812 1046 601.1 425.0 352.0 295.9 211.0 175.0 92.47

1.70V/cell 4375 3194 2460 1791 1038 595.6 422.4 350.3 295.0 209.2 174.1 91.56

1.75V/cell 3939 2951 2346 1750 1028 590.1 419.9 347.8 292.2 207.4 172.2 90.66

1.80V/cell 3543 2680 2156 1670 1003 581.4 409.7 338.4 287.7 202.9 170.4 89.75

1.85V/cell 3059 2380 1925 1565 950.0 554.6 389.3 322.3 273.2 195.8 165.0 86.12

1
Discharge Characteristics Curve Charging Characteristics Curve

Temperature:25℃
(V/cell) Constant Voltage Change Characteristic
Charge
Volume
Charge 2.23V( /Cell,25℃) Charging
Current
2.16 Voltage
% (V)
Terminal Voltage(V)

130
2.00
120 2.40 0.1
110 Charged Volume
1.84 100
0.1C 0.05C 2.30 0.08
90
1.68 0.4C 0.2C 80 Charging voltage
0.6C
70 2.20 0.06
3C 2C 1C
60 After 50% Discharge
1.52
50 After 100% Discharge
2.10 0.04
40
1.36
30
2.00 0.02
20
0
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 10 Charging Current
min h 0
0 4 8 12 16 20 24 28 32 36 40
0

Discharge Time Charging Time(h)

Cycle life in relation to depth of Discharge Temperature effects on Capacity

120 120

100 100 A
0.1C
A
0 .2 C

Capacity(%)
80 80
Capacity(%)

60 60
100% 50% 30%
DOD DOD DOD 1.0C
A A
2 .0 C
40 40 A
3 .0C
Testing condition(25℃ )
20 Charging volume:120% of discharged capacity 20

0 0
300 600 900 1200 1500 1800 2100 -20 -10 0 10 20 30 40 50

Number of cycles Temperature(℃)

Relationship between charging voltage and temperature Self-discharge Characteristics


V/Cell

No supplementary
100 charge required
(Carry out supplementary
2 .6 10℃ charge before use if 100%
capacity is required.)
Remaining Capacity(%)

80
CYCL
2 .5 E US 20℃
E
Supplementary charge
60
2 .4 required before use.
STAN 40℃ 30℃
DB Y
2 .3 U SE 40
Supplementary charge
may fail to recoverthe
2 .2 20 capacity.The battery should
never be left standing till
this is reached
0
-40 -20 0 10 20 30 40 60 0
2 4 6 8 10 12
Ambient Temperature(℃) Storage time(months)

Temperature effects on Float life Life Characteristics of Standby use

120
Life expectancy (years)

100
Charging voltage:2.23V/Cell
20 80
Capacity(%)

Testing condition
60 Floating voltage:2.23V/Cell
10 Ambient temperature:25℃

40
5
20

0 10 20 30 40 50 0 3 6 9 12 15
Temperature (℃) Life expectancy (years)

12