Professional Documents
Culture Documents
Karvena-Head Sluice
Karvena-Head Sluice
500 500
9500 23940 10000 30000 10000 30000 8125 28875 6000 21000 5000 25000 5000 25000 5000 19600 9500
13740
13530
1600
1400
1200
1200
3000
VALUE OF n 0.0180
3500
VELOCITY 1.892 m/sec
2500 2500
4700
2950
2950
2950
2950
A B
26000
26000
4700
900
900
900
900
3000
2950
2950
2950
24000 8000
4700
3000
1200
1200
1400
1600
13530
13740
14530
14740
500
5500
7000
NOTES: 13) THE BACK FILLING BEHIND HEAD WALLS, WINGS & RETURNS SHALL BE CARRIED OUT WITH SOILS
1) ALL DIMENSIONS ARE IN MILLIMETRES AND LEVELS IN METRES. ONLY FIGURED DIMENSIONS SHALL OF HEAD WALLS, WINGS & RETURNS AS SHOWN IN THE DRAWING SHALL BE FORMED IN STEPS.BACK
BE CONSIDERED. FILLING SHALL BE DONE SIMULTANEOUSLY WITH RAISING OF WALL.
2) THE DRAWINGS IS BASED ON THE DATA FURNISHED BY CE/MBNR THROUGH LETTER NO 14) THE HEAD WALL, WINGS & RETURNS ARE PROPOSED CC M15 GRADE CONCRETE WITH 100 DIA WEEP HYDRAULIC PARTICULARS:
i) CE/IRR/MBNR/OT2/TS2/Pkg.15/2/2021, DT:01.05.2021 HOLES AT 1500 C/C(STAGGERED) DULY PROVIDING INVERTED FILTERS IN RESPECT OF D/S HEAD WALL
ii) CE(I)/MBNR/DCE/OT1/TS6/P-15/OT/1050, DT:28.10.2021 ,WINGS & RETURNS . THE WEEP HOLES ARE PROVIDED ABOVE F.S.L OF CANAL. RESERVOIR :
3) HEAVY EARTH MOVING MACHINARY SHALL NOT BE ALLOWED DIRECTLY OVER BARREL ROOF TBL +536.000
15) CONTRACTION JOINTS ARE TO BE PROVIDED IN BETWEEN THE WELL AND BARREL & UPSTREAM /
DURING EARTH DAM FORMATION. DOWNSTREAM WINGS WITH PVC WATER STOPS AS INDICATED IN THE DRAWING NOT MORE THAN 24.0 M
FRL +533.000
C/C.
4) GRADING OF CONCRETE, WORKABILITY & WORKMANSHIP SHALL CONFORM TO I.S. 456-2000.
MWL +533.900
16) THE BARREL REINFORCEMENT IS CONTINUED IN THE WELL PORTION AND THE STEINING
5) THE REINFORCEMENT IS OF HIGH YIELD STRENGTH DEFORMED BARS (GRADE Fe 500) CONFORMING TO REINFORCEMENT IS ANCHORED INTO THE BOTTOM SLAB OF BARREL AS SHOWN IN THE DRAWING. THE
I.S 1786-1985 (REAFFIRMED IN 1990). THE CLEAR COVER FOR REINFORCEMENT OF BARREL, WELL & CUT BARREL AND WELL SHALL BE CONSTRUCTED SIMULTANEOUSLY IN THIS PORTION. MDDL(FOR HEAD SLUICE) +495.200 m (CONSIDERED)
OFF COLLARS IS 40 MM. REFERENCE DRAWINGS:
6) THE BARREL IS OF 1200, 1400, 1600 THICK FOR ZONES I,II AND III RESPECTIVELY IN RCC M30 GRADE
17) ALL THE VULNERABLE AND SEEPAGE ENTRY POINTS ON U/S SIDE INCLUDING EXCAVATED
FOUNDATIONS AT WELL, WINGS RETURNS AND BELOW THE BARREL SHALL BE SEALED EFFECTIVELY
CANAL:
DRG. NO: CE/CDO/SE2/EE1/Pkg-15/PRLIS/26/02/2022 GOVERNMENT OF TELANGANA
WITH 20 MSA AND REINFORCEMENT AS INDICATED IN THE SCHEDULE GIVEN IN SEPARATE DRAWING. DISCHARGE (R/D) 254.850/256.190 cumecs DRG. NO: CE/CDO/SE2/EE1/Pkg-15/PRLIS/26/03/2022
R.C.C. CUT OFF COLLARS AT 8000 INTERVALS ARE PROVIDED IN RCC M30 GRADE WITH 20 MSA. THE
WITH LEAN CONCRETE.
DRG. NO: CE/CDO/SE2/EE1/Pkg-15/PRLIS/26/04/2022 IRRIGATION AND CAD DEPARTMENT
WEARING COAT SHALL BE LAID MONOLITHIC WITH THE BARREL CONCRETE IN CC M35 GRADE WITH 20
MSA.
18) THE TOP SLAB OF THE BARREL SHALL CONTINUE IN THE WELL PORTION ALSO WITH OPENING FOR CBL +488.500 DRG. NO: CE/CDO/SE2/EE1/Pkg-15/PRLIS/26/052022 CENTRAL DESIGNS ORGANISATION
TWO GATE GROOVES.
7) ALL THE MATERIALS AND WORKMANSHIP SHOULD STRICTLY CONFORM TO LATEST BIS STANDARDS
FSL +493.200 PRLIS-HEAD SLUICE AT KM 11.800-PACKAGE-15
19) NECESSARY APPROACH CHANNEL HAS TO BE EXCAVATED ALONG THE SHORTEST POSSIBLE LENGTH
8) COARSE AND FINE AGGREGATES USED SHALL CONFORM TO I.S 383-1970 (REAFFIRMED IN 1997) AND
DULY MAINTAINING STRAIGHT ALIGNMENT AS FAR AS POSSIBLE FROM THE END OF UPSTREAM FSD 4.70 m KURUMURTHYRAYA RESERVOIR(KARVENA)
TRANSITION. THE EXCAVATED SOIL SHALL BE DUMPED AT FAR OFF PLACES AND SHOULD NOT CAUSE
MAXIMUM SIZE OF AGGREGATE USED SHALL BE 40 MM WELL GRADED FOR ALL PCC WORKS AND 20MM ANY SILTING PROBLEM TO THE APPROACH CHANNEL FREE BOARD 0.90 m GENERAL PLAN AND SECTION
FOR ALL R.C.C. WORKS.
20) THE COT SHALL BE PRELOADED BELOW THE BARREL FOUNDATION AT THE SLUICE LOCATION BED WIDTH 26.00 m DRAWN BY
9) SUITABLE SIZE AND NUMBER OF DOWEL BARS SHALL BE PROVIDED FOR PROPER BOND BETWEEN RECOMMENDED BY
BEFORE EXECUTION OF THE HEAD SLUICE.
FIRST AND SECOND STAGE CONCRETE.
SIDE SLOPES 1.5:1
21) THE FOUNDATION SHALL BE GOT VERIFIED BY THE GEOLOGIST OF G.S.I AND THE
10) IT SHALL BE ENSURED THAT THERE WILL NOT BE ANY DISCONTINUITY IN THE FOUNDATION RECOMMENDATIONS OF THE GEOLOGIST TO BE CARRIED OUT. ANUSHA.E A.E.E.
BED FALL 1 IN 6200
TREATMENT i.e. GROUTING etc. OF EARTH DAM.
CHECKED BY
22) ON THE SIDES AND TOP OF BARREL 1000 THICK CLAYEY SOILS SHALL BE LAID WITH MOISTURE VALUE OF n 0.0180 C.SRINIVAS SE-II/CDO
11) THE FOUNDATION TREATMENT ADOPTED ON EITHER SIDE OF SLUICE FOR IMPROVED EARTH DAM CONTENT SLIGHTLY HIGHER THAN O.M.C. AND EFFECTIVELY COMPACTED TO PROCTOR'S DENSITY.
SHALL BE CONTINUED BELOW THE HEAD SLUICE PORTION ALSO. APPROVED BY
VELOCITY 1.660 m/sec V.RAMAKRISHNA D.E.E.
23) THE PROJECT AUTHORITIES ARE REQUESTED TO SATISFY THEM SELVES ABOUT THE PROPOSAL AND
12) DIMENSIONS OF GATE GROOVES,2ND STAGE CONCRETE, HOIST PLATFORM DETAILS ETC., INDICATED LOCATION OF THE LEFT HEAD SLUICE WITH RESPECT TO THE SITE CONDITIONS ACTUALLY EXISTING SUBMITTED BY
IN THE DRAWING ARE TENTATIVE AND ARE AS PER MECHANICAL DRAWINGS TO BE FINALISED BEFORE TAKING UP EXECUTION.
SEPARATELY.
24) MINIMUM DRIVING HEAD OF 2.00 M IS ADOPTED IN THE DESIGN. K.DAYAKAR REDDY DIV-1 Z.SRINIVASA RAO CE/CDO/HYD
25) OVERBREAKAGES SHALL BE FILLED WITH CCM15 GRADE OF CONCRETE. FILE NO: CE/CDO/SE2/EE1/Pkg-15/PRLIS/HS@11.8/2021 AUG 2022 DWG.NO.: CE/CDO/SE2/EE1/Pkg-15/PRLIS/ /01/2022
NOTES
1. ALL DIMENSIONS ARE IN MILLIMETRES AND LEVELS ARE IN METRES.
ONLY FIGURED DIMENSIONS SHALL BE CONSIDERED.
500
2. THE DIMENSIONS OF GATE GROOVES, 2ND STAGE CONCRETE, HOIST
PLATFORM DETAILS ETC., INDICATED IN THE DRAWING ARE TENTATIVE AND
500 REFER SEPARATE MECHANICAL DRAWINGS FOR DETAILS.
3. CONTRACTION JOINTS IN BARREL SHALL BE PROVIDED AT THE SPECIFIED
LOCATIONS WITH PVC WATER STOP AS INDICATED IN THE DRAWING AT NOT
MORE THAN 25.0 M C/C..
9660
C.C M15
9170
C.C M15
400 400
400 400 OVERBREAKAGES IN CC M15
OVERBREAKAGES IN CC M15
3260
1000 THICK 1000 THICK +488.500
CLAY COVER CLAY COVER
3700 4100
BARREL CONCRETE IN RCC M30 BARREL CONCRETE IN RCC M30
GOVERNMENT OF TELANGANA
IRRIGATION AND CAD DEPARTMENT
600
M15
KURUMURTHYRAYA RESERVOIR(KARVENA)
DRAWN BY
RECOMMENDED BY
OVER BREAKAGES FILLED IN CC M15 GRADE
500
ANUSHA.E, A.E.E.
500 CHECKED BY
C.SRINIVAS, SE-II/CDO
600
600
BITUMEN FILLER
12 DIA RODS (6 NOS)
R C C M30
2000
2000
12 DIA RODS
4700
4700
150 WIDE PVC
WATER STOP
WC M35
150
150
2000
2000
R C C M30 M30 200 THICK LEVELLING
COURSE IN CC M10
200
26100
1850
3600
1750
650
1800
1800
900
70 70 70 200 900
SERVICE GATE VENT SERVICE GATE VENT SERVICE GATE VENT
250
750
1750
950
950
12500
3500
1750
70 70 70 70
900
900
70
EMERGENCY GATE VENT EMERGENCY GATE VENT EMERGENCY GATE VENT
750
3600
3600
GOVERNMENT OF TELANGANA
IRRIGATION AND CAD DEPARTMENT
CENTRAL DESIGNS ORGANISATION
PRLIS-HEAD SLUICE AT KM 11.800-PACKAGE-15
KURUMURTHYRAYA RESERVOIR(KARVENA)
3000 4700 3000 4700 3000 4700 3000 DETAILS OF WELL AND CUTOFF COLLARS
DRAWN BY
RECOMMENDED BY
ANUSHA.E, A.E.E.
CHECKED BY
C.SRINIVAS, SE-II/CDO
8850
11.THE AREA TAKEN UP FOR CONSTRUCTION FIRST OF ALL EXCAVATED
UPTO LEVEL ABOUT 15CM HIGHER THAN THE REQUIRED LEVELS. THE
BALANCE EXCAVATION IS THEN TO BE PRECISELY OBTAIN THE DERIVED
LEVELS. ANY EXCESS EXCAVATION HAS TO BE FILLED WITH M15 GRADE
CONCRETE.
12.IF THE WATER TABLE IS ABOVE THE EXCAVATION AREA, DE-WATERING OF
150
THE AREA SHALL BE DONE TO GRADUALLY LOWER THE WATER TABLE AND
BAR SHALL BE KEPT BELOW THE EXCAVATION LEVELS TILL THE CONCRETE LAID
BAR DETAILS BAR TYPE BAR SHAPE
NO. HAS ATTAINED SUFFICIENT STRENGTH.
13.BEFORE PLACING THE REINFORCEMENT IN POSITION, THE SURFACE OF
2000
E3 MAIN REINFORCEMENT
C3
I3
F3 MAIN REINFORCEMENT
G3 MAIN REINFORCEMENT
D3
H3 DISTRIBUTION REINFORCEMENT
H3 H3
E3 F3 G3 I3 DISTRIBUTION REINFORCEMENT
B3
J3 J3 HAUNCH BARS
I3
GOVERNMENT OF TELANGANA
A3 IRRIGATION AND CAD DEPARTMENT
CENTRAL DESIGNS ORGANISATION
PRLIS-HEAD SLUICE AT KM 11.800-PACKAGE-15
KURUMURTHYRAYA RESERVOIR(KARVENA)
ANUSHA.E, A.E.E.
CHECKED BY
C.SRINIVAS, SE-II/CDO
8050
11.THE AREA TAKEN UP FOR CONSTRUCTION FIRST OF ALL EXCAVATED
UPTO LEVEL ABOUT 15CM HIGHER THAN THE REQUIRED LEVELS. THE
BALANCE EXCAVATION IS THEN TO BE PRECISELY OBTAIN THE DERIVED
LEVELS. ANY EXCESS EXCAVATION HAS TO BE FILLED WITH M15 GRADE
CONCRETE.
12.IF THE WATER TABLE IS ABOVE THE EXCAVATION AREA, DE-WATERING OF
150
THE AREA SHALL BE DONE TO GRADUALLY LOWER THE WATER TABLE AND
BAR SHALL BE KEPT BELOW THE EXCAVATION LEVELS TILL THE CONCRETE LAID
BAR DETAILS BAR TYPE BAR SHAPE
NO. HAS ATTAINED SUFFICIENT STRENGTH.
1600
E3 MAIN REINFORCEMENT
C3 C3 C3 C3
F3 MAIN REINFORCEMENT
I3
E3 G3 MAIN REINFORCEMENT
E3
D3 H3 DISTRIBUTION REINFORCEMENT
F3 E3
H3 I3 DISTRIBUTION REINFORCEMENT
E3 F3 I3
G3 G3 G3 G3
G3
B3 J3 HAUNCH BARS
J3
E3 E3
GOVERNMENT OF TELANGANA
A3 I3 A3 A3 IRRIGATION AND CAD DEPARTMENT
CENTRAL DESIGNS ORGANISATION
PRLIS-HEAD SLUICE AT KM 11.800-PACKAGE-15
KURUMURTHYRAYA RESERVOIR(KARVENA)
ANUSHA.E, A.E.E.
CHECKED BY
C.SRINIVAS, SE-II/CDO
UPTO LEVEL ABOUT 15CM HIGHER THAN THE REQUIRED LEVELS. THE
7650
BALANCE EXCAVATION IS THEN TO BE PRECISELY OBTAIN THE DERIVED
LEVELS. ANY EXCESS EXCAVATION HAS TO BE FILLED WITH M15 GRADE
BAR CONCRETE.
BAR DETAILS BAR TYPE BAR SHAPE
NO. 12.IF THE WATER TABLE IS ABOVE THE EXCAVATION AREA, DE-WATERING OF
THE AREA SHALL BE DONE TO GRADUALLY LOWER THE WATER TABLE AND
SHALL BE KEPT BELOW THE EXCAVATION LEVELS TILL THE CONCRETE LAID
150
F2 MAIN REINFORCEMENT
C2 C2 C2 C2
I2 G2 MAIN REINFORCEMENT
E2 E2 H2 DISTRIBUTION REINFORCEMENT
E2 I2 DISTRIBUTION REINFORCEMENT
D2 F2
G2 H2 G2
E2 F2 I2 J2 HAUNCH BARS
G2
B2 G2
J2
E2 E2
GOVERNMENT OF TELANGANA
IRRIGATION AND CAD DEPARTMENT
A2 I2 A2 A2 CENTRAL DESIGNS ORGANISATION
PRLIS-HEAD SLUICE AT KM 11.800-PACKAGE-15
KURUMURTHYRAYA RESERVOIR(KARVENA)
DRAWN BY
RCC DETAILS OF BARREL-Z2 -30.9m RECOMMENDED BY
ANUSHA.E, A.E.E.
CHECKED BY
C.SRINIVAS, SE-II/CDO
7250
TO THE RELEVANT B.I.S SPECIFICATIONS ISSUED FROM TIME TO TIME.
11.THE AREA TAKEN UP FOR CONSTRUCTION FIRST OF ALL EXCAVATED
A1 MAIN REINFORCEMENT UPTO LEVEL ABOUT 15CM HIGHER THAN THE REQUIRED LEVELS. THE
BALANCE EXCAVATION IS THEN TO BE PRECISELY OBTAIN THE DERIVED
LEVELS. ANY EXCESS EXCAVATION HAS TO BE FILLED WITH M15 GRADE
B1 MAIN REINFORCEMENT CONCRETE.
150
MAIN REINFORCEMENT
HAS ATTAINED SUFFICIENT STRENGTH.
13.BEFORE PLACING THE REINFORCEMENT IN POSITION, THE SURFACE OF
REINFORCEMENT SHALL BE CLEANED OF ALL RUST, SCALES AND OTHER
D1 MAIN REINFORCEMENT OBJECTIONABLE SUBSTANCES.
G1 MAIN REINFORCEMENT
C1 C1 C1 C1
I1 H1 DISTRIBUTION REINFORCEMENT
I1 DISTRIBUTION REINFORCEMENT
E1
E1
D1 J1 HAUNCH BARS
H1
F1 E1
E1 F1 G1 G1 I1
G1 G1 G1
B1
J1
E1 E1
A1 I1
GOVERNMENT OF TELANGANA
IRRIGATION AND CAD DEPARTMENT
CENTRAL DESIGNS ORGANISATION
PRLIS-HEAD SLUICE AT KM 11.800-PACKAGE-15
KURUMURTHYRAYA RESERVOIR(KARVENA)
DRAWN BY
RECOMMENDED BY
ANUSHA.E, A.E.E.
CHECKED BY
C.SRINIVAS, SE-II/CDO
2350
9. THIS DRAWING IS EXCLUSIVELY ISSUED FOR RC DETAILS ONLY.
FRL +533.000
10. SPECIFICATIONS FOR ALL MATERIALS AND WORKMANSHIP SHALL CONFIRM TO THE RELEVANT B.I.SSPECIFICATIONS ISSUED
FROM TIME TO TIME.
T32 @90 C/C T36 @90 C/C T32 @90 C/C
3000
11. ANY EXCESS EXCAVATION HAS TO BE FILLED WITH LEAN CONCRETE FOR FOUNDATIONS IN ROCK WITH M15 CONCRETE.
12. IF THE WATER TABLE IS ABOVE THE EXCAVATION AREA, DE-WATERING OF THE AREA SHALL BE DONE TO GRADUALLY
LOWERS THE WATER TABLE AND SHALL BE KEPT BELOW THE EXCAVATION LEVELS TILL THE CONCRETE LAID HAS ATTEND
T32 @160 C/C T32 @120 C/C T32 @160 C/C
SUFFICIENT STRENGTH.
3000
13. BEFORE PLACING THE REINFORCEMENT IN POSITION, THE SURFACE OF REINFORCEMENT SHALL BE CLEANED OF ALL RUST,
3000 4700 3000 4700 3000 4700 3000 SCALES AND OTHER OBJECTIONABLE SUBSTANCES.
D D
14.
3000
700 700 15. LAPS SPLICING SHALL CONFIRM TO IS-465:2000 AND LAPS IN REGIONS OF MAXIMUM STRESS SHALL BE AVOIDED (SUCH AS
CENTRAL LOCATIONS FOR BOTTOM MAIN BARS AND AT WALL FACE LOCATIONS FOR TOP MAIN BARS).
16. SUITABLE CHAIR , SPACERS SHALL BE PROVIDED TO KEEP THE REINFORCEMENT BAR IN POSITION BEFORE CONCRETING.
17. WELDING OF REINFORCEMENT BARS SHALL NOT BE PERMITTED.
3000
600 T16 @150 C/C T16 @150 C/C 18. THE MECHANICAL CONNECTIONS SUCH AS COUPLERS TO BE USED SHALL BE IN CONFIRMATION TO SP-24.THE ENGINEER IN
T25 @120 C/C T25 @120 C/C CHARGE SHALL BE ENSURED THE STRENGTH AND PLACEMENT REQUIREMENTS AS PER SP-34.
19. REFER SEPARATE DRAWING FOR THE DETAILS OF MECHANICAL GATE GROOVE SIZES AND SECONDARY CONCRETE IN
3000
GROOVES.
20. THE STRESS AT THE FOUNDATION LEVEL IS 550 KN/M2, PLATE LOAD TEST SHALL BE CONDUCTED FOR LOAD UPTO 825 KN/M2
900
300
+515.000 +515.000
BIS-CODES:
T32 @90 C/C
2800
T36 @90 C/C 1. QUALITY AND WORKMANSHIP OF CONCRETE SHALL CONFORM TO IS:456-2000.
C T12 @ 125 C/C
IN 3-LAYERS IN 2-LAYERS C
2. QUALITY AND GRADING OF AGGREGATES SHALL CONFORM TO IS:383-1970.
T32 @90 C/C 3. REINFORCEMENT SHALL CONSIST OF HYSD (Fe 500) BARS CONFORMING TO IS:1786-1985.
2500 3500 2500 IN 2-LAYERS
1000 1000 1000 1000 4. THE HEAD SLUICE IS DESIGNED ADOPTING THE FOLLOWING IS CODES.
3000
T16 @130 C/C T16 @130 C/C T32 @120 C/C i) IS 456-2000 ii) IS 4997-1995 iii) IS 8826 -1978.
T32 @90 C/C IN 2-LAYERS T32 @90 C/C
3000
+505.000 +505.000
F F
3000
+494.400
2000
+493.200 B B
+493.200
4700 T36 @90 C/C T32 @90 C/C
T32 @90 C/C
IN 3-LAYERS IN 3-LAYERS
IN 3-LAYERS
4700
4700
A
+485.000 +485.000
12500
GOVERNMENT OF TELANGANA
IRRIGATION AND CAD DEPARTMENT
3 NOS-T16 CENTRAL DESIGNS ORGANISATION
(SKIN REINFORCEMENT)
SECTION G-G PRLIS- PKG15-HEAD SLUICE @ KM 11.800
OF KURUMURTHYRAYA RESERVOIR
10 NOS-T20
SKIN REINFORCEMENT REINFORCEMENT DETAILS OF WELL SLUICE (1/2)
SECTION F-F DESIGNED AND DRAWN BY: RECOMMENDED BY:
SAAD AHMED
ASSISTANT EXECUTIVE ENGINEER
CHECKED BY: C. SRINIVAS
SUPERINTENDING ENGINEER-II
V. RAMAKRISHNA APPROVED BY:
DEPUTY EXECUTIVE ENGINEER
SUBMITTED BY:
2300 6100 1600 6100 1600 6100 2300 6. ALL REINFORCING BARS SHALL BE OF Fe-500 GRADE HYSD BARS CONFORMING TO IS 1786-2008 REVISED.
7. CLEAR COVER TO REINFORCEMENT SHALL BE 40MM UNLESS OTHERWISE SPECIFIED IN THE DRAWINGS. PRECAST MORTAR
BLOCKS OF SAME STRENGTH AS CONCRETE SHALL BE USED UNDER THE REINFORCEMENT DULY SECURED TO IT BY WIRE
IMPLANTED IN THE BLOCK TO ENSURE THE REQUIRED COVER.
T32 @180 C/C T32 @180 C/C 8. SPLICING OF MAIN REINFORCEMENT SHALL BE AVOIDED AS FAR AS POSSIBLE. WHEREVER REQUIRED NECESSARY LAPS
T32 @180 C/C
SHALL BE PROVIDED CONFORMING TO IS 456-2000.
T20 @180 C/C T16 @180 C/C T20 @180 C/C 9. THIS DRAWING IS EXCLUSIVELY ISSUED FOR RC DETAILS ONLY.
10. SPECIFICATIONS FOR ALL MATERIALS AND WORKMANSHIP SHALL CONFIRM TO THE RELEVANT B.I.SSPECIFICATIONS ISSUED
12500
FROM TIME TO TIME.
11. ANY EXCESS EXCAVATION HAS TO BE FILLED WITH LEAN CONCRETE FOR FOUNDATIONS IN ROCK WITH M15 CONCRETE.
12. IF THE WATER TABLE IS ABOVE THE EXCAVATION AREA, DE-WATERING OF THE AREA SHALL BE DONE TO GRADUALLY
LOWERS THE WATER TABLE AND SHALL BE KEPT BELOW THE EXCAVATION LEVELS TILL THE CONCRETE LAID HAS ATTEND
SUFFICIENT STRENGTH.
FLOW 13. BEFORE PLACING THE REINFORCEMENT IN POSITION, THE SURFACE OF REINFORCEMENT SHALL BE CLEANED OF ALL RUST,
SCALES AND OTHER OBJECTIONABLE SUBSTANCES.
14.
15. LAPS SPLICING SHALL CONFIRM TO IS-465:2000 AND LAPS IN REGIONS OF MAXIMUM STRESS SHALL BE AVOIDED (SUCH AS
26100 CENTRAL LOCATIONS FOR BOTTOM MAIN BARS AND AT WALL FACE LOCATIONS FOR TOP MAIN BARS).
16. SUITABLE CHAIR , SPACERS SHALL BE PROVIDED TO KEEP THE REINFORCEMENT BAR IN POSITION BEFORE CONCRETING.
SECTION E-E (+535.000 TO +542.000)
17. WELDING OF REINFORCEMENT BARS SHALL NOT BE PERMITTED.
18. THE MECHANICAL CONNECTIONS SUCH AS COUPLERS TO BE USED SHALL BE IN CONFIRMATION TO SP-24.THE ENGINEER IN
CHARGE SHALL BE ENSURED THE STRENGTH AND PLACEMENT REQUIREMENTS AS PER SP-34.
3000 4700 3000 4700 3000 4700 3000 T25 @120 C/C 19. REFER SEPARATE DRAWING FOR THE DETAILS OF MECHANICAL GATE GROOVE SIZES AND SECONDARY CONCRETE IN
400
GROOVES.
T16 @150 C/C 20. THE STRESS AT THE FOUNDATION LEVEL IS 550 KN/M2, PLATE LOAD TEST SHALL BE CONDUCTED FOR LOAD UPTO 825 KN/M2
T32 @90 C/C T36 @90 C/C T32 @90 C/C TO ENSURE THAT THE DEFLECTIONS ARE WITHIN THE PERMISSIBLE LIMITS.
T32 @160 C/C T32 @120 C/C T32 @160 C/C BIS-CODES:
11700
12500
1. QUALITY AND WORKMANSHIP OF CONCRETE SHALL CONFORM TO IS:456-2000.
2. QUALITY AND GRADING OF AGGREGATES SHALL CONFORM TO IS:383-1970.
3. REINFORCEMENT SHALL CONSIST OF HYSD (Fe 500) BARS CONFORMING TO IS:1786-1985.
4. THE HEAD SLUICE IS DESIGNED ADOPTING THE FOLLOWING IS CODES.
i) IS 456-2000 ii) IS 4997-1995 iii) IS 8826 -1978.
FLOW
12500
26100
T32 @120 C/C
SECTION C-C (+505.000 TO +515.000)
FLOW
4000
SAAD AHMED
ASSISTANT EXECUTIVE ENGINEER
CHECKED BY: C. SRINIVAS
SUPERINTENDING ENGINEER-II
V. RAMAKRISHNA APPROVED BY:
DEPUTY EXECUTIVE ENGINEER
T36 @90 C/C T32 @90 C/C
26100 SUBMITTED BY:
IN 3-LAYERS IN 3-LAYERS
SECTION A-A (+485.000 TO +488.500)
K.DAYAKAR REDDY Z. SRINIVASA RAO
EXECUTIVE ENGINEER,DIV-1 CHIEF ENGINEER,CDO,HYD.
FILE NO: AUG 2022 DRG NO. CE/CDO/SE-2/EE-1/DEE1/AEE/24/02/2022