Grey Water Connection Point Calculations:

All below data is taken from Table *** Chapter ***
of International Plumbing Code  IPC (2002)

A. LOAD VALUES, IN WATER SUPPLY FIXTURE UNITS (wsfu) 

 Fixture 
Number of 
Fixture Type  Occupancy Demand  TOTAL
Fixtures
(wsfu)
Water Closet Public 5 44 220.00
Kitchen Sink Public 4 0 0.00
Urinal Public 3 0 0.00
Lavatory Public 2 0 0.00
Pantry Sink Public 3 0 0.00
Hand Spray Public 0.5 0 0.00
Janitor Sink Public 3 0 0.00
Total 220.00

Total Cold Water Demand =  220 wsfu


Total Cold Water Demand =  4.35 L/s
Usage Diversity =  80 %
Diversified Flow Rate =  3.48
The Required Pipe Size = 75 ∅

B. PRESSURE REQUIREMENTS

1. Longest Pipe Run 211 m
2. Prssure Drop 400 Pa/m

3. Dynamic Head 12.66
4. Static Head 10 m
5. Pressure Drop through Electric Heater 1m
6. Residual Head 10 m

Total Head  =  33.66 m
Total Pressure  =  3.366 Bar