Professional Documents
Culture Documents
Grundfosliterature 2127821
Grundfosliterature 2127821
LC 108
Installation and operating instructions
Declaration of Conformity
We, Grundfos, declare under our sole responsibility that the product
LC/LCD 108, to which this declaration relates, is in conformity with these
Council directives on the approximation of the laws of the EC member
states:
— Machinery Directive (98/37/EC).
Standard used: EN 809: 2000.
— Low Voltage Directive (2006/95/EC).
Standards used: EN 60335-1: 2002 and EN 60335-2-51: 2003.
— EMC Directive (2004/108/EC).
Standards used: EN 61000-6-2 and EN 61000-6-3.
Niels Vinther
Technical Manager
2
CONTENTS 1. General
Page The LC 108 controller is designed for the control of pumps in
1. General 3 wastewater, water supply and drainage systems.
1.1 Applications 3 Type key:
1.2 Variants 4
2. Location and mounting 4 Example LC 108 400 3 23 SD
2.1 Location 4
LC = one-pump controller
2.2 Mounting of LC 108 for direct-on-line starting 4
3. Systems with 2 float switches 5 108 = type designation
3.1 Electrical connection 5 Phase voltage [V]
3.2 Setting 5 1 = single-phase
3.3 Control panel 7 3 = three-phase
3.4 Battery back-up functions 7
Maximum operating current per pump [A]
3.5 Reset button and ON-OFF-AUTO selector switch 8
SMS = with SMS unit
4. Systems with 3 float switches 9
4.1 Electrical connection 9
1.1 Applications
4.2 Setting 9
4.3 Control panel 11 The LC 108 enables:
4.4 Battery back-up functions 11 • control of one pump based on signals from float switches or
4.5 Reset button and ON-OFF-AUTO selector switch 12 electrodes,
5. Systems with 4 float switches 12 • selection of automatic test run during long periods of inactivity
5.1 Electrical connection 12 (every 24 hours),
5.2 Setting 13 • battery back-up in case of mains supply failure (accessory for
5.3 Control panel 14 certain variants),
5.4 Battery back-up functions 15 • starting delay within the range from 0 to 255 sec. (random)
5.5 Reset button and ON-OFF-AUTO selector switch 16 after returning from battery operation to mains operation
6. Systems with 2 electrodes 17 (resulting in an even mains load when several pumping sta-
6.1 Electrical connection 17 tions are started up at the same time),
6.2 Setting 17 • selection of automatic alarm resetting,
6.3 Control panel 19
• selection of automatic restarting,
6.4 Battery back-up functions 19
6.5 Reset button and ON-OFF-AUTO selector switch 20 • setting of stop delays matching the actual operating condi-
tions,
7. Systems with 3 electrodes 21
7.1 Electrical connection 21 • indication of liquid level,
7.2 Setting 21 • alarm indication of:
7.3 Control panel 23 - inadmissibly high liquid level,
7.4 Battery back-up functions 23 - overload (via motor protection relay),
7.5 Reset button and ON-OFF-AUTO selector switch 24
- overtemperature (via PTC resistance or thermal switch in
8. Systems for filling applications 25 motor),
8.1 Electrical connection 25
- wrong phase sequence (only certain variants),
8.2 Setting 25
8.3 Control panel 27 - mains supply failure (only certain variants),
8.4 Battery back-up functions 27 - defective float switch, electrode or flow switch,
8.5 Reset button and ON-OFF-AUTO selector switch 28 - dry running.
9. Systems for drainage applications 29 As standard, the LC 108 has one alarm output for common alarm.
9.1 Electrical connection 29 Certain variants have an additional alarm output for separate
9.2 Setting 29 high-level alarm.
9.3 Control panel 31 Furthermore, the controller incorporates a buzzer (only certain
9.4 Battery back-up functions 31 variants).
9.5 Reset button and ON-OFF-AUTO selector switch 32
10. Start-up 32
11. Maintenance 33
12. Technical data 33
13. Fault finding chart 34
14. Disposal 34
3
1.2 Variants Figure 1 shows the terminals listed under positions 2 and 3.
The actual controller type, voltage variant, etc. are stated in the
type key on the nameplate situated on the side of the controller
cabinet.
The LC 108 is available for either direct-on-line starting or star-
delta starting.
The LC 108 can be connected and set to operation/control in 7
different ways, see sections 3. to 9.:
• Section 3. Systems with 2 float switches.
T12
12
22
32
42
• Section 4. Systems with 3 float switches.
T11
21
31
41
11
(Electrodes can also be used.)
• Section 5. Systems with 4 float switches.
(Electrodes can also be used.) Fig. 1
• Section 6. Systems with 2 electrodes.
Key to the symbols in figs. 1 and 1:
• Section 7. Systems with 3 electrodes.
• Section 8. Systems for filling applications. Pos. Description
• Section 9. Systems for drainage applications.
Terminal block for level inputs
1
(11-12, 21-22, 31-32, 41-42).
2. Location and mounting Terminal block with:
Before starting any work on pumps used to pump • input for the PTC resistance/thermal switch of the
liquids which could be constituted as being hazard- motor (T11-T21),
ous to health, thorough cleaning/venting of pumps, 2 • output for external alarm device for high-level alarm
pits, etc. must be carried out according to local regu- (H-NC, H-COM, H-NO) (only certain variants),
lations. • output for external alarm device for common alarm
Before making any connections in the LC 108 or work (G-NC, G-COM, G-NO).
on pumps, pits, etc., it must be ensured that the elec-
tricity supply has been switched off and that it cannot Note: If the distance between the controller and pit exceeds
be accidentally switched on. 20 metres, it is not advisable to use electrodes as problems with
the signal values sent back to the controller may arise.
The installation must be carried out by authorized personnel in
accordance with local regulations. In such cases, it is recommended to use float switches.
Note: Cables of up to 100 metres can be connected between the
2.1 Location controller and the float switches.
4
3. Systems with 2 float switches Key to the symbols in fig. A1 on page 35 and fig. A2 on
page 36:
Description (see also page 35 or 36):
The pump is controlled by the liquid level in the pit. Terminal
Pos. Description
• The pump is started when the float switch, pos. 1, registers number
liquid.
1 Float switch for start/stop of pump. 11-12
• When the float switch, pos. 1, no longer registers liquid, the
stop delay (can be set) is activated. After expiration of the stop 2 Float switch for high-level alarm. 31-32
delay, the pump is stopped.
3.2 Setting
• The upper float switch, pos. 2, activates the high-level alarm.
2 float switches, pages 35 and 36.
Before starting any work on pumps used to pump The module CU 211 has a 10-pole DIP switch in the bottom right
liquids which could be constituted as being hazard- corner, see fig. 2.
ous to health, thorough cleaning/venting of pumps, Note: During setting, the controller must be off circuit for at least
pits, etc. must be carried out according to local regu- 1 minute to ensure the correct configuration during start-up after
lations. change of the DIP switch setting.
Before making any connections in the LC 108 or work The DIP switch setting offers the following possibilities:
on pumps, pits, etc., it must be ensured that the elec-
• selection of starting delay and automatic test run (switch 4),
tricity supply has been switched off and that it cannot
be accidentally switched on. • setting of stop delay (switches 5, 6 and 7),
• selection of automatic alarm resetting (switch 9),
3.1 Electrical connection • selection of automatic restarting (switch 10).
2 float switches, pages 35 and 36.
5
• Switch 4, starting delay and automatic test run AC/DC selector:
(only in the case of battery back-up): The AC/DC selector switch for electrodes and/or float switches is
When the DIP switch setting is changed, the controller must placed as shown in fig. 3.
be switched off for at least 1 minute!
The stop delay is the time from the stop signal is given until the
pump is stopped. Fig. 3
It must be ensured that the pump is not running dry.
Operation with electrodes and
0 sec. 60 sec. float switches:
Selector switch in position AC:
15 sec. 90 sec. 13-18 VAC 0V
It is possible to connect 3 elec-
trodes (1 as reference electrode)
AC 1 2 G 3 4 and 2 float switches.
30 sec. 120 sec. AC DC The controller transmits a
13-18 VAC signal.
Operation with float switches:
45 sec. 180 sec.
Selector switch in position AC:
It is possible to connect 4 float
• Switch 8: 13-18 VAC 0V
switches.
When the DIP switch setting is changed, the controller must The controller transmits a
be switched off for at least 1 minute! AC 1 2 G 3 4
13-18 VAC signal.
AC DC
6
3.3 Control panel 3.4 Battery back-up functions
2 float switches, pages 35 and 36. 2 float switches, pages 35 and 36.
Figure 4 shows the control panel of the CU 211 module. If a back-up battery for CU 211 (accessory for certain variants) is
installed, the following functions will be carried out if the normal
electricity supply to the LC 108 fails (see also the illustrations
1 2 34 5 below):
• The common alarm is active, the red indicator light is on –
CU 211 1 cannot be reset!
1
12 • If the external alarm device for common alarm is supplied from
11 an external power source, this device will be active – cannot
10 be reset by means of the reset button!
9, 10 switch for high-level alarm. • The top orange indicator light is flash-
and In case of high-level alarm, the top indicator light is ing.
11 flashing and the two other indicator lights are perma- • The second orange indicator light from
nently on. the top is on.
Green indicator light, indicating that the electricity sup- • The green indicator light (electricity
12
ply has been switched on. supply switched on) is off.
7
3.5 Reset button and ON-OFF-AUTO selector switch
2 float switches, pages 35 and 36.
The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:
ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long
period, the pump will be damaged!
In explosion hazard areas, switch 10 of the DIP switch must be set as stated in section 3.2. Consequently, the
pump cannot be started when the PTC resistance/thermal switch of the motor registers overtemperature.
8
4. Systems with 3 float switches Key to the symbols in fig. B1 on page 37 and fig. B2 on
page 38:
Description (see also page 37 or 38):
The pump is controlled by the liquid level in the pit. Pos. Description Terminal number
• The float switch, pos. 2, starts the pump.
1 Float switch for stop of pump. 11-12
• The float switch, pos. 1, stops the pump. It is possible to set a
2 Float switch for start of pump. 21-22
"stop delay" which delays the stop of the pump.
• The top float switch, pos. 3, activates the high-level alarm. 3 Float switch for high-level alarm. 31-32
Before starting any work on pumps used to pump liq- 4.2 Setting
uids which could be constituted as being hazardous 3 float switches, pages 37 and 38.
to health, thorough cleaning/venting of pumps, pits,
The module CU 211 has a 10-pole DIP switch in the bottom right
etc. must be carried out according to local regula-
corner, see fig. 5.
tions.
Note: During setting, the controller must be off circuit for at least
Before making any connections in the LC 108 or work
1 minute to ensure the correct configuration during start-up after
on pumps, pits, etc., it must be ensured that the elec-
change of the DIP switch setting.
tricity supply has been switched off and that it cannot
be accidentally switched on. The DIP switch setting offers the following possibilities:
• selection of starting delay and automatic test run (switch 4),
4.1 Electrical connection • setting of stop delay (switches 5, 6 and 7),
3 float switches, pages 37 and 38. • selection of automatic alarm resetting (switch 9),
Before starting work on the system, switch off the • selection of automatic restarting (switch 10).
supply voltage and lock the mains switch in
position 0.
Any external voltage connected to the system must
be switched off before work is started.
Fig. B1 on page 37.
The figures show all electrical connections required to connect
the LC 108 for direct-on-line starting, 3 float switches.
Fig. B2 on page 38.
The figure shows all electrical connections required to connect
the LC 108 for start-delta starting, 3 float switches.
9
• Switches 5, 6 and 7, stop delay: AC/DC selector:
When the DIP switch setting is changed, the controller must The AC/DC selector switch for electrodes and/or float switches is
be switched off for at least 1 minute! placed as shown in fig. 6.
The stop delay is the time from the stop signal is given until the
pump is stopped.
It must be ensured that the pump is not running dry.
0 sec. 60 sec.
15 sec. 90 sec.
• Switch 8:
Fig. 6
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
Operation with electrodes and
Switch 8 has no function in connection with the actual float switches:
application (3 float switches, pages 37 and 38), but this Selector switch in position AC:
setting must be maintained! 13-18 VAC 0V
It is possible to connect 3 elec-
• Switch 9, automatic alarm resetting: trodes (1 as reference electrode)
When the DIP switch setting is changed, the controller must AC 1 2 G 3 4 and 2 float switches.
be switched off for at least 1 minute!
AC DC The controller transmits a
13-18 VAC signal.
This setting ensures automatic resetting of alarm sig- Operation with float switches:
nals to external alarm devices and the built-in buzzer.
However, an alarm signal will only be reset if the cause Selector switch in position AC:
of the fault no longer exists. It is possible to connect 4 float
13-18 VAC 0V
switches.
At this setting, the alarm signal must be reset manually
The controller transmits a
by means of the reset button (the reset button is AC 1 2 G 3 4
13-18 VAC signal.
described in section 4.5). AC DC
10
4.3 Control panel 4.4 Battery back-up functions
3 float switches, pages 37 and 38. 3 float switches, pages 37 and 38.
Figure 7 shows the control panel of the CU 211 module. If a back-up battery for CU 211 (accessory for certain variants) is
installed, the following functions will be carried out if the normal
1 234 5
electricity supply to the LC 108 fails (see also the illustrations
below):
• The common alarm is active, the red indicator light is on –
CU 211 1 cannot be reset!
1
12 • If the external alarm device for common alarm is supplied from
11 an external power source, this device will be active – cannot
10 be reset by means of the reset button!
9 • The built-in buzzer (only certain variants) is activated – can be
11
4.5 Reset button and ON-OFF-AUTO selector switch
3 float switches, pages 37 and 38.
The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:
ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long pe-
riod, the pump will be damaged!
In explosion hazard areas, switch 10 of the DIP switch must be set as stated in section 4.2. Consequently, the
pump cannot be started when the PTC resistance/thermal switch of the motor registers overtemperature.
Description (see also page 39 or 40): The figure shows all electrical connections required to connect
the LC 108 for star-delta starting, 4 float switches.
The pump is controlled by the liquid level in the pit.
• The float switch, pos. 3, starts the pump. The LC 108 must be connected in accordance with
• The float switch, pos. 2, stops the pump. It is possible to set a the rules and standards in force for the application in
"stop delay" which delays the stop of the pump. question.
• The top float switch, pos. 4, activates the high-level alarm.
The operating voltage and frequency are marked on the controller
• The bottom float switch, pos. 1, activates the dry-running nameplate. Make sure that the controller is suitable for the elec-
alarm. tricity supply on which it will be used.
Before starting any work on pumps used to pump liq- All cables/wires must be fitted through the Pg cable entries and
uids which could be constituted as being hazardous gaskets (IP 65).
to health, thorough cleaning/venting of pumps, pits, Maximum back-up fuse is stated on the controller nameplate.
etc. must be carried out according to If required according to local regulations, an external mains
local regulations. switch must be installed.
Before making any connections in the LC 108 or work Note: If the PTC resistance/thermal switch of the motor is con-
on pumps, pits, etc., it must be ensured that the elec- nected, the factory-fitted short-circuit jumper must be removed
tricity supply has been switched off and that it cannot (terminals T11-T21).
be accidentally switched on. Single-phase motors must be connected to an external operating
capacitor and in certain cases also to a starting capacitor. Further
5.1 Electrical connection details can be found in the installation and operating instructions
4 float switches, pages 39 and 40. for the pump in question.
12
Each individual switch (1 to 10) of the DIP switch can be set to
Float switches or electrodes placed in an explosion
position OFF or ON.
hazard area must be connected via an EEx barrier,
e.g. Grundfos number 96440300. Note: The DIP switch must not be set to other switch combina-
The EEx barrier must not be installed in the explosion tions than those described in this section.
hazard area. Set the switches 1 to 10 as follows:
Equipment used in explosion hazard areas must in • Switches 1, 2 and 3, application type:
each individual case have been approved for this When the DIP switch setting is changed, the controller must
particular application. Furthermore, the cables into be switched off for at least 1 minute!
the explosion hazard area must be laid in accordance
with local regulations. This setting determines the actual application type
Note: Float switches of the same type as Grundfos product (4 float switches, pages 39 and 40).
number 96003332 or 96003695, i.e. float switches with
gold-plated contacts suitable for low voltages and currents • Switch 4, starting delay and automatic test run
(40 V/100 mA), must be used. All EEx-approved float switches (only in the case of battery back-up):
are also suitable. When the DIP switch setting is changed, the controller must
The float switches must be connected as NO contacts, i.e. brown be switched off for at least 1 minute!
and black leads, when float switches, Grundfos product number
96003332 or 96003695, are used. At this setting, the start-up is delayed within the range
from 0 to 255 sec. (random) after the electricity supply
Key to the symbols in fig. C1 on page 39 and fig. C2 on has been switched on when the liquid level is suffi-
page 40: ciently high.
Automatic test run carried out every 24 hours.
Terminal
Pos. Description After the electricity has been switched on, the pump will
number
start immediately when the liquid level is sufficiently
1 Float switch for dry-running alarm. 11-12 high.
2 Float switch for stop of pump. 21-22 No automatic test run.
3 Float switch for start of pump. 31-32 • Switches 5, 6 and 7, stop delay:
4 Float switch for high-level alarm. 41-42 When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
5.2 Setting
4 float switches, pages 39 and 40. The stop delay is the time from the stop signal is given until the
pump is stopped.
The module CU 211 has a 10-pole DIP switch in the bottom right
It must be ensured that the pump is not running dry.
corner, see fig. 8.
Note: During setting, the controller must be off circuit for at least 0 sec. 60 sec.
1 minute to ensure the correct configuration during start-up after
change of the DIP switch setting.
The DIP switch setting offers the following possibilities: 15 sec. 90 sec.
• selection of starting delay and automatic test run (switch 4),
• setting of stop delay (switches 5, 6 and 7),
30 sec. 120 sec.
• selection of automatic alarm resetting (switch 9),
• selection of automatic restarting (switch 10).
45 sec. 180 sec.
• Switch 8:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
13
• Switch 10, automatic restarting: 5.3 Control panel
When the DIP switch setting is changed, the controller must 4 float switches, pages 39 and 40.
be switched off for at least 1 minute!
Figure 10 shows the control panel of the CU 211 module.
This setting enables automatic restarting after the PTC
resistance/thermal switch of the motor has cut out the 1 234 5
pump. Restarting will not be carried out until the motor
has cooled to normal temperature.
CU 211 1
When the pump connected is used in an explosion 1
hazard area, switch 10 must not be in this position! 12
At this setting, the pump must be restarted manually after 11
10
the PTC resistance/thermal switch of the motor has cut
9
14
5.4 Battery back-up functions
4 float switches, pages 39 and 40.
If a back-up battery for CU 211 (accessory for certain variants) is
installed, the following functions will be carried out if the normal
electricity supply to the LC 108 fails (see also the illustrations
below):
• The common alarm is active, the red indicator light is on –
cannot be reset!
• If the external alarm device for common alarm is supplied from
an external power source, this device will be active – cannot
be reset by means of the reset button!
• The built-in buzzer (only certain variants) is activated – can be
reset by means of the reset button!
• If the liquid level in the pit rises above the level for high-level
alarm, the top orange indicator light will be flashing and the
second orange indicator light from the top will be permanently
on.
• If the starting delay function and automatic test run were
selected (switch 4 of the DIP switch), the start-up will be
delayed after the electricity supply has been switched on when
the liquid level is sufficiently high, see section 5.2.
The table below shows the situations which may occur if the nor-
mal electricity supply to the LC 108 fails and a back-up battery is
connected:
= the indicator light is off.
= the indicator light is on.
= the indicator light is flashing.
CU 211 1
Mains supply failure:
• The common alarm is active.
The red indicator light is on.
• The green indicator light (electricity
supply switched on) is off.
15
5.5 Reset button and ON-OFF-AUTO selector switch
4 float switches, pages 39 and 40.
The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:
ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long pe-
riod, the pump will be damaged!
In explosion hazard areas, switch 10 of the DIP switch must be set as stated in section 5.2. Consequently, the
pump cannot be started when the PTC resistance/thermal switch of the motor registers overtemperature.
16
6. Systems with 2 electrodes Key to the symbols in fig. D1 on page 41 and fig. D2 on
page 42:
Description (see also page 41 or 42):
The pump is controlled by the liquid level in the borehole. Terminal
Pos. Description
• The electrode, pos. 1, is the reference electrode. number
• When the electrode, pos. 2, registers liquid, the "waiting time" 1 Reference electrode. 11
is initiated (can be set). After expiration of the waiting time, the
2 Electrode for start/stop of pump. 12
pump is started.
3 Pressure switch. 41-42
• The pump is stopped when the electrode, pos. 2, does not reg-
ister any liquid. 6.2 Setting
• The pressure switch, pos. 3, stops the pump if the discharge
2 electrodes, pages 41 and 42.
pressure exceeds the stop pressure of the pressure switch. Re-
starting at the starting pressure of the pressure switch is only The module CU 211 has a 10-pole DIP switch in the bottom right
effected if the electrode, pos. 2, registers liquid. corner, see fig. 11.
Note: During setting, the controller must be off circuit for at least
Before starting any work on pumps used to pump liq- 1 minute to ensure the correct configuration during start-up after
uids which could be constituted as being hazardous change of the DIP switch setting.
to health, thorough cleaning/venting of pumps, pits,
The DIP switch setting offers the following possibilities:
etc. must be carried out according to local regula-
tions. • selection of starting delay and automatic test run (switch 4),
Before making any connections in the LC 108 or work • setting of waiting time (switches 5, 6, 7 and 8),
on pumps, pits, etc., it must be ensured that the elec- • selection of automatic alarm resetting (switch 9),
tricity supply has been switched off and that it cannot • selection of automatic restarting (switch 10).
be accidentally switched on.
The operating voltage and frequency are marked on the controller Fig. 11
nameplate. Make sure that the controller is suitable for the elec-
Set the DIP switch as shown in fig. 11.
tricity supply on which it will be used.
Each individual switch (1 to 10) of the DIP switch can be set to
All cables/wires must be fitted through the Pg cable entries and
position OFF or ON.
gaskets (IP 65).
Note: The DIP switch must not be set to other switch combina-
Maximum back-up fuse is stated on the controller nameplate.
tions than those described in this section.
If required according to local regulations, an external mains
Set the switches 1 to 10 as follows:
switch must be installed.
• Switches 1, 2 and 3, application type:
Note: If the PTC resistance/thermal switch of the motor is con-
nected, the factory-fitted short-circuit jumper must be removed When the DIP switch setting is changed, the controller must
(terminals T11-T21). be switched off for at least 1 minute!
Single-phase motors must be connected to an external operating
capacitor and in certain cases also to a starting capacitor. Further This setting determines the actual application type
details can be found in the installation and operating instructions (2 electrodes, pages 41 and 42).
for the pump in question.
17
• Switch 4, starting delay and automatic test run AC/DC selector:
(only in the case of battery back-up): The AC/DC selector switch for electrodes and/or float switches is
When the DIP switch setting is changed, the controller must placed as shown in fig. 12.
be switched off for at least 1 minute!
The waiting time is the time from the electrode registers liquid
until the pump starts (starting delay). Fig. 12
18
6.3 Control panel 6.4 Battery back-up functions
2 electrodes, pages 41 and 42. 2 electrodes, pages 41 and 42.
For these applications, the foil supplied with the LC 108 must be If a back-up battery for CU 211 (accessory for certain variants) is
attached to the CU 211 control panel as shown in fig. 13. The foil installed, the following functions will be carried out if the normal
can be found inside the LC 108 cabinet at the bottom. electricity supply to the LC 108 fails (see also the illustrations
Figure 13 shows how the foil is attached to the CU 211 module. below):
• The common alarm is active, the red indicator light is on – can-
CU 211 1 not be reset!
8
CU 211 1
Mains supply failure:
• The common alarm is active.
7 The red indicator light is on.
Pos. Description
Green indicator light, indicating starting delay (flashing)
1
and pump operation (permanently on).
Red indicator light, indicating pump fault.
2 Flashing: Fault in PTC resistor/thermal switch
On: Fault in motor-protective circuit breaker.
Red indicator light, indicating wrong phase sequence
3
(only certain variants and three-phase pumps only).
4 Red indicator light, indicating common alarm.
ON-OFF-AUTO selector switch, three positions, see
5
section 6.5.
Reset button, push-button for manual resetting of alarm
7 signals to external alarm devices and the built-in buzzer
(only certain variants), see section 6.5.
Orange indicator light, which is activated by the elec-
8
trode for start/stop of pump.
9
Have no function in connection with the actual applica-
and
tion!
10
Orange indicator light, which is activated by the pres-
sure switch in the discharge pipe.
The pump is stopped if the pressure is higher than the
stop pressure of the pressure switch (the indicator light
11 is permanently on).
The pump is started if the pressure is lower than the
starting pressure of the pressure switch and the elec-
trode for start/stop of pump (see pos. 8 above) gives a
starting signal at the same time.
Green indicator light, indicating that the electricity sup-
12
ply has been switched on.
19
6.5 Reset button and ON-OFF-AUTO selector switch
2 electrodes, pages 41 and 42.
The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:
ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long pe-
riod, the pump will be damaged!
In explosion hazard areas, switch 10 of the DIP switch must be set as stated in section 6.2. Consequently,
the pump cannot be started when the PTC resistance/thermal switch of the motor registers overtemperature.
20
7. Systems with 3 electrodes Key to the symbols in fig. E1 on page 43 and fig. E2 on
page 44:
Description (see also page 43 or 44):
The pump is controlled by the liquid level in the borehole. Terminal
Pos. Description
• The electrode, pos. 1, is the reference electrode. number
• The electrode, pos. 3, starts the pump. 1 Reference electrode. 11
• The electrode, pos. 2, stops the pump. It is possible to set a
2 Electrode for stop of pump. 12
"stop delay" which delays the stop of the pump.
• The pressure switch, pos. 4, stops the pump if the discharge 3 Electrode for start of pump. 22
pressure exceeds the stop pressure of the pressure switch. 4 Pressure switch. 41-42
Restarting at the starting pressure of the pressure switch is
only effected if the electrode, pos. 3, registers liquid. 7.2 Setting
3 electrodes, pages 43 and 44.
Before starting any work on pumps used to pump liq-
The module CU 211 has a 10-pole DIP switch in the bottom right
uids which could be constituted as being hazardous
corner, see fig. 15.
to health, thorough cleaning/venting of pumps, pits,
etc. must be carried out according to local regula- Note: During setting, the controller must be off circuit for at least
tions. 1 minute to ensure the correct configuration during start-up after
change of the DIP switch setting.
Before making any connections in the LC 108 or work
on pumps, pits, etc., it must be ensured that the elec- The DIP switch setting offers the following possibilities:
tricity supply has been switched off and that it cannot • selection of starting delay and automatic test run (switch 4),
be accidentally switched on. • setting of stop delay (switches 5, 6 and 7),
• selection of automatic alarm resetting (switch 9),
7.1 Electrical connection
• selection of automatic restarting (switch 10).
3 electrodes, pages 43 and 44.
21
• Switch 4, starting delay and automatic test run AC/DC selector:
(only in the case of battery back-up): The AC/DC selector switch for electrodes and/or float switches is
When the DIP switch setting is changed, the controller must placed as shown in fig. 16.
be switched off for at least 1 minute!
The stop delay is the time from the stop signal is given until the
pump is stopped. Fig. 16
It must be ensured that the pump is not running dry.
Operation with electrodes and
0 sec. 60 sec. float switches:
Selector switch in position AC:
15 sec. 90 sec. 13-18 VAC 0V
It is possible to connect 3 elec-
trodes (1 as reference electrode)
AC 1 2 G 3 4 and 2 float switches.
30 sec. 120 sec. AC DC The controller transmits a
13-18 VAC signal.
Operation with float switches:
45 sec. 180 sec.
Selector switch in position AC:
It is possible to connect 4 float
• Switch 8: 13-18 VAC 0V
switches.
When the DIP switch setting is changed, the controller must The controller transmits a
be switched off for at least 1 minute! AC 1 2 G 3 4
13-18 VAC signal.
AC DC
22
7.3 Control panel 7.4 Battery back-up functions
3 electrodes, pages 43 and 44. 3 electrodes, pages 43 and 44.
For these applications, the foil supplied with the LC 108 must be If a back-up battery for CU 211 (accessory for certain variants) is
attached to the CU 211 control panel as shown in fig. 17. The foil installed, the following functions will be carried out if the normal
can be found inside the LC 108 cabinet at the bottom. electricity supply to the LC 108 fails (see also the illustrations
Figure 17 shows how the foil is attached to the CU 211 module. below):
• The common alarm is active, the red indicator light is on – can-
CU 211 1 not be reset!
1
8
CU 211 1
Mains supply failure:
• The common alarm is active.
7 The red indicator light is on.
Fig. 18 • The green indicator light (electricity
supply switched on) is off.
Key to the symbols in fig. 18:
Pos. Description
Green indicator light, indicating starting delay (flashing)
1
and pump operation (permanently on).
Red indicator light, indicating pump fault.
2 Flashing: Fault in PTC resistor/thermal switch
On: Fault in motor-protective circuit breaker.
Red indicator light, indicating wrong phase sequence
3
(only certain variants and three-phase pumps only).
4 Red indicator light, indicating common alarm.
ON-OFF-AUTO selector switch, three positions, see
5
section 7.5.
Reset button, push-button for manual resetting of alarm
7 signals to external alarm devices and the built-in buzzer
(only certain variants), see section 7.5.
Orange indicator light, which is activated by the elec-
8
trode for stop of pump.
Orange indicator light, which is activated by the elec-
9
trode for start of pump.
Has no function in connection with the actual applica-
10
tion!
Orange indicator light, which is activated by the pres-
sure switch in the discharge pipe.
The pump is stopped if the pressure is higher than the
stop pressure of the pressure switch (the indicator light
11 is permanently on).
The pump is started if the pressure is lower than the
starting pressure of the pressure switch and the elec-
trode for start of pump (see pos. 9 above) gives a start-
ing signal at the same time.
Green indicator light, indicating that the electricity
12
supply has been switched on.
23
7.5 Reset button and ON-OFF-AUTO selector switch
3 electrodes, pages 43 and 44.
The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:
ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long pe-
riod, the pump will be damaged!
In explosion hazard areas, switch 10 of the DIP switch must be set as stated in section 7.2. Consequently, the
pump cannot be started when the PTC resistance/thermal switch of the motor registers overtemperature.
24
8. Systems for filling applications Key to the symbols in fig. F1 on page 45 and fig. F2 on
page 46:
Description (see also page 45 or 46):
The pump is controlled by the liquid level in the filling tank. Terminal
Pos. Description
• The electrode, pos. 1, is the reference electrode. number
• The electrode, pos. 2, starts the pump. 1 Reference electrode.* 11
• The electrode, pos. 3, stops the pump. It is possible to set a
2 Electrode for start of pump.* 12
"stop delay", which delays the stop of the pump.
• The float switch, pos. 4, activates the high-level alarm. 3 Electrode for stop of pump.* 22
• The manual on/off switch, pos. 5, will stop the pump when the 4 Float switch for high-level alarm. 31-32
switch is set to position off. Manual on/off switch (or another external
5 41-42
input).
Before starting any work on pumps used to pump liq-
uids which could be constituted as being hazardous * Alternatively, float switches can be connected between termi-
to health, thorough cleaning/venting of pumps, pits, nals: 11-12 and 21-22.
etc. must be carried out according to local regula-
tions. 8.2 Setting
Before making any connections in the LC 108 or work Filling application, pages 45 and 46.
on pumps, pits, etc., it must be ensured that the elec- The module CU 211 has a 10-pole DIP switch in the bottom right
tricity supply has been switched off and that it cannot corner, see fig. 19.
be accidentally switched on. Note: During setting, the controller must be off circuit for at least
1 minute to ensure the correct configuration during start-up after
8.1 Electrical connection change of the DIP switch setting.
Filling application, pages 45 and 46. The DIP switch setting offers the following possibilities:
Before starting work on the system, switch off the • selection of starting delay and automatic test run (switch 4),
supply voltage and lock the mains switch in • setting of stop delay (switches 5, 6 and 7),
position 0. • selection of automatic alarm resetting (switch 9),
Any external voltage connected to the system must • selection of automatic restarting (switch 10).
be switched off before work is started.
Fig. F1 on page 45.
The figures show all electrical connections required to connect
the LC 108 for direct-on-line starting, filling application.
Fig. F2 on page 46.
The figure shows all electrical connections required to connect
the LC 108 for star-delta starting, filling application.
25
• Switch 4, starting delay and automatic test run AC/DC selector:
(only in the case of battery back-up): The AC/DC selector switch for electrodes and/or float switches is
When the DIP switch setting is changed, the controller must placed as shown in fig. 20.
be switched off for at least 1 minute!
The stop delay is the time from the stop signal is given until the
pump is stopped.
Fig. 20
It must be ensured that the pump is not running dry.
26
8.3 Control panel 8.4 Battery back-up functions
Filling application, pages 45 and 46. Filling application, pages 45 and 46.
For these applications, the foil supplied with the LC 108 must be If a back-up battery for CU 211 (accessory for certain variants) is
attached to the CU 211 control panel as shown in fig. 21. The foil installed, the following functions will be carried out if the normal
can be found inside the LC 108 cabinet at the bottom. electricity supply to the LC 108 fails (see also the illustrations
Figure 21 shows how the foil is attached to the CU 211 module. below):
• The common alarm is active, the red indicator light is on –
CU 211 1 cannot be reset!
1
8
= the indicator light is on.
= the indicator light is flashing.
7
CU 211 1
Mains supply failure:
Fig. 22
• The common alarm is active.
Key to the symbols in fig. 22: The red indicator light is on.
• The green indicator light (electricity
Pos. Description supply switched on) is off.
Green indicator light, indicating starting delay (flashing)
1 Mains supply failure and high-level alarm:
and pump operation (permanently on). CU 211 1
• The common alarm is active.
Red indicator light, indicating pump fault. The red indicator light is on.
2 Flashing: Fault in PTC resistor/thermal switch
On: Fault in motor-protective circuit breaker. • The orange indicator light is flashing.
• The green indicator light (electricity
Red indicator light, indicating wrong phase sequence
3 supply switched on) is off.
(only certain variants and three-phase pumps only).
4 Red indicator light, indicating common alarm.
ON-OFF-AUTO selector switch, three positions,
5
see ection 8.5.
Reset button, push-button for manual resetting of alarm
7 signals to external alarm devices and the built-in buzzer
(only certain variants), see section 8.5.
Orange indicator light, which is activated by the elec-
8
trode for start of pump.
Orange indicator light, which is activated by the elec-
9
trode for stop of pump.
Orange indicator light, which is activated by the float
10 switch for high-level alarm. In case of high-level alarm,
the indicator light is flashing.
Orange indicator light, which is activated by the manual
on/off switch.
The pump is stopped when the switch is set to position
11 off (the indicator light is permanently on).
The pump is started when the switch is set to position on
unless the electrode for stop of pump (see pos. 9 above)
gives a stop signal at the same time.
Green indicator light, indicating that the electricity supply
12
has been switched on.
27
8.5 Reset button and ON-OFF-AUTO selector switch
Filling application, pages 45 and 46.
The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:
ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long pe-
riod, the pump will be damaged!
In explosion hazard areas, switch 10 of the DIP switch must be set as stated in section 8.2. Consequently,
the pump cannot be started when the PTC resistance/thermal switch of the motor registers overtemperature.
28
9. Systems for drainage applications Key to the symbols in fig. G1 on page 47 and fig. G2 on
page 48:
Description (see also page 47 or 48):
The pump is controlled by the flow switch, pos. 2, in the discharge Terminal
pipe. Pos. Description
number
• The pump is stopped when the flow switch does not register
1 Switch for manual restarting. 41-42
any liquid flow.
2 Flow switch. 11-12
• After a stop signal, the pump will attempt to restart when the
"restarting time" (can be set) has expired. The restarting
9.2 Setting
attempt will be interrupted if the flow switch does not register
any liquid flow before the expiration of the "dead time" Drainage application, pages 47 and 48.
(can be set). The module CU 211 has a 10-pole DIP switch in the bottom right
• The switch for manual restarting, pos. 1, will initiate a restart- corner, see fig. 23.
ing attempt when the switch is set to position on (restarting). Note: During setting, the controller must be off circuit for at least
1 minute to ensure the correct configuration during start-up after
Before starting any work on pumps used to pump liq- change of the DIP switch setting.
uids which could be constituted as being hazardous
The DIP switch setting offers the following possibilities:
to health, thorough cleaning/venting of pumps, pits,
etc. must be carried out according to local regula- • setting of dead time (switches 4, 5 and 6),
tions. • setting of restarting time (switches 7, 8, 9 and 10).
Before making any connections in the LC 108 or work
on pumps, pits, etc., it must be ensured that the elec-
tricity supply has been switched off and that it cannot
be accidentally switched on.
1 min. 5 min.
29
• Switches 7, 8, 9 and 10, restarting time: AC/DC selector:
When the DIP switch setting is changed, the controller must The AC/DC selector switch for electrodes and/or float switches is
be switched off for at least 1 minute! placed as shown in fig. 24.
The restarting time is the time from the last stop signal until the
pump attempts to restart.
No restarting* 15 min.
1 min. 17 min.
2 min. 20 min.
30
9.3 Control panel 9.4 Battery back-up functions
Drainage application, pages 47 and 48. Drainage application, pages 47 and 48.
For these applications, the foil supplied with the LC 108 must be If a back-up battery for CU 211 (accessory for certain variants) is
attached to the CU 211 control panel as shown in fig. 25. The foil installed, the following functions will be carried out if the normal
can be found inside the LC 108 cabinet at the bottom. electricity supply to the LC 108 fails (see also the illustrations
Figure 25 shows how the foil is attached to the CU 211 module. below):
• The common alarm is active, the red indicator light is on –
CU 211 1 cannot be reset!
1
Fig. 26
Pos. Description
Green indicator light, indicating starting delay (flashing)
1
and pump operation (permanently on).
Red indicator light, indicating pump fault.
2 Flashing: Fault in PTC resistor/thermal switch
On: Fault in motor-protective circuit breaker.
Red indicator light, indicating wrong phase sequence
3
(only certain variants and three-phase pumps only).
4 Red indicator light, indicating common alarm.
ON-OFF-AUTO selector switch, three positions, see
5
section 9.5.
Reset button, push-button for manual resetting of alarm
7 signals to external alarm devices and the built-in buzzer
(only certain variants), see section 9.5.
Orange indicator light, which is activated by the flow
switch.
When the flow switch registers a liquid flow, the indica-
8 tor light is permanently on.
The pump is stopped if the flow switch does not register
any liquid flow and the dead time has expired, see sec-
tion 9.2.
9
Have no function in connection with the actual
and
application!
10
Orange indicator light, which is activated by the switch
for manual restarting.
The pump is started when the switch is set to position
11 on (restarting) (the indicator light is permanently on).
The pump is stopped if the flow switch does not register
any liquid flow and the dead time has expired, see sec-
tion 9.2.
Green indicator light, indicating that the electricity
12
supply has been switched on.
31
9.5 Reset button and ON-OFF-AUTO selector switch
Drainage application, pages 47 and 48.
The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:
ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long pe-
riod, the pump will be damaged!
10. Start-up
5. Switch on the electricity supply.
Before starting any work on pumps used to pump liq-
Three-phase pumps only: Check for wrong phase sequence,
uids which could be constituted as being hazardous
(the pump cannot be started if the phase sequence is wrong!).
to health, thorough cleaning/venting of pumps, pits,
etc. must be carried out according to local regula- 6. Start the pump, see section 3.5, 4.5, 5.5, 6.5, 7.5, 8.5 or 9.5.
tions. 7. Check that the pump is not running dry. The risk of dry running
Before making any connections in the LC 108 or work can be eliminated by a renewed time setting by means of the
on pumps, pits, etc., it must be ensured that the elec- DIP switch according to section 3.2, 4.2, 5.2, 6.2, 7.2 or 8.2
tricity supply has been switched off and that it cannot and/or by moving the float switches or the electrodes.
be accidentally switched on. 8. Three-phase pumps only: Check whether the direction of
Prior to start-up, the connection and DIP switch setting must have rotation of the pump is correct according to the installation and
operating instructions for the pump in question.
been carried out according to sections 3. to 9.
9. Select the required operating mode by means of the ON-OFF-
Start-up must be carried out by authorized personnel.
AUTO selector switch, see section 3.5, 4.5, 5.5, 6.5, 7.5, 8.5
Proceed as follows:
or 9.5.
1. Check whether the float switches, electrodes or the flow
switch have been connected according to the wiring diagram
for the actual application.
2. Check that the pump inlet is submerged in the liquid to be
pumped.
3. Set the motor protection relay to the rated current stated on
the nameplate.
4. Warning:
32
11. Maintenance 12. Technical data
Voltage variants, nominal voltages
Before starting any work on pumps used to pump liq-
uids which could be constituted as being hazardous • 1 x 230 V.
to health, thorough cleaning/venting of pumps, pits, • 3 x 415 V.
etc. must be carried out according to local regula- Voltage tolerances for LC 108
tions. –15 %/+10 % of nominal voltage.
Before making any connections in the LC 108 or work See also installation and operating instructions for the pump in
on pumps, pits, etc., it must be ensured that the elec- question.
tricity supply has been switched off and that it cannot
Mains frequency for LC 108
be accidentally switched on.
50/60 Hz.
During normal application and operation, the controller LC 108 is
See also installation and operating instructions for the pump in
maintenance-free.
question.
However, it is advisable to carry out minor checks of the LC 108
controller, pump pits, tanks, pumps, etc. at suitable intervals. Supply system earthing
These checks should be carried out by authorized personnel. For TN systems and TT systems.
• Check the gaskets of the LC 108 cabinet front and those of the Rated insulation voltage, Ui
Pg cable entries. 4 kV.
• Check for possible deposits/sludge build-up in the pump pit/
Rated impulse withstand voltage, Uimp
tank. Sludge may settle in areas with almost stagnant liquid.
4 kV.
• Check for beginning sludge build-up around the float switches,
electrodes or the flow switch. Short-circuit protection of supply
• Check for possible blockage on the suction side of the pump. Depending on variant, see nameplate.
A blockage will typically be a large solid object. Control circuit fuse
• If the LC 108 has been installed in a particularly aggressive Fine-wire fuse: 250 mA / F / 32 mm x ∅6 mm.
environment, it is advisable to check the motor protection con-
tacts in order to identify possible chemical attack resulting in Ambient temperature
corrosion. In typical installations, the motor protection contacts • During operation: –30 to +50 °C
will work for several years and do not require any inspection. (must not be exposed to direct sunlight).
Note: The above list is not complete. The LC 108 may be • In stock: –30 to +60 °C.
installed in systems, installations and/or environments which Enclosure class
require thorough and regular maintenance.
IP 65.
EMC (electromagnetic compatibility)
According to EN 61 000-6-2 and EN 61 000-6-3.
Cabinet LC 108 for direct-on-line starting
• External dimensions (including glands):
Height = 590 mm, width = 380 mm, depth = 220 mm.
• Material: ABS (Acrylonitrile butadiene styrene).
• Weight: Depending on variant, see nameplate.
Outputs for alarm devices
Max. 230 VAC / max. 2 A / min. 10 mA / AC1.
33
13. Fault finding chart
Before starting any work on pumps used to pump liquids which could be constituted as being hazardous to health, thorough
cleaning/venting of pumps, pits, etc. must be carried out according to local regulations.
Before making any connections in the LC 108 or work on pumps, pits, etc., it must be ensured that the electricity supply has
been switched off and that it cannot be accidentally switched on.
14. Disposal
Disposal of this product or parts of it must be carried out
according to the following guidelines:
1. Use the local public or private waste collection service.
2. In case such waste collection service does not exist or cannot
handle the materials used in the product, please deliver the
product or any hazardous materials from it to your nearest
Grundfos company or service workshop.
Subject to alterations.
34
Fig. A1
M
T11
Ext.
T21
U1
N1 H-NO
H-COM
max. 2A
1~
max. 230V
H-NC
1U2 1N2
G-NO
G-COM
G-NC
11
12
21
22
TM01 4864 1808
31
32
41
42
1
2
LC 108
U1
V1
W1
N1
ON
1U2 1V2
3~
1W2
DIP
1 2 3 4 5 6 7 8 9 10
35
36
Fig. A2
U1
V1
W1
N1
L1 L2 L3 N PE
1U2
1V2
1W2
2W2
2U2
2V2
T11
T12
Ext.
H-NO
1
2
H-COM
H-NC
max. 2A
G-NO
max. 230V
G-COM
G-NC
11
ON
12
21
22
31
32
41
42
1 2 3 4 5 6 7 8 9 10
DIP
LC 108
T11
Ext.
T21
U1 H-NO
N1
H-COM
H-NC
max. 2A
1~
G-NO
1U2 1N2
max. 230V
G-COM
G-NC
11
12
21
22
31
TM01 4864 1808
32
41
42
1
2
3
LC 108
U1
V1
W1
N1
1U2 1V2
3~
37
38
Fig. B2
U1
V1
W1
N1
1U2
L1 L2 L3 N PE
1V2
1W2
2W2
2U2
2V2
T11
T12
Ext.
H-NO
2
3
1
H-COM
H-NC
G-NO
max. 2A
max. 230V
G-COM
G-NC
11
ON
12
21
22
31
32
41
42
LC 108
1 2 3 4 5 6 7 8 9 10
DIP
T11
T21
U1
N1 H-NO
H-COM
max. 2A
H-NC
1~
max. 230V
1U2 1N2
G-NO
G-COM
G-NC
11
12
21
22
TM01 4864 1808
31
32
41
42
U1
V1
W1
N1
1U2 1V2
3~
1W2
TM01 4862 1808 TM01 6620 1808
39
40
Fig. C2
U1
V1
W1
N1
1U2
L1 L2 L3 N PE
1V2
1W2
2W2
2U2
2V2
T11
T12
Ext.
H-NO
1
2
3
4
H-COM
H-NC
max. 2A
G-NO
max. 230V
G-COM
G-NC
11
ON
12
21
22
31
32
41
42
LC 108
DIP
1 2 3 4 5 6 7 8 9 10
T11
T21
U1
N1
H-NO
H-COM
max. 2A
H-NC
max. 230V
1~
1U2 1N2
G-NO
G-COM
G-NC
11
12
21
22
TM01 4864 1808
31
32
41
42
U1
V1
W1
N1
1U2 1V2
3~
41
42
Fig. D2
U1
V1
W1
PE
N1
1U2
L1 L2 L3 N PE
1V2
1W2
2W2
2U2
2V2
T11
T12
Ext.
H-NO
1
H-COM
H-NC
G-NO
max. 2A
max. 230V
G-COM
G-NC
11
ON
12
21
22
31
32
41
42
NC
1 2 3 4 5 6 7 8 9 10
DIP
LC 108
T11
Ext.
T21
H-NO
U1
N1
H-COM
max. 2A
max. 230V
H-NC
1~
G-NO
1U2 1N2
G-COM
G-NC
11
12
21
22
31
TM01 4864 1808
32
41
1
2
3
42
LC 108
U1
V1
W1
N1
1U2 1V2
3~
3~
1W2
4
43
44
Fig. E2
U1
V1
W1
PE
N1
L1 L2 L3 N PE
1U2
1V2
1W2
2W2
2U2
2V2
T11
T12
Ext.
2
3
1
H-NO
H-COM
H-NC
G-NO
max. 2A
max. 230V
G-COM
G-NC
11
ON
12
21
22
31
32
41
42
NC
1 2 3 4 5 6 7 8 9 10
DIP
LC 108
T11
T21
U1 H-NO
N1
H-COM
H-NC
1~
G-NO
max. 2A
1U2 1N2
max. 230V
G-COM
G-NC
11
12
1
2
3
21
22
TM01 4864 1808 31
32
41
42
U1
V1
W1
N1
1U2 1V2
3~
1W2
TM01 4862 1808 TM01 6623 1808
45
46
Fig. F2
U1
V1
W1
PE
N1
L1 L2 L3 N PE
1U2
1V2
1W2
2W2
2U2
2V2
T11
T12
Ext.
H-NO
1
2
3
H-COM
H-NC
G-NO
max. 2A
max. 230V
G-COM
G-NC
ON
11
12
21
22
31
32
41
1 2 3 4 5 6 7 8 9 10
DIP
42
LC 108
NC
5
T11
U1
N1 T21
H-NO
H-COM
1~
1U2 1N2
H-NC
max. 2A
G-NO
max. 230V
G-COM
G-NC
11
12
21
U1
V1
W1
N1
1U2 1V2
3~
1W2
TM01 4862 1808 TM01 6624 1808
47
48
Fig. G2
U1
V1
W1
PE
N1
1U2
L1 L2 L3 N PE
1V2
1W2
2W2
2U2
2V2
T11
T12
Ext.
H-NO
H-COM
H-NC
G-NO
max. 2A
max. 230V
G-COM
G-NC
11
ON
12
21
22
31
32
41
42
1 2 3 4 5 6 7 8 9 10
DIP
LC 108
2
1
97502176 0609
GB
www.grundfos.com