Download as pdf or txt
Download as pdf or txt
You are on page 1of 52

GRUNDFOS INSTRUCTIONS

LC 108
Installation and operating instructions
Declaration of Conformity
We, Grundfos, declare under our sole responsibility that the product
LC/LCD 108, to which this declaration relates, is in conformity with these
Council directives on the approximation of the laws of the EC member
states:
— Machinery Directive (98/37/EC).
Standard used: EN 809: 2000.
— Low Voltage Directive (2006/95/EC).
Standards used: EN 60335-1: 2002 and EN 60335-2-51: 2003.
— EMC Directive (2004/108/EC).
Standards used: EN 61000-6-2 and EN 61000-6-3.

Bjerringbro, 15th December 2008

Niels Vinther
Technical Manager

2
CONTENTS 1. General
Page The LC 108 controller is designed for the control of pumps in
1. General 3 wastewater, water supply and drainage systems.
1.1 Applications 3 Type key:
1.2 Variants 4
2. Location and mounting 4 Example LC 108 400 3 23 SD
2.1 Location 4
LC = one-pump controller
2.2 Mounting of LC 108 for direct-on-line starting 4
3. Systems with 2 float switches 5 108 = type designation
3.1 Electrical connection 5 Phase voltage [V]
3.2 Setting 5 1 = single-phase
3.3 Control panel 7 3 = three-phase
3.4 Battery back-up functions 7
Maximum operating current per pump [A]
3.5 Reset button and ON-OFF-AUTO selector switch 8
SMS = with SMS unit
4. Systems with 3 float switches 9
4.1 Electrical connection 9
1.1 Applications
4.2 Setting 9
4.3 Control panel 11 The LC 108 enables:
4.4 Battery back-up functions 11 • control of one pump based on signals from float switches or
4.5 Reset button and ON-OFF-AUTO selector switch 12 electrodes,
5. Systems with 4 float switches 12 • selection of automatic test run during long periods of inactivity
5.1 Electrical connection 12 (every 24 hours),
5.2 Setting 13 • battery back-up in case of mains supply failure (accessory for
5.3 Control panel 14 certain variants),
5.4 Battery back-up functions 15 • starting delay within the range from 0 to 255 sec. (random)
5.5 Reset button and ON-OFF-AUTO selector switch 16 after returning from battery operation to mains operation
6. Systems with 2 electrodes 17 (resulting in an even mains load when several pumping sta-
6.1 Electrical connection 17 tions are started up at the same time),
6.2 Setting 17 • selection of automatic alarm resetting,
6.3 Control panel 19
• selection of automatic restarting,
6.4 Battery back-up functions 19
6.5 Reset button and ON-OFF-AUTO selector switch 20 • setting of stop delays matching the actual operating condi-
tions,
7. Systems with 3 electrodes 21
7.1 Electrical connection 21 • indication of liquid level,
7.2 Setting 21 • alarm indication of:
7.3 Control panel 23 - inadmissibly high liquid level,
7.4 Battery back-up functions 23 - overload (via motor protection relay),
7.5 Reset button and ON-OFF-AUTO selector switch 24
- overtemperature (via PTC resistance or thermal switch in
8. Systems for filling applications 25 motor),
8.1 Electrical connection 25
- wrong phase sequence (only certain variants),
8.2 Setting 25
8.3 Control panel 27 - mains supply failure (only certain variants),
8.4 Battery back-up functions 27 - defective float switch, electrode or flow switch,
8.5 Reset button and ON-OFF-AUTO selector switch 28 - dry running.
9. Systems for drainage applications 29 As standard, the LC 108 has one alarm output for common alarm.
9.1 Electrical connection 29 Certain variants have an additional alarm output for separate
9.2 Setting 29 high-level alarm.
9.3 Control panel 31 Furthermore, the controller incorporates a buzzer (only certain
9.4 Battery back-up functions 31 variants).
9.5 Reset button and ON-OFF-AUTO selector switch 32
10. Start-up 32
11. Maintenance 33
12. Technical data 33
13. Fault finding chart 34
14. Disposal 34

Before beginning installation procedures, these


installation and operating instructions should be
studied carefully. The installation and operation
should also be in accordance with local regulations
and accepted codes of good practice.

3
1.2 Variants Figure 1 shows the terminals listed under positions 2 and 3.
The actual controller type, voltage variant, etc. are stated in the
type key on the nameplate situated on the side of the controller
cabinet.
The LC 108 is available for either direct-on-line starting or star-
delta starting.
The LC 108 can be connected and set to operation/control in 7
different ways, see sections 3. to 9.:
• Section 3. Systems with 2 float switches.

TM04 4915 2209


(Electrodes can also be used.)

G-NC G-COM G-NO


H-NC H-COM H-NO

T12

12

22

32

42
• Section 4. Systems with 3 float switches.

T11

21

31

41
11
(Electrodes can also be used.)
• Section 5. Systems with 4 float switches.
(Electrodes can also be used.) Fig. 1
• Section 6. Systems with 2 electrodes.
Key to the symbols in figs. 1 and 1:
• Section 7. Systems with 3 electrodes.
• Section 8. Systems for filling applications. Pos. Description
• Section 9. Systems for drainage applications.
Terminal block for level inputs
1
(11-12, 21-22, 31-32, 41-42).
2. Location and mounting Terminal block with:
Before starting any work on pumps used to pump • input for the PTC resistance/thermal switch of the
liquids which could be constituted as being hazard- motor (T11-T21),
ous to health, thorough cleaning/venting of pumps, 2 • output for external alarm device for high-level alarm
pits, etc. must be carried out according to local regu- (H-NC, H-COM, H-NO) (only certain variants),
lations. • output for external alarm device for common alarm
Before making any connections in the LC 108 or work (G-NC, G-COM, G-NO).
on pumps, pits, etc., it must be ensured that the elec-
tricity supply has been switched off and that it cannot Note: If the distance between the controller and pit exceeds
be accidentally switched on. 20 metres, it is not advisable to use electrodes as problems with
the signal values sent back to the controller may arise.
The installation must be carried out by authorized personnel in
accordance with local regulations. In such cases, it is recommended to use float switches.
Note: Cables of up to 100 metres can be connected between the
2.1 Location controller and the float switches.

The LC 108 controller and an EEx barrier, if required,


must not be installed in explosion hazard areas.
Only float switches approved for use in explosion
hazard areas may be used. The float switches must
be connected via an EEx barrier, e.g. Grundfos
number 96440300.
The LC 108 can be mounted at ambient temperatures ranging
from –30 °C to +50 °C.
Enclosure class: IP 65.
When installed outdoors, the LC 108 must be placed in a protec-
tive shed or cupboard.
The LC 108 must not be exposed to direct sunlight.

2.2 Mounting of LC 108 for direct-on-line starting


Before mounting, remove the transport protectors, if any, from
inside the cabinet.
Mount the LC 108:
• on a plane wall surface,
• with the Pg cable entries pointing downwards
(additional Pg cable entries, if required, must be fitted in the
bottom plate of the cabinet),
• with four screws through the mounting holes in the back plate
of the cabinet. The mounting holes must be bored with a 4 mm
bore. Fit the screws into the mounting holes and tighten
securely. Fit the plastic caps supplied with the controller on the
screws (IP 65).

4
3. Systems with 2 float switches Key to the symbols in fig. A1 on page 35 and fig. A2 on
page 36:
Description (see also page 35 or 36):
The pump is controlled by the liquid level in the pit. Terminal
Pos. Description
• The pump is started when the float switch, pos. 1, registers number
liquid.
1 Float switch for start/stop of pump. 11-12
• When the float switch, pos. 1, no longer registers liquid, the
stop delay (can be set) is activated. After expiration of the stop 2 Float switch for high-level alarm. 31-32
delay, the pump is stopped.
3.2 Setting
• The upper float switch, pos. 2, activates the high-level alarm.
2 float switches, pages 35 and 36.
Before starting any work on pumps used to pump The module CU 211 has a 10-pole DIP switch in the bottom right
liquids which could be constituted as being hazard- corner, see fig. 2.
ous to health, thorough cleaning/venting of pumps, Note: During setting, the controller must be off circuit for at least
pits, etc. must be carried out according to local regu- 1 minute to ensure the correct configuration during start-up after
lations. change of the DIP switch setting.
Before making any connections in the LC 108 or work The DIP switch setting offers the following possibilities:
on pumps, pits, etc., it must be ensured that the elec-
• selection of starting delay and automatic test run (switch 4),
tricity supply has been switched off and that it cannot
be accidentally switched on. • setting of stop delay (switches 5, 6 and 7),
• selection of automatic alarm resetting (switch 9),
3.1 Electrical connection • selection of automatic restarting (switch 10).
2 float switches, pages 35 and 36.

Before starting work on the system, switch off the


supply voltage and lock the mains switch in
position 0.
Any external voltage connected to the system must
be switched off before work is started.
Fig. A1 on page 35.
The figures show all electrical connections required to connect
the LC 108 for direct-on-line starting, 2 float switches.
Fig. A2 on page 36.
The figure shows all electrical connections required to connect
the LC 108 for star-delta starting, 2 float switches.

The LC 108 must be connected in accordance with

TM01 6870 2308


the rules and standards in force for the application in
question.

The operating voltage and frequency are marked on the controller


nameplate. Make sure that the controller is suitable for the elec-
tricity supply on which it will be used.
Fig. 2
All cables/wires must be fitted through the Pg cable entries and
gaskets (IP 65). Set the DIP switch as shown in fig. 2.
Maximum back-up fuse is stated on the controller nameplate. Each individual switch (1 to 10) of the DIP switch can be set to
If required according to local regulations, an external mains position OFF or ON.
switch must be installed. Note: The DIP switch must not be set to other switch combina-
Note: If the PTC resistance/thermal switch of the motor is con- tions than those described in this section.
nected, the factory-fitted short-circuit jumper must be removed Set the switches 1 to 10 as follows:
(terminals T11-T21). • Switches 1, 2 and 3, application type:
Single-phase motors must be connected to an external operating
When the DIP switch setting is changed, the controller must
capacitor and in certain cases also to a starting capacitor. Further
be switched off for at least 1 minute!
details can be found in the installation and operating instructions
for the pump in question.
This setting determines the actual application type
Float switches or electrodes placed in an explosion (2 float switches, pages 35 and 36).
hazard area must be connected via an EEx barrier,
e.g. Grundfos number 96440300.
The EEx barrier must not be installed in the explosion
hazard area.
Equipment used in explosion hazard areas must in
each individual case have been approved for this
particular application. Furthermore, the cables into
the explosion hazard area must be laid in accordance
with local regulations.
Note: Float switches of the same type as Grundfos product
number 96003332 or 96003695, i.e. float switches with gold-
plated contacts suitable for low voltages and currents
(40 V/100 mA), must be used. All EEx-approved float switches
are also suitable.
The float switches must be connected as NO contacts, i.e. brown
and black leads, when float switches, Grundfos product number
96003332 or 96003695, are used.

5
• Switch 4, starting delay and automatic test run AC/DC selector:
(only in the case of battery back-up): The AC/DC selector switch for electrodes and/or float switches is
When the DIP switch setting is changed, the controller must placed as shown in fig. 3.
be switched off for at least 1 minute!

At this setting, the start-up is delayed within the range


from 0 to 255 sec. (random) after the electricity supply
has been switched on when the liquid level is suffi-
ciently high.
Automatic test run carried out every 24 hours.
After the electricity has been switched on, the pump will
start immediately when the liquid level is sufficiently
high.
No automatic test run.

TM02 5747 3902


• Switches 5, 6 and 7, stop delay:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!

The stop delay is the time from the stop signal is given until the
pump is stopped. Fig. 3
It must be ensured that the pump is not running dry.
Operation with electrodes and
0 sec. 60 sec. float switches:
Selector switch in position AC:
15 sec. 90 sec. 13-18 VAC 0V
It is possible to connect 3 elec-
trodes (1 as reference electrode)
AC 1 2 G 3 4 and 2 float switches.
30 sec. 120 sec. AC DC The controller transmits a
13-18 VAC signal.
Operation with float switches:
45 sec. 180 sec.
Selector switch in position AC:
It is possible to connect 4 float
• Switch 8: 13-18 VAC 0V
switches.
When the DIP switch setting is changed, the controller must The controller transmits a
be switched off for at least 1 minute! AC 1 2 G 3 4
13-18 VAC signal.
AC DC

Switch 8 has no function in connection with the actual


application (2 float switches, pages 35 and 36), but this Operation with float switches:
setting must be maintained!
Selector switch in position DC:
• Switch 9, automatic alarm resetting: It is possible to connect 4 float
When the DIP switch setting is changed, the controller must 12 VDC 0V
switches.
be switched off for at least 1 minute! Cables of up to 100 metres can be
connected between the controller
This setting ensures automatic resetting of alarm sig- AC 1 2 G 3 4
and the float switches.
nals to external alarm devices and the built-in buzzer. AC DC
The controller transmits a 12 VDC
However, an alarm signal will only be reset if the cause signal.
of the fault no longer exists.
If the distance between the controller and pit exceeds 20 metres,
At this setting, the alarm signal must be reset manually
it is not advisable to use electrodes as problems with the signal
by means of the reset button (the reset button is de-
values sent back to the controller may arise. In such cases, it is
scribed in section 3.5).
recommended to use float switches.
• Switch 10, automatic restarting:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!

This setting enables automatic restarting after the PTC


resistance/thermal switch of the motor has cut out the
pump. Restarting will not be carried out until the motor
has cooled to normal temperature.
When the pump connected is used in an explosion
hazard area, switch 10 must not be in this position!
At this setting, the pump must be restarted manually after
the PTC resistance/thermal switch of the motor has cut
out the pump. To restart the pump, push the ON-OFF-
AUTO selector switch into position OFF for a short period
(the ON-OFF-AUTO selector switch is described in
section 3.5).
When the pump connected is used in an explosion
hazard area, switch 10 must be in this position!

6
3.3 Control panel 3.4 Battery back-up functions
2 float switches, pages 35 and 36. 2 float switches, pages 35 and 36.
Figure 4 shows the control panel of the CU 211 module. If a back-up battery for CU 211 (accessory for certain variants) is
installed, the following functions will be carried out if the normal
electricity supply to the LC 108 fails (see also the illustrations
1 2 34 5 below):
• The common alarm is active, the red indicator light is on –
CU 211 1 cannot be reset!
1
12 • If the external alarm device for common alarm is supplied from
11 an external power source, this device will be active – cannot
10 be reset by means of the reset button!

TM01 6425 3902


9 • The built-in buzzer (only certain variants) is activated – can be
8 reset by means of the reset button!
• If the liquid level in the pit rises above the level for high-level
alarm, the top orange indicator light will be flashing and the
7
second orange indicator light from the top will be permanently
Fig. 4 on.
• If the starting delay function and automatic test run were
Key to the symbols in fig. 4: selected (switch 4 of the DIP switch), the start-up will be
delayed after the electricity supply has been switched on when
Pos. Description the liquid level is sufficiently high, see section 3.2.
Green indicator light, indicating starting delay (flashing) The table below shows the situations which may occur if the nor-
1
and pump operation (permanently on). mal electricity supply to the LC 108 fails and a back-up battery is
Red indicator light, indicating pump fault. connected:
2 Flashing: Fault in PTC resistor/thermal switch = the indicator light is off.
On: Fault in motor-protective circuit breaker. = the indicator light is on.
Red indicator light, indicating wrong phase sequence = the indicator light is flashing.
3
(only certain variants and three-phase pumps only).
4 Red indicator light, indicating common alarm. CU 211 Mains supply failure:
1

ON-OFF-AUTO selector switch, three positions, • The common alarm is active.


5
see section 3.5. The red indicator light is on.
Reset button, push-button for manual resetting of alarm • The green indicator light (electricity
7 signals to external alarm devices and the built-in buzzer supply switched on) is off.
(only certain variants), see section 3.5.
Orange indicator light, which is activated by the float Mains supply failure and high-level alarm:
8 • The common alarm is active.
switch for start/stop of pump.
CU 211 The red indicator light is on.
3 orange indicator lights, which are activated by the float 1

9, 10 switch for high-level alarm. • The top orange indicator light is flash-
and In case of high-level alarm, the top indicator light is ing.
11 flashing and the two other indicator lights are perma- • The second orange indicator light from
nently on. the top is on.
Green indicator light, indicating that the electricity sup- • The green indicator light (electricity
12
ply has been switched on. supply switched on) is off.

7
3.5 Reset button and ON-OFF-AUTO selector switch
2 float switches, pages 35 and 36.

The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:

ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long
period, the pump will be damaged!
In explosion hazard areas, switch 10 of the DIP switch must be set as stated in section 3.2. Consequently, the
pump cannot be started when the PTC resistance/thermal switch of the motor registers overtemperature.

OFF ( ), middle position:


1 • The pump cannot start when the selector switch has been set to this position.
• The alarm memory is reset by pushing the selector switch into position OFF ( ). The alarm memory is the light
indication of a fault condition which has disappeared. If a fault condition still exists when the selector switch is
pushed into position ON ( ) or AUTO ( ), the alarm indication will be repeated immediately.

AUTO ( ), bottom position:


• The pump is controlled by the input signals from the float switches and the pump according to the selected DIP
switch setting.
• Alarm signals will automatically be reset. Switch 9 of the DIP switch can, however, be set to manual resetting
which is carried out by means of the reset button, see section 3.2.
• The pump will restart automatically when a given fault condition disappears. However, this is dependent on the
setting of switch 10 of the DIP switch, see section 3.2.
• When the pump starts automatically after a fault condition which has disappeared, the indicator light will continue
to show the fault condition (alarm memory) and the indication can only be removed by resetting the alarm memory,
see position OFF ( ).

8
4. Systems with 3 float switches Key to the symbols in fig. B1 on page 37 and fig. B2 on
page 38:
Description (see also page 37 or 38):
The pump is controlled by the liquid level in the pit. Pos. Description Terminal number
• The float switch, pos. 2, starts the pump.
1 Float switch for stop of pump. 11-12
• The float switch, pos. 1, stops the pump. It is possible to set a
2 Float switch for start of pump. 21-22
"stop delay" which delays the stop of the pump.
• The top float switch, pos. 3, activates the high-level alarm. 3 Float switch for high-level alarm. 31-32

Before starting any work on pumps used to pump liq- 4.2 Setting
uids which could be constituted as being hazardous 3 float switches, pages 37 and 38.
to health, thorough cleaning/venting of pumps, pits,
The module CU 211 has a 10-pole DIP switch in the bottom right
etc. must be carried out according to local regula-
corner, see fig. 5.
tions.
Note: During setting, the controller must be off circuit for at least
Before making any connections in the LC 108 or work
1 minute to ensure the correct configuration during start-up after
on pumps, pits, etc., it must be ensured that the elec-
change of the DIP switch setting.
tricity supply has been switched off and that it cannot
be accidentally switched on. The DIP switch setting offers the following possibilities:
• selection of starting delay and automatic test run (switch 4),
4.1 Electrical connection • setting of stop delay (switches 5, 6 and 7),
3 float switches, pages 37 and 38. • selection of automatic alarm resetting (switch 9),
Before starting work on the system, switch off the • selection of automatic restarting (switch 10).
supply voltage and lock the mains switch in
position 0.
Any external voltage connected to the system must
be switched off before work is started.
Fig. B1 on page 37.
The figures show all electrical connections required to connect
the LC 108 for direct-on-line starting, 3 float switches.
Fig. B2 on page 38.
The figure shows all electrical connections required to connect
the LC 108 for start-delta starting, 3 float switches.

The LC 108 must be connected in accordance with


the rules and standards in force for the application in
question.

TM04 2341 2308


The operating voltage and frequency are marked on the controller
nameplate. Make sure that the controller is suitable for the elec-
tricity supply on which it will be used.
All cables/wires must be fitted through the Pg cable entries and
gaskets (IP 65).
Maximum back-up fuse is stated on the controller nameplate. Fig. 5
If required according to local regulations, an external mains Set the DIP switch as shown in fig. 5.
switch must be installed.
Each individual switch (1 to 10) of the DIP switch can be set to
Note: If the PTC resistance/thermal switch of the motor is con- position OFF or ON.
nected, the factory-fitted short-circuit jumper must be removed
Note: The DIP switch must not be set to other switch
(terminals T11-T21).
combinations than those described in this section.
Single-phase motors must be connected to an external operating
capacitor and in certain cases also to a starting capacitor. Further Set the switches 1 to 10 as follows:
details can be found in the installation and operating instructions • Switches 1, 2 and 3, application type:
for the pump in question. When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
Float switches or electrodes placed in an explosion
hazard area must be connected via an EEx barrier,
This setting determines the actual application type
e.g. Grundfos number 96440300.
(3 float switches, pages 37 and 38).
The EEx barrier must not be installed in the explosion
hazard area.
• Switch 4, starting delay and automatic test run
Equipment used in explosion hazard areas must in (only in the case of battery back-up):
each individual case have been approved for this
When the DIP switch setting is changed, the controller must
particular application. Furthermore, the cables into
be switched off for at least 1 minute!
the explosion hazard area must be laid in accordance
with local regulations. At this setting, the start-up is delayed within the range
Note: Float switches of the same type as Grundfos product from 0 to 255 sec. (random) after the electricity supply
number 96003332 or 96003695, i.e. float switches with gold- has been switched on when the liquid level is suffi-
plated contacts suitable for low voltages and currents (40 V/ ciently high.
100 mA), must be used. All EEx-approved float switches are also Automatic test run carried out every 24 hours.
suitable. After the electricity has been switched on, the pump will
The float switches must be connected as NO contacts, i.e. brown start immediately when the liquid level is sufficiently
and black leads, when float switches, Grundfos product number high.
96003332 or 96003695, are used. No automatic test run.

9
• Switches 5, 6 and 7, stop delay: AC/DC selector:
When the DIP switch setting is changed, the controller must The AC/DC selector switch for electrodes and/or float switches is
be switched off for at least 1 minute! placed as shown in fig. 6.

The stop delay is the time from the stop signal is given until the
pump is stopped.
It must be ensured that the pump is not running dry.

0 sec. 60 sec.

15 sec. 90 sec.

30 sec. 120 sec.

TM02 5747 3902


45 sec. 180 sec.

• Switch 8:
Fig. 6
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
Operation with electrodes and
Switch 8 has no function in connection with the actual float switches:
application (3 float switches, pages 37 and 38), but this Selector switch in position AC:
setting must be maintained! 13-18 VAC 0V
It is possible to connect 3 elec-
• Switch 9, automatic alarm resetting: trodes (1 as reference electrode)
When the DIP switch setting is changed, the controller must AC 1 2 G 3 4 and 2 float switches.
be switched off for at least 1 minute!
AC DC The controller transmits a
13-18 VAC signal.
This setting ensures automatic resetting of alarm sig- Operation with float switches:
nals to external alarm devices and the built-in buzzer.
However, an alarm signal will only be reset if the cause Selector switch in position AC:
of the fault no longer exists. It is possible to connect 4 float
13-18 VAC 0V
switches.
At this setting, the alarm signal must be reset manually
The controller transmits a
by means of the reset button (the reset button is AC 1 2 G 3 4
13-18 VAC signal.
described in section 4.5). AC DC

• Switch 10, automatic restarting:


Operation with float switches:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute! Selector switch in position DC:
It is possible to connect 4 float
This setting enables automatic restarting after the PTC switches.
0V
resistance/thermal switch of the motor has cut out the
12 VDC
Cables of up to 100 metres can be
pump. Restarting will not be carried out until the motor connected between the controller
has cooled to normal temperature. AC 1 2 G 3 4
and the float switches.
AC DC
When the pump connected is used in an explosion The controller transmits a 12 VDC
hazard area, switch 10 must not be in this position! signal.
At this setting, the pump must be restarted manually after If the distance between the controller and pit exceeds 20 metres,
the PTC resistance/thermal switch of the motor has cut it is not advisable to use electrodes as problems with the signal
out the pump. To restart the pump, push the ON-OFF- values sent back to the controller may arise. In such cases, it is
AUTO selector switch into position OFF for a short period recommended to use float switches.
(the ON-OFF-AUTO selector switch is described in sec-
tion 4.5).
When the pump connected is used in an explosion
hazard area, switch 10 must be in this position!

10
4.3 Control panel 4.4 Battery back-up functions
3 float switches, pages 37 and 38. 3 float switches, pages 37 and 38.
Figure 7 shows the control panel of the CU 211 module. If a back-up battery for CU 211 (accessory for certain variants) is
installed, the following functions will be carried out if the normal
1 234 5
electricity supply to the LC 108 fails (see also the illustrations
below):
• The common alarm is active, the red indicator light is on –
CU 211 1 cannot be reset!
1
12 • If the external alarm device for common alarm is supplied from
11 an external power source, this device will be active – cannot
10 be reset by means of the reset button!
9 • The built-in buzzer (only certain variants) is activated – can be

TM01 6425 3902


8 reset by means of the reset button!
• If the liquid level in the pit rises above the level for high-level
alarm, the top orange indicator light will be flashing and the
7 second orange indicator light from the top will be permanently
Fig. 7 on.
• If the starting delay function and automatic test run were
Key to the symbols in fig. 7: selected (switch 4 of the DIP switch), the start-up will be
delayed after the electricity supply has been switched on when
Pos. Description the liquid level is sufficiently high, see section 4.2.
Green indicator light, indicating starting delay (flashing) The table below shows the situations which may occur if the nor-
1
and pump operation (permanently on). mal electricity supply to the LC 108 fails and a back-up battery is
Red indicator light, indicating pump fault connected:
2 Flashing: Fault in PTC resistor/thermal switch = the indicator light is off.
On: Fault in motor-protective circuit breaker = the indicator light is on.
Red indicator light, indicating wrong phase sequence = the indicator light is flashing.
3
(only certain variants and three-phase pumps only).
4 Red indicator light, indicating common alarm. CU 211 1
Mains supply failure:
ON-OFF-AUTO selector switch, three positions, • The common alarm is active.
5
see section 4.5. The red indicator light is on.
Reset button, push-button for manual resetting of alarm • The green indicator light (electricity
7 signals to external alarm devices and the built-in buzzer supply switched on) is off.
(only certain variants), see section 4.5.
Mains supply failure and high-level alarm:
Orange indicator light, which is activated by the float
8 • The common alarm is active.
switch for stop of pump.
CU 211 The red indicator light is on.
Orange indicator light, which is activated by the float 1
9 • The top orange indicator light is flash-
switch for start of pump.
ing.
2 orange indicator lights, which are activated by the float
10 • The second orange indicator light from
switch for high-level alarm.
and the top is on.
In case of high-level alarm, the top indicator light is
11
flashing and the other indicator light is permanently on. • The green indicator light (electricity
Green indicator light, indicating that the electricity sup- supply switched on) is off.
12
ply has been switched on.

11
4.5 Reset button and ON-OFF-AUTO selector switch
3 float switches, pages 37 and 38.

The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:

ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long pe-
riod, the pump will be damaged!
In explosion hazard areas, switch 10 of the DIP switch must be set as stated in section 4.2. Consequently, the
pump cannot be started when the PTC resistance/thermal switch of the motor registers overtemperature.

OFF ( ), middle position:


1 • The pump cannot start when the selector switch has been set to this position.
• The alarm memory is reset by pushing the selector switch into position OFF ( ). The alarm memory is the light in-
dication of a fault condition which has disappeared. If a fault condition still exists when the selector switch is
pushed into position ON ( ) or AUTO ( ), the alarm indication will be repeated immediately.

AUTO ( ), bottom position:


• The pump is controlled by the input signals from the float switches and the pump according to the selected DIP
switch setting.
• Alarm signals will automatically be reset. Switch 9 of the DIP switch can, however, be set to manual resetting
which is carried out by means of the reset button, see section 4.2.
• The pump will restart automatically when a given fault condition disappears. However, this is dependent on the
setting of switch 10 of the DIP switch, see section 4.2.
• When the pump starts automatically after a fault condition which has disappeared, the indicator light will continue
to show the fault condition (alarm memory) and the indication can only be removed by resetting the alarm memory,
see position OFF ( ).

5. Systems with 4 float switches Fig. C2 on page 40.

Description (see also page 39 or 40): The figure shows all electrical connections required to connect
the LC 108 for star-delta starting, 4 float switches.
The pump is controlled by the liquid level in the pit.
• The float switch, pos. 3, starts the pump. The LC 108 must be connected in accordance with
• The float switch, pos. 2, stops the pump. It is possible to set a the rules and standards in force for the application in
"stop delay" which delays the stop of the pump. question.
• The top float switch, pos. 4, activates the high-level alarm.
The operating voltage and frequency are marked on the controller
• The bottom float switch, pos. 1, activates the dry-running nameplate. Make sure that the controller is suitable for the elec-
alarm. tricity supply on which it will be used.
Before starting any work on pumps used to pump liq- All cables/wires must be fitted through the Pg cable entries and
uids which could be constituted as being hazardous gaskets (IP 65).
to health, thorough cleaning/venting of pumps, pits, Maximum back-up fuse is stated on the controller nameplate.
etc. must be carried out according to If required according to local regulations, an external mains
local regulations. switch must be installed.
Before making any connections in the LC 108 or work Note: If the PTC resistance/thermal switch of the motor is con-
on pumps, pits, etc., it must be ensured that the elec- nected, the factory-fitted short-circuit jumper must be removed
tricity supply has been switched off and that it cannot (terminals T11-T21).
be accidentally switched on. Single-phase motors must be connected to an external operating
capacitor and in certain cases also to a starting capacitor. Further
5.1 Electrical connection details can be found in the installation and operating instructions
4 float switches, pages 39 and 40. for the pump in question.

Before starting work on the system, switch off the


supply voltage and lock the mains switch in
position 0.
Any external voltage connected to the system must
be switched off before work is started.
Fig. C1 on page 39.
The figures show all electrical connections required to connect
the LC 108 for direct-on-line starting, 4 float switches.

12
Each individual switch (1 to 10) of the DIP switch can be set to
Float switches or electrodes placed in an explosion
position OFF or ON.
hazard area must be connected via an EEx barrier,
e.g. Grundfos number 96440300. Note: The DIP switch must not be set to other switch combina-
The EEx barrier must not be installed in the explosion tions than those described in this section.
hazard area. Set the switches 1 to 10 as follows:
Equipment used in explosion hazard areas must in • Switches 1, 2 and 3, application type:
each individual case have been approved for this When the DIP switch setting is changed, the controller must
particular application. Furthermore, the cables into be switched off for at least 1 minute!
the explosion hazard area must be laid in accordance
with local regulations. This setting determines the actual application type
Note: Float switches of the same type as Grundfos product (4 float switches, pages 39 and 40).
number 96003332 or 96003695, i.e. float switches with
gold-plated contacts suitable for low voltages and currents • Switch 4, starting delay and automatic test run
(40 V/100 mA), must be used. All EEx-approved float switches (only in the case of battery back-up):
are also suitable. When the DIP switch setting is changed, the controller must
The float switches must be connected as NO contacts, i.e. brown be switched off for at least 1 minute!
and black leads, when float switches, Grundfos product number
96003332 or 96003695, are used. At this setting, the start-up is delayed within the range
from 0 to 255 sec. (random) after the electricity supply
Key to the symbols in fig. C1 on page 39 and fig. C2 on has been switched on when the liquid level is suffi-
page 40: ciently high.
Automatic test run carried out every 24 hours.
Terminal
Pos. Description After the electricity has been switched on, the pump will
number
start immediately when the liquid level is sufficiently
1 Float switch for dry-running alarm. 11-12 high.
2 Float switch for stop of pump. 21-22 No automatic test run.
3 Float switch for start of pump. 31-32 • Switches 5, 6 and 7, stop delay:
4 Float switch for high-level alarm. 41-42 When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!
5.2 Setting
4 float switches, pages 39 and 40. The stop delay is the time from the stop signal is given until the
pump is stopped.
The module CU 211 has a 10-pole DIP switch in the bottom right
It must be ensured that the pump is not running dry.
corner, see fig. 8.
Note: During setting, the controller must be off circuit for at least 0 sec. 60 sec.
1 minute to ensure the correct configuration during start-up after
change of the DIP switch setting.
The DIP switch setting offers the following possibilities: 15 sec. 90 sec.
• selection of starting delay and automatic test run (switch 4),
• setting of stop delay (switches 5, 6 and 7),
30 sec. 120 sec.
• selection of automatic alarm resetting (switch 9),
• selection of automatic restarting (switch 10).
45 sec. 180 sec.

• Switch 8:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!

Switch 8 has no function in connection with the actual


application (4 float switches, pages 39 and 40), but this
setting must be maintained!

• Switch 9, automatic alarm resetting:


When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!

This setting ensures automatic resetting of alarm sig-


nals to external alarm devices and the built-in buzzer.
TM04 2340 2308

However, an alarm signal will only be reset if the cause


of the fault no longer exists.
At this setting, the alarm signal must be reset manually
by means of the reset button (the reset button is de-
scribed in section 5.5).
Fig. 8

Set the DIP switch as shown in fig. 8.

13
• Switch 10, automatic restarting: 5.3 Control panel
When the DIP switch setting is changed, the controller must 4 float switches, pages 39 and 40.
be switched off for at least 1 minute!
Figure 10 shows the control panel of the CU 211 module.
This setting enables automatic restarting after the PTC
resistance/thermal switch of the motor has cut out the 1 234 5
pump. Restarting will not be carried out until the motor
has cooled to normal temperature.
CU 211 1
When the pump connected is used in an explosion 1
hazard area, switch 10 must not be in this position! 12
At this setting, the pump must be restarted manually after 11
10
the PTC resistance/thermal switch of the motor has cut
9

TM01 6425 3902


out the pump. To restart the pump, push the ON-OFF-
8
AUTO selector switch into position OFF for a short period
(the ON-OFF-AUTO selector switch is described in
section 5.5).
7
When the pump connected is used in an explosion
hazard area, switch 10 must be in this position! Fig. 10

AC/DC selector: Key to the symbols in fig. 10:


The AC/DC selector switch for electrodes and/or float switches is
placed as shown in fig. 9. Pos. Description
Green indicator light, indicating starting delay (flashing)
1
and pump operation (permanently on).
Red indicator light, indicating pump fault.
2 Flashing: Fault in PTC resistor/thermal switch
On: Fault in motor-protective circuit breaker.
Red indicator light, indicating wrong phase sequence
3
(only certain variants and three-phase pumps only).
4 Red indicator light, indicating common alarm.
ON-OFF-AUTO selector switch, three positions, see
5
section 5.5.
TM02 5747 3902

Reset button, push-button for manual resetting of alarm


7 signals to external alarm devices and the built-in buzzer
(only certain variants), see section 5.5.
Orange indicator light, which is activated by the float
switch for dry-running alarm.
Fig. 9
8 In case of dry-running alarm, the indicator light is flash-
ing. Under normal operating conditions, the indicator
Operation with electrodes and light is permanently on.
float switches:
Orange indicator light, which is activated by the float
9
Selector switch in position AC: switch for stop of pump.
13-18 VAC 0V
It is possible to connect 3 elec- Orange indicator light, which is activated by the float
trodes (1 as reference electrode) 10
switch for start of pump.
AC 1 2 G 3 4 and 2 float switches.
Orange indicator light, which is activated by the float
AC DC The controller transmits a
11 switch for high-level alarm.
13-18 VAC signal.
In case of high-level alarm, the indicator light is flashing.
Operation with float switches:
Green indicator light, indicating that the electricity sup-
12
Selector switch in position AC: ply has been switched on.
It is possible to connect 4 float
13-18 VAC 0V
switches.
The controller transmits a
AC 1 2 G 3 4
13-18 VAC signal.
AC DC

Operation with float switches:

Selector switch in position DC:


It is possible to connect 4 float
12 VDC 0V switches.
Cables of up to 100 metres can be
connected between the controller
AC 1 2 G 3 4
AC DC
and the float switches.
The controller transmits a 12 VDC
signal.

If the distance between the controller and pit exceeds 20 metres,


it is not advisable to use electrodes as problems with the signal
values sent back to the controller may arise. In such cases, it is
recommended to use float switches.

14
5.4 Battery back-up functions
4 float switches, pages 39 and 40.
If a back-up battery for CU 211 (accessory for certain variants) is
installed, the following functions will be carried out if the normal
electricity supply to the LC 108 fails (see also the illustrations
below):
• The common alarm is active, the red indicator light is on –
cannot be reset!
• If the external alarm device for common alarm is supplied from
an external power source, this device will be active – cannot
be reset by means of the reset button!
• The built-in buzzer (only certain variants) is activated – can be
reset by means of the reset button!
• If the liquid level in the pit rises above the level for high-level
alarm, the top orange indicator light will be flashing and the
second orange indicator light from the top will be permanently
on.
• If the starting delay function and automatic test run were
selected (switch 4 of the DIP switch), the start-up will be
delayed after the electricity supply has been switched on when
the liquid level is sufficiently high, see section 5.2.
The table below shows the situations which may occur if the nor-
mal electricity supply to the LC 108 fails and a back-up battery is
connected:
= the indicator light is off.
= the indicator light is on.
= the indicator light is flashing.

CU 211 1
Mains supply failure:
• The common alarm is active.
The red indicator light is on.
• The green indicator light (electricity
supply switched on) is off.

Mains supply failure and high-level alarm:


• The common alarm is active.
CU 211 1
The red indicator light is on.
• The top orange indicator light is flash-
ing.
• The second orange indicator light from
the top is on.
• The green indicator light (electricity
supply switched on) is off.

15
5.5 Reset button and ON-OFF-AUTO selector switch
4 float switches, pages 39 and 40.

The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:

ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long pe-
riod, the pump will be damaged!
In explosion hazard areas, switch 10 of the DIP switch must be set as stated in section 5.2. Consequently, the
pump cannot be started when the PTC resistance/thermal switch of the motor registers overtemperature.

OFF ( ), middle position:


1 • The pump cannot start when the selector switch has been set to this position.
• The alarm memory is reset by pushing the selector switch into position OFF ( ). The alarm memory is the light in-
dication of a fault condition which has disappeared. If a fault condition still exists when the selector switch is
pushed into position ON ( ) or AUTO ( ), the alarm indication will be repeated immediately.

AUTO ( ), bottom position:


• The pump is controlled by the input signals from the float switches and the pump according to the selected DIP
switch setting.
• Alarm signals will automatically be reset. Switch 9 of the DIP switch can, however, be set to manual resetting
which is carried out by means of the reset button, see section 5.2.
• The pump will restart automatically when a given fault condition disappears. However, this is dependent on the
setting of switch 10 of the DIP switch, see section 5.2.
• When the pump starts automatically after a fault condition which has disappeared, the indicator light will continue
to show the fault condition (alarm memory) and the indication can only be removed by resetting the alarm memory,
see position OFF ( ).

16
6. Systems with 2 electrodes Key to the symbols in fig. D1 on page 41 and fig. D2 on
page 42:
Description (see also page 41 or 42):
The pump is controlled by the liquid level in the borehole. Terminal
Pos. Description
• The electrode, pos. 1, is the reference electrode. number
• When the electrode, pos. 2, registers liquid, the "waiting time" 1 Reference electrode. 11
is initiated (can be set). After expiration of the waiting time, the
2 Electrode for start/stop of pump. 12
pump is started.
3 Pressure switch. 41-42
• The pump is stopped when the electrode, pos. 2, does not reg-
ister any liquid. 6.2 Setting
• The pressure switch, pos. 3, stops the pump if the discharge
2 electrodes, pages 41 and 42.
pressure exceeds the stop pressure of the pressure switch. Re-
starting at the starting pressure of the pressure switch is only The module CU 211 has a 10-pole DIP switch in the bottom right
effected if the electrode, pos. 2, registers liquid. corner, see fig. 11.
Note: During setting, the controller must be off circuit for at least
Before starting any work on pumps used to pump liq- 1 minute to ensure the correct configuration during start-up after
uids which could be constituted as being hazardous change of the DIP switch setting.
to health, thorough cleaning/venting of pumps, pits,
The DIP switch setting offers the following possibilities:
etc. must be carried out according to local regula-
tions. • selection of starting delay and automatic test run (switch 4),
Before making any connections in the LC 108 or work • setting of waiting time (switches 5, 6, 7 and 8),
on pumps, pits, etc., it must be ensured that the elec- • selection of automatic alarm resetting (switch 9),
tricity supply has been switched off and that it cannot • selection of automatic restarting (switch 10).
be accidentally switched on.

6.1 Electrical connection


2 electrodes, pages 41 and 42.

Before starting work on the system, switch off the


supply voltage and lock the mains switch in
position 0.
Any external voltage connected to the system must
be switched off before work is started.
Fig. D1 on page 41.
The figures show all electrical connections required to connect
the LC 108 for direct-on-line starting, 2 electrodes.
Fig. D2 on page 42.
The figure shows all electrical connections required to connect
the LC 108 for star-delta starting, 2 electrodes.

TM04 2342 2308


The LC 108 must be connected in accordance with
the rules and standards in force for the application in
question.

The operating voltage and frequency are marked on the controller Fig. 11
nameplate. Make sure that the controller is suitable for the elec-
Set the DIP switch as shown in fig. 11.
tricity supply on which it will be used.
Each individual switch (1 to 10) of the DIP switch can be set to
All cables/wires must be fitted through the Pg cable entries and
position OFF or ON.
gaskets (IP 65).
Note: The DIP switch must not be set to other switch combina-
Maximum back-up fuse is stated on the controller nameplate.
tions than those described in this section.
If required according to local regulations, an external mains
Set the switches 1 to 10 as follows:
switch must be installed.
• Switches 1, 2 and 3, application type:
Note: If the PTC resistance/thermal switch of the motor is con-
nected, the factory-fitted short-circuit jumper must be removed When the DIP switch setting is changed, the controller must
(terminals T11-T21). be switched off for at least 1 minute!
Single-phase motors must be connected to an external operating
capacitor and in certain cases also to a starting capacitor. Further This setting determines the actual application type
details can be found in the installation and operating instructions (2 electrodes, pages 41 and 42).
for the pump in question.

Float switches or electrodes placed in an explosion


hazard area must be connected via an EEx barrier,
e.g. Grundfos number 96440300.
The EEx barrier must not be installed in the explosion
hazard area.
Equipment used in explosion hazard areas must in
each individual case have been approved for this
particular application. Furthermore, the cables into
the explosion hazard area must be laid in accordance
with local regulations.
Note: The motor/pump housing must not be used as reference
electrode.
The pressure switch, pos. 3, must be connected as an NC
contact.

17
• Switch 4, starting delay and automatic test run AC/DC selector:
(only in the case of battery back-up): The AC/DC selector switch for electrodes and/or float switches is
When the DIP switch setting is changed, the controller must placed as shown in fig. 12.
be switched off for at least 1 minute!

At this setting, the start-up is delayed within the range


from 0 to 255 sec. (random) after the electricity supply
has been switched on when the liquid level is
sufficiently high.
Automatic test run carried out every 24 hours.
After the electricity has been switched on, the pump will
start immediately when the liquid level is sufficiently
high.
No automatic test run.

TM02 5747 3902


• Switches 5, 6, 7 and 8, waiting time:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!

The waiting time is the time from the electrode registers liquid
until the pump starts (starting delay). Fig. 12

1 min. 30 min. Operation with electrodes and


float switches:

2 min. 35 min. Selector switch in position AC:


13-18 VAC 0V
It is possible to connect 3 elec-
trodes (1 as reference electrode)
3 min. 40 min. AC 1 2 G 3 4 and 2 float switches.
AC DC The controller transmits a
13-18 VAC signal.
5 min. 45 min. Operation with float switches:
Selector switch in position AC:
10 min. 50 min. It is possible to connect 4 float
13-18 VAC 0V
switches.
The controller transmits a
15 min. 55 min. AC 1 2 G 3 4
13-18 VAC signal.
AC DC

20 min. 60 min. Operation with float switches:


Selector switch in position DC:
It is possible to connect 4 float
25 min. 65 min.
12 VDC 0V
switches.
Cables of up to 100 metres can be
• Switch 9, automatic alarm resetting: connected between the controller
AC 1 2 G 3 4
When the DIP switch setting is changed, the controller must and the float switches.
AC DC
be switched off for at least 1 minute! The controller transmits a 12 VDC
signal.
This setting ensures automatic resetting of alarm sig-
nals to external alarm devices and the built-in buzzer. If the distance between the controller and pit exceeds 20 metres,
However, an alarm signal will only be reset if the cause it is not advisable to use electrodes as problems with the signal
of the fault no longer exists. values sent back to the controller may arise. In such cases, it is
recommended to use float switches.
At this setting, the alarm signal must be reset manually
by means of the reset button (the reset button is
described in section 6.5).

• Switch 10, automatic restarting:


When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute
!

This setting enables automatic restarting after the PTC


resistance/thermal switch of the motor has cut out the
pump. Restarting will not be carried out until the motor
has cooled to normal temperature.
When the pump connected is used in an explosion
hazard area, switch 10 must not be in this position!
At this setting, the pump must be restarted manually after
the PTC resistance/thermal switch of the motor has cut
out the pump. To restart the pump, push the ON-OFF-
AUTO selector switch into position OFF for a short period
(the ON-OFF-AUTO selector switch is described in sec-
tion 6.5).
When the pump connected is used in an explosion
hazard area, switch 10 must be in this position!

18
6.3 Control panel 6.4 Battery back-up functions
2 electrodes, pages 41 and 42. 2 electrodes, pages 41 and 42.
For these applications, the foil supplied with the LC 108 must be If a back-up battery for CU 211 (accessory for certain variants) is
attached to the CU 211 control panel as shown in fig. 13. The foil installed, the following functions will be carried out if the normal
can be found inside the LC 108 cabinet at the bottom. electricity supply to the LC 108 fails (see also the illustrations
Figure 13 shows how the foil is attached to the CU 211 module. below):
• The common alarm is active, the red indicator light is on – can-
CU 211 1 not be reset!

TM01 6413 2299


1

• If the external alarm device for common alarm is supplied from


an external power source, this device will be active – cannot be
reset by means of the reset button!
• The built-in buzzer (only certain variants) is activated – can be
reset by means of the reset button!
Fig. 13
• If the starting delay function and automatic test run were se-
Figure 14 shows the control panel of the CU 211 module. lected (switch 4 of the DIP switch), the start-up will be delayed
after the electricity supply has been switched on when the liq-
1 234 5 uid level is sufficiently high, see section 6.2.
The table below shows the situation which may occur if the nor-
mal electricity supply to the LC 108 fails and a back-up battery is
CU 211 1 connected:
1
12 = the indicator light is off.
11 = the indicator light is on.
10
= the indicator light is flashing.
9 TM01 6424 2399

8
CU 211 1
Mains supply failure:
• The common alarm is active.
7 The red indicator light is on.

Fig. 14 • The green indicator light (electricity


supply switched on) is off.
Key to the symbols in fig. 14:

Pos. Description
Green indicator light, indicating starting delay (flashing)
1
and pump operation (permanently on).
Red indicator light, indicating pump fault.
2 Flashing: Fault in PTC resistor/thermal switch
On: Fault in motor-protective circuit breaker.
Red indicator light, indicating wrong phase sequence
3
(only certain variants and three-phase pumps only).
4 Red indicator light, indicating common alarm.
ON-OFF-AUTO selector switch, three positions, see
5
section 6.5.
Reset button, push-button for manual resetting of alarm
7 signals to external alarm devices and the built-in buzzer
(only certain variants), see section 6.5.
Orange indicator light, which is activated by the elec-
8
trode for start/stop of pump.
9
Have no function in connection with the actual applica-
and
tion!
10
Orange indicator light, which is activated by the pres-
sure switch in the discharge pipe.
The pump is stopped if the pressure is higher than the
stop pressure of the pressure switch (the indicator light
11 is permanently on).
The pump is started if the pressure is lower than the
starting pressure of the pressure switch and the elec-
trode for start/stop of pump (see pos. 8 above) gives a
starting signal at the same time.
Green indicator light, indicating that the electricity sup-
12
ply has been switched on.

19
6.5 Reset button and ON-OFF-AUTO selector switch
2 electrodes, pages 41 and 42.

The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:

ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long pe-
riod, the pump will be damaged!
In explosion hazard areas, switch 10 of the DIP switch must be set as stated in section 6.2. Consequently,
the pump cannot be started when the PTC resistance/thermal switch of the motor registers overtemperature.

OFF ( ), middle position:


1 • The pump cannot start when the selector switch has been set to this position.
• The alarm memory is reset by pushing the selector switch into position OFF ( ). The alarm memory is the light in-
dication of a fault condition which has disappeared. If a fault condition still exists when the selector switch is
pushed into position ON ( ) or AUTO ( ), the alarm indication will be repeated immediately.

AUTO ( ), bottom position:


• The pump is controlled by the input signals from the electrodes and the pump according to the selected DIP switch
setting.
• Alarm signals will automatically be reset. Switch 9 of the DIP switch can, however, be set to manual resetting
which is carried out by means of the reset button, see section 6.2.
• The pump will restart automatically when a given fault condition disappears. However, this is dependent on the
setting of switch 10 of the DIP switch, see section 6.2.
• When the pump starts automatically after a fault condition which has disappeared, the indicator light will continue
to show the fault condition (alarm memory) and the indication can only be removed by resetting the alarm memory,
see position OFF ( ).

20
7. Systems with 3 electrodes Key to the symbols in fig. E1 on page 43 and fig. E2 on
page 44:
Description (see also page 43 or 44):
The pump is controlled by the liquid level in the borehole. Terminal
Pos. Description
• The electrode, pos. 1, is the reference electrode. number
• The electrode, pos. 3, starts the pump. 1 Reference electrode. 11
• The electrode, pos. 2, stops the pump. It is possible to set a
2 Electrode for stop of pump. 12
"stop delay" which delays the stop of the pump.
• The pressure switch, pos. 4, stops the pump if the discharge 3 Electrode for start of pump. 22
pressure exceeds the stop pressure of the pressure switch. 4 Pressure switch. 41-42
Restarting at the starting pressure of the pressure switch is
only effected if the electrode, pos. 3, registers liquid. 7.2 Setting
3 electrodes, pages 43 and 44.
Before starting any work on pumps used to pump liq-
The module CU 211 has a 10-pole DIP switch in the bottom right
uids which could be constituted as being hazardous
corner, see fig. 15.
to health, thorough cleaning/venting of pumps, pits,
etc. must be carried out according to local regula- Note: During setting, the controller must be off circuit for at least
tions. 1 minute to ensure the correct configuration during start-up after
change of the DIP switch setting.
Before making any connections in the LC 108 or work
on pumps, pits, etc., it must be ensured that the elec- The DIP switch setting offers the following possibilities:
tricity supply has been switched off and that it cannot • selection of starting delay and automatic test run (switch 4),
be accidentally switched on. • setting of stop delay (switches 5, 6 and 7),
• selection of automatic alarm resetting (switch 9),
7.1 Electrical connection
• selection of automatic restarting (switch 10).
3 electrodes, pages 43 and 44.

Before starting work on the system, switch off the


supply voltage and lock the mains switch in
position 0.
Any external voltage connected to the system must
be switched off before work is started.
Fig. E1 on page 43.
The figures show all electrical connections required to connect
the LC 108 for direct-on-line starting, 3 electrodes.
Fig. E2 on page 44.
The figure shows all electrical connections required to connect
the LC 108 for star-delta starting, 3 electrodes.

The LC 108 must be connected in accordance with

TM04 2343 2308


the rules and standards in force for the application in
question.

The operating voltage and frequency are marked on the controller


nameplate. Make sure that the controller is suitable for the elec-
tricity supply on which it will be used.
Fig. 15
All cables/wires must be fitted through the Pg cable entries and
gaskets (IP 65). Set the DIP switch as shown in fig. 15.
Maximum back-up fuse is stated on the controller nameplate. Each individual switch (1 to 10) of the DIP switch can be set to
If required according to local regulations, an external mains position OFF or ON.
switch must be installed. Note: The DIP switch must not be set to other switch combina-
Note: If the PTC resistance/thermal switch of the motor is con- tions than those described in this section.
nected, the factory-fitted short-circuit jumper must be removed Set the switches 1 to 10 as follows:
(terminals T11-T21). • Switches 1, 2 and 3, application type:
Single-phase motors must be connected to an external operating
When the DIP switch setting is changed, the controller must
capacitor and in certain cases also to a starting capacitor. Further
be switched off for at least 1 minute!
details can be found in the installation and operating instructions
for the pump in question.
This setting determines the actual application type
Float switches or electrodes placed in an explosion (3 electrodes, pages 43 and 44).
hazard area must be connected via an EEx barrier,
e.g. Grundfos number 96440300.
The EEx barrier must not be installed in the explosion
hazard area.
Equipment used in explosion hazard areas must in
each individual case have been approved for this
particular application. Furthermore, the cables into
the explosion hazard area must be laid in accordance
with local regulations.
Note: The motor/pump housing must not be used as reference
electrode.
The pressure switch, pos. 4, must be connected as an NC
contact.

21
• Switch 4, starting delay and automatic test run AC/DC selector:
(only in the case of battery back-up): The AC/DC selector switch for electrodes and/or float switches is
When the DIP switch setting is changed, the controller must placed as shown in fig. 16.
be switched off for at least 1 minute!

At this setting, the start-up is delayed within the range


from 0 to 255 sec. (random) after the electricity supply
has been switched on when the liquid level is suffi-
ciently high.
Automatic test run carried out every 24 hours.
After the electricity has been switched on, the pump will
start immediately when the liquid level is sufficiently
high.
No automatic test run.

TM02 5747 3902


• Switches 5, 6 and 7, stop delay:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!

The stop delay is the time from the stop signal is given until the
pump is stopped. Fig. 16
It must be ensured that the pump is not running dry.
Operation with electrodes and
0 sec. 60 sec. float switches:
Selector switch in position AC:
15 sec. 90 sec. 13-18 VAC 0V
It is possible to connect 3 elec-
trodes (1 as reference electrode)
AC 1 2 G 3 4 and 2 float switches.
30 sec. 120 sec. AC DC The controller transmits a
13-18 VAC signal.
Operation with float switches:
45 sec. 180 sec.
Selector switch in position AC:
It is possible to connect 4 float
• Switch 8: 13-18 VAC 0V
switches.
When the DIP switch setting is changed, the controller must The controller transmits a
be switched off for at least 1 minute! AC 1 2 G 3 4
13-18 VAC signal.
AC DC

Switch 8 has no function in connection with the actual


application (3 electrodes, pages 43 and 44), but this Operation with float switches:
setting must be maintained!
Selector switch in position DC:
• Switch 9, automatic alarm resetting: It is possible to connect 4 float
When the DIP switch setting is changed, the controller must 12 VDC 0V
switches.
be switched off for at least 1 minute! Cables of up to 100 metres can be
connected between the controller
This setting ensures automatic resetting of alarm sig- AC 1 2 G 3 4
and the float switches.
nals to external alarm devices and the built-in buzzer. AC DC
The controller transmits a 12 VDC
However, an alarm signal will only be reset if the cause signal.
of the fault no longer exists.
If the distance between the controller and pit exceeds 20 metres,
At this setting, the alarm signal must be reset manually
it is not advisable to use electrodes as problems with the signal
by means of the reset button (the reset button is de-
values sent back to the controller may arise. In such cases, it is
scribed in section 7.5).
recommended to use float switches.
• Switch 10, automatic restarting:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!

This setting enables automatic restarting after the PTC


resistance/thermal switch of the motor has cut out the
pump. Restarting will not be carried out until the motor
has cooled to normal temperature.
When the pump connected is used in an explosion
hazard area, switch 10 must not be in this position!
At this setting, the pump must be restarted manually after
the PTC resistance/thermal switch of the motor has cut
out the pump. To restart the pump, push the ON-OFF-
AUTO selector switch into position OFF for a short period
(the ON-OFF-AUTO selector switch is described in
section 7.5).
When the pump connected is used in an explosion
hazard area, switch 10 must be in this position!

22
7.3 Control panel 7.4 Battery back-up functions
3 electrodes, pages 43 and 44. 3 electrodes, pages 43 and 44.
For these applications, the foil supplied with the LC 108 must be If a back-up battery for CU 211 (accessory for certain variants) is
attached to the CU 211 control panel as shown in fig. 17. The foil installed, the following functions will be carried out if the normal
can be found inside the LC 108 cabinet at the bottom. electricity supply to the LC 108 fails (see also the illustrations
Figure 17 shows how the foil is attached to the CU 211 module. below):
• The common alarm is active, the red indicator light is on – can-
CU 211 1 not be reset!
1

TM01 6413 2299


• If the external alarm device for common alarm is supplied from
an external power source, this device will be active – cannot be
reset by means of the reset button!
• The built-in buzzer (only certain variants) is activated – can be
reset by means of the reset button!
Fig. 17 • If the starting delay function and automatic test run were se-
lected (switch 4 of the DIP switch), the start-up will be delayed
Figure 18 shows the control panel of the CU 211 module.
after the electricity supply has been switched on when the liq-
1 234 5 uid level is sufficiently high, see section 7.2.
The table below shows the situation which may occur if the nor-
mal electricity supply to the LC 108 fails and a back-up battery is
CU 211 1 connected:
1
12 = the indicator light is off.
11 = the indicator light is on.
10 = the indicator light is flashing.
9 TM01 6424 2399

8
CU 211 1
Mains supply failure:
• The common alarm is active.
7 The red indicator light is on.
Fig. 18 • The green indicator light (electricity
supply switched on) is off.
Key to the symbols in fig. 18:

Pos. Description
Green indicator light, indicating starting delay (flashing)
1
and pump operation (permanently on).
Red indicator light, indicating pump fault.
2 Flashing: Fault in PTC resistor/thermal switch
On: Fault in motor-protective circuit breaker.
Red indicator light, indicating wrong phase sequence
3
(only certain variants and three-phase pumps only).
4 Red indicator light, indicating common alarm.
ON-OFF-AUTO selector switch, three positions, see
5
section 7.5.
Reset button, push-button for manual resetting of alarm
7 signals to external alarm devices and the built-in buzzer
(only certain variants), see section 7.5.
Orange indicator light, which is activated by the elec-
8
trode for stop of pump.
Orange indicator light, which is activated by the elec-
9
trode for start of pump.
Has no function in connection with the actual applica-
10
tion!
Orange indicator light, which is activated by the pres-
sure switch in the discharge pipe.
The pump is stopped if the pressure is higher than the
stop pressure of the pressure switch (the indicator light
11 is permanently on).
The pump is started if the pressure is lower than the
starting pressure of the pressure switch and the elec-
trode for start of pump (see pos. 9 above) gives a start-
ing signal at the same time.
Green indicator light, indicating that the electricity
12
supply has been switched on.

23
7.5 Reset button and ON-OFF-AUTO selector switch
3 electrodes, pages 43 and 44.

The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:

ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long pe-
riod, the pump will be damaged!
In explosion hazard areas, switch 10 of the DIP switch must be set as stated in section 7.2. Consequently, the
pump cannot be started when the PTC resistance/thermal switch of the motor registers overtemperature.

OFF ( ), middle position:


1 • The pump cannot start when the selector switch has been set to this position.
• The alarm memory is reset by pushing the selector switch into position OFF ( ). The alarm memory is the light in-
dication of a fault condition which has disappeared. If a fault condition still exists when the selector switch is
pushed into position ON ( ) or AUTO ( ), the alarm indication will be repeated immediately.

AUTO ( ), bottom position:


• The pump is controlled by the input signals from the electrodes and the pump according to the selected DIP switch
setting.
• Alarm signals will automatically be reset. Switch 9 of the DIP switch can, however, be set to manual resetting
which is carried out by means of the reset button, see section 7.2.
• The pump will restart automatically when a given fault condition disappears. However, this is dependent on the
setting of switch 10 of the DIP switch, see section 7.2.
• When the pump starts automatically after a fault condition which has disappeared, the indicator light will continue
to show the fault condition (alarm memory) and the indication can only be removed by resetting the alarm memory,
see position OFF ( ).

24
8. Systems for filling applications Key to the symbols in fig. F1 on page 45 and fig. F2 on
page 46:
Description (see also page 45 or 46):
The pump is controlled by the liquid level in the filling tank. Terminal
Pos. Description
• The electrode, pos. 1, is the reference electrode. number
• The electrode, pos. 2, starts the pump. 1 Reference electrode.* 11
• The electrode, pos. 3, stops the pump. It is possible to set a
2 Electrode for start of pump.* 12
"stop delay", which delays the stop of the pump.
• The float switch, pos. 4, activates the high-level alarm. 3 Electrode for stop of pump.* 22

• The manual on/off switch, pos. 5, will stop the pump when the 4 Float switch for high-level alarm. 31-32
switch is set to position off. Manual on/off switch (or another external
5 41-42
input).
Before starting any work on pumps used to pump liq-
uids which could be constituted as being hazardous * Alternatively, float switches can be connected between termi-
to health, thorough cleaning/venting of pumps, pits, nals: 11-12 and 21-22.
etc. must be carried out according to local regula-
tions. 8.2 Setting
Before making any connections in the LC 108 or work Filling application, pages 45 and 46.
on pumps, pits, etc., it must be ensured that the elec- The module CU 211 has a 10-pole DIP switch in the bottom right
tricity supply has been switched off and that it cannot corner, see fig. 19.
be accidentally switched on. Note: During setting, the controller must be off circuit for at least
1 minute to ensure the correct configuration during start-up after
8.1 Electrical connection change of the DIP switch setting.
Filling application, pages 45 and 46. The DIP switch setting offers the following possibilities:
Before starting work on the system, switch off the • selection of starting delay and automatic test run (switch 4),
supply voltage and lock the mains switch in • setting of stop delay (switches 5, 6 and 7),
position 0. • selection of automatic alarm resetting (switch 9),
Any external voltage connected to the system must • selection of automatic restarting (switch 10).
be switched off before work is started.
Fig. F1 on page 45.
The figures show all electrical connections required to connect
the LC 108 for direct-on-line starting, filling application.
Fig. F2 on page 46.
The figure shows all electrical connections required to connect
the LC 108 for star-delta starting, filling application.

The LC 108 must be connected in accordance with


the rules and standards in force for the application in
question.

The operating voltage and frequency are marked on the controller


nameplate. Make sure that the controller is suitable for the elec-
tricity supply on which it will be used.

TM04 2344 2308


All cables/wires must be fitted through the Pg cable entries and
gaskets (IP 65).
Maximum back-up fuse is stated on the controller nameplate.
If required according to local regulations, an external mains
switch must be installed.
Fig. 19
Note: If the PTC resistance/thermal switch of the motor is con-
nected, the factory-fitted short-circuit jumper must be removed Set the DIP switch as shown in fig. 19.
(terminals T11-T21). Each individual switch (1 to 10) of the DIP switch can be set to
Single-phase motors must be connected to an external operating position OFF or ON.
capacitor and in certain cases also to a starting capacitor. Further
Note: The DIP switch must not be set to other switch combina-
details can be found in the installation and operating instructions
tions than those described in this section.
for the pump in question.
Set the switches 1 to 10 as follows:
Float switches or electrodes placed in an explosion • Switches 1, 2 and 3, application type:
hazard area must be connected via an EEx barrier,
When the DIP switch setting is changed, the controller must
e.g. Grundfos number 96440300.
be switched off for at least 1 minute!
The EEx barrier must not be installed in the explosion
hazard area.
This setting determines the actual application type
Equipment used in explosion hazard areas must in (filling application, pages 45 and 46).
each individual case have been approved for this
particular application. Furthermore, the cables into
the explosion hazard area must be laid in accordance
with local regulations.
Note: The motor/pump housing must not be used as reference
electrode.
The pressure switch, pos. 5, must be connected as an NC
contact.

25
• Switch 4, starting delay and automatic test run AC/DC selector:
(only in the case of battery back-up): The AC/DC selector switch for electrodes and/or float switches is
When the DIP switch setting is changed, the controller must placed as shown in fig. 20.
be switched off for at least 1 minute!

At this setting, the start-up is delayed within the range


from 0 to 255 sec. (random) after the electricity supply
has been switched on when the liquid level is suffi-
ciently high.
Automatic test run carried out every 24 hours.
After the electricity has been switched on, the pump will
start immediately when the liquid level is sufficiently
high.
No automatic test run.

• Switches 5, 6 and 7, stop delay:

TM02 5747 3902


When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!

The stop delay is the time from the stop signal is given until the
pump is stopped.
Fig. 20
It must be ensured that the pump is not running dry.

0 sec. 60 sec. Operation with electrodes and


float switches:
Selector switch in position AC:
15 sec. 90 sec. 13-18 VAC 0V
It is possible to connect 3 elec-
trodes (1 as reference electrode)
AC 1 2 G 3 4 and 2 float switches.
30 sec. 120 sec. AC DC The controller transmits a
13-18 VAC signal.

45 sec. 180 sec. Operation with float switches:


Selector switch in position AC:
• Switch 8: It is possible to connect 4 float
13-18 VAC 0V
switches.
When the DIP switch setting is changed, the controller must
The controller transmits a
be switched off for at least 1 minute! AC 1 2 G 3 4
13-18 VAC signal.
AC DC
Switch 8 has no function in connection with the actual
application (filling application, pages 45 and 46),
Operation with float switches:
but this setting must be maintained!
Selector switch in position DC:
• Switch 9, automatic alarm resetting:
It is possible to connect 4 float
When the DIP switch setting is changed, the controller must switches.
be switched off for at least 1 minute! 12 VDC 0V
Cables of up to 100 metres can be
connected between the controller
This setting ensures automatic resetting of alarm sig- AC 1 2 G 3 4
and the float switches.
nals to external alarm devices and the built-in buzzer. AC DC
The controller transmits a 12 VDC
However, an alarm signal will only be reset if the cause
signal.
of the fault no longer exists.
At this setting, the alarm signal must be reset manually If the distance between the controller and pit exceeds 20 metres,
by means of the reset button (the reset button is it is not advisable to use electrodes as problems with the signal
described in section 8.5). values sent back to the controller may arise. In such cases, it is
recommended to use float switches.
• Switch 10, automatic restarting:
When the DIP switch setting is changed, the controller must
be switched off for at least 1 minute!

This setting enables automatic restarting after the PTC


resistance/thermal switch of the motor has cut out the
pump. Restarting will not be carried out until the motor
has cooled to normal temperature.
When the pump connected is used in an explosion
hazard area, switch 10 must not be in this position!
At this setting, the pump must be restarted manually after
the PTC resistance/thermal switch of the motor has cut
out the pump. To restart the pump, push the ON-OFF-
AUTO selector switch into position OFF for a short period
(the ON-OFF-AUTO selector switch is described in
section 8.5).
When the pump connected is used in an explosion
hazard area, switch 10 must be in this position!

26
8.3 Control panel 8.4 Battery back-up functions
Filling application, pages 45 and 46. Filling application, pages 45 and 46.
For these applications, the foil supplied with the LC 108 must be If a back-up battery for CU 211 (accessory for certain variants) is
attached to the CU 211 control panel as shown in fig. 21. The foil installed, the following functions will be carried out if the normal
can be found inside the LC 108 cabinet at the bottom. electricity supply to the LC 108 fails (see also the illustrations
Figure 21 shows how the foil is attached to the CU 211 module. below):
• The common alarm is active, the red indicator light is on –
CU 211 1 cannot be reset!
1

TM01 6413 2299


• If the external alarm device for common alarm is supplied from
an external power source, this device will be active – cannot
be reset by means of the reset button!
• The built-in buzzer (only certain variants) is activated – can be
reset by means of the reset button!
Fig. 21 • If the liquid level in the pit rises above the level for high-level
alarm, the second orange indicator light from the top will be
Figure 22 shows the control panel of the CU 211 module. flashing.
1 234 5 • If the starting delay function and automatic test run were
selected (switch 4 of the DIP switch), the start-up will be
delayed after the electricity supply has been switched on when
CU 211 1 the liquid level is sufficiently high, see section 8.2.
1
12 The table below shows the situations which may occur if the nor-
11 mal electricity supply to the LC 108 fails and a back-up battery is
10 connected:
9 = the indicator light is off.
TM01 6424 2399

8
= the indicator light is on.
= the indicator light is flashing.

7
CU 211 1
Mains supply failure:
Fig. 22
• The common alarm is active.
Key to the symbols in fig. 22: The red indicator light is on.
• The green indicator light (electricity
Pos. Description supply switched on) is off.
Green indicator light, indicating starting delay (flashing)
1 Mains supply failure and high-level alarm:
and pump operation (permanently on). CU 211 1
• The common alarm is active.
Red indicator light, indicating pump fault. The red indicator light is on.
2 Flashing: Fault in PTC resistor/thermal switch
On: Fault in motor-protective circuit breaker. • The orange indicator light is flashing.
• The green indicator light (electricity
Red indicator light, indicating wrong phase sequence
3 supply switched on) is off.
(only certain variants and three-phase pumps only).
4 Red indicator light, indicating common alarm.
ON-OFF-AUTO selector switch, three positions,
5
see ection 8.5.
Reset button, push-button for manual resetting of alarm
7 signals to external alarm devices and the built-in buzzer
(only certain variants), see section 8.5.
Orange indicator light, which is activated by the elec-
8
trode for start of pump.
Orange indicator light, which is activated by the elec-
9
trode for stop of pump.
Orange indicator light, which is activated by the float
10 switch for high-level alarm. In case of high-level alarm,
the indicator light is flashing.
Orange indicator light, which is activated by the manual
on/off switch.
The pump is stopped when the switch is set to position
11 off (the indicator light is permanently on).
The pump is started when the switch is set to position on
unless the electrode for stop of pump (see pos. 9 above)
gives a stop signal at the same time.
Green indicator light, indicating that the electricity supply
12
has been switched on.

27
8.5 Reset button and ON-OFF-AUTO selector switch
Filling application, pages 45 and 46.

The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:

ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long pe-
riod, the pump will be damaged!
In explosion hazard areas, switch 10 of the DIP switch must be set as stated in section 8.2. Consequently,
the pump cannot be started when the PTC resistance/thermal switch of the motor registers overtemperature.

OFF ( ), middle position:


1 • The pump cannot start when the selector switch has been set to this position.
• The alarm memory is reset by pushing the selector switch into position OFF ( ). The alarm memory is the light in-
dication of a fault condition which has disappeared. If a fault condition still exists when the selector switch is
pushed into position ON ( ) or AUTO ( ), the alarm indication will be repeated immediately.

AUTO ( ), bottom position:


• The pump is controlled by the input signals from the electrodes/float switches and the pump according to the se-
lected DIP switch setting.
• Alarm signals will automatically be reset. Switch 9 of the DIP switch can, however, be set to manual resetting
which is carried out by means of the reset button, see section 8.2.
• The pump will restart automatically when a given fault condition disappears. However, this is dependent on the
setting of switch 10 of the DIP switch, see section 8.2.
• When the pump starts automatically after a fault condition which has disappeared, the indicator light will continue
to show the fault condition (alarm memory) and the indication can only be removed by resetting the alarm memory,
see position OFF ( ).

28
9. Systems for drainage applications Key to the symbols in fig. G1 on page 47 and fig. G2 on
page 48:
Description (see also page 47 or 48):
The pump is controlled by the flow switch, pos. 2, in the discharge Terminal
pipe. Pos. Description
number
• The pump is stopped when the flow switch does not register
1 Switch for manual restarting. 41-42
any liquid flow.
2 Flow switch. 11-12
• After a stop signal, the pump will attempt to restart when the
"restarting time" (can be set) has expired. The restarting
9.2 Setting
attempt will be interrupted if the flow switch does not register
any liquid flow before the expiration of the "dead time" Drainage application, pages 47 and 48.
(can be set). The module CU 211 has a 10-pole DIP switch in the bottom right
• The switch for manual restarting, pos. 1, will initiate a restart- corner, see fig. 23.
ing attempt when the switch is set to position on (restarting). Note: During setting, the controller must be off circuit for at least
1 minute to ensure the correct configuration during start-up after
Before starting any work on pumps used to pump liq- change of the DIP switch setting.
uids which could be constituted as being hazardous
The DIP switch setting offers the following possibilities:
to health, thorough cleaning/venting of pumps, pits,
etc. must be carried out according to local regula- • setting of dead time (switches 4, 5 and 6),
tions. • setting of restarting time (switches 7, 8, 9 and 10).
Before making any connections in the LC 108 or work
on pumps, pits, etc., it must be ensured that the elec-
tricity supply has been switched off and that it cannot
be accidentally switched on.

9.1 Electrical connection


Drainage application, pages 47 and 48.

Before starting work on the system, switch off the


supply voltage and lock the mains switch in
position 0.
Any external voltage connected to the system must
be switched off before work is started.
Fig. G1 on page 47.
The figures show all electrical connections required to connect

TM04 2341 2308


the LC 108 for direct-on-line starting, drainage application, flow
switch.
Fig. G2 on page 48.
The figure shows all electrical connections required to connect
the LC 108 for start-delta starting, drainage application, flow Fig. 23
switch.
Set the DIP switch as shown in fig. 23.
The LC 108 must be connected in accordance with Each individual switch (1 to 10) of the DIP switch can be set to
the rules and standards in force for the application in position OFF or ON.
question.
Note: The DIP switch must not be set to other switch combina-
The operating voltage and frequency are marked on the controller tions than those described in this section.
nameplate. Make sure that the controller is suitable for the elec- Set the switches 1 to 10 as follows:
tricity supply on which it will be used. • Switches 1, 2 and 3, application type:
All cables/wires must be fitted through the Pg cable entries and When the DIP switch setting is changed, the controller must
gaskets (IP 65). be switched off for at least 1 minute!
Maximum back-up fuse is stated on the controller nameplate.
If required according to local regulations, an external mains This setting determines the actual application type
switch must be installed. (drainage application, pages 47 and 48).
Note: If the PTC resistance/thermal switch of the motor is con-
nected, the factory-fitted short-circuit jumper must be removed • Switches 4, 5 and 6, dead time:
(terminals T11-T21). When the DIP switch setting is changed, the controller must
Single-phase motors must be connected to an external operating be switched off for at least 1 minute!
capacitor and in certain cases also to a starting capacitor. Further
details can be found in the installation and operating instructions The dead time is the time the pump is allowed to run after start-
for the pump in question. ing without a liquid flow being registered by the flow switch. The
pump will be stopped again if the flow switch does not registers
LC 108 must not be used for drainage applications any liquid flow.
(pages 47 and 48) in explosion hazard areas as the
motor will restart automatically after the PTC resist- 10 sec. 2 min.
ance/thermal switch in the motor has caused a cut-
out. However, the motor will not restart until it has
cooled to normal temperature. 20 sec. 3 min.
The switch for manual restarting, pos. 1, must be connected as
an NC contact.
The flow switch, pos. 2, must be connected as an NO contact. 40 sec. 4 min.

1 min. 5 min.

29
• Switches 7, 8, 9 and 10, restarting time: AC/DC selector:
When the DIP switch setting is changed, the controller must The AC/DC selector switch for electrodes and/or float switches is
be switched off for at least 1 minute! placed as shown in fig. 24.

The restarting time is the time from the last stop signal until the
pump attempts to restart.

No restarting* 15 min.

1 min. 17 min.

2 min. 20 min.

TM02 5747 3902


3 min. 25 min.

5 min. 30 min. Fig. 24

Operation with electrodes and


7 min. 50 min. float switches:
Selector switch in position AC:
10 min. 70 min.
13-18 VAC 0V
It is possible to connect 3 elec-
trodes (1 as reference electrode)
AC 1 2 G 3 4 and 2 float switches.
12 min. 90 min.
AC DC The controller transmits a
13-18 VAC signal.
Operation with float switches:
* At the setting "no restarting", the pump can only be restarted by
means of the switch for manual restarting. Selector switch in position AC:
It is possible to connect 4 float
13-18 VAC 0V
switches.
The controller transmits a
AC 1 2 G 3 4
13-18 VAC signal.
AC DC

Operation with float switches:


Selector switch in position DC:
It is possible to connect 4 float
12 VDC 0V
switches.
Cables of up to 100 metres can be
connected between the controller
AC 1 2 G 3 4
and the float switches.
AC DC
The controller transmits a 12 VDC
signal.

If the distance between the controller and pit exceeds 20 metres,


it is not advisable to use electrodes as problems with the signal
values sent back to the controller may arise. In such cases, it is
recommended to use float switches.

30
9.3 Control panel 9.4 Battery back-up functions
Drainage application, pages 47 and 48. Drainage application, pages 47 and 48.
For these applications, the foil supplied with the LC 108 must be If a back-up battery for CU 211 (accessory for certain variants) is
attached to the CU 211 control panel as shown in fig. 25. The foil installed, the following functions will be carried out if the normal
can be found inside the LC 108 cabinet at the bottom. electricity supply to the LC 108 fails (see also the illustrations
Figure 25 shows how the foil is attached to the CU 211 module. below):
• The common alarm is active, the red indicator light is on –
CU 211 1 cannot be reset!
1

TM01 6413 2299


• If the external alarm device for common alarm is supplied from
an external power source, this device will be active – cannot
be reset by means of the reset button!
• The built-in buzzer (only certain variants) is activated – can be
reset by means of the reset button!
Fig. 25 The table below shows the situation which may occur if the nor-
mal electricity supply to the LC 108 fails and a back-up battery is
Figure 26 shows the control panel of the CU 211 module.
connected:
1 2 3 4 5 = the indicator light is off.
= the indicator light is on.
CU 211 1 = the indicator light is flashing.
1
12
11 CU 211 1
Mains supply failure:
10 • The common alarm is active.
9 TM01 6424 2399 The red indicator light is on.
8
• The green indicator light (electricity
supply switched on) is off.
7

Fig. 26

Key to the symbols in fig. 26:

Pos. Description
Green indicator light, indicating starting delay (flashing)
1
and pump operation (permanently on).
Red indicator light, indicating pump fault.
2 Flashing: Fault in PTC resistor/thermal switch
On: Fault in motor-protective circuit breaker.
Red indicator light, indicating wrong phase sequence
3
(only certain variants and three-phase pumps only).
4 Red indicator light, indicating common alarm.
ON-OFF-AUTO selector switch, three positions, see
5
section 9.5.
Reset button, push-button for manual resetting of alarm
7 signals to external alarm devices and the built-in buzzer
(only certain variants), see section 9.5.
Orange indicator light, which is activated by the flow
switch.
When the flow switch registers a liquid flow, the indica-
8 tor light is permanently on.
The pump is stopped if the flow switch does not register
any liquid flow and the dead time has expired, see sec-
tion 9.2.
9
Have no function in connection with the actual
and
application!
10
Orange indicator light, which is activated by the switch
for manual restarting.
The pump is started when the switch is set to position
11 on (restarting) (the indicator light is permanently on).
The pump is stopped if the flow switch does not register
any liquid flow and the dead time has expired, see sec-
tion 9.2.
Green indicator light, indicating that the electricity
12
supply has been switched on.

31
9.5 Reset button and ON-OFF-AUTO selector switch
Drainage application, pages 47 and 48.

The reset button is a push-button for manual resetting of alarm signals to external alarm devices and the built-in
buzzer (i.e. not for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch,
see position OFF ( )).
Even if the fault condition still exists, the external alarm devices and the built-in buzzer will be reset when the reset
button is pressed.
The ON-OFF-AUTO selector switch has three different positions:

ON ( ), top position:
• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut
out the pump).
• If the PTC resistance/thermal switch of the motor registers overtemperature, the pump will not be switched off.
Note: It is the user’s responsibility to decide how long the pump is to run with this fault indication. Over a long pe-
riod, the pump will be damaged!

OFF ( ), middle position:


1 • The pump cannot start when the selector switch has been set to this position.
• The alarm memory is reset by pushing the selector switch into position OFF ( ). The alarm memory is the light in-
dication of a fault condition which has disappeared. If a fault condition still exists when the selector switch is
pushed into position ON ( ) or AUTO ( ), the alarm indication will be repeated immediately.

AUTO ( ), bottom position:


• The pump is controlled by the input signals from the flow switch and the pump according to the selected DIP
switch setting.
• Alarm signals will automatically be reset.
• The pump will restart automatically when a given fault condition disappears.
• When the pump starts automatically after a fault condition which has disappeared, the indicator light will continue
to show the fault condition (alarm memory) and the indication can only be removed by resetting the alarm memory,
see position OFF ( ).

10. Start-up
5. Switch on the electricity supply.
Before starting any work on pumps used to pump liq-
Three-phase pumps only: Check for wrong phase sequence,
uids which could be constituted as being hazardous
(the pump cannot be started if the phase sequence is wrong!).
to health, thorough cleaning/venting of pumps, pits,
etc. must be carried out according to local regula- 6. Start the pump, see section 3.5, 4.5, 5.5, 6.5, 7.5, 8.5 or 9.5.
tions. 7. Check that the pump is not running dry. The risk of dry running
Before making any connections in the LC 108 or work can be eliminated by a renewed time setting by means of the
on pumps, pits, etc., it must be ensured that the elec- DIP switch according to section 3.2, 4.2, 5.2, 6.2, 7.2 or 8.2
tricity supply has been switched off and that it cannot and/or by moving the float switches or the electrodes.
be accidentally switched on. 8. Three-phase pumps only: Check whether the direction of
Prior to start-up, the connection and DIP switch setting must have rotation of the pump is correct according to the installation and
operating instructions for the pump in question.
been carried out according to sections 3. to 9.
9. Select the required operating mode by means of the ON-OFF-
Start-up must be carried out by authorized personnel.
AUTO selector switch, see section 3.5, 4.5, 5.5, 6.5, 7.5, 8.5
Proceed as follows:
or 9.5.
1. Check whether the float switches, electrodes or the flow
switch have been connected according to the wiring diagram
for the actual application.
2. Check that the pump inlet is submerged in the liquid to be
pumped.
3. Set the motor protection relay to the rated current stated on
the nameplate.
4. Warning:

Ensure that the short-circuit protection is suitable for


the installation.

32
11. Maintenance 12. Technical data
Voltage variants, nominal voltages
Before starting any work on pumps used to pump liq-
uids which could be constituted as being hazardous • 1 x 230 V.
to health, thorough cleaning/venting of pumps, pits, • 3 x 415 V.
etc. must be carried out according to local regula- Voltage tolerances for LC 108
tions. –15 %/+10 % of nominal voltage.
Before making any connections in the LC 108 or work See also installation and operating instructions for the pump in
on pumps, pits, etc., it must be ensured that the elec- question.
tricity supply has been switched off and that it cannot
Mains frequency for LC 108
be accidentally switched on.
50/60 Hz.
During normal application and operation, the controller LC 108 is
See also installation and operating instructions for the pump in
maintenance-free.
question.
However, it is advisable to carry out minor checks of the LC 108
controller, pump pits, tanks, pumps, etc. at suitable intervals. Supply system earthing
These checks should be carried out by authorized personnel. For TN systems and TT systems.
• Check the gaskets of the LC 108 cabinet front and those of the Rated insulation voltage, Ui
Pg cable entries. 4 kV.
• Check for possible deposits/sludge build-up in the pump pit/
Rated impulse withstand voltage, Uimp
tank. Sludge may settle in areas with almost stagnant liquid.
4 kV.
• Check for beginning sludge build-up around the float switches,
electrodes or the flow switch. Short-circuit protection of supply
• Check for possible blockage on the suction side of the pump. Depending on variant, see nameplate.
A blockage will typically be a large solid object. Control circuit fuse
• If the LC 108 has been installed in a particularly aggressive Fine-wire fuse: 250 mA / F / 32 mm x ∅6 mm.
environment, it is advisable to check the motor protection con-
tacts in order to identify possible chemical attack resulting in Ambient temperature
corrosion. In typical installations, the motor protection contacts • During operation: –30 to +50 °C
will work for several years and do not require any inspection. (must not be exposed to direct sunlight).
Note: The above list is not complete. The LC 108 may be • In stock: –30 to +60 °C.
installed in systems, installations and/or environments which Enclosure class
require thorough and regular maintenance.
IP 65.
EMC (electromagnetic compatibility)
According to EN 61 000-6-2 and EN 61 000-6-3.
Cabinet LC 108 for direct-on-line starting
• External dimensions (including glands):
Height = 590 mm, width = 380 mm, depth = 220 mm.
• Material: ABS (Acrylonitrile butadiene styrene).
• Weight: Depending on variant, see nameplate.
Outputs for alarm devices
Max. 230 VAC / max. 2 A / min. 10 mA / AC1.

33
13. Fault finding chart
Before starting any work on pumps used to pump liquids which could be constituted as being hazardous to health, thorough
cleaning/venting of pumps, pits, etc. must be carried out according to local regulations.
Before making any connections in the LC 108 or work on pumps, pits, etc., it must be ensured that the electricity supply has
been switched off and that it cannot be accidentally switched on.

Fault Cause Remedy


1. The pump does not a) No electricity supply. Switch on the electricity supply.
run. Without battery back-up:
None of the indicator lights are on.
With battery back-up
(accessory for certain variants):
See section 3.4, 4.4, 5.4, 6.4, 7.4, 8.4 or 9.4.
b) The ON-OFF-AUTO selector switch is in posi- Push the ON-OFF-AUTO selector switch into position
tion OFF ( ), see section 3.5, 4.5, 5.5, 6.5, ON ( ) or AUTO ( ).
7.5, 8.5 or 9.5.
c) Control circuit fuses are blown. Check and eliminate the cause. Replace the control cir-
cuit fuses (see pos. 6 in fig. 1 or fig. 3).
d) The motor protection relay has cut out the Check the pump/pit.
pump
(the red indicator light for pump fault is
permanently on).
e) The PTC resistance/thermal switch has cut out Allow the pump to cool. After cooling, the pump will
the pump restart automatically unless the LC 108 has been set to
(the red indicator light for pump fault is flash- manual restarting, see section 3.2, 4.2, 5.2, 6.2, 7.2 or
ing, see section). 8.2. If so, the ON-OFF-AUTO selector switch must be
pushed into position OFF ( ) for a short period.
If the pump cutout was caused by choked-up float
switches, electrodes or flow switch, these must be
cleaned or replaced.
f) The control circuit for the motor protection relay Check the control circuit.
has been broken or fails
(the green indicator light indicating pump oper-
ation is permanently on, see section 3.3, 4.3,
5.3, 6.3, 7.3, 8.3 or 9.3).
g) Motor/supply cable is defective. Check motor and cable.
h) The float switches, electrodes or the flow Check cables, float switches, electrodes or the flow
switch are/is defective. switch.
i) The CU 211 module is defective. Replace the CU 211 module.
j) The new DIP switch setting does not work Switch off the electricity supply to the controller for
correctly. 1 minute and switch it on again (normal procedure).
See section 3.2, 4.2, 5.2, 6.2, 7.2, 8.2 or 9.2.
2. The pump is a) The float switches, electrodes or the flow Check cables, float switches, electrodes or the flow
starting/stopping too switch are/is defective. switch.
frequently.

See also installation and operating instructions for the pump in


question.

14. Disposal
Disposal of this product or parts of it must be carried out
according to the following guidelines:
1. Use the local public or private waste collection service.
2. In case such waste collection service does not exist or cannot
handle the materials used in the product, please deliver the
product or any hazardous materials from it to your nearest
Grundfos company or service workshop.

Subject to alterations.

34
Fig. A1

M
T11

Ext.
T21
U1
N1 H-NO
H-COM
max. 2A

1~
max. 230V

H-NC

1U2 1N2
G-NO
G-COM
G-NC
11
12
21
22
TM01 4864 1808
31
32
41
42

1
2
LC 108

U1
V1
W1
N1
ON

1U2 1V2
3~

1W2
DIP

1 2 3 4 5 6 7 8 9 10

TM01 4862 1808 TM01 6882 1808

35
36
Fig. A2

U1
V1
W1
N1

L1 L2 L3 N PE
1U2
1V2
1W2
2W2
2U2
2V2
T11
T12

Ext.
H-NO

1
2
H-COM
H-NC
max. 2A

G-NO
max. 230V

G-COM
G-NC
11
ON

12
21
22
31
32
41
42
1 2 3 4 5 6 7 8 9 10
DIP

LC 108

TM01 7871 1808


M
Fig. B1

T11

Ext.
T21
U1 H-NO
N1
H-COM
H-NC
max. 2A

1~
G-NO

1U2 1N2
max. 230V

G-COM
G-NC
11
12
21
22
31
TM01 4864 1808
32
41
42

1
2
3
LC 108

U1
V1
W1
N1

1U2 1V2
3~

TM01 4862 1808 1W2 TM01 6619 1808

37
38
Fig. B2

U1
V1
W1
N1
1U2

L1 L2 L3 N PE
1V2
1W2
2W2
2U2
2V2
T11
T12

Ext.
H-NO

2
3

1
H-COM
H-NC
G-NO
max. 2A
max. 230V

G-COM
G-NC
11
ON

12
21
22
31
32
41
42
LC 108
1 2 3 4 5 6 7 8 9 10
DIP

TM01 8128 1808


Fig. C1

T11
T21
U1
N1 H-NO
H-COM
max. 2A

H-NC

1~
max. 230V

1U2 1N2
G-NO
G-COM
G-NC
11
12
21
22
TM01 4864 1808
31
32
41
42

U1
V1
W1
N1

1U2 1V2
3~

1W2
TM01 4862 1808 TM01 6620 1808

39
40
Fig. C2

U1
V1
W1
N1
1U2

L1 L2 L3 N PE
1V2
1W2
2W2
2U2
2V2
T11
T12

Ext.
H-NO

1
2
3
4
H-COM
H-NC
max. 2A

G-NO
max. 230V

G-COM
G-NC
11
ON

12
21
22
31
32
41
42
LC 108
DIP

1 2 3 4 5 6 7 8 9 10

TM01 8126 1808


Fig. D1

T11
T21
U1
N1
H-NO
H-COM
max. 2A

H-NC
max. 230V

1~

1U2 1N2
G-NO
G-COM
G-NC
11
12
21
22
TM01 4864 1808
31
32
41
42

U1
V1
W1
N1

1U2 1V2
3~

TM01 4862 1808 1W2 TM01 6621 1808

41
42
Fig. D2

U1
V1
W1

PE
N1
1U2

L1 L2 L3 N PE
1V2
1W2
2W2
2U2
2V2
T11
T12

Ext.
H-NO

1
H-COM
H-NC
G-NO
max. 2A
max. 230V

G-COM
G-NC
11
ON

12
21
22
31
32
41
42
NC
1 2 3 4 5 6 7 8 9 10
DIP

LC 108

TM01 8127 1808


M
Fig. E1

T11

Ext.
T21
H-NO
U1
N1
H-COM
max. 2A
max. 230V

H-NC

1~
G-NO

1U2 1N2
G-COM
G-NC
11
12
21
22
31
TM01 4864 1808
32
41

1
2
3
42
LC 108

U1
V1
W1
N1

1U2 1V2
3~
3~

1W2
4

TM01 4862 1808 TM01 6622 1808

43
44
Fig. E2

U1
V1
W1

PE
N1

L1 L2 L3 N PE
1U2
1V2
1W2
2W2
2U2
2V2
T11
T12

Ext.

2
3

1
H-NO
H-COM
H-NC
G-NO
max. 2A
max. 230V

G-COM
G-NC
11
ON

12
21
22
31
32
41
42
NC
1 2 3 4 5 6 7 8 9 10
DIP

LC 108

TM01 8129 1808


Fig. F1

T11
T21
U1 H-NO
N1
H-COM
H-NC

1~
G-NO
max. 2A

1U2 1N2
max. 230V

G-COM
G-NC
11
12

1
2
3
21
22
TM01 4864 1808 31
32
41
42

U1
V1
W1
N1

1U2 1V2
3~

1W2
TM01 4862 1808 TM01 6623 1808

45
46
Fig. F2

U1
V1
W1

PE
N1

L1 L2 L3 N PE
1U2
1V2
1W2
2W2
2U2
2V2
T11
T12

Ext.
H-NO

1
2
3
H-COM
H-NC
G-NO
max. 2A
max. 230V

G-COM
G-NC
ON

11
12
21
22
31
32
41
1 2 3 4 5 6 7 8 9 10
DIP

42
LC 108

NC
5

TM01 8130 1808


Fig. G1

T11
U1
N1 T21
H-NO
H-COM

1~

1U2 1N2
H-NC
max. 2A

G-NO
max. 230V

G-COM
G-NC
11
12
21

TM01 4864 1808


22
31
32
41
42

U1
V1
W1
N1

1U2 1V2
3~

1W2
TM01 4862 1808 TM01 6624 1808

47
48
Fig. G2

U1
V1
W1

PE
N1
1U2

L1 L2 L3 N PE
1V2
1W2
2W2
2U2
2V2
T11
T12

Ext.
H-NO
H-COM
H-NC
G-NO
max. 2A
max. 230V

G-COM
G-NC
11
ON

12
21
22
31
32
41
42
1 2 3 4 5 6 7 8 9 10
DIP

LC 108

2
1

TM01 8131 1808


49
50
Argentina Finland Malaysia Switzerland
Bombas GRUNDFOS de Argentina S.A. OY GRUNDFOS Pumput AB GRUNDFOS Pumps Sdn. Bhd. GRUNDFOS Pumpen AG
Ruta Panamericana km. 37.500 Lote 34A Mestarintie 11 7 Jalan Peguam U1/25 Bruggacherstrasse 10
1619 - Garin FIN-01730 Vantaa Glenmarie Industrial Park CH-8117 Fällanden/ZH
Pcia. de Buenos Aires Phone: +358-3066 5650 40150 Shah Alam Tel.: +41-1-806 8111
Phone: +54-3327 414 444 Telefax: +358-3066 56550 Selangor Telefax: +41-1-806 8115
Telefax: +54-3327 411 111 Phone: +60-3-5569 2922
France Telefax: +60-3-5569 2866 Taiwan
Australia Pompes GRUNDFOS Distribution S.A. GRUNDFOS Pumps (Taiwan) Ltd.
GRUNDFOS Pumps Pty. Ltd. Parc d’Activités de Chesnes México 7 Floor, 219 Min-Chuan Road
P.O. Box 2040 57, rue de Malacombe Bombas GRUNDFOS de México S.A. de Taichung, Taiwan, R.O.C.
Regency Park F-38290 St. Quentin Fallavier (Lyon) C.V. Phone: +886-4-2305 0868
South Australia 5942 Tél.: +33-4 74 82 15 15 Boulevard TLC No. 15 Telefax: +886-4-2305 0878
Phone: +61-8-8461-4611 Télécopie: +33-4 74 94 10 51 Parque Industrial Stiva Aeropuerto
Telefax: +61-8-8340 0155 Apodaca, N.L. 66600 Thailand
Germany Phone: +52-81-8144 4000 GRUNDFOS (Thailand) Ltd.
Austria GRUNDFOS GMBH Telefax: +52-81-8144 4010 92 Chaloem Phrakiat Rama 9 Road,
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. Schlüterstr. 33 Dokmai, Pravej, Bangkok 10250
Grundfosstraße 2 40699 Erkrath Netherlands Phone: +66-2-725 8999
A-5082 Grödig/Salzburg Tel.: +49-(0) 211 929 69-0 GRUNDFOS Netherlands Telefax: +66-2-725 8998
Tel.: +43-6246-883-0 Telefax: +49-(0) 211 929 69-3799 Veluwezoom 35
Telefax: +43-6246-883-30 e-mail: infoservice@grundfos.de 1326 AE Almere Turkey
Service in Deutschland: Postbus 22015 GRUNDFOS POMPA San. ve Tic. Ltd. Sti.
Belgium e-mail: kundendienst@grundfos.de 1302 CA ALMERE Gebze Organize Sanayi Bölgesi
N.V. GRUNDFOS Bellux S.A. Tel.: +31-88-478 6336 Ihsan dede Caddesi,
Boomsesteenweg 81-83 Greece Telefax: +31-88-478 6332 2. yol 200. Sokak No. 204
B-2630 Aartselaar GRUNDFOS Hellas A.E.B.E. e-mail: info_gnl@grundfos.com 41490 Gebze/ Kocaeli
Tél.: +32-3-870 7300 20th km. Athinon-Markopoulou Av. Phone: +90 - 262-679 7979
Télécopie: +32-3-870 7301 P.O. Box 71 New Zealand Telefax: +90 - 262-679 7905
GR-19002 Peania GRUNDFOS Pumps NZ Ltd. E-mail: satis@grundfos.com
Belorussia Phone: +0030-210-66 83 400 17 Beatrice Tinsley Crescent
Представительство ГРУНДФОС в Telefax: +0030-210-66 46 273 North Harbour Industrial Estate Ukraine
Минске Albany, Auckland ТОВ ГРУНДФОС УКРАЇНА
220123, Минск, Hong Kong Phone: +64-9-415 3240 01010 Київ, Вул. Московська 8б,
ул. В. Хоружей, 22, оф. 1105 GRUNDFOS Pumps (Hong Kong) Ltd. Telefax: +64-9-415 3250 Тел.:(+38 044) 390 40 50
Тел.: +(37517) 233 97 65, Unit 1, Ground floor Фах.: (+38 044) 390 40 59
Факс: +(37517) 233 97 69 Siu Wai Industrial Centre Norway E-mail: ukraine@grundfos.com
E-mail: grundfos_minsk@mail.ru 29-33 Wing Hong Street & GRUNDFOS Pumper A/S
68 King Lam Street, Cheung Sha Wan Strømsveien 344 United Arab Emirates
Bosnia/Herzegovina Kowloon Postboks 235, Leirdal GRUNDFOS Gulf Distribution
GRUNDFOS Sarajevo Phone: +852-27861706 / 27861741 N-1011 Oslo P.O. Box 16768
Trg Heroja 16, Telefax: +852-27858664 Tlf.: +47-22 90 47 00 Jebel Ali Free Zone
BiH-71000 Sarajevo Telefax: +47-22 32 21 50 Dubai
Phone: +387 33 713 290 Hungary Phone: +971-4- 8815 166
Telefax: +387 33 659 079 GRUNDFOS Hungária Kft. Poland Telefax: +971-4-8815 136
e-mail: grundfos@bih.net.ba Park u. 8 GRUNDFOS Pompy Sp. z o.o.
H-2045 Törökbálint, ul. Klonowa 23 United Kingdom
Brazil Phone: +36-23 511 110 Baranowo k. Poznania GRUNDFOS Pumps Ltd.
Mark GRUNDFOS Ltda. Telefax: +36-23 511 111 PL-62-081 Przeźmierowo Grovebury Road
Av. Humberto de Alencar Castelo Branco, Tel: (+48-61) 650 13 00 Leighton Buzzard/Beds. LU7 8TL
630 India Fax: (+48-61) 650 13 50 Phone: +44-1525-850000
CEP 09850 - 300 GRUNDFOS Pumps India Private Limited Telefax: +44-1525-850011
São Bernardo do Campo - SP 118 Old Mahabalipuram Road Portugal
Phone: +55-11 4393 5533 Thoraipakkam Bombas GRUNDFOS Portugal, S.A. U.S.A.
Telefax: +55-11 4343 5015 Chennai 600 096 Rua Calvet de Magalhães, 241 GRUNDFOS Pumps Corporation
Phone: +91-44 2496 6800 Apartado 1079 17100 West 118th Terrace
Bulgaria P-2770-153 Paço de Arcos Olathe, Kansas 66061
GRUNDFOS Pumpen Vertrieb Indonesia Tel.: +351-21-440 76 00 Phone: +1-913-227-3400
Representative Office - Bulgaria PT GRUNDFOS Pompa Telefax: +351-21-440 76 90 Telefax: +1-913-227-3500
Bulgaria, 1421 Sofia Jl. Rawa Sumur III, Blok III / CC-1
Lozenetz District Kawasan Industri, Pulogadung România Usbekistan
105-107 Arsenalski blvd. Jakarta 13930 GRUNDFOS Pompe România SRL Представительство ГРУНДФОС в
Phone: +359 2963 3820, 2963 5653 Phone: +62-21-460 6909 Bd. Biruintei, nr 103 Ташкенте
Telefax: +359 2963 1305 Telefax: +62-21-460 6910 / 460 6901 Pantelimon county Ilfov 700000 Ташкент ул.Усмана Носира 1-й
Phone: +40 21 200 4100 тупик 5
Canada Ireland Telefax: +40 21 200 4101 Телефон: (3712) 55-68-15
GRUNDFOS Canada Inc. GRUNDFOS (Ireland) Ltd. E-mail: romania@grundfos.ro Факс: (3712) 53-36-35
2941 Brighton Road Unit A, Merrywell Business Park
Oakville, Ontario Ballymount Road Lower Russia
L6H 6C9 Dublin 12 ООО Грундфос
Phone: +1-905 829 9533 Phone: +353-1-4089 800 Россия, 109544 Москва, ул. Школьная
Telefax: +1-905 829 9512 Telefax: +353-1-4089 830 39
Тел. (+7) 495 737 30 00, 564 88 00
China Italy Факс (+7) 495 737 75 36, 564 88 11
GRUNDFOS Pumps (Shanghai) Co. Ltd. GRUNDFOS Pompe Italia S.r.l. E-mail grundfos.moscow@grundfos.com
51 Floor, Raffles City Via Gran Sasso 4
No. 268 Xi Zang Road. (M) I-20060 Truccazzano (Milano) Serbia
Shanghai 200001 Tel.: +39-02-95838112 GRUNDFOS Predstavništvo Beograd
PRC Telefax: +39-02-95309290 / 95838461 Dr. Milutina Ivkovića 2a/29
Phone: +86-021-612 252 22 YU-11000 Beograd
Telefax: +86-021-612 253 33 Japan Phone: +381 11 26 47 877 / 11 26 47 496
GRUNDFOS Pumps K.K. Telefax: +381 11 26 48 340
Croatia Gotanda Metalion Bldg., 5F,
GRUNDFOS CROATIA d.o.o. 5-21-15, Higashi-gotanda Singapore
Cebini 37, Buzin Shiagawa-ku, Tokyo GRUNDFOS (Singapore) Pte. Ltd.
HR-10010 Zagreb 141-0022 Japan 24 Tuas West Road
Phone: +385 1 6595 400 Phone: +81 35 448 1391 Jurong Town
Telefax: +385 1 6595 499 Telefax: +81 35 448 9619 Singapore 638381
www.grundfos.hr Phone: +65-6865 1222
Korea Telefax: +65-6861 8402
Czech Republic GRUNDFOS Pumps Korea Ltd.
GRUNDFOS s.r.o. 6th Floor, Aju Building 679-5 Slovenia
Čajkovského 21 Yeoksam-dong, Kangnam-ku, 135-916 GRUNDFOS PUMPEN VERTRIEB
779 00 Olomouc Seoul, Korea Ges.m.b.H.,
Phone: +420-585-716 111 Phone: +82-2-5317 600 Podružnica Ljubljana
Telefax: +420-585-716 299 Telefax: +82-2-5633 725 Šlandrova 8b, SI-1231 Ljubljana-Črnuče
Phone: +386 1 568 0610
Denmark Latvia Telefax: +386 1 568 0619
GRUNDFOS DK A/S SIA GRUNDFOS Pumps Latvia E-mail: slovenia@grundfos.si
Martin Bachs Vej 3 Deglava biznesa centrs
DK-8850 Bjerringbro Augusta Deglava ielā 60, LV-1035, Rīga, Spain
Tlf.: +45-87 50 50 50 Tālr.: + 371 714 9640, 7 149 641 Bombas GRUNDFOS España S.A.
Telefax: +45-87 50 51 51 Fakss: + 371 914 9646 Camino de la Fuentecilla, s/n
E-mail: info_GDK@grundfos.com E-28110 Algete (Madrid)
www.grundfos.com/DK Lithuania Tel.: +34-91-848 8800
GRUNDFOS Pumps UAB Telefax: +34-91-628 0465
Estonia Smolensko g. 6
GRUNDFOS Pumps Eesti OÜ LT-03201 Vilnius Sweden
Peterburi tee 92G Tel: + 370 52 395 430 GRUNDFOS AB
11415 Tallinn Fax: + 370 52 395 431 Box 333 (Lunnagårdsgatan 6)
Tel: + 372 606 1690 431 24 Mölndal
Fax: + 372 606 1691 Tel.: +46(0)771-32 23 00
Telefax: +46(0)31-331 94 60

Addresses revised 15.06.2009


Being responsible is our foundation
Thinking ahead makes it possible
Innovation is the essence

97502176 0609
GB

www.grundfos.com

You might also like