Contents 

1. Product Specifications…………………………………………..2 

2. Operation…………………………………………………………..5 

3. Parameter Setting Method………………………………………6 

4. Wiring Diagram Of Inverter………………………………………7 

om
5. Door Width Self‐learning…………………………………………9 

6. Parameter Setting………………………………………………...10 

.c
7. Parameter Table………………………………………………….11 

or
 

 
t
va
 
le

 
ae

 
 
ov

 
 
 
.n

 
 
w

 
 
w

 
 
w

 
 
 
 
 
 
 
 
 

‐ 1 ‐ 
1. Product Specifications 
1.1   Model Description 
EV3200 - 2 S 0004 A

Code Load type


Drive series
Asynchronous motor for
A
elevator door control
Synchronous motor for
S elevator door control
Voltage level Code

om
220V 2
Code Motor power (kW)
0004 0.4
Input Volt Code
0002 0.2

.c
Single-phase S
 
 

or
1.2   Nameplate 
The nameplate is on the bottom of the inverter enclosure, as shown in Figure 
 
t
va
le

MODEL: EV3200 -2
-2S0002A Drive model
ae

POWER: 0.2kW Motor capacity


INPUT: 1PH AC 200~240V Rated input voltage,
00
2.65A 50/60Hz current and frequency
ov

OUTPUT: 3PH AC 0~240V Rated output capacity, current,


0~128 Hz 0.5kVA 1.3A frequency range and voltage

S/N:
.n

Bar code
w

Emerson Network Power Co., Ltd.


w

 
 
w

1.3   Models 
Rated input current Rated capacity Rated output Motor power
Inverter model
(A) (kVA) current (A) (kW)
EV3200-2S0002A
2.65 0.5 1.3 0.2
EV3200-2S0002S
EV3200-2S0004A
5.3 1.0 2.5 0.4
EV3200-2S0004S
 
1.4   Installation Size 

‐ 2 ‐ 
om
Installation size External size
Installation
hole Weight
Inverter model
A (mm) B (mm) L (mm) W (mm) H (mm) diameter (kg)

.c
(mm)
EV3200-2S0002A

or
EV3200-2S0002S
289 172.5 298 190 60 Φ4 0.9
EV3200-2S0004A
EV3200-2S0004S
t
va
 
1.5   Specifications 
Items Subitems Specifications
le

Voltage range Single-phase AC power, 180V ~ 264V


Input
Frequency range 50Hz ± 5%, 60Hz ± 5%
ae

Voltage range Three-phase: 0V ~ input voltage


Frequency range 0Hz ~ 128Hz
Output
ov

150% rated current for 1 minute, 180% rated current for 10


Overload ability
seconds
Main control Three-phase AC asynchronous motor, three-phase AC
Load motor type
.n

functions synchronous motor


Modulation
Optimized space voltage vector PWM modulation
mode
w

Control
Sensorless vector control, vector control with speed sensor
w

algorithm
Two modes: 1. The inverter operates as an inverter specially
w

Operation mode used for controlling the elevator door (elevator door control
mode), 2. The inverter operates as a general purpose inverter
Frequency
Digital setting: 0.01Hz
resolution
The inverter operates at the auto-learnt speed, and operates in
Door width auto the logic procedure of close door (CD)→open door (OD)→CD
learning →stop. After the auto-learning operation, the door width
information is saved and the auto learning process is over

‐ 3 ‐ 
Items Subitems Specifications
Auto tuning of Purpose of auto tuning function of inverter is to obtain the
motor's motor's parameters automatically, and these parameters will be
parameters saved automatically after the tuning process is over
Speed-adjusting Under rated load condition, 1:100 for vector control with speed
range sensor; 1:50 for sensorless vector control
OD,
CDcontrol Terminal control mode; keypad control mode;
command communication control mode (reserved)
input

om
Frequency Set the frequency via keypad; communication control
setting mode (reserved)
External reset signal, light curtain signal, safety edge

.c
Operation signal, OD position limiting signal, CD position
functions limiting signal, OD speed decrease signal, CD speed

or
Multi-function
decrease signal, OD prohibition signal, torque
terminal input
maintaining signal, slow OD and CD signals, lock
signal

t
signal, emergency firemen service (EFS) signal, rush
va
hour operation enable operation, operation enable
signal, auto-learning command signal
le

3 relay-output: 250Vac/2A (cosΦ=1), 250Vac/1A


Output signal
(cosΦ=0.4), 30Vdc/1A
ae

Running frequency, reference frequency, output


4-digit LED voltage, output current, output torque, DC bus voltage,
Display
display status of input terminals, status of output terminals,
ov

door-operating position (pulse number)


Over current protection, over voltage protection, low
.n

voltage protection, over heat protection, overload


protection, output phase failure protection, motor
w

protection, motor tuning error alarm, parameter


Protection functions
setting error alarm, door width auto-learning error
w

alarm, OD/CD error alarm, pulse generator (PG) error


w

alarm, current detection circuit fault alarm, EEPROM


read/write error alarm, over-speed protection
Application Inside, free from direct sunlight, dust, corrosive gas,
Environment
environment combustible gas, oil mist, steam, water drop, and so on
Lower than 1000m. Max altitude: 3000m (deration
Altitude curve should be observed at 1000m ~ 3000m: derated
10% for every rise of 100m)

‐ 4 ‐ 
Items Subitems Specifications
-10°C ~ + 40°C, temperature change less than 0.5°C
/minute
Working
Must be derated above 40°C: The output current must
temperature
be derated 2% for every rise of 1°C.
Max temperature: 50°C
Humidity Less than 95%RH, no condensation
3.5mm (2 ~ 9Hz), 10m/s2 (9 ~ 200Hz), 15m/s2 (200 ~
Vibration
500Hz)

om
Storage
-40°C ~ + 70°C
temperature
Protection IP21

.c
Forced air cooling (EV3200-2S0004A and
Structure EV3200-2S0004S)
Cooling

or
Natural air cooling (EV3200-2S0002A and
EV3200-2S0002S)
 
t
va
2. Operation 
le
ae

LED
Function and data
switchover key
Programming key
Save key
ov

Digit modification key


.n

Shift key

Stop key
w

OD key
Reset key
w

CD key
w

 
 
Key Name Function
Switches between stopping status/operating status and
Programming
programming state.
Function /Data Select data monitor mode and data input confirmation

Up Increase

Down Decrease

‐ 5 ‐ 
In the status of RUN and STOP, press this key to select the
Shift parameters that you want to display on the screen; when setting
data, press this key to select the digit you want to modify
In the keypad control mode, pressing this key opens the door
OD key
(or initiates forward (FWD) spinning)
In the keypad control mode, pressing this key closes the door
CD key
(or initiates reverse (REV) spinning)
In the keypad control mode, press this key to stop operating, or
Stop/Reset
to reset and exit fault alarming status.

om
3. Parameter Setting Method
The function parameters are set through the operation keypad. Look at the example below:

.c
modifying F1.04 (max CD speed) from 20Hz to 30Hz.

1. Press the key to enter programming state. The LED on the keypad will display the F0

or
parameter group.

2. Press the key to search the desired parameter group (F1).

t
va
3. Press the key to enter the corresponding function parameter F1.00 in F1 parameter group.

4. Press the key to enter the desired function parameter F1.04.


le

5. Press the key to display the function parameter value (20.00, with the ones place “0”
ae

blinking).

6. Press the key to shift to the digit to be modified, and press the or key to
ov

change the setting to 30.00.

7. Press the key to save and display the next parameter (F1.05).
.n

8. Press the key to exit to parameter group F1.

9. Press the key to exit programming state (30.00 blinking).


w

(LED display) -F0- -F1- F1.00 F1.04 20.00 30.00 F1.05


w

/
w

2. Press ▲ to 4. Press ▲ to

1. Press PRG 3. Press FUNC/ 5. Press FUNC/ 6. Press▲, , ▲▲ 7. Press FUNC/


to enter search the DATA to enter the enter the desired DATA to display to change the DATA to save
programming desired corresponding function parameter the function setting to 30.00 and display the
state and parameter function parameter F1.04 parameter value next parameter
display curent group F1 F1.00 in F1 F1.05
parameter parameter group
group
Continue to modify parameters

-F1- Exit after modification

Return to previous display Abandon the modification

‐ 6 ‐ 
4.Wiring Diagram Of Inverter 
4.1    Wiring Diagram Of Inverter 
MCCB
L U
Single phase V M
power supply
W
50/60Hz N EV3200 inverter PE

P24 PG

COM
A
mechanical system

om
B
Light curtain NO input PG: pulse generator
X1 PA3
Elevator door

Fault relay
Safety edge NO input PB3
X2
PC3
COM

.c
PA1

Complete OD

or
Control system
relay output
Control system

PC1

OD command input PA2


OD

t Complete CD
va
CD command input PC2 relay output
CD
 
4.2    Wiring Of Power Terminals 
le

4.2.1    Introduction To Power Terminals 
ae

EV3200
ov

PE L N
.n
w

A amplified view
w

Terminal Function description


w

Single-phase 220Vac power input


L, N
terminal
PE Protective earth point
 
4.2.2 Output power terminals 

‐ 7 ‐ 
EV3200

P(+) PB (-) U V W

A
A amplified view

om
Terminal Function description
P ( + ): positive DC bus output terminal; PB: reserved; (-): negative
P ( + ), PB, (-)
DC bus output terminal

.c
U, V, W Motor connection terminal
Safety earth point

or
 
4.2.3 Control Terminals 

t
va
EV3200
le

A
ae

P24 COM A B X1 X2 X3 X4 X5 COM OD CD


ov

A amplified view

Terminal Terminal function Specifications


.n

User terminal 24V power supply +24V ± 15%, max output current: 200mA,
P24, COM
(COM being the reference earth) with output shortcircuit protection function
w

AB pulse input terminal of incremental Meeting the input requirements of pulse


A, B
PG signal with frequency below 35kHz
w

Multi-function input terminals


(functions programmable, COM being
X1 ~ X5
w

the reference earth), or Z pulse input Terminal command valid when shorted
terminal of incremental PG with COM
OD OD command input terminal
CD CD command input terminal
 
4.2.4 User Relay Output Terminals 

‐ 8 ‐ 
EV3200

PA1 PC1 PA2 PC2 PA3 PB3 PC3

A
A amplified view

om
Terminal Terminal function Specifications
When F9.22 is 0: normally closed
contact output

.c
PA1, PC1
When F9.22 is 1: normally open
contact output

or
When F9.22 is 0: normally closed Contact rating
contact output AC: 250V/1A (cosΦ=0.4), 250V/2A
PA2, PC2

t
When F9.22 is 1: normally open (cosΦ=1)
va
contact output DC: 30V/1A
PA3, PB3: Normally closed
contact output
le

PA3, PB3, PC3


PA3, PC3: Normally open
contact output
ae

5. Door Width Self‐learning 
ov

1. Do the wiring
2. Switch on the inverter, set F9.18 to 3 to restore the factory settings.
.n

3. Set F0.01 to 1, set F4.01 and F4.02 (0: forward, 1: reverse) correctly. After exiting the

programming status, press (or ) to start the operation in keypad control mode, and
w

adjust F4.02 setting according to the actual operating conditions. If over current or over load
occurs, or the output current exceeds the motor rated current, adjust the setting of F4.02 to ensure
w

correct PG parameter settings, and restart the inverter. F4.11Asynchronous single/dual motor
selection (F4.11=1 dual motor)
w

4. Switch off the inverter, connect the elevator door mechanical system and switch on the inverter
again.
5. Set F0.02 to 1 (keypad control mode), select auto-learning speed properly via F4.04, set F4.05

to 1, press to start door-width auto learning, and the motor operates according to the
procedures of CD→OD→CD. The inverter stops after the last motor catching. The door width
information will be saved automatically after auto-learning.

‐ 9 ‐ 
6. Switch on the inverter again, in first time operation (OD or CD), the inverter will operate at the
speed set by F3.00. When the door is opened or closed completely, the inverter will switch to OD
(or CD) completion torque maintaining status.
7. Set relevant parameters according to Table 7-3. The CD and OD parameters can be adjusted
according to Figure 6-8 and Figure 6-9.
8. Set F0.02 to 2 (terminal control mode), and the inverter can work normally.

6. Parameter Settings 
Setting  of    F1.04(OD  reference  frequency)and  F1.06(OD  speed  decrease  point  in  distance 
control)to change the open speed 

om
Setting  of    F2.04(CD  reference  frequency)and  F2.06(CD  speed  decrease  point  in  distance 
control)to change the close speed 
Setting of F1.04(OD reference frequency)and F2.04(CD reference frequency) ,and Setting of   
F1.06(OD  speed  decrease  point  in  distance  control)and  F2.06(CD  speed  decrease  point  in 

.c
distance control)to change te open and close speed.   

or
Frequency
F1.04
F1.07 F1.10

t
va
F1.03 F1.11
F1.02
F1.08
Time
le

OD ON OFF
ae

OD start
creep distance F1.01×door width
Door width
0
ov

OD speed D1
decrease distance F1.06×door width
Door width
0
.n

D2
OD position F1.09
limiting distance Door width
0 D3
w

 
OD operation curve for distance control 
w
w

‐ 10 ‐ 
Frequency
F2.04
F2.00 F2.07 F2.10

F2.03 F2.11
F2.02
F2.08
Time
CD ON OFF

om
CD speed
OFF ON
decrease signal
CD position

.c
limiting signal OFF ON
 
CD operation curve for speed control 

or
7.Parameter Table 
Set F9.18 to 3 to restore the factory settings. 
t
va
7.1    Basic Operation Parameters F0 
Min.
Parameter Name Setting range Default Mod.
unit
le

User
F0.00 0 ~ 9999 (0000 means no password) 1 0 ○
password
ae

0: speed control
1: distance control 1
F0.01 Control mode 1 1 ×
2: distance control 2
ov

3: distance control 3
0: keypad control mode of general-purpose
.n

inverter
1: keypad control mode of the inverter used for
controlling elevator door
w

2: terminal control mode of the inverter used for


controlling elevator door
w

Control
3: communication control mode of the inverter
F0.02 command 1 2 ×
used for controlling elevator door (reserved)
w

selection
4: Auto-demo mode
5: terminal control mode of general-purpose
inverter
6: reserved
7: communication control mode of
general-purpose inverter (reserved)

‐ 11 ‐ 
Min.
Parameter Name Setting range Default Mod.
unit
0: same as direction preset by actual motor
Running
wiring
F0.03 direction 1 0 ×
1: reverse to direction preset by actual motor
selection
wiring
Max.output 50.00Hz ~ 128.0Hz 0.01Hz 50.00Hz ×
F0.04
frequency
F0.05 ~ Reserved
F0.08

om
 
7.2 OD Operation Parameters F1 
Min.
Parameter Name Setting range Default Mod.
unit

.c
OD start creep time for speed
F1.00 10 ~ 9999ms 1ms 500ms ○
control

or
OD start creep distance for
F1.01 pulse number (door width) 0 0 ○
distance control
F1.02 OD start creep speed

t
1.00 ~ 25.00Hz 0.01Hz 2.50Hz ○
va
F1.03 OD Acc time 0.1 ~ 3600s 0.1s 3.5s ○
F1.04 OD reference frequency 0.00 ~ F0.04 max frequency 0.01Hz 14.00Hz ○
F1.05 Rush hour operation OD speed 0.00 ~ F0.04 max frequency 0.01Hz 14.00Hz ○
le

OD speed decrease point in


F1.06 pulse number (door width) 1 1000 ○
ae

distance control
F1.07 OD Dec time 0.1 ~ 3600s 0.1s 3s ○
F1.08 OD ending creep speed 0 ~ 15.00Hz 0.01Hz 2.5Hz ○
ov

OD position limit in distance


F1.09 1 ~ 9999 (pulse number) 1 250 ○
control
Switching point of OD 0.0% ~ 100.0% (motor rated
.n

F1.10 0.1% 45.0% ○


complet maintaining torque torque)
OD complet maintaining 0.0% ~ 100.0% (motor rated
w

F1.11 0.1% 45.0% ○


torque torque)
0: selecting manually preset
w

OD operation curve selection curve


F1.12 1 0 ×
in distance control 1: selecting optimum curve by
w

auto-learning
OD optimum curve correction
F1.13 3.0% ~ 15.0% (door width) 0.1% 10.0% ○
factor
F1.14 ~
Reserved
F1.15
 
7.3 CD Operation Parameters F2 
Min.
Parameter Name Setting range Default Mod.
unit

‐ 12 ‐ 
Min.
Parameter Name Setting range Default Mod.
unit
CD start creep time for speed
F2.00 10 ~ 9999ms 1ms 500ms ○
control
F2.01 CD start creep distance 0 ~ 30.0% (door width) 0% 0% ○
F2.02 CD start creep speed 1.00 ~ 25.00Hz 0.01Hz 1.00Hz ○
F2.03 CD Acc time 0.1 ~ 3600s 0.1s 3s ○
F2.04 CD reference frequency 0.00 ~ F0.04 max frequency 0.01Hz 10.00Hz ○
F2.05 Rush hour operation CD speed 0.00 ~ F0.04 max frequency 0.01Hz 10.00Hz ○
CD speed decrease point in

om
F2.06 pulse number (door width) 1 1000 ○
distance control
F2.07 CD Dec time 0.1 ~ 3600s 0.1s 3s ○
F2.08 CD ending creep speed 0 ~ 15.00Hz 0.01Hz 2Hz ○

.c
CD position limit in distance
F2.09 1 ~ 9999 (pulse number) 1 250 ○
control

or
Swithcing point of CD 0.0% ~ 100.0% (motor rated
F2.10 0.1% 40.0% ○
complete maintainging torque torque)

F2.11
CD complete maintainging

t
0.0% ~ 100.0% (motor rated
0.1% 40.0% ○
va
torque torque)
F2.12 CD speed for EFS 5.00 ~ 25.00Hz 0.01Hz 10.00Hz ○
0: selecting manually preset
le

CD operation curve selection in curve;


F2.13 1 0 ×
distance control 1: selecting optimum curve
ae

by auto-learning
CD optimum curve correction
F2.14 3.0% ~ 15.0% (door width) 0.1% 10.0% ○
factor
ov

Distance control CD door


F2.15 000 ~ 9999 1 362 ○
locking point
.n

CD speed after door locking 0.00 ~ 20.00Hz 0.01Hz 1.80Hz ○


F2.16
point
 
w

7.4 Enhanced Function Parameters F3 
w

Min.
Parameter Name Setting range Default Mod.
unit
w

F3.00 INI operation speed 0.00 ~ 20.00Hz 0.01Hz 5.00Hz ○


F3.01 OD time limit 0 ~ 3600s 1s 300s ○
F3.02 CD time limit 0 ~ 3600s 1s 300s ○
F3.03 Slow speed operation time limit 0 ~ 3600s 1s 400s ○
Delay time for external OD
F3.04 0 ~ 9999S 1s 1200s ○
command
Delay time for external CD
F3.05 0 ~ 9999S 1s 600s ○
command

‐ 13 ‐ 
Min.
Parameter Name Setting range Default Mod.
unit
Position of safety edge lift signal
F3.06 0% ~ 40.0% (door width) 0.1% 10.0% ×
output
Function selection of OD upon 0: stop; 1: open the elevator
F3.07 1 1 ×
CD obstruction door
0 ~ 150.0% (motor rated
F3.08 CD obstruction sensitivity 0.1% 100.0% ○
torque)
F3.09 Dec time upon CD obstruction 10 ~ 2500ms 1ms 300ms ○
0 ~ 150.0% (motor rated
F3.10 OD obstruction sensitivity 0.1% 0% ○

om
torque)
Maintaining time for complete
F3.11 1 ~ 3600s 1s 2s ○
OD in demo mode
Maintaining time for complete

.c
F3.12 1 ~ 3600s 1s 2s ○
CD in demo mode
Preset CD/OD times in demo

or
F3.13 0 ~ 9999 1 0 ○
mode
CD/OD times record in demo
F3.14 0 ~ 9999 1 0 ○
mode
t
va
F3.15 Auto reset times upon fault 0 ~ 100 1 0 ×
F3.16 Torque enhance coefficient 100% ~ 350% 1% 115% ×
0: fan does not start during
le

inverter operation
1: fan starts when heatsink
ae

temperature is higher than


F3.17 Fan control 1 0 ×
65°C during inverter
operation
ov

2: fan starts during inverter


operation
0: F1.01, F1.06, F1.13,
.n

F2.01, F2.06 and F2.14 are


Percentage or pulse number percentages.
w

F3.18 0 1 ×
selection 1: F1.01, F1.06, F1.13,
F2.01, F2.06 and F2.14 are
w

numbers
w

 
7.5 Door Width Self‐learning Parameters F4 
Min.
Parameter Name Setting range Default Mod.
unit
0: 24V incremental PG
F4.00 PG type 1 0 ×
1: UVW incremental PG (5V)
F4.01 Pulse number per revolution 0 ~ 4000 1 500 ×

‐ 14 ‐ 
Min.
Parameter Name Setting range Default Mod.
unit
0: same as direction preset by
PG wiring
F4.02 PG direction 1 0 ×
1: reverse to direction preset
by PG wiring
F4.03 Magnetic pole initial angle 0.0 ~ 359.9° 0.1 0 ×
Speed during door width ×
F4.04 2 ~ 20.00Hz 0.01Hz 5.00
auto-learning
Selection of door-width 0: disabled
F4.05 1 0 ×

om
auto-learning 1: enabled
Low digits of pulse count for
F4.06 0 ~ 9999 (pulse number) 1 0 ×
door wicth
High digits of pulse count for

.c
F4.07 0 ~ 9999 (×10000) 1 0 ×
door width
F4.08 Actual door width 0 ~ 9999mm 1mm 0mm ×

or
PG cable broken detection
F4.09 0 ~ 10s 0.1s 0s ×
time for asynchronous motor
F4.10 Ratio of gear
t
1 ~ 100 1.0 1.0 ×
va
0: single motor control
(asynchronous or
Asynchronous single/dual
F4.11 synchronous). 0 0 ×
le

motor selection
1: dual motors control
(asynchronous)
ae

F4.12 Carrier frequency 0.1 10


 
ov

7.6 Multi‐function Input Terminal Parameters F5 
Min. Defa Mo
Parameter Name Setting range
unit ult d.
.n
w
w
w

‐ 15 ‐ 
Min. Defa Mo
Parameter Name Setting range
unit ult d.
0: No functions (can be set repetitively)
1: External reset (RESET) signal input
2: Normally open input contacts for light
curtain signal
3: Normally closed input contacts for light
curtain signal
4: Normally open input contacts for safety
edge

om
5: Normally closed input contacts for safety
edge
6: Normally open input for OD position
limiting

.c
7: Normally closed input for OD position
limiting

or
8: Normally open input for CD position
limiting
9: Normally closed input for CD position
limiting
t
va
F5.00
Function selection 10: Normally open input contacts for OD
F5.01
for control speed decrease
F5.02 1 0 ×
terminals X1 ~ 11: Normally closed input contacts for OD
le

F5.03
X5 speed decrease
F5.04
12: Normally open input contacts for CD
ae

speed decrease
13: Normally closd input contacts for CD
ov

speed decrease
14: Terminal for inputting OD prohibition
signal
.n

15: Terminal for inputting torque


maintaining prohibition signal
16: Low speed OD/CD enable signal input
w

17: Normally open input for lock signal


18: Normally closed input for lock signal
w

19: Emergency Firemen Service (EFS)


w

function input
20: Rush hour operation enable signal input
21: Operation enable signal input (valid for
X5 only)
22: Door width auto-learning command
input (valid for X5 only)

‐ 16 ‐ 
Min. Defa Mo
Parameter Name Setting range
unit ult d.
Function of 0: Output signal 0 for complete OD
programmable (immediately output upon position limiting)
F5.05 0
relay output 1: Output signal 0 for complete CD
PA1/PC1 (immediately output upon position limiting)
Function of 2: Output signal 1 for complete OD
programmable (output after position limiting and lock)
F5.06 1
relay output 3: Output signal 1 for complete CD
PA2/PC2 (output after position limiting and lock)

om
4: Output signal 2 for complete OD
(output after position limiting, lock, and
door lock invalid)
1 ×
5: Output signal 2 for complete CD

.c
(output after position limiting, lock, and
Function of door lock valid)

or
programmable 6: Fault relay output 1
F5.07 6
relay output (not including POFF status)
PA3/PB3/PC3 7: Fault relay output 2

t
(including POFF status)
va
8: Safety edge lift signal output
9: Lock signal synchronous output
10: Re-opening signal output
le

11: Obstruction signal output


ae

 
7.7 Motor Parameters F6 
Min.
Parameter Name Setting range Default Mod.
ov

unit
0: asynchronous motor;
F6.00 Motor type selection 1 0 ×
1: synchronous motor
.n

F6.01 Motor rated power 0 ~ 500W 1W 250 ×


F6.02 Motor rated voltage 0 ~ 250V 1V 220 ×
w

F6.03 Motor rated current 0.10 ~ 9.90A 0.01A 1.1 ×


Motor max allowable 100.0% ~ 200.0% (motor
F6.04 0.1% 150.0% ×
w

operation current rated current)


F6.05 Motor rated frequency 1.00Hz ~ 128.0Hz 0.01Hz 50.00Hz ×
w

Motor rated spinning


F6.06 1 ~ 9999rpm 1r/min 900 ×
speed
0: disable 1:
F6.07 Motor tuning 1 0 ×
enable
F6.08 Stator resistance 00.00 ~ 99.99ohm 0.01ohm 24.71 ×
F6.09 Stator inductance 0 ~ 9999mH 1mH 998 ×
F6.10 Rotor resistance 00.00 ~ 99.99ohm 0.01ohm 19.37 ×
F6.11 Rotor inductance 0 ~ 9999mH 1mH 998 ×
F6.12 Mutual inductance 0 ~ 9999mH 1mH 921 ×

‐ 17 ‐ 
Min.
Parameter Name Setting range Default Mod.
unit
Exciting current with
F6.13 0.00 ~ 99.99A 0.01A 0.39 ×
no load
 
7.8 Vector Control Parameters F7 
Parameter Name Setting range Min. unit Default Mod.
ASR proportional gain
F7.00 0.000 ~ 6.000 0.001 0.600 ×
1
0 (integral function
F7.01 ASR integral time 1 0.001s 1.000 ×

om
disabled), 0.032-32.00s
ASR proportional gain
F7.02 0.000 ~ 6.000 0.001 0.600 ×
2
0 (integral function

.c
F7.03 ASR integral time 2 0.001s 1.000 ×
disabled), 0.032-32.00s
ASR changing

or
F7.04 0.00 ~ 50.0Hz 0.01Hz 5.00 ×
frequency
0 (reserved), 50.0 ~ 250.0%
F7.05

t
Slip compensation gain (for accounting the slip 0.1% 100.0% ×
va
value)
0.0 ~ 200.0% (inverter rated
F7.06 Motoring torque limit 0.1% 100.0% ×
current)
le

0.0 ~ 200.0% (inverter rated


F7.07 Braking torque limit 0.1% 100.0% ×
current)
ae

Current loop’s
F7.08 0 ~ 9999 1 500 ○
proportional gain KP
Current loop’s integral
ov

F7.09 0 ~ 9999 1 300 ○


time KI
F7.10 Filtering coefficient 0 ~ 63 1 27 ○
.n

 
7.9 Communication Parameters F8 (Reserved) 
w

Min.
Parameter Name Setting range Default Mod.
unit
w

0: 1200bps
1: 2400bps
w

2: 4800bps
Modbus baud rate 3: 9600bps
F8.00 1 4 ×
selection 4: 19200bps
5: 38400bps
6: 76800bps
7: 125000bps

‐ 18 ‐ 
Min.
Parameter Name Setting range Default Mod.
unit
0: RTU, 1 start bit, 8 data bits, 2 stop bits,
no parity
1: RTU, 1 start bit, 8 data bits, 1 stop bit,
even parity
2: RTU, 1 start bit, 8 data bits, 1 stop bit,
odd parity
F8.01 Modbus data format 1 0 ×
3: ASCII, 1 start bit, 7 data bits, 2 stop
bits, no parity
4: ASCII, 1 start bit, 7 data bits, 1 stop

om
bit, even parity
5: ASCII, 1 start bit, 7 data bits, 1 stop
bit, odd parity

.c
F8.02 Local number 0 (broadcast address), 1 ~ 127 1 5 ×
Modbus
communication 0: disable the function

or
F8.03 0.1s 0 ×
failure detection 0.1 ~ 100.0s
time
Modbus
t
va
F8.04 communication 0.01 ~ 1.000s 0.001s 0.01s ×
delay
Bit0: station 1 enable
le

Bit1: station 2 enable


Bit2: station 3 enable
ae

CAN
Bit3: station 4 enable
F8.05 communication 1 0 ×
Corresponding station =1 means to enable
station enable
the station
ov

Corresponding station=0 means to disable


the station
0: 10000bps
.n

1: 20000bps
CAN baud rate
F8.06 2: 40000bps 1 0 ×
selection
w

3: 80000bps
4: 1250000bps
w

CAN
communication 0: disable the function
w

F8.07 0.1s 0s ×
failure detection 0.1 ~ 100.0s
time
CAN
F8.08 communication 0.01 ~ 1.000s 0.001s 0.01s ×
delay
F8.09 ~
Reserved
F8.10
 
7.10   Monitoring And Recording Parameters F9 

‐ 19 ‐ 
Min.
Parameter Name Setting range Default Mod.
unit
The display of each parameter is
controlled by a binary bit. “1” for
display:
Bit0: running frequency (Hz)
Bit1: reference frequency (Hz)
Bit2: output voltage (V)
Bit3: output current (A)
Parameters Bit4: output torque (%)
31

om
F9.00 displayed by Bit5: DC bus voltage (V) 1 ○
(0000011111B)
LED Bit6: Status of input terminal (No
unit)
Bit7: Status of output terminal (No

.c
unit)
Bit8: low digits of pulse of door

or
position (0 ~ 9999)
Bit9: high digits of pulse of door
position (0 ~ 9999)

t
0: preset OD frequency (Hz)
va
1: preset CD frequency (Hz)
Selection of 2: status of input terminal (no unit)
le

parameters 3: status of output terminal (no


displayed by unit)
F9.01 1 0 ○
LED in 4: DC bus voltage (V)
ae

stopping status 5: low digits of pulse counted for


(blink) door position (0 ~ 9999)
ov

6: high digits of pulse counted for


door position (0 ~ 9999)
0: no fault record
.n

1: Over-current in Acc process


(E001)
w

2: Overcurrent in Dec process


(E002)
Type of latest
w

3: Overcurrent in constant speed


fault
operation (E003)
F9.02 Type of
w

4: Overvoltage in Acc process


F9.03 second lastest 1 0 *
(E004)
F9.04 fault
5: Overvoltage in Dec process
Type of third
(E005)
lastest fault
6: Overvoltage in constant speed
operation (E006)
7 ~ 8: Reserved
9: Output phase loss (E009)
10: Reserved

‐ 20 ‐ 
Min.
Parameter Name Setting range Default Mod.
unit
11: Heatsink overheating (E011)
12: Reserved
13: Inverter overload (E013)
14: Motor protection (E014)
15: Reserved
16: EEPROM read or write fault
(E016)
17: Reserved

om
18: Reserved
19: Current detecting circuit fault
(E019)
20 ~ 23: Reserved

.c
24: Motor tuning error (E024)
25: PG error (E025)

or
26: Overspeed protection (E026)
27: Reserved
28: Parameter setting error (E028)

t
29: Door width auto-learning error
va
(E029)
30: OD overtime error (E030)
31: CD overtime error (E031)
le

DC Bus
F9.05 Voltage (V) at 0 ~ 999V 1V 0V *
ae

the latest fault


Output current
ov

F9.06 (A) at the 0.00 ~ 99.99A 0.01A 0.00A *


latest fault
Frequency
.n

F9.07 (Hz) at the 0.00Hz ~ 128.00Hz 0.01Hz 0.00Hz *


latest fault
w

Status of input
0 ~ 127 (0: OFF;1: ON)
F9.08 terminal at the 1 0 *
CD/OD/X5/X4/X3/X2/X1
w

latest fault
Status of
w

output 0 ~ 7 (0: OFF;1: ON)


F9.09 1 0 *
terminal at the PC3/PC2/PC1
latest fault
High digits of
pulse counted
F9.10 for door 0 ~ 9999 (×10000) 1 0 *
position at
fault time
F9.11 Low digits of 0 ~ 9999 1 0 *

‐ 21 ‐ 
Min.
Parameter Name Setting range Default Mod.
unit
pulse counted
for door
position at
fault time
High digit of
F9.12 0 ~ 9999 (×10000) 1 0 *
OD times
Low digit of
F9.13 0 ~ 9999 1 0 *
OD times

om
High digit of
F9.14 0 ~ 9999 (×10000) 1 0 *
CD times
Low digit of
F9.15 0 ~ 9999 1 0 *
CD times

.c
Total
F9.16 0 ~ 65535 hours (max.) 1 hour 0 *
operation time

or
Total running
F9.17 0 ~ 65535 hours (max) 1 hour 0 *
time
0: no operation

t
va
Parameter 1: Clear the record
F9.18 1 0 ×
initialization 2: Load defaults
3 ~ 100: reserved
le

Software Actual version


F9.19 1.00 ~ 99.99 0.01 -
version No. No.
ae

Product Actual
F9.20 configuration 3200 ~ 3299 1 configuration -
No. No.
ov

Heatsink
F9.21 0 ~ 100°C 1 0 *
temperature
0: relays PA1/PC1 and PA2/PC2
.n

Relay output
serve as output NC relays
F9.22 polarity 0 1 ×
1: relays PA1/PC1 and PA2/PC2
selection
w

serve as output NO relays


 
w

8. Troubleshooting 
w

EV3200 can detect 19 types of faults. When fault occurs, you can get the information of fault 
codes, DC bus voltage, output current, operating frequency and terminal status by reviewing the 
values of F9.02 ~ F9.09. You can check the faults according to the following table and note down 
the fault phenomena before seeking technical service. 
Fault
Fault type Possible cause Action to take
code
1) Acc time is too short. 1) Prolong the Acc time;
Over-current in
E001 2) Restart the motor in motion when 2) Start the motor after it
Acc process
momentary stop occurs. stops.

‐ 22 ‐ 
Fault
Fault type Possible cause Action to take
code
3) Incorrect external wiring 3) Wiring correctly
4) Incorrect wiring of PG 4) Change the setting of
5) Output phase failure F4.02 or the wiring of PG
5) Check the cable
connection of the motor
1) Increase Dec time or
Overcurrent in 1) Dec time is too short adjust PI parameters
E002
Dec process 2) Output phase failure 2) Check the cable

om
connection of the motor
1) Adjust PI parameters
Overcurrent in 1) Sudden change of load
2) Check load
E003 constant speed 2) Abnormal load
3) Check the cable
operation 3) Output phase failure

.c
connection of the motor
1) Check input power

or
1) Abnormal input voltage source.
Overvoltage in
E004 2) Unsuitable setting of PI parameters 2) Adjust PI parameters
Acc process
3) Big load inertia 3) Connect external

t braking resistor
va
1) Dec time is short 1) Prolong Dec time
2) Unsuitable selection of braking 2) Re-select the braking
Overvoltage in
le

E005 resistor resistor


Dec process
3) Abnormal input voltage 3) Check input voltage
ae

4) Unsuitable setting of PI parameters 4) Adjust PI parameters


Overvoltage in 1) Abnormal change of input voltage 1) Mount input reactor
E006 constant speed 2) Energy regenerated by negative 2) Connect external
ov

operation torque load braking resistor


E007
Reserved
E008
.n

Check the 3-phase output


The output cables of the inverter are
Output phase cables of the inverter and
E009 broken, phase failure or 3-phase loads
w

loss check if the 3-phase loads


are severely unbalanced
are balanced
w

E010 Reserved
Heatsink 1) Air duct blocked 1) Clear the air duct
E011
w

overheating 2) IGBT abnormal 2) Seek service


E012 Reserved
1) Select inverters with
1) Heavy load bigger ratings
Inverter
E013 2) Low mains voltage 2) Check mains voltage
overload
3) PG error 3) Check the PG wiring or
replace the PG
1) Motor rated current setting error 1) Check the setting of
E014 Motor protection
2) Motor’s max allowable operating F6.03

‐ 23 ‐ 
Fault
Fault type Possible cause Action to take
code
current set too small 2) Check the setting of
3) Motor model selection error F6.04
3) Select applicable motor
E015 Reserved
EEPROM read Fault occurs during the read-write of
E016 Seek service
or write fault control parameters
E017,
Reserved
E018

om
Current
1) Current detecting circuit fails
E019 detecting circuit Seek service
2) Power source fails
fault
E020

.c
E021
Reserved
E022

or
E023
1) Set the motor parameters

t correctly according to the


va
Motor tuning 1) Motor parameter setting error motor nameplate
E024
error 2) Tuning overtime 2) Check if the motor is
broken away from its load
le

and check the motor cables


1) Rectify the PG
ae

connection
2) Change the setting of
1) PG signal cable broken F4.02 (PG reversed) or
ov

2) PG signal reverse-connected change the connection of


E025 PG error
3) Output cable connection error or any two phases of the
disconnected (synchronous motor) motor
.n

3) Check the output cable


connection (synchronous
w

motor)
1) Check that the output
w

cable is not disconnected


1) Output cable phase failure
2) Check that the initial
E026 Overspeed error 2) Initial angle of synchronous motor
w

angle of the synchronous


error
motor is correct through
tuning
E027 Reserved
1) OD width auto-learning is not set as 1) Set F0.02=1 or F0.02=2
keypad control mode or terminal control in OD width auto-learning
Parameter
E028 mode 2) Set F002 to 0 in motor
setting error
2) General keypad operation mode is tuning
not used in motor tuning process 3) Set the OD and CD time

‐ 24 ‐ 
Fault
Fault type Possible cause Action to take
code
3) CD and OD time is set shorter than to a bigger value and
all the settings of CD and OD time ensure the setting of F006
4) In the dual motors control mode, is bigger than the sum of
tuning is conducted or synchronous all the settings of CD and
motor is used OD time
5) F5.00 (X1 terminal) is not set as zero 4) The tuning can be
(0) when the load is a synchronous conducted only in the
motor, and incremental PG is used single motor mode (F4.11

om
= 0), and only one motor
can be connected. Besides,
the synchronous motor can
only be used in the single

.c
motor mode (F4.11 = 0).
5) F5.00 (X1 terminal)

or
must be set as zero (0)
when the load is a
synchronous motor, and

t incremental PG is used
va
1) The OD width obtained from the
1) Check the PG wiring
Door width auto-learning process is 0.
and relevant parameters
le

E029 auto-learning 2) The OD width obtained from the


2) Check the mechanical
error auto-learning process is out of the limits
system of the elevator door
3) Door width auto-learning overtime
ae

1) Change the phase


rotation of the motor or set
ov

1) The motor running direction is F0.03 to 1


OD overtime reverse to the definition of OD 2) Check OD contacts
E030
error 2) OD contacts error or setting error signal
.n

3) PG cable is broken 3) Check PG cable


4) Check the mechanical
w

system of elevator door


1) Change the phase
w

1) The motor running direction is rotation of motor or set


CD overtime reverse to the definition of CD F0.03 to 1
E031
w

error 2) CD contacts error or setting error 2) Check CD contacts


3) PG cable is broken signal
3) Check PG cable
 

‐ 25 ‐ 