Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 1

Packing facility

TOTAL GMP
Designed
ROOM MOTER AHU DIAMENTOINS ( MM ) Require
AHU ID discharge ACPH
ROOM Name VOLUME d airflow
No. air flow @ NLT 20
@ VFD
( Fᵌ ) 50Hz Kw L W H
driven
SECONDARY PACKING HALL 66861 11144 10
IPQA ROOM 682 114 10
CATRTON PRINTING ROOM 829 138 10
AHU 01 P LABLE PRINTING ROOM 829 12000 18.5 4295 2665 1845 138 10
PRINTED PACKING MATERIALS 2171 362 10
OVER PRINTED PACKING MATERIALS 2863 477 10
REJECTION ROOM 572 95 10
AHU 02 P BULK PACKING ROOM 3241 1420 2.2 2850 965 660 1080 20
SECONDARY PACKING CORRIDOR 5938 2.2 660 1979 20
AHU 03 P 1420 2925 1265
PRIMARY PACKING CORRIDOR 7237 2.2 660 2412 20
AHU 04 P BLISTER PACKING 1 2820 1550 2.2 2850 965 660 940 20
AHU 05 P BLISTER PACKING 2 2820 1550 2.2 2850 965 660 940 20
AHU 06 P BLISTER PACKING 3 2820 1420 2.2 2850 965 660 940 20
WASHING AREA 636 2.2 106 10
CHANGE PARTS STORAGE 7206 2.2 1201 10
AHU 07 P 710 2950 1360 760
PRIMARY PACKING MATERIAL STORAGE
7206 2.2
( WARE HOUSE 7 ) 1201 10
AHU 08 P BLISTER PACKING 4 2820 1550 3 2925 1265 660 470 10
QUARANTINE STORE I 10025 1671 10
AHU 09 P 1600 3 2925 1265 660
QUARANTINE STORE II 10025 1671 10
AHU 10 P BLISTER PACKING 5 2820 7500 3 2925 1265 660 940 20
AHU 11 P BLISTER PACKING 6 2820 4860 3 2925 1265 660 940 20
NO AHU HOUSE KEEPING AREA 197            
NO AHU CHANGE ROOM ( PRIMARY AREA ) 736            
NO AHU TOOL TRANSFER 736            

You might also like