TECHNICAL SPECIFICATION
UNIT QTY - 1 NO
Fan CFM
20000
SPECIAL INSTRUCTIONS ITEM BY CUSTOMER
1- MOTOR WILL HAVE IE-2. 1. MAGNEHELIC GAUGE.
2- LIGHT , LIMIT SWITCH , WIRE GUARD & VIEW GLASS WILL BE PROVIDED IN FAN SECTION ONLY. 2. TEMP. GAUGE.
3- MANUALLY OPERATED ALL DAMPER IN ALUMINIUM CONSTRUCTION.
4- DX COIL TUBE TYPE 0.5MM THK (IGT TYPE).
5- DX COIL HAVE SUCTION LINE SIZE: …………. & LIQUID LINE SIZE: …………..
6- DX COIL HAVE: 06 NOS. OF DISTRIBUTORS.
7- REFRIGERANT USE:………….& OUTDOOR MAKE: …………….
8- TWO BEND PVC ELIMINATOR SIZE- 1524H X 2440W.
9- ON/OFF SWITCH WILL BE PROVIDED.
10- ONLY PORT FOR MAGNEHELIC GAUGE ACROSS FILTERS WILL BE PROVIDED.
11- ONLY TEMPERATURE PORT ACROSS COIL WILL BE PROVIDED.
Outer Skin Inner Skin Panel Thk Insulation Profile Frame Work
0.8 PRE COATED GI 0.8 PLAIN GI 45±2MM 40±2KG/M³ CFC FREE PUF THERMAL BREAK Aluminium
Unit Colour Panel const. Unit Base Suspension arrangment Type of unit Filter Make
OFF WHITE DOUBLE SKIN G.S.S NA FLOOR MOUNTED THERMADYNE/PUROMATIC/MECHMARK/EQ.
Supply Air Fan Static Pressure-mmwg r.p.m/HZ Outlet Velocity(M/S) Fan Discharge Fan Make
BNC-Q800/DII(II) 175 1553/53 #DIV/0! TH KRUGER
Motor Kw Pole Motor RPM@50HZ Frame Motor Mounting Motor Make
30 4 1470 200 180-200 BHARAT BIJLEE
Motor Pulley Fan Pulley Belt Size Isolator-Model/Qty
#VALUE! #N/A #VALUE! STANDARD
Motor Phase 3 PH
Cooling Coil 1NO-DX COIL
FH FL RD FPI Area (Sqft.) Tube Size(OD)
1524 2440 6 12 40.0 3/8"-IGT
Heating Coil NO
FH FL RD FPI Area (Sqft.) Tube Size(OD)