SITE LOCATION
240
DTVC LOT-240 H
KKA
PCRC BUILDING MA
THREADED ROD
.
CONCRETE IS 'E' DRAWING CONTROL LOG No. GN001.
TRANSVERSE BRACE
MINIMUM EMBEDMENT OF
ANCHOR IN CONCRETE IS 'E' THREADED ROD
.
1 (MIN.)
LOAD 1
'X'
(2.8mm MAXIMUM LENGTH) 1 MIN.
'E'
1
'F'
ADJUSTABLE HINGE
'X'
CHANNEL LONGITUDINAL
1 OR TRANSVERSE BRACE
DOUBLE BOLT
1 (MIN.)
PIPE CLAMP
LOAD
ADJUSTABLE HINGE
LIGHT WEIGHT OR NORMAL CONCRETE METAL DECK
STRUCTURE LOAD ANCHOR* MINIMUM MINIMUM MINIMUM DISTANCE MINIMUM MAXIMUM DISTANCE FROM TOP OF
BOLT EMBEDMENT DISTANCE FROM EDGE TO CENTER CONCRETE ROD STIFFENER CHART
CONNECTION CHANNEL WHERE THE HANGER ROD IS
TYPE DIA.'D' OF ANCHOR IN BETWEEN OF BOLT COVERAGE 'T' ATTACHED TO THE FIRST BOLT OF THE
.
CONCRETE ANCHORS 'F' THREADED 'X'
CHANNEL ROD STIFFENER IS 6" (152.4mm) PIPE SLEEVE
LBS IN. (mm) IN. 'E'**(mm) IN. (mm) IN. (mm) IN. (mm)
ROD SIZE MAX. SPACING LEGENDS:
I 175 3/8" (9.5) 2 1/4" (57.1) 6 2/3" (169.3) 6 1/2" (165.1) 3/4" (19) 3/8"-16 in. (mm)
II,III 450 5/8" (15.9) 4 1/2" (114.3) 10 2/3" (270.9) 11" (279.4) 1 3/8" (35) 1/2"-13 13" (330.2)
5/8"-11 18" (457.2) CLEVIS HANGER
*HILTI KWIK BOLT II IN 3000 PSI (20.7 MPa) MINIMUM LIGHT CONCRETE ADJUSTABLE HINGES, LONGITUDINAL &
RANSVERSE BRACES 3/4"-10 23" (584.2)
CHANNEL SIZE AS REQUIRED 7/8"-9 28" (711.2)
NORMAL WEIGHT CONCRETE
STRUCTURE LOAD ANCHOR* MINIMUM MINIMUM MINIMUM DISTANCE MINIMUM CONCRETE
CONNECTION BOLT EMBEDMENT DISTANCE FROM EDGE TO CENTER COVERAGE 'T'
TYPE DIA.'D' OF ANCHOR IN BETWEEN OF BOLT 'F' ROD STIFFENERS REQUIRED ONLY ON HANGER RODS THAT HAVE SEISMIC BRACING
CONCRETE ANCHORS ATTACHED TO THE HANGER OR TRAPEZE
IN. 'E'**
LBS (mm) IN. (mm) IN. (mm) IN. (mm) IN. (mm)
I,II 300 3/8" (9) 2 1/2" (63) 5" (127) 4 7/8" (124) 3/4" (19)
III 450 1/2" (13) 3 1/2" (89) 7" (178) 6 3/4" (171) 1 1/16" (27)
IV 675 5/8" (16) 4" (101) 8" (203) 8 1/4" (209) 1 3/8" (35)
V 975 3/4" (19) 4 3/4" (120) 9 1/2" (241) 9 3/4" (247) 1 7/16" (36)
*HILTI KWIK BOLT II IN 3000 PSI (20.7 MPa) MINIMUM NORMAL WEIGHT CONCRETE
CONCRETE ATTACHMENTS ROD STIFFENER CHART PIPE CLAMP TRANSVERSE BRACING CLEVIS HANGER TRANSVERSE BRACING
1 NTS
2 NTS
3 NTS
4 NTS
'E'
74
6
T
ROD COUPLER, HEX NUT &
SQUARE WASHER
TRANSVERSE BRACE
NOTES: THREADED ROD THREADED ROD
PLATE SHALL BE OF BRASS WITH A PLAIN CENTRAL HOLE WITHOUT BURRS.
THE THICKNESS T SHALL BE:-
- 3 mm FOR PIPE SIZE BETWEEN 2" AND 3" LOAD
- 6 mm BETWEEN 4" AND 6" ADJUSTABLE HINGE
- 9 mm FOR 8"PIPE
DIAMETER 'D' ALLOWABLE LOAD (IN MINIMUM EMBEDMENT
HOLE DIAMETER d SHALL BE DETERMINED BASED UPON THE FLOW RATE TENSION) 'E'
AND PRESSURE LOSS USING THE DATA GIVEN IN APENDIX B OF BS5306 ALLOWABLE LOAD
ATR SIZE in (mm) in (mm) in (mm)
PART:2:1990 SECTION 5.
LBS (KN) 3/8" (9) 3/8" (9) 2 1/2" (63)
HOLE DIAMETER d SHALL NOT BE LESS THEN 1/2D OTHERWISE MORE PLATES 3/8"-16 610 (2.71)
1/2" (13) 1/2" (13) 3 1/2" (89)
COULD BE USED IN SERIES
1/2"-13 1130 (5.02)
5/8" (16) 5/8" (16) 4" (101)
PLATE SHALL BE FITTED NOT LESS THAN THE TWO PIPE DIAMETERS DOWN 5/8"-11 1810 (8.05) 'J' HANGER
3/4" (19) 3/4" (19) 4 3/4" (120)
STREAM FROM ANY ELBOW OR BEND. 3/4"-10 2710 (12.05)
7/8"-9 3770 (16.77) *HILTI KWIK BOLT II IN 3000 PSI (20.7 MPa) MINIMUM NORMAL WEIGHT CONCRETE
EACH PLATE SHALL HAVE AN IDENTIFICATION TAG.
ORIFICE PLATE DETAILS THREADED ROD "J" HANGER TRANSVERSE BRACING CONCRETE ATTACHMENTS TO SLABS
5 NTS
6 NTS
7 NTS 8 NTS
FIRE EXTINGUISHER
12 FIRE ALARM CONTROL PANEL WIRH BATTERY BACK-UP
ACCIDENTAL OPENING OF ONE OF THE RELEASING TRIM ASSEMBLY WILL ONLY CAUSE AN ALARM.
13 MANUAL SYSTEM RELEASE PULL CONTROL STATION *
ADJUSTABLE HINGE
ADJUSTABLE HINGE LONGITUDINAL BRACE 14 ALARM BELL *
TRANSVERSE BRACE DESIGNER:
. CHANNEL-SIZE AS 15 SMOKE DETECTORS
PIPE STRAPS REQUIRED BRACKET FOR
SEE NOTE * FIRE 16 AUTOMATIC SPRINKLERS
EXTINGUISHER 17 WATER SUPPLY WATER GAUGE
102MM MINIMUM
NOTES:
18 SYSTEM AIR PRESSURE GAUGE
CONTRACTOR:
1-ADJUSTABLE HINGES FOR LONGITUDINAL BRACES MAY BE ATTACHED ON EITHER SIDE ADJACENT TO THE THREAD ROD, OR ATTACHED TO THE ALL THREAD ROD ITSELF. A POWER SUPPLY TO PANEL * KABBANI GENERAL CONTRACTING
2-ADJUSTABLE HINGES FOR TRANSVERSE BRACES MAY BE ATTACHED TO THE THREAD ROD. B AUDIBLE ALARM CIRCUIT *
KABBANI ARCHITECTURAL CONCEPTS
3-TWO ADJUSTABLE HINGES MAY BE ATTACHED TO THE STRUT TRAPEZE USING THE SAME BOLT OR ALL THREAD ROD. C FIRE DETECTION INITIATING CIRCUIT *
FINISHED FLOOR LEVEL D WATER FLOW INITIATING CIRCUIT
4-IT IS NOT NECESSARY TO INSTALL BOTH TRANSVERSE BRACES AND LONGITUDINAL BRACES ON THE SAME TRAPEZE SUPPORT. EITHER SET OF BRACES MAY BE REMOVED TO FROM A LONGITUDINAL BRACE ONLY OR A TRANSVERSE BRACE PROJECT TITLE
ONLY DESIRED.
E SUPERVISORY ALARM INITIATING CIRCUIT * PETROLEUM CONVERSION
5-LONGITUDINAL BRACES, WHEN NEEDED, MUST BE INSTALLED AT BOTH ENDS OF TRAPEZE. F RELEASING CIRCUIT * RESEARCH CENTER- DTVC
6-ANY NUMBER OF PIPES, DUCTWORK MAY BE SUPPORTED FOLLOWING THE SYSTEM WEIGHT AND SUPPORT SPANS. G MANUAL PULL INITIATING CIRCUIT *
*DETERMINE LENGTH OF TRAPEZE, MAKING SURE SUFFICIENT LENGTH IS ADDED TO ATTACH THE ALL THREAD ROD AND BRACING ATTACHMENTS. DRAWING TITLE
* AS PER ELECTRICAL DRAWING
FIRE FIGHTING MISCELLANEOUS
DETAILS 2/2
DESIGNED KA PROJECT No.
TRAPEZE TRANSVERSE AND LONGITUDINAL BRACING FIRE EXTINGUISHER MOUNTING DETAIL (EXPOSED INSTALLATION) PREACTION VALVE ASSEMBLY-DOUBLE INTERLOCK SYSTEM REVIEWED KA
9 NTS
10 NTS
11 NTS VERIFIED KA KH21029
KH21029 00 GN DD FG502 0C