MMD Sizer Station - Hardware and Control Philosophy
1. Introduction
This document has been produced to provide an outline of the proposed control philosophy for the
operation of the new Sizer station from an Electrical prospective and in conjunction with MMD
standard requirements. This document does not detail mechanical, personnel, material handling or
any other control that may be required to operate the entirity of the new plant. We recommend that
this document is in part or in full incorporated into the complete design of the plant.
Note: This document is for MMD equipment only and not intended to supersede site
specifications or standards.
List of Abreviations
There are two available methods of operation, manual and automatic; the preferred method of
operation is automatic and controlled by the main plant PLC. On occasions it may be necessary to
operate the the Sizer in manual mode, to facilitate clearing of to blockages, carry out maintenance
etc.
Automatic Control:
The purpose of automatic control is to provide the facility to start the plant remotely via the main
plant PLC, to acheive sequence control for processing material. Selecting between automatic and
manual is done by a three position selector switch mounted on the auxiliary cabinet door. When in
automatic mode, a remote run signal from the main plant PLC will be required to initiate start up.
The motor must be in Remote Operating Mode on the drive controller keypad mounted on the
cubicle door. Only authorised personnel should carry out any alterations to the Drive
Controller.
Page 3 of 8
Manual Control:
The purpose of Manual control is to provide the facility to start and stop the Sizer via start and stop
push buttons located on the Local Control Panel door. Manual control must only be used to clear
materials from the Sizer in the event of blockages or for maintenance purposes only. Manual control
must not be used for normal operation.
The electrical power and control specification for the MMD Sizer station is as follows.
Power 3 Phase - 460V AC, 60Hz
Power 1 Phase - 230V AC, 60Hz
Control - 24V DC
Instruments - 24V DC.
The Sizer Local Control Panel, generally comprise of the following listed items:
The main incomer is a 500A rated Isolator, door interlocked, mounted inside the
Auxiliary/Marshalling Cabinet.
All electrical power to devices on the Sizer have this as the single point of distribution & isolation.
The Auxiliary Cabinet door indication and control generally comprises of the following:
Page 4 of 8
PLC
The PLC is an Allen-Bradley Micrologix 1200 24VDC 40 point and 2 x RS232 outputs.
All inputs and outputs including spares will be wired to terminals within the marshalling section.
Drive:
Sizer Motor Compartment
The Sizer plant must be operated in Automatic Mode for processing material. In Automatic mode,
the Sizer drive will start and stop in sequence and all safety control devices are activated.
The emergency stop protection on the plant and Sizer Local Control Panel, irrespective of Manual or
Automatic control, will shutdown all of the 24V DC control circuits within the local control panel.
In the event of an emergency stop pressed, the sizer drive control circuitry will be de-energised
immediately and shutdown the sizer plant operation.
The operator, prior to operating the sizer and associated equipment, must carry out the following
checks:
Page 5 of 8
Controls:-
When the plant is started in Automatic Sequence Start from the LCP door; the selector switch in the
“Auto” position, the sequence of events will be as follows:
When the plant is shut down in Automatic Sequence from the LCP door by pressing the stop
pushbutton , the sequence of events will be as follows:
1. The operator should initiate sequence stop by pressing the Sequence Stop pushbutton on
the LCP door
2. Sizer main motor stops.
3. After 20seconds customer conveyor stops.
A plant fault will occur in the event of any of the following developing a fault, the Sizer LCP
common fault detected lamp comes on:
The sizer drive preceding the specific fault will immediately stop,and the drive after the fault will
continue to run until either the plant is shut down or re-started.
Page 6 of 8
Checks to carry out when Sizing:
In the event that the sizer motor has stalled the operator should proceed as follows.
1. Inspect the sizer shafts to determine the reason for the stall
2. If there is metal located within the shaft, this needs to be removed prior to re-starting.
3. If there is no metal identified, then the sizer should be prepared for Manual-Reverse
operation.
4. Place the Sizer position selector switch to the Manual- Reverse position. This will allow
the Sizer to run in reverse.
5. If the sizer runs in reverse, run for no more than two minutes at a time to remove as much
of the material as possible.
6. If the sizer remains stalled or only reverses slightly, the motor will stop again
automatically after 6 seconds due to loss of rotation. In this event wait a further 90
seconds and start the Sizer forward. Again if the Sizer stalls and does not remove the
blockage then isolate the motor (LCP) and proceed to remove the blockage by hand.
7. Re-energise the LCP only when clear and press RESET.
8. Upon clearing of any blockage and the Sizer drive moves freely in either forward or
reverse, then switch the Sizer direction selector switch to Automatic-forward and press
the sequence start pushbutton to bring the sizer motor online.
The clients takeaway conveyor system, if provided, must always be running before the MMD 850
Sizer Starts and remains running for a time after the MMD 850 Sizer stops. This is to enable material
to be cleared off the takeaway conveyor and to avoid depositing material from the sizer discharge
chute on to a stationary belt.
Page 7 of 8
4. Electrical Control Philosophy: Manual Operation Of Drive
4.1 Start and Stop Sizer motors from its associated motor controller keypad display
unit in Local operating mode:
Follow the below steps to start an individual motor independently from the drive controller door key
pad.