Professional Documents
Culture Documents
Ansul Sentry Hydrostatic Test Procedure
Ansul Sentry Hydrostatic Test Procedure
INSTRUCTIONS
SENTRY, CLEANGUARD, and the product names listed in this manual are marks and/or
registered marks. Unauthorized use is strictly prohibited.
EXPLANATION OF SAFETY ALERTS Hydrostatic Test Instructions
REV. 0 2017-FEB-1 (Form No. T-2017001)
! DANGER
p
Indicates a hazardous situation in which a person will experi-
ence serious personal injury or death if the situation is not
avoided.
! WARNING
Indicates a hazardous situation in which a person could expe-
rience serious personal injury or death if the situation is not
avoided.
! CAUTION
Indicates a hazardous situation in which a person could expe-
rience minor or moderate personal injury if the situation is not
avoided.
CAUTION
Addresses practices not related to personal injury, such as a
system part malfunctioning, property damage, or system failure.
NOTICE
Addresses general practices or observations
related to system function that are not related
to personal injury.
Hydrostatic Test Instructions TABLE OF CONTENTS
(Form No. T-2017001) 2017-FEB-1 REV. 0 PAGE TOC-1
PAGE
General Information 1–4
Introduction 1
Tools and Accessories 1
Hydrotest Recommendations 1
Table 1 – Periodic Hydrostatic 2–3
Retest Requirements
Reference Numbers for Code of 4
Federal Regulations
Manufacturing Dates 4
Safety Considerations 4
NOTES:
Hydrostatic Test Instructions GENERAL INFORMATION
(Form No. T-2017001) 2017-FEB-1 REV. 0 PAGE 1
SENTRY Stored Pressure Dry 10 12 years Factory test pressure (not to 1, 2 12 years
Chemical and CLEANGUARD exceed 3X the normal operating
Clean Agent (HFC-236fa), pressure)
Extinguishers
SENTRY Stored Pressure Water 10 5 years Factory test pressure (not to 1, 2 5 years
Hand Portable Extinguishers exceed 3X the normal operating
pressure)
CO2 Cylinders for all SENTRY 10 5 years 5/3 service pressure as 1 5 years
Wheeled Extinguishers stamped into the cylinder
— As used in this chart, service pressure and operating pressure are the same.
Hydrostatic Test Instructions GENERAL INFORMATION
(Form No. T-2017001) 2017-FEB-1 REV. 0 PAGE 3
Factory test pressure (not to exceed 5 years 200 psi (13.8 bar) Agent hose assemblies must be tested at
2X the service pressure) same intervals @ 100 psi (69 bar) or at service
pressure whichever is higher.
5/3 service pressure 5 years 5/3 service pressure • Aluminum shells suspected of being exposed
to temperatures in excess of 350 °F (177 °C)
shall be removed from service and subjected to
a hydrostatic test.
• Agent hose assemblies must be tested at same
intervals @ 2,000 psi (137.9 bar) or at service
pressure, whichever is higher.
5/3 service pressure 5 years 5/3 service pressure • Agent hose assemblies must be tested at same
intervals @ 2,000 psi (137.9 bar) or at service
pressure, whichever is higher.
— Factory test pressures are indicated on the extinguisher nameplates. * See page 4 for references to Code of Federal Regulations.
— Recording of hydrostatic testing shall be in accordance with NFPA-10 recommendations.
GENERAL INFORMATION Hydrostatic Test Instructions
PAGE 4 REV. 0 2017-FEB-1 (Form No. T-2017011)
HYDROSTATIC TEST FOR PRESSURE VESSELS 8. Turn on hydrostatic pump and apply pressure at a rate-of-
The following general instructions are used with Table 2, pressure rise to reach the designated test pressure within
pages 6-7, which lists the specific adaptors required to test the 1 minute. (See Table 1, pages 2-3 for test pressure.)
different types of extinguishers. 9. Maintain the test pressure for 1 full minute observing shell
Always be alert for any indications of damage or inability to for any distortion or leakage. If no distortion or leakage is
operate the extinguisher. No manual can anticipate every- noted and the test pressure has not dropped, the hydro-
thing that could happen to an extinguisher. In the event that static test is successful. Stop the hydrostatic pump and
something not covered in the manual is found, determine open the vent valve to relieve the pressure in the shell.
whether any potential for damage, effect on operation or
Note: Any shell that fails this hydrostatic test must
safety exists, and repair or replace, as necessary. be destroyed (see page 4, step 7) to prevent its
1. Carefully release any pressure from the extinguisher and further use as a pressure vessel. Shells passing this
remove external and internal parts from the shell. (Refer hydrostatic test must have all water and all traces of
to the Operation, Recharge, Inspection, and Maintenance moisture completely removed before reassembly of
Manual provided with the extinguisher for proper components.
procedures.)
2. Remove agent from shell and place in a labeled ! CAUTION
container. (Closed removal system recommended to limit
Relieve pressure through vent valve only. Do not attempt
exposure to personnel.)
to remove adaptors, fittings, fill caps, etc., until pressure
3. Remove all traces of dry chemical from the shell using dry is released.
air or nitrogen.
10. Disconnect all test fittings and remove water from the
! CAUTION shell. Completely dry the shell (for all non-water type of
extinguishers) using a commercial warm air dryer that
Restrain object being cleaned and wear proper protective does not exceed a temperature of 150 °F (65 °C). Do not
clothing and eye protection. place dry chemical in shell until the shell and all attach-
ments are completely dry.
4. Thoroughly examine the entire shell for signs of corrosion 11. Perform hose test on hose assemblies as designated in
or mechanical damage. Refer to the “Standards for Table 1, pages 2-3.
Visual Inspection of Steel Compressed Gas Cylinders,”
Pamphlet CGA C-6, from the Compressed Gas 12. Examine all parts; replace worn or damaged parts with
Association, Inc. original factory components. Reassemble and refill shell
according to the Operation, Recharge, Inspection, and
Maintenance Manual provided with the extinguisher.
! CAUTION 13. Record hydrostatic test information (month, year, test
Do not perform hydrostatic test on shell in poor condition. pressure, name or initials of person performing the test,
If the shell shows evidence of parent metal missing due and name of agency performing the test) on the hydro-
to severe corrosion or mechanical damage, it must be static test record label (see Figure 1), Part No. 11790 (or
destroyed and replaced. (See page 4, step 7.) equal) and attach it to the shell. Update the permanent
file on each tested extinguisher.
5. Connect the appropriate adaptors, fittings, and hose from
the hydrostatic pump as indicated in Table 2, pages 6-7.
6. Place shell in test cage or place shield between shell and
all personnel.
7. Open vent valve and pump water into the shell. When
water starts to flow freely from the valve, rock the shell
gently to release all air entrapped in the shell – then close
vent valve.
! WARNING
All air must be removed. Failure to comply may cause the FIGURE 1
shell to rupture resulting in severe personal injury or death.
Note: Refer to current issue of NFPA No. 10 (Test
Records) for latest test label requirements.
HYDROSTATIC TESTING Hydrostatic Test Instructions
PAGE 6 REV. 0 2017-FEB-1 (Form No. T-2017001)
Extinguisher
Identification Part No. Description Directions
SENTRY
Universal Valve:
02, 05, 10, 20 429644 Hydrostatic Test Adaptor Select appropriate assembly and attach to shell
(Standard and Industrial) (Universal Valve) opening; hand tighten.
Dry Chemical
Connect hydrostatic hose to assembly.
SENTRY Water 430074 Hydrostatic Test Adaptor Connect hydrostatic hose to assembly
SENTRY CO2 CO2 Filling Adaptor Use 3/8 in. NPT high pressure steel straight connec-
tor, ANSI (ASME specification B1.20.1, Class 3000
or 6000 (psi)
CAUTION: All test fittings are to be high pressure (3000 psi (207 bar)) steel construction.
Hydrostatic Test Instructions HYDROSTATIC TESTING
(Form No. T-2017001) 2017-FEB-1 REV. 0 PAGE 7
Components
HYDROSTATIC
TEST ADAPTOR
VENT VALVE,
PART NO. 10580
HOSE TO
HYDROSTATIC
PUMP
TEST ADAPTOR,
PART NO. 429645
O-RING, PART
NO. 428327
UNIVERSAL VALVE
HYDROSTATIC TEST ADAPTOR,
PART NO. 429644
HYDROSTATIC
TEST ADAPTOR
HOSE TO
HYDROSTATIC
PUMP
HYDROSTATIC
TEST ADAPTOR
PART NO. 430074
HYDROSTATIC TESTING Hydrostatic Test Instructions
PAGE 8 REV. 0 2017-FEB-1 (Form No. T-2017011)
NOTES: