NOTES: GENERAL NOTES NOTES FOR SANITARY PIPING INSTALLATION LEGEND CONSTRUCTION DRAWING

1. ALL SANITARY PIPING MATERIALS SHALL BE AS FOLLOW : 1. ALL DETAILS SHOWN ARE TO BE READ IN CONJUCTION WITH ARCHITECTURAL
1. HEAVY DUTY INSPECTION CHAMBER FRAMES AND COVERS ARE TO BE SOIL WASTE PIPE
a) EXPOXY COATED HUBLESS CAST IRON PIPE, UNLESS OTHERWISE STATED. DRAWINGS, DISCREPANCIES, IF ANY, SHALL REFER TO THE ENGINEERS AND/OR
USED ON CARPARKS DRIVEWAY WHERE VEHICULAR TRAFFIC IS EXPECTED.
INCLUSIVE OF VEN PIPE. THE ARCHITECTS BEFORE PROCEEDING FURTHER. VENT PIPE
2. THE COMPLETE SANITARY PLUMBING & DRAINAGE INSTALLATION SHALL COMPLY WITH ALL
2. THE CONTRACTOR SHALL NOT SCALE FROM THE DRAWINGS.
2. MINIMUM INTERNAL DIAMETER OF WASTE PIPE FOR EACH TYPE BY-LAWS, REGULATIONS & CODE OF PRACTICE OF THE SEWERAGE DEPARTMENT (PUB) FLOOR TRAP
3. FULL TIME LICENSED PLUMBER AND GAS SERVICE WORKER SHALL BE ENGAGED FT
OF WASTE SANITARY APPLIANCE AND FITTING. 3. THE CONNECTION FROM LAST INSPECTION CHAMBER TO SEWER MANHOLE SHALL BE OF (C/W ANTI-MOSQUITOS DEVICE)
TO SUPERVISE THE PLUMBING/SANITARY AND GAS INSTALLATION.
MINIMUM 225 DIAMETER VITRIFIED CLAY PIPE UNLESS OTHERWISE INDICATED.
MINIMUM INTERNAL DIAMETER 4. ALL EQUIPMENT OFFER SHALL BE JUSTIFIED BY CALCULATION SUBMITTED FOR 4. ALL INDOOR INSPECTION CHAMBER / WASTE SUMP FRAMES AND COVERS
TYPE OF APPLIANCE/FITTING OF WASTE PIPE IN mm ARCHITECTS APPROVAL PRIOR TO ORDERING OF EQUIPMENT. FW FLOOR WASTE
SHALL BE AIR TIGHT & RECESS TYPE.
5. ALL EQUIPMENT CATALOGUES/PUMP CURVES (WITH OPERATION POINT MARKED) 5. FLOOR TRAP SERVING CONDENSATE WATER SHALL BE INSULATED WITH APPROVED
SHALL BE SUBMITTED FOR APPROVAL PRIOR TO ORDERING OF MATERIAL. INSPECTION CHAMBER
WASH BASIN 32 MATERIALS. ALL SUBSEQUENT HORIZONTAL PIPING UP TO 5m SHALL BE INSULATED.
6. ALL BRACKET SUPPORTS, C CHANNELS, RODS, SCREWS AND NUTS, WASHERS ETC....
SINK (SINGLE OR DOUBLE BOWL) 40 6. THE GRATING COVER FOR FLOOR TRAP/FLOOR WASTE SHALL BE STAINLESS STEEL MATERIAL VENT COWL
SHALL BE HOT DIPPED GALVANIZED STEEL MATERIAL. TO SS 304 OF MIN 3 mm THICK.
LONGBATH/SHOWER TRAY 50 7. PIPE SUPPORTS DETAILS SHALL BE SUBMITTED PRIOR TO INSTALLATION BY
7. ALL VENT PIPE RUN HORIZONTALLY ABOVE THE CEILING LEVEL SHALL BE OF ACCEPTABLE GRADIENT.
REGISTERED PLUMBER. ABBREVIATION
WASH TROUGH/CUSTOM-MADE SINK 50 8. ALL HANGERS SUPPORTS, BRACKETS ANCHORS, BOLTS AND NUTS FOR PIPES, TRUNKINGS,
8. PIPE PENETRATIONS THROUGH CONCRETE WALLS SHALL PROPERLY SEALED CONDUITS TRAYS EQUIPMENT ETC. SHALL BE HOT DIPPED GALVANISED.
FLOOR TRAP 100 AND MADE WATER TIGHT. SWP SOIL & WASTE PIPE
9. ALL SOIL AND WASTE PIPES SHOWN ON PLANS SHALL BE RUN BELOW THE FLOOR SLAB OF
9. CONTRACTOR TO CO-ORDINATE WITH SWC FOR THE FINAL EQUIPMENT LAYOUT AND THAT RESPECTIVE FLOOR UNLESS OTHERWISE STATED. VP VENT PIPE
FLOOR WASTE IN WC CUBICAL 50 PROVIDE CONCRETE PLINTH / STUMPE FOR ALL EQUIPMENT, PIPE ROUTING,
PIPE VALVES AND PIPE HEADERS THAT NEED TO BE MOUNTED ON THE FLOOR 10. ALL BRANCH VENTS SHALL BE Ø50 UNLESS OTHERWISE INDICATED. WP WASTE PIPE
FLOOR WASTE IN OTHER AREA 75
SLABS IN ALL WET ROOMS / AREAS. 11. CROSS VENTINGS SHALL BE PROVIDED AT UPPER AND LOWER BENDINGS F/A FROM ABOVE
10. NO WATER PIPE OR P&D WASTE PIPES ROUTING THROUGH ANY ELECTRICAL / OF ANY OFFSET OF STACKS AND AS SHOWN ON DRAWINGS. T/A TO ABOVE
3. THE GRADIENT OF THE DRAIN LINE SHALL BE 1 IN 90, UNLESS OTHERWISE STATED.
ELECTRONIC ROOM ARE ALLOWED UNLESS THERE IS A COMPARTMENT TO HOUSE 12. ALL VENT PIPE RUN HORIZONTALLY ABOVE THE CEILING LEVEL T/B TO BELOW
THE WATER PIPE OR P&D WASTE PIPES. SHALL BE OF ACCEPTABLE GRADIENT.
4. ALL PIPE PENTRATE THROUGH WALL SHALL BE PROVIDED WITH F/B FROM BELOW
HOT DIPPED GI PIPE SLEEVE, DIAMETER 1 SIZE GREATER. 11. PIPE PASSING THROUGH EXTERNAL WALLS AND SLABS BELOW GROUND LEVEL 13. EVERY FLOOR TRAP SHALL COMPLETE WITH AN ANTI MOSQUITO DEVICE.
AND UP TO 500MM ABOVE FINISH FLOOR LEVEL, SHALL BE FITTED WITH A PUDDLE H/L HIGH LEVEL
FLANGE. THE FLANGE TO BE CAST OR BUILT INTO THE MIDWAY POINTS OF THE 14. INSPECTION CHAMBER EXCEEDING 2500MM DEEP SHALL BE CONSTUCTED IN
5. ALL C.I. PIPES SHOULD PERMIT THE APPLICATION OF ADDITIONAL EXTERNAL FINISHING ACCORDANCE TO ENV STANDARD DRAWING NO. ENV/SEW/76/2B. C/W COMPLETE WITH
EXTERNAL FINISHING COATINGS, AND CORROSION - RESISTANT FITTING SUCH AS WALL TO CREATE A WATER BAR.
15. FINAL CONNECTION TO EXISTING MANHOLE BY APPROVED PIPE JACKING METHOD TL TOP LEVEL
SUCH AS STAINLESS STEEL BRACKETS, CONNECTIONS AND SUPPORTS SHOULD BE USED. 12. ALL PIPE WORKS SHALL BE LOCATED 100MM BELOW THE SLAB. INCLUDING APPLICATION AND COMPLIANCE TO ALL AUTHORITES REQUIPMENTS. IL INVERT LEVEL
THE FITTINGS SHALL BE PROPERLY ANCHORED INTO SOLID WALL. M&E CONTRACTOR SHALL CO-ORDINATE WITH STRUCTURAL CONTRACTOR FOR ALL BEAM
PENETRATION REQUIRED TO MAINTAIN THE SAME MOUNTING LEVEL FOR THE PIPE WORKS 16. ALL FLOOR TRAP, FLOOR WASTE ARE INDICATIVE ONLY, ACTUAL LOCATION TO
6. FOR ALL IC BAKAU PILE TO PRICE IN IF NECESSARY. OF THE SAME SERVICES. CONFIRMED BEFORE SITE INSTALLATION.

4 5 6 7 8 9 10 11 12 13 14 15 16

/ / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /
/ / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /

/ / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /
/

/
/ / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /
/ / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /

/
/

/
/

/
/

/
/

/
/
/
/

/
/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/
/

/
/

/
/

/
/
K

/
/

/
/

/
/

/
/

/
/

/
/

/
/

L
/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
ELEC
/

/
/

/
/

/
/

/
/

/
/

AC

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

M
/

/
/

/
/

/
/

/
/

/
/

/
/

VP

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/
/

/
J

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

NARROW

/
/

/
/

/
/

/
/
I

/
PS
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

N
/

/
/

/
0 CONSTRUCTION DRAWING JUNE'22
/

/
H

/
/

/
/

/
/

/
/

/
ACRYLIC PANEL
/

/
/

/
/

/
/

/
REV DESCRIPTION DATE
/

/
/

/
DB
/

/
/

/
/

/
/

/
/

/
/
/

/
/
/

Owner

/
/

/
/

RP

/
/

DB

/
/

AC

/
RP
/

/
/

/
/

DB

/
/

/
/
MOUNT ROSIE ROAD

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/
G

/
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

O
/

/
/

/
/

/
/

/
/

/
/

/
/
/

/
/

/
/

/
ACRYLIC PANEL
/

/
/

/
/

/
/

/
/

/
/

/
/

/
/

ARCHITECT:
/

/
/

/
/

/
/

/
/
F

/
/

/
/

RT+Q
/

/
/

ARCHITECTS PTE LTD

/
/
/

/
/
/
/
/
/
/

/
/
/

/
32A Mosque Street
/
/

/
/
/
/

/
/
/

/
/
/

/
/
/
/

/
/
/

/
/
/

/
/
/
/

Singapore 059510

/
/
/

/
/
/

/
/
/
/
/
/
/
E

/
/
/

20

/
/
/
/
/
/
/

/
/
/

Tel: 6221 1366 Fax: 6222 2080

/
/
/
/
/
/
/

/
/
/

/
/
/

/
/
/
/

/
/
/

/
/
/

/
/
/
/

M&E CONSULTANT :

/
/
/

/
/
/

/
/
/
/

/
/
/

/
/
/

/
/
/

/
/
/
/

/
/

19

/
/
/

/
/
/

/
/
/
/
/

/
/
/

/
/
/
/

/
/
/

18
/

Kunda Consulting Engineers

/
/
/
/

/
/
/
/

/
/
/
/
/

/
/
/ /

/
/
/
/

/
/
/
/ /

17

/
/

/ /
/
/
/
/

/
/
/
/

/
/

1 Pemimpin Drive,
/
/
/

/
/
/
/

/
/

/
/

/
/

/
/
/

/
/
/
/

/
/

#12-05 One Pemimpin,


/
D

/
/

/
/
/

/
/
/

/
/
/
/

/
/
/
/
/

/
/

Singapore 576151
/
/

/
/
/
/

/
/

/
/
/

/
/
/
/

/
/
VP

/
/

/
/
/
/
/

Tel: (65) 6356 6061

/
/
/

/
/
/
/

/
/
/
/
/

/
/

/
/

/
/

/
/
/

/
/

/
/

Fax: (65) 6358 1169


/
/

/
/
/

/
/
/
/

/
/

/
/
/

/
/

/
/

/
/
/

/
/

Email: info@kunda.com.sg
/

/
/

/
/
/
/
/

/
/

/
/

/
/

/
/
/

/
/

/
/

/
/

/
/
/

/
/

/
/

/
/

/
/
/

/
/
/

/
C

Project Title :
/
/

/
/ /
/

/
/

/
/

PROPOSED SANITARY INSTALLATION TO


/

/
/

/
/

PROPOSED ERECTION OF A 2-STOREY ENVELOPE


/

/
/

/
/

CONTROL DETACHED DWELLING HOUSE WITH


/

/
/

BASEMENT, ATTIC AND SWIMMING POOL ON LOT NO.


/

00046C MK 17 AT 15 MOUNT ROSIE (NOVENA PLANNING


/

/
/

AREA), SINGAPORE
/

/
/

/
/

/
/

/
/
/
/
/

/
/
/
/

/
/
/

Drawing Title :
/

/
/
/
/ /
/
/
/
/

/
/
/
/

/
/
/
/
/
/
/
/
/

/
/
/
/

/
/
/
/

/
/

SANITARY SERVICES
/
/
/

/
/
/ /
/
/
/
/

/
/
/
/
/

/
/
/ /
/
/
/
/

/
/
/
/

/
/
/
/
/

/
/
/
/

/
/
/
/

NOTES & LEGEND


/
/
/
/

/
/
/
/
/

/
/
/ /
/
/
/
/

/
/
/
/
/

/
/
/
/

/
/
/

SITE PLAN
/

/
/
58

/
/
/

/
/
/
/

/
/
/
/
/

/
/
/
/
/
/
/
/

/
/
/
/
/

/
/
/
/
/
/
/
/
/

/
/
/
/

/
/
/
/

/
/
7

/
/

/
ON .915

/
/
/
/

/
TN

Designed : Checked :
AY MK
..10
S

Drawn: AP Date: MAR '22


RL.

Scale:
AS SHOWN
BM

Drawing No. : Rev.


T

P2037-SA-100 0
THE OWNERSHIP OF THE COPYRIGHT IN THIS DRAWING IS RETAINED BY KUNDA CONSULTING
ENGINEERS WHOSE CONSENT MUST BE SOUGHT BEFORE ANY USE OR REPRODUCTION OF
THE DRAWING OR ANY PART THEREOF CAN BE MADE