to a 1 x 150MVA transformer whose typical X/R value is 42. The calculated value of Ip will determine the
making rating of the circuit breaker.
Value of Ib/kA
tmin = 60 msec tmin = 70 msec tmin = 80 msec tmin = 90 msec
3 Phase fault at 22kV of Figure 8.5 11.83 11.82 11.80 11.79
3 Phase fault at 6.6kV of Figure 8.5 8.10 8.07 8.04 8.01
3 Phase fault at 400 volts at Figure 8.5 23.66 23.57 23.49 23.41
TABLE 8.3 : Variation of Ib for Various Miniumum Time Delay of the Circuit Breaker
This is the value of fault current when all transient components, both AC and DC, have decayed to
zero. The value of IK will largely depend on the parameters of the generator, where the rated current and
excitation voltage are the more important parameters.