IEC 60567

Sampling of gasses and oil for analysis of free and dissolved gases
p g g y g
Oil filled electrical equipment ‐
Sampling of gasses and oil for analysis 
of free and dissolved gases ‐ Guidance

JMPS J.M.PANG & SEAH (PTE) LTD IEC 60567 - 1


Sampling Of Oil From Oil-Filled
Equipment

It is important to bear in mind that receiving a


qualitative and a representative sample is crucial for
obtaining a reliable diagnosis of the electrical
equipment.
q p Even the most sophisticated
p extraction or
diagnosis methods cannot overcome faulty samples.

JMPS J.M.PANG & SEAH (PTE) LTD IEC 60567 - 2


Sampling Of Oil From Oil-Filled
Equipment

Precautions should be taken to deal with any sudden


release of oil and avoid oil spillage when sampling oil.
oil
There are two common methods of sampling of the oil:
• By syringe
• By bottle

JMPS J.M.PANG & SEAH (PTE) LTD IEC 60567 - 3


S
Sampling
li Of Free
F Gases
G By
B Syringe
S i

Figure 1 – Sampling of gas by syringe

JMPS J.M.PANG & SEAH (PTE) LTD IEC 60567 - 4


S
Sampling Of Free Gases
G By Vacuum

Figure 2 – Sampling of free gases by vacuum

JMPS J.M.PANG & SEAH (PTE) LTD IEC 60567 - 5


M th d 1:
Method 1 Sampling
S li ByB Syringe
S i

Figure 3 – Sampling of oil by syringe


JMPS J.M.PANG & SEAH (PTE) LTD IEC 60567 - 6
Method 2: Sampling
S By Bottles

Figure 4 – Sampling
S off oil bottles

JMPS J.M.PANG & SEAH (PTE) LTD IEC 60567 - 7


Gas Chromatography

Dissolved gas
Gas
Oil sample
l t d tto free
converted f
chromatoghraphy
gas

or

Free gas from Gas


gas relay chromatoghraphy

JMPS J.M.PANG & SEAH (PTE) LTD IEC 60567 - 8


Gas Chromatography
A gas chromatograph uses two detection methods
methods.

Hydrocarbon gases
Flame Ionisation detects Methane, Ethane,
Ethylene, Acetylene,
Detection (FID) Carbon monoxide,
Carbon dioxide

Gas Chromatograph

Thermal detects Hydrogen,


Conductivity Oxygen,
Detection (TCD) Nitrogen