Professional Documents
Culture Documents
Transformer Case Study (Doble)
Transformer Case Study (Doble)
Mike Anderson
Principal Engineer
Doble Engineering Company
Please remember to complete
your evaluation form.
Transformer Field Testing
• Dielectric Testing
• Transformer
Insulation system health (PF & Capacitance)
• Bushings
• Surge Arresters
• Exciting Current & Losses Core magnetizing circuit
• Leakage Reactance & Loss
Mechanical integrity
• Frequency Response Analysis (FRA)
• Turns Ratio Testing (LV TTR, Doble TTR) Turns ratio of the transformer
• Winding Resistance HV, LV, TV winding DC resistance
• Insulating Fluid (DGA, moisture, etc) Oil analysis – probably single most important test
Transformer Field Testing
• Dielectric Testing
• Transformer
• Bushings
• Surge Arresters
• Exciting Current & Losses
• Leakage Reactance & Loss
• Sweep Frequency Response Analysis (SFRA)
• Turns Ratio Testing (LV TTR, Doble TTR)
• Winding Resistance
• Insulating Fluid (DGA, moisture, etc)
Transformer Construction
Dielectric Testing
Materials fall into two main categories
Imeas
• Apply a voltage (VAPP)
• AC voltage at power frequency
Insulation
• Measure a response ( Imeas ) VAPP System
Under Test
• At same frequency as signal
• Referenced to the applied voltage
• Calculate measured parameters
• measure the fundamental AC electrical characteristics of
the insulation system
Reactive & Real Component Measurements
What are these “fundamental AC electrical characteristics of the insulation
system” we are talking about?
HV Core
LV
Tank Tank
Capacitance Measurement
𝐴𝐴𝜀𝜀
𝐶𝐶 =
𝑑𝑑
• A = Area of the conductors
• ε = Permittivity or Dielectric Constant
• both directly proportional to
Capacitance
IC Imeas Imeas
VAPP I C R I
C R
PF = Cos θ
θ
IR VAPP • Remember, overall, IR <<< IC
• Therefore, Imeas ~ IC
%Power Factor
θ (°) PF (%)
90 0 (perfect insulation)
89.714 0.5
89.427 1.0
45 70.7
30 86.6
0 100 (resistance only)
25000
between 0.2% – 0.5% PF (corrected).
20000 18077
These are general limits – there are MANY
15000
exceptions!
10176
8869
10000
5207
5000
2480
1361
813 520 317 240
0
0.1 to 0.2 0.2 to 0.3 0.3 to 0.4 0.4 to 0.5 0.5 to 0.6 0.6 to 0.7 0.7 to 0.8 0.8 to 0.9 0.9 to 1.0 1.0 to 1.1 1.1 to 1.2
%PF Corrected to 20°C
Power Factor (%PF) Limits
Typical limits for most modern oil-filled power
transformers rated 230 kV and below (temperature
corrected)
• Less Than 0.5% -- GOOD
• >0.5% but < 0.7% -- DETERIORATED
• >0.5% but <0.8% & increasing -- INVESTIGATE
• Greater than 0.7% -- BAD
Epoxy-Encapsulated
Ventilated Transformers
Transformers
CHL ≤ 2.0%
CHL ≤ 1.0%
CH ≤ 3.0%
CH ≤ 3.0%
CL ≤ 4.0%
CL ≤ 2.0%
Two Winding Transformer Test Setup
HV LV
H2 CHL X2
X1
H1 H3 X0
X3
CH CL
Tank & Core
Insulation Systems (CH and CL)
• CH & CL – insulation between the winding conductors and the grounded tank
& core
• Winding insulation
• HV & LV bushings (for each winding)
• Structural insulating members
• DETC and/or LTC (if present)
• Insulating fluid
Insulation Systems (CH and CL)
11
Various Types of Bushings
Capacitor/Condenser Type Non-Condenser Type
Complex insulation system employing a mechanism to Simple insulation system, no voltage grading, typically
grade voltage across the insulation system employed on low voltage
• Oil-Impregnated Paper (OIP) or gas-filled bushings
GE Type U
Solid
•
• ABB O+C •
• Westinghouse Type O • Alternate Layers of Solid and Liquid
• Trench COTA
• Lapp POC Insulation
Ohio Brass
•
• Gas-Filled
• Resin Bonded Paper (RBP)
• Lapp PRC
• Resin Impregnated paper (Dry Type) This discussion will focus on
Micafil
Capacitor/Condenser Type bushings
•
• HSP
• Polymer (Solid)
• Solid
Typical Bushing Construction
Center Conductor
Sight-Glass
Liquid or Compound Filler
Insulating Weathershed
Top/Center
Conductor
Oil Sight
Glass
Bottom
Tap
Flange
16
Main Core Construction
Semi-Conducting Paper
Foil or Ink Herringbone Pattern
Core Wind Core Wind
17
Main Core Construction (ABB O+C Bushing)
Foil Layers
18
Main Core Construction (GE Type U Bushing)
19
Bushing C2 Plate (ABB O+C Bushing)
Tapped Layer
Main Core Voltage Grading
Main Insulation
C1
Insulation C2
CA = CB = CC = CD = CE = CF = CG = CH = CI = CJ CK
Center Grounded
Conductor Layer/Flange
V1 = V2 = V3 = V4 = V5 = V6 = V7 = V8 = V9 = V10 Tap
Electrode
22
Routine Bushing Tests
24
C1 (Main Core Insulation) Test Setup
HV Lead
LV Lead
Ground
Lead
Guard LV Lead
Ground Lead
Bushing and
Apparatus Ground
28
C1 (Main Core Insulation) Test – Dielectric Circuit
Center Conductor
HV Lead
Tap Electrode
C1
C2
LV Ground
Lead Lead
IC1
Guard
Test
Measurement Circuit Ground
29
C2 (Tap Insulation) Test
LV Lead
C2 Test
• Tap Insulator
• Core Insulation between tapped Layer and Bushing Ground
Sleeve
• Portion of Liquid or Compound Filler
• Portion of Weathershed near Flange
HV Lead
IC2
Guard
Ground
Measurement Circuit
Lead
31
Bushing C2 (Tap Insulation) Test - Dielectric Circuit
LV Lead
Center Conductor
HV Lead Tap Electrode
C1
C2
Measurement Test
Circuit Ground
32
Results Analysis - %Power Factor
% PF and Watts Loss measurement – provides indication of the
severity of the CONTAMINATION and/or DETERIORATION of the
apparatus insulation system
• Contaminants (moisture) in the oil
• Deterioration of the solid (paper or resin) insulation
• Contaminants* and/or moisture (high humidity) on bushing surface
• Contaminants* and/or moisture (high humidity) in tap area
40
Results Analysis - Capacitance
41
C1 (Main Core Insulation) Limits – % Power Factor
• Good Rating (typical modern condenser type bushings):
• Typically less than 0.5%
• Deteriorated:
• Between 0.5% to 1.0%
• Investigate:
• Above 1.0%
• ANY sharp increase (ex: doubling from nameplate)
• These are GENERAL values – there are MANY exceptions
• Depends on manufacturer and bushing type - contact manufacturer for
specific recommendations
• Results temperature corrected to 20° C
42
C1 (Main Core Insulation) Limits – Capacitance
• Doble suggested/recommended limits:
Change (+/-) in Capacitance (pF) Rating
< 5% Good
between 5-10% Investigate
> 10% Bad
• Each shorted capacitance layer will cause an increase in C1 capacitance of
5% to 15%.
• If the tap electrode becomes disconnected from the C2 plate there will
usually be a dramatic decrease in C2 capacitance.
• Oil or compound leaks may cause a decrease in capacitance.
43
C2 (Tap Insulation) Limits – % Power Factor
• Good Rating (typical modern condenser type bushings):
• Typically on the order of 0.5% to 1.0%
• Deteriorated: C2 results are heavily
• Between 1.0% to 2.0%
influenced by test conditions!
• Investigate:
• Above 2.0%
• ANY sharp increase (ex: doubling from nameplate)
• These are GENERAL values – there are MANY exceptions
• Depends on the manufacturer and bushing type – contact manufacturer for
specific recommendations
• No temperature correction factors are used
44
C2 (Tap Insulation) Limits – Capacitance
• Doble suggested/recommended limits
Change (+/-) in Capacitance (pF) Rating
< 5% Good
between 5-10% Investigate
> 10% Bad
• Varies according to bushing & test conditions and depends on:
• Manufacturer and bushing type
• Type of tap (Test Tap or Potential Tap)
• Test conditions (metal stand, near ground plane, installed, etc)
45
Exciting Current & Losses
Testing
What is an Exciting Current test?
An open-circuit (secondary winding floated) test measurement of
current and losses using low-voltage (up to 10 kV), single-phase,
50/60 Hz, power source for excitation of the winding.
• Typically performed on the high-voltage winding
• Used to evaluate the magnetizing circuit of the transformer
core
What can it detect?
• Exciting Current and Loss Test is performed primarily to detect problems in the
transformer core structure (shorted core laminations, joint dislocations, etc)
• Can also detect:
• Turn-to-turn insulation issues (shorted turns) – REMEMBER THIS!
• Open Circuits
• Tap changer issues, shorted core laminations, joint dislocations, etc
• Changes in these conditions result in changes to the effective reluctance of the
electromagnetic circuit (core), which changes the exciting current required to
produce a given flux in the core (for a given voltage).
Electro-magnetic Process – No Load Conditions
Iex Φmain
Iex Φmain
ZLOAD ISec ΦSec is created which opposes the Φmain Φmain weakens
• Φmain will draw the necessary Iex from the source for a given Vapp in order to
do this
• Anything that affects the main field (Φmain ) will therefore be indicated by a
change in exciting current ( Iex )
Test Setup and Recommended Testing
Delta Winding Wye Winding
Test H1 H2 H3 H2
Test HV cable
instrument HV cable instrument
UST
UST LV lead H0
LV lead H1 H3
DETC with
LTC in N
2 24.1 12.2 24.9
3 25.2 12.8 26.0
4 26.4 13.4 27.2
5 27.6 14.1 28.5
1L 67.6 56.5 68.3
DETC pattern 1R
2R
67.5
25.2
56.5
12.8
68.2
26.0
3R 202.8 191.6 203.1
4R 25.2 12.8 26.1
Phase pattern
12R 25.2 12.8 26.1
13R 67.5 56.5 68.3
14R 25.2 12.8 26.1
15R
16R
202.9 191.9
25.2 12.8
203.3
26.1
“High-Low-High”
Pattern Analysis
High-Low-High Pattern
WARNING
Safety must be carefully considered before disconnecting test leads. Energy stored
in the transformer winding from the applied direct current can create large
discharge voltages (inductive kickback).
A discharge circuit must be employed that can dissipate the stored energy quickly.
* It is assumed that Lm and di/dt remain constant during 2 µsec following switch opening.
Questions?
Before condemning the apparatus verify…
• Test procedures, test setup, test connections, etc
• Operation of test set
• Condition of test leads
• Grounding
• Nameplate information
• Environmental conditions
• Why are you testing? Commissioning? Routine? Fault?
• With any apparatus, sometimes best to step back and take a minute
Before condemning the transformer…
For transformers:
• CH, CHL, CL – what changed? How did it change?
• Is the problem with %PF? Capacitance? Both?
• Is there more than one issue?
• How do the measurements compare with the other results?
• Do the CHL (high-low & low-high) match?
• If more than one measurement affected, what they have in common?
• What is the test mode (GST-Ground, GST-Guard, UST)?
• Have you tested the bushings yet (CH and CL)?
Before condemning the transformer…(cont.)
For transformers:
• Do results of other tests confirm suspect test data?
• %PF
• Bushing C1 (for CH and CL)
• Tip-up test
• Iex, TTR, WR
• Oil analysis (DGA, moisture, etc)
• Capacitance issues
• Leakage Reactance
• SFRA Mechanical integrity
• Internal inspection – last resort!
Before condemning the transformer…(cont.)
For transformers:
• Do results of other tests confirm suspect test data?
• Exciting Current & Loss Test
• HV and/or LV TTR
• WR
• SFRA (and to lesser degree, LR)
• Turns Ratio
• Exciting Current & Loss Test
• HV TTR (compared to LV TTR) and LV TTR (compared to HV TTR)
• WR
• LR and/or SFRA
Before condemning the bushing…
For bushings:
• C1 and/or C2 – what changed? How did it change?
• Is the problem with %PF? Capacitance? Both?
• Is there more than one issue?
• How do the measurements compare with each other?
• If more than one measurement affected, what they have in common?
• What is the test mode (GST-Guard, UST)?
• Environmental conditions, particularly with C2?
Example #1
Transformer Information
• Westinghouse
• 115 kV : 13.8 kV
• 24/32/40 MVA,
• D-Y
• Manuf. 1982
• Overall test performed 2006
• Previous results from 1986 and 1998
Overall Results from November 2006
History of CH, CHL and CL
CH
CHL
CL
Water Content
• Water Content is difficult to assess without oil temperatures at time of sample
• Latest sample indicated transformer very wet
Date Sampled Top Oil Temp, Moisture % Relative
°C Content, ppm Saturation
11/15/2006 30 29 35
9/14/2005 Not given 36 -
11/16/2004 Not given 17 -
8/13/2004 Not given 26 -
10/29/1997 Not given 19 -
Oil Quality – End of Life
• McGraw Edison
• 138 kV : 69 kV : 12 kV
• 60 MVA
• Autotransformer w/ tert.
• Overall test performed 1982
• Previous results from 1965, 1968, and 1974
CHT Test Results
Change in Capacitance
• Problem evident between 1968 and 1974 test results – did they act?
• Even worse for most recent results.
Winding Deformation
Example #3
1st Test – BRAND NEW Transformer
1st Tests - New Transformer
Test PF PF Corr Insulation
# kV mA W Meas Corr Factor Cap Measured
1 2 11.76 0.600 0.71 3121 CH + CHL
2 2 3.040 0.955 3.14 2.23 0.71 805.9 CH
3 2 8.729 -0.350 -0.40 -0.3 0.71 2315 CHL
4 8.720 -0.355 -0.41 -0.3 0.71 2315 CHL
5 1 15.23 1.634 0.71 4041 CL + CHL
6 1 6.514 1.952 3.00 2.13 0.71 1727 CL
7 1 8.729 -0.330 -0.38 -0.3 0.71 2315 CHL
8 1 8.716 -0.318 -0.36 -0.3 0.71 2314 CHL
What stands out?
HV LV
H2 CHL X2
X1
H1 H3 X0
X3
CH Heat/Watts CL
Tank & Core
Improper ground – high
resistance connection!
CHL Measurement
HV Cable ICHL
High Low
ICH
Tank & Core
ICH
Ground ICHL
UST
ICH Lead
ICHL
LV Lead
Guard Measurement Circuit
2nd Test – Tank Properly Grounded
2nd Tests - New Transformer
Test PF PF Insulation
# kV mA W Meas Corr CF Cap Measured
1 10 11.82 0.314 0.80 3135 CH + CHL
2 10 3.206 0.111 0.35 0.28 0.80 850.4 CH
3 10 8.616 0.205 0.24 0.19 0.80 2285 CHL
4 8.614 0.203 0.24 0.19 0.80 2284.6 CHL
5 1 15.49 0.335 0.80 4109 CL + CHL
6 1 6.874 0.123 0.18 0.14 0.80 1823 CL
7 1 8.616 0.191 0.22 0.18 0.80 2285 CHL
8 1 8.616 0.212 0.25 0.20 0.80 2286 CHL
Example #4
Transformer Information
• Westinghouse
• 140 kV : 72 kV : 13.2 kV
• 80MVA
• Autotransformer w/ tert.
• Manuf. 1975
• Tripped out on No. 2 transformer differential 9/25
• Tests performed: PF/cap, excitation, TTR (HV and LV), winding
resistance, and SFRA
• DGA samples taken on 9/25 & 9/27
Overall Results
Excitation Currents
33
When to perform
37
When to perform (continued)
38
Hot Collar Test Setup
• Tightly wrap hot collar under weather shed closest to external
termination
• Larger bushings may required multiple connection points
• Connect HV hook to Hot Collar D-ring
• Test voltage 10 kV for all Hot Collar tests – remember, not energizing
any conductors or windings
34
Single Hot Collar Test
Single Hot Collar Test
LV Lead Measured
HV Lead surface
leakage
Unmeasured
I(mA) Ground surface
Lead leakage
Guard Measurement
Circuit
Hot Collar Limits – Watts Loss
• Watt-Loss – increase in measured results
• Contamination of the insulation
• Maximum acceptable limit: 0.1 Watts
• Compare results between like bushings in same environment
• Current (mA) - similar values for same type bushings
• Decrease in current (mA) indication of
• Voids
• Low liquid level or loss of compound material
• Results are heavily influenced by environmental conditions
©2017 Doble Engineering Company. All Rights Reserved 46
Hot Collar Test Results Westinghouse Type “S” Bushing
Good Condition General Contamination
Bushing Current Watts Bushing Current Watts
• Westinghouse
• 69 kV : 24 kV : 3.75 kV
• 5.25 MVA
• Manuf. 1965
• Routine maintenance
Transformer Power Factor and Capacitance
Transformer Power Factor and Capacitance
• CH 91.8% PF
• CHL 0.205% PF
• CT 0.253% PF
• CHT current too small, don’t evaluate PF
Troubleshooting
• Waukesha
• 138 kV : 13.2 kV
• 41.7 MVA
• Manuf. 2006
• Routine maintenance testing
Transformer Overall Power Factor Results
Insulation Watts Loss %PF Capacitance
Structure (%) (pF)
CH 0.679 .605 2912
CHL 0.226 0.123 4779
CL 1.288 0.199 16,762
CH’ 0.667 1.068 1622
CL’ 1.145 0.197 15,072
• CH high for a transformer less than 10 years old
• No other test results indicated an issue within the transformer
• CH’ appears to indicate that issues (contamination. moisture, PD,
etc.) appear to exist within the transformer.
C1 Power Factor Results
Nameplate Measured/Corrected
Designation %PF Capacitance Watts Loss %PF Capacitance
(%) (pF) (W) (%) (pF)
H1 0.26 435 -0.010 -0.061 432
H2 0.27 436 0.012 0.073 433
H3 0.26 427 0.010 0.062 435
• Westinghouse
• 142.8 kV : 13.2 kV
• 12/16/20 MVA
• Manuf. 1968
• Westinghouse Type O bushings on H winding
Bushing C1 and C2 Overall PF/Capacitance
Troubleshooting
Only changed C2 %PF, not capacitance. Does that make sense with the findings?
Example #12
Transformer Description
• Northern Transformer
• 44 kV : 4.16 kV
• 13MVA
• Manuf. 1991
Transformer Overall PF/Capacitance Results
• On each side, the majority of the current flows from the winding (either high or
low) to ground
• This is typically indicative of an electrostatic shield between the windings
• Disregard PF if current <0.3mA, evaluate W only
Confirm Shield on Nameplate
Confirm Shield on Nameplate
• Jordan Transformer
• 69 kV : 12.47 kV
• 10/12/14 MVA
• Manuf. 1960
Reason for Concern - DGA
date Hydrogen Methane Ethylene Ethane Acetylene Carbon Carbon
Monoxide Dioxide
Performed at 100V
TEST
REPEATED
Observation
• Anomaly only observed with a low voltage test potential was applied
• Unlikely a dielectric breakdown issue
• Possibility a continuity problem (high resistance)
• Recommended a Winding Resistance measurement
• Best if two independent measurements confirm a problem
Winding Resistance Results
• Confirmation
Example #14
Transformer Description
• GE Prolec
• 13.8 kV : 4.16kV
• 10/11.2 MVA
• Manuf. 2006
• Tested after transporting
Test Results
Test Results
• Expect high-low-high pattern
• Exceptionally high mA and Watts on H2-H3
• LV TTR at 40V good
• What else might confirm an issue?
Test Results – Doble Ratio (HV TTR)
Test 1 – 5 kV
Test 2 – 2 kV
Teardown and Findings
High resistance
turn-to-turn short
Example #15
Transformer Description
• General Electric
• 110 kV : 12.47kV
• 10/12.5/15 MVA
• Manuf. 1982
• Tested during routine maintenance
Test Results
Test Results
• What could impact our shots from the low side so much?
• No other results pointed to problems
• CHL not impacted… what does this tell us?
• Think test modes
Test Results
• Rubber blankets and line-hose used for clearance on X
terminals
• HV cable was resting across “dirty” blanket
• Does it make sense?
• High losses to ground
• UST test (CHL) not impacted significantly
• Buswork completely removed, tests acceptable
Test Results After Removing Buswork/Insulation
Final Questions?
Mike Anderson
(617) 963-0871
manderson@doble.com
Please remember to complete
your evaluation form.
Thank you!