TRUNG TAM DIEU DQ HTD QUOC GIA ‘TRUNG TAM DIEU DO HTD MIEN BAC 86 phigus A1-08-2021/63.77220 ‘Trang: 1/8 PHIEU CHINH BINH RO-LE BAO VE Tram: 220kV NAM DINH (E3.7) ‘M6 ta chung: ‘Thiét bj duge bao ve: Pd 174 Nam Dinh - 172 Phi Truong (E3.4) | Kiéu bao ve: Bao vé qua dong 67/67N (ACCC367-6.2km) (kem FR/FL) May clit: 174 ‘Tén ro-le: ‘TSI86 Phién ban:V6.2 Sor dé dint sb: 180S07/DMB- BD 6 higu role: 7SI86-DAAA-AAG-OAAAAO- ‘LOL 12-2311 1B-AAA0O0- 000A A0-CBIBA1-CEOEAO ‘Ty sb biém dong dign: 1500/1 Nha ehé tgo: Siemens Ty sb ign dign 4p: 1010.11 KV (G pha TU 174) Nim lip ait: 2016 Sé higu bm vé mot soit Phin mém: DigsiS _ Phig bin: V7.0 Ti bao ve: Mach bao vé: Mach 1 Neguyén tic hogt dng ciia cdc chite ning bio vé chinh trong ro-le: aarti chp aug cin ab _ ning bao vé Gis tri aici Geer The dong 67 Dit.OC-3phiDefinite-T4 906A 03s 67 Dir.OC-3ph/Definite-T3 33A Lis 67 Dit.OC-3ph/Definite-T2 16A 28s 6T167N | 67 Dir.OC-3phDefinite-T1 080A 110s cic 174 GIN GFP gndDefinite-T3 80a 035 GTN GFP gndDefinite-12 26A Lis 67N GFP gnd/Definte-T1 16a 20s Luu ¥: ‘Mue dich ban hanh phiéu chinh dinh: thay day siéu nhigt DZ 174 T220 Nam Dinh ~ 172 T110 Phi Tring, Pham vi thay di: TO chite nang Neuing chink dinh ACRaAeUN LI Tac dong. Yéu cdu cia Trung tim Dieu i Newdi Ip phié i 2a ‘Van Khién ‘Xem chi tid ede WAY trong Dial, \ ign thy Faw/Emai 0243-2669171/ 0243-2669215 pttal@nlde.evn.vn, phieurole.al@nldc.evn.vn Pham Manh Cudng Neay lp phiéu Ngay/gi¢:chinh djah ‘Nguoi chink djnh ‘Nguoi gidm sit 2ut2021 NVVH tram! NV tryc TLD) Xe nhgn cia nngudi chinh dj ‘Dang theo phiéu Khong theo phiéu TRUNG TAM DIEU DO HTD QUOC GIA ‘TRUNG TAM DIEU BQ HTD MIEN BAC PHIEU CHINH DINH RO-LE BAO. 6 phigus A1-08-2021/83.77220 ‘Trang: 2/8 Y kién cia Nguoi chinh dinh vé céc gia tri khong cai dit theo phiéu Dia chi Gia tri chinh dinh theo phiéu Gia tri cdi dat trén role ‘TRUNG TAM DIEU DO HTD QUOC GIA. 'S6 phiéu: A1-08-2021/E3.7/220 TRUNG TAM DIEU DQ HTD MIEN BAC Trang: 3/8 PHIEU CHINH DINH RO-LE BAO VE Device settings/ Device settings Settings Value Edit mode Secondary Number of settings groups |1 Active settings group ‘settings group 1 Device settings/ General/Device j Number Settings Value 91.101 Rated frequency 50 He 91.102 Minimum operate tine Os 91.115, Set. format residu.comp, | Kr, Kx 91.138 Block monitoring dir. [off Device settings/ General/ Spontan.indic. : Wonber Settings Value 91.139 Fault-display with pickup Power system/ General/General Wumber ‘Settings Value 11.2311, 101 Phase sequence RBC Power system/ Meas.point I-3ph 1/ CT 3-phase / General Wanber Settings Value 11.931,8881,115 | CT connection S-phase + IN 11.931.8881.127 | Tracking active 11,931,8881.130 | Measuring-point ID I (theo thye eé) Power system/ Meas.point I-3ph 1/ CT 3-phase / CT phases umber Settings Value 11,931,8881,101 | Rated primary current 1500 A 11,931.8881.102 | Rated secondary current Ta 11.931.8881.117 | Current range 100 % IR 11.931.8881.118 | Internal CT type cr protection 11.931. 6881.116 Neutr.point in dir.of ref.obj | theo dau noi thyc té 11.931.8881.114 | Inverted phases none Power system/Meas.point I-3ph 1/ CT 1 Wamber Settings Value 11,931,3841,103 | Magnitude correction 1.0 11,931,3641.117 | Phase TA (theo thye t&) Power system/ Meas.point I-3ph 1/ CT 2 amber Settings Value 11.931.3842.103 | Magnitude correction 1.0 11.931.3842.117 [Phase TB (theo thye t6) Power system/Meas.point I-3ph 1/ CT 3 Wonber Settings Value 11,931.3643.103 | Magnitude correction 1.0 11, 931.3843.117 | Phase Ic (theo thye t€) Power system/Meas.point I-3ph 1/ CT 4 Number Settings Value 11.931.3844.103 | Magnitude correction 1.0 11.931.3844.117 | Phase IN (theo thuc té) ‘TRUNG TAM DIEU DO HTD QUOC GIA Sb phigu: A1-08-2021/83.7/220 ‘TRUNG TAM DIEU DO HTD MIEN BAC Trang: 4/8 Power system/ Meas.point I-3ph 1/ Supv. balan. I Number Settings Value 11,931.2491.1 Mode on, Power system/ Meas.point I-3ph 1/ Supv. ph.seq.I Number Settings Value 11.931.2551.1 Mode on Power system/ Meas.point I-3ph 1/ Supv. sum Number Settings Value 11.931.2431.1 Mode on Power system/ Meas.point V-3ph 1/VT 3-phase Wanber, Settings Value 11.941,8911.101 | Rated primary voltage | 110 kV 11,941.8911.102 | Rated secondary voltage | 110 V 11, 941,8811.104 | VP connection 3 ph-to-gnd voltages 11.941.8911.106 | Inverted phases none 11.941.8911.111 | Tracking active 11.941.8911.130 | Measuring-point 1D 2 (theo thye te) Power system/ Meas.point V-3ph W/VT 1 Wanber, Settings Value 11,941,3811,103 | Magnitude correction 1,000 11,941.3811.108 | Phase VA(theo thye té) Power system/ Meas.point V-3ph VT 2 Waaber Settings Value 11,941,3812.103 | Magnitude correction 1.000 11.941.3812.108 Phase VB(theo thuc té) Power system/ Meas.point V-3ph 1/VT 3 Wanber Settings Value 11. 941,3813.103 | Magnitude correction 1.000 1i.941.3813.108 | Phase ve(theo thye té) Power system/Meas.point V-3ph 1/VT 4 Number, Settings Value 11,941.3814.103 Magnitude correction 1,000 T1.941.3814.108 | Phase VW (theo thue té) Power system/Meas.point V-3ph 1/ Supv. balan. V Number Settings Value 11.941,2521.1 Mode on, 11.941.2521.101 | Release threshold 30 V 11.941.2521.102 | Threshold min/max 0.75 11.941.2521.6 Operate delay 5 Power system/ Meas.point V-3ph 1/ Supv. ph.seq.V Number Settings Value 11.941,2581.1 Mode on, 11, 941.2581.6 Delay supervision alarm [5 s Power system/ Meas.point V-3ph 1/ Supy. Sum V Number ‘Settings Value TRUNG TAM DIEU DO HTD QUOC GIA Sé phigu: A1-08-2021/83.7/220 TRUNG TAM DIEU DO HTD MIEN BAC ‘Trang: 5/8 11.941.2461.1 Mode off ] Power system/ Meas.point V-3ph 1/ VT miniatureCB Womber Settings Value 11,941,2641.101 | Response time 0.08 Recording /Fault recorder/Control Nonber Settings Value 51. 791,2761.130 | Fault recording with pickup 51.791.2761.131 | Storage always 51.791.2761.111 | Maximum record time 6.0 s 51.791.2761.112 | Pre-trigger tine 0.5 51,791.2761.113 | Post-trigger tine 0.58 51,791.2761.116 |Manual record tine 0.5 s 51,791.2761.140 | Sampling frequency 2_kiz Line1/General/ Rated values Number Settings Value 21.9001, 101 Rated current 1500 A 21.9001, 102 Rated voltage Ti0_kv 21.3001. 103 Rated apparent power 285.8 HVA Linel/General/ Line Data Wonber Settings Value 21.9001,149 Neutral point grounded 21.9001-111 ‘Series compensation All [no Line1/General/ Measurements Number Settings Value 21,9001,158 P, Q sign not reversed (theo thy t6) Linel/Process monitor/ Closure detec. Number Settings Value 21,1131, 4681.101 | Operating mode Band I open 21.1131. 4681. 102 Action time after closure |0.05 s (zi-1131- 4661. 103 [win. time feeder open 0.25 s Line1/Process monitor/ 1pol.open det. Number Settings Value (21.1137.a7i7, 101 operating mode with measurement Line1/Process monitor/ Volt.criterion Number Settings Value 21.1131, 4801,101 | Threshold U open. 30_V Linel/ Mes.v.fail.det / Mes.v.fail.det Nunber Settings Value 21.2671, Mode on 21.2671.107 ‘Switch-on 3ph, failure on Linel/ Switch onto fault 1/ Stage 1 Number Settings Value 21.1341, 5841,102 | Configuration 21.1341.5941.102 | 67 Dir.OC-3ph=Al.Definite-Ti | False 21.1341, 5941,102 | 67 Dir.OC-3ph-Al.Definite-T2 | True 21.1341,5941.102 | 67 Dir.OC-3ph-Al.Definite-T3 | False 21.1341.5941.102 | 67 Dir.OC-3ph=Al.Definite-T4 | False (2i-134i.5941.102__[67N GFP ond. sys.1.Definite-Ti| True A (2 ‘TRUNG TAM DIEU DO HTD QUOC GIA Sé phigu: a1-08-2021/63.77220 ‘TRUNG TAM DIEU DQ HTD MIEN BAC ‘Trang: 6/8 21.1341.5941.102 | 67N GFP gnd.sys.1.Definite-Ta| False 21.1341.5941.102 | 67N GFP gnd.sys.1.befinite-T3| False 21,1341,5941.1 Mode on, 21,1341,5941.2 Operate & flt.rec. blocked | no 21.1341.5941.6 ‘Operate delay 0.0 5 Linel/ 67 Dir.OC-3ph-A1/ General Number Settings Value 21.1461.2311.101__| Emergency mode no) 21.1461.2311.102 | Rotation angle of ref.volt. | 45 (theo thuc té) Linel/ 67 Dir.OC-3ph-A1/ Definite-T 1 Number Settings Value 21.1461.8131.1 Mode on 21.1461.8131.2 Operate & fit.rec. blocked | no . 21.1461.6131.105 | Directional mode forward ¢ 21.1461-8131.8 Hethod of measurement Fundamental comp : 21.1461.8131.107 | Non-directional pickup no. i 21,1461.8131.104 | Directional comparation yes u 21.1461.8131.106 | Release via input signal no a 21.1461.8131.10 | Blk. by meas.- volt. failure | yes “ 21.1461.8131.26 | Dynamic settings no Z 21.1461.8131.27 | Blk. w.inrush curr.detect. |no 21.1461.8131.3 Threshold 0.80 8 21.1461.8131.4 Dropout ratio 0.95 21.1461.8131.101 | Dropout delay 0.0 5 21.1461.8131.6 ‘Operate delay 11.0 5 Linel/ 67 Dir.OC-3ph-A1/ Definite-T 2 Number Settings Value 21.1461.6132.1 Mode on 21,1461.8132.2 Operate & fit.rec. blocked | no 21.1461.8132.105 | Directional mode forward 21.1461.8132.8 Method of measurement Fundamental comp 21,1461.8132.107 | Non-directional pickup no 21.1461.8132.104 | Directional comparation yes 21.1461.8132.106 | Release via input signal no 21.1461.8132.10 | Blk. by meas.- volt. failure | yes 21.1461.8132.26 | Dynamic settings no 21.1461.8132.27 | Blk. w.inrush curr.detect. | no 21. 1461.8132.3 ‘Threshold 1.608 21.1461.8132.4 Dropout ratio 0.95 21.1461.8132.101 | Dropout _delay 0.0 5 21.1461.8132.6 Operate delay 2.8 5 Linel/ 67 Dir-OC-3ph-A1/ Definite-T3 Number ‘Settings Value 21,1461. 6133.1 Mode. ‘on 21.1461.8133.2 Operate & fit.rec. blocked | no 21.1461.8133.105 | Directional mode forward 21,1461. 8133.8 Method of measurement Fundamental comp 21.1461.8133.107 | Non-directional pickup no 21,1461.8133.104 | Directional comparation Yes 21.1461.8133.106 | Release via input signal no. 21,1461.8133.10 | Blk. by meas.- volt. failure | yes 21,1461.8133.26 | Dynamic settings no 21,1461.8133.27 | Blk. w.inrush curr.detect. | no 21.1461.8133.3 ‘Threshold 3.38 TRUNG TAM DIEU DO HTD QUOC GIA 'S6 phiéu: A1-08-2021/E3.7/220 ‘TRUNG TAM DIEU DQ HTD MIEN BAC ‘Trang: 7/8 21.1461.8133.4 Dropout ratio 0.35 21.1461.8133.101 | Dropout delay 0.0 8 21.1461.8133.6 Operate delay ils Linel/ 67 Dir.OC-3ph-A1/ Definite-T4 Number Settings Value 21.1461.8134.1 Mode on 21,1461.8134.2 ‘Operate & fit.rec. blocked | no 21.1461.8134.105 Directional mode forward 21,1461.8134.8 Method of measurement Fundamental comp 21.1461.8134.107 | Non-directional pickup Ro 21.1461.8134.104 | Directional comparation Yes 21.1461.8134.106 | Release via input signal RO 21.1461.8134.10 | Blk. by meas.- volt. failure | yes 21.1461.8134.26 | Dynamic settings no 21.1461.8134.27 Blk. w.inrush curr.detect. [no 21.1461.8134.3 Threshold 3.60.8 21.1461.8134.4 Dropout ratio 0.95 21.1461.8134.101 | Dropout delay 0.0 5 21.1461.8134.6 Operate delay O38 Line1/ 67N GFP gnd.sys.1/ General Number Settings Value 21.1111.2311.114 Polarization with vo + IY or v2 + 12 Linel/ 67N GFP gnd.sys.1/ Definite-T 1 Number Settings Value 21.1111, 4861.1 | Mode on. 21.1111. 4861.2 | Operate & fit.rec. blocked [no 21.1111.4861.114 | Directional mode forward 21.1111.4861.11 | 1-pole operate allowed no 21.1111,4861.8 [Method of measurement I-cyele filter 21.1111.4861.116 | Blk. w.inrush curr.detect. |no 21,1111. 4861.129 Op.mode at lp dead time blocked 21.1111. 4861.112 [Hold mode Ip dead tine 0.04 5 21.1111.4861.115 | Dynamic settings nO 21.1111,4861.111 | Stabiliz. w. phase current | 108 21.1111, 4861.3 Threshold 1.608 21,1111.4861.6 | Operate delay 2.0 8 Linel/ 67N GFP gnd.sys.1/ Definite-T 2 Number Settings Value 21.1111, 4862.1 | Mode on. 21.1111. 4862.2 | Operate & flt.rec, blocked [no 21.1111, 4862.114 | Directional mode forward 21.1111.4862.11 | 1-pole operate allowed no. 21.1111. 4862.8 [Method of measurement T-cyele Filter 21.1111, 4862.116 | Blk. w.inrush curr.detect. [no 21.1111. 4862.129 | op.node at 1p dead tine blocked 21.1111, 4862.112 [Hold mode ip dead tine 0.04 = 21.1111, 4862.115 | Dynamic settings no) 21.1111, 4862.111 | Stabiliz. w. phase current [108 21.1111, 4862.3 | Threshold 2.68 21.1111.4862.6 | Operate dela: Tis Linel/67N GFP gnd.sys.1/ Definite-T 3 Nunber Settings Value 21.1111, 4863.1 [Mode on Nérwten ‘TRUNG TAM DIEU DO HTD QUOC GIA S6 phiéu: A1-08-2021/E3.7/220 TRUNG TAM DIEU DQ HTD MIEN BAC ‘Trang: 8/8 21.1111.4863.2 | Operate ec. blocked | no 21.1111.4863.114 | Directional mode forward 21.1111.4863.11 | 1-pole operate allowed no 21.1111. 4863.8 fethod of measurement _ i-cycle filter 21,1111, 4863.116 Bik. w.inrush curr.detect, [no 21,1111, 4863.129 | op.mode at 1p dead time | blocked 21,1111, 4863.112 [Hold mode ip dead time 0.04 5 21,1111, 4863.115 | Dynamic settings no 21,1111, 4863.111 | Stabiliz. w. phase current | 10% 21.1111,4863.3 | Threshold €.0% 21.1111, 4863.6 Operate delay 0.30 8 Circuit breaker 1 / General / Ref. for %-values Number ‘Settings Value 201.2311.101 Rated normal current 1500 _& 201,2311.102 Rated voltage 110_kV Circuit breaker 1 / General / Breaker settings Number Settings Value 201.2311.112 Current thresh. CB open 0.05 A (theo thyc té) Circuit breaker 1 / Trip logic / Trip logic Number Settings Value 201.5341. 103 Reset of trip command with I< Circuit breaker 1 / Circuit break./ Circuit break. Number Settings Value 201. 4261.101 Output _time 0.1 s Circuit breaker 1 / Manual close / Manual close Wunber Settings Value 201.6541, 101, ‘Action tine 0.28 Luu y: 1, Tin higu cét cua bao vé qué dong cdc cp 67-14, 67N-T3 ding thoi di khéi dong chic nang tu dong déng Iai (F79) trong ro-le khoang cach cia duing day. 2, Bao vé qua dong ede cdip 67-T4, 67-13, 67-T2, 67-T1, 6TN-T3, 67N-T2, 67N-T1 dat huéng tir thanh ci ra dung day (4 nghj dat logic phit hyp). 3, Cac chite nang bao vé khdc trong ro-le, dé nghi khdng str dung va khod lai. 4, Cac tham sé do ludng, diéu khién gidm sét dé nghj dat theo khuyén cao cia nha ché tao va pha hgp véi thyc té. 5, Phiéu nay thay phiéu s6 A1-01-2019/E3.7/220 ban hanh ngay 21/01/2019 va dug cai dat khi thay day siéu nhiét DZ 174 1220 Nam Dinh- 172 T110 Phi Trudng theo dé nghj tai céng van s6 6438/BDALD-TH2 ngay 16/12/2021

You might also like